Transformers Equivalent Series Impedance: Transformer bank of three single-phase transformers Z 0 = Z1 = Z 2 = Z l Three-phase transformer with a three-leg core Z1 = Z 2 = Z l Z0 > Zl Wye-Delta Wound Transformers Wiring connection will always cause a phase shift Positive Sequence rotates by a +30 degrees from HV to LV side Negative Sequence rotates by a -30 degrees from HV to LV side Zero Sequence does not rotate © March 2004 Power Systems I 1 Zero-Sequence in a Transformer Dependent on the winding connection on each side Dependent on the ground connection wye or delta ungrounded or grounded Types of connections wye-grounded to wye-grounded wye-grounded to wye wye-grounded to delta wye to wye wye to delta delta to delta © March 2004 Power Systems I 2 Zero-Sequence in a Transformer wye-grounded to wye-grounded wye-grounded to wye wye-grounded to delta © March 2004 Power Systems I 3 Zero-Sequence in a Transformer wye to wye wye to delta delta to delta © March 2004 Power Systems I 4 Generators Synchronous Reactance Dependent on the time period of the study Steady-state Transient Sub-transient Generator is modeled as a wye-connected machine for the positive- and negative-sequence impedances The zero-sequence is dependent on the winding connections of the machine © March 2004 wye-grounded wye-grounded through an impedance wye delta Power Systems I 5 Solidly Grounded Generators ZS E E E ZS ZS © March 2004 Power Systems I 6 Solidly Grounded Generators A E 012 = E abc Ea E abc = Eb Ec 0 E 012 = Ea 0 X 0 = X1 = X 2 = X d © March 2004 jXd Zero Seq Pos Seq E Neg Seq Power Systems I jXd jXd VG0 VG1 VG2 7 Impedance Grounded Generators ZS E Zn E E ZS ZS © March 2004 Power Systems I 8 Impedance Grounded Generators 0 E 012 = Ea 0 jX d + 3Z n 0 Z 012 = 0 Zero Seq 0 Xd 0 0 0 X d Pos Seq Neg Seq © March 2004 jXd+3Zn Power Systems I E jXd jXd VG0 VG1 VG2 9 Wye Connected Generators ZS E E E ZS ZS © March 2004 Power Systems I 10 Wye Connected Generators 0 E 012 = Ea 0 0 0 Z 012 = 0 X d 0 0 Zero Seq 0 0 X d Pos Seq Neg Seq © March 2004 jXd Power Systems I E jXd jXd VG0 VG1 VG2 11 Delta Connected Generators ZS E E ZS E ZS © March 2004 Power Systems I 12 Delta Connected Generators 0 E 012 = Ea 0 0 0 Z 012 = 0 X d 0 0 Zero Seq 0 0 X d Pos Seq Neg Seq © March 2004 jXd Power Systems I E VG0 jXd jXd VG1 VG2 13