ELE B7 Power System Engineering Unbalanced Fault Analysis Analysis of Unbalanced Systems z z z ELE B7 Except for the balanced three-phase fault, faults result in an unbalanced system. The most common types of faults are single lineground (SLG) and line-line (LL). Other types are double line-ground (DLG), open conductor, and balanced three phase. The easiest method to analyze unbalanced system operation due to faults is through the use of symmetrical components Slide # 1 Symmetrical Components z z The key idea of symmetrical component analysis is to decompose the unbalanced system into three sequence of balanced networks. The networks are then coupled only at the point of the unbalance (i.e., the fault) The three sequence networks are known as the – – – ELE B7 positive sequence (this is the one we’ve been using) negative sequence zero sequence Slide # 2 Symmetrical Components Balance Systems Unbalance Currents Unsymmetrical Fault IA IC IB zero sequence Zero Sequence Symmetrical components Unbalance System Sequence Currents Positive Sequence positive sequence Three balanced Systems Negative Sequence negative sequence ELE B7 Slide # 3 Symmetrical Components Assuming three unbalance voltage phasors, VA, VB and VC having a positive sequence (abc). Using symmetrical components it is possible to represent each phasor voltage as: VA = VA0 + VA+ + VA− + B − B VB = V + V + V 0 B VC = VC0 + VC+ + VC− Zero Sequence Component Positive Sequence Component Negative Sequence Component Where the symmetrical components are: ELE B7 Slide # 4 Symmetrical Components + + + The Positive Sequence Components ( VA , VB , VC ) Three phasors Equal in magnitude Displaced by 120o in phase Having the same sequence as the original phasors (abc) The Negative Sequence Components ( VA− , VB− , VC− ) Three phasors Equal in magnitude Displaced by 120o in phase Having the opposite sequence as the original phasors (acb) 0 0 0 The zero Sequence Components ( VA , VB , VC Three phasors Equal in magnitude Having the same phase shift ( in phase) ELE B7 ) VA+ VC+ 120 o 120 o 120 o VB+ VA− − B V 120 o 120 o 120 o VC− VB0 VA0 VC0 Slide # 5 Example VA = VA0 + VA+ + VA− VB = VB0 + VB+ + VB− V A0 VB 0 VC 0 Zero Sequence VA VC = VC0 + VC+ + VC− V A0 V A+ Positive Sequence VC = 0 V A− VC + 120 o V A+ 120 o VB + VA VC = 0 V A− VB Unbalance Voltage ELE B7 Negative Sequence 120 o 120 o VC − VB − VB Synthesis Unsymmetrical phasors using symmetrical components Slide # 6 Sequence Set Representation z Any arbitrary set of three phasors, say Ia, Ib, Ic can be represented as a sum of the three sequence sets I a = I a0 + I a+ + I a− I b = I b0 + I b+ + I b− I c = I c0 + I c+ + I c− where I a0 , I b0 , I c0 is the zero sequence set I a+ , I b+ , I c+ is the positive sequence set I a− , I b− , I c− is the negative sequence set ELE B7 Slide # 7 Conversion Sequence to Phase Only three of the sequence values are unique, I0a , I a+ , I a− ; the others are determined as follows: α = 1∠120° 0 0 0 Ia = I b = Ic I b+ = α 2 I a+ α +α2 + α3 = 0 α3 = 1 (since by definition they are all equal) I c+ = α I a+ I b− = α I a− I c+ = α 2 I a− 0⎤ ⎡ 1 1 1 1 I ⎡ ⎤ ⎤ a ⎡1⎤ ⎡ ⎡ Ia ⎤ ⎡1⎤ ⎢ I ⎥ = I0 ⎢1⎥ + I + ⎢α 2 ⎥ + I − ⎢ α ⎥ = ⎢1 α 2 α ⎥ ⎢ I + ⎥ ⎢ ⎥ b a a a a ⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢⎥ ⎢α ⎥ ⎢α 2 ⎥ ⎢1 α α 2 ⎥ ⎢ I − ⎥ ⎢⎣ I c ⎥⎦ ⎢⎣1⎥⎦ ⎣ ⎦ ⎣ ⎣ ⎦ ⎦ ⎢⎣ a ⎥⎦ ELE B7 Slide # 8 Conversion Sequence to Phase Define the symmetrical components transformation matrix 1⎤ ⎡1 1 ⎢ ⎥ 2 α⎥ A = ⎢1 α ⎢1 α α 2 ⎥ ⎣ ⎦ 0⎤ 0⎤ ⎡ ⎡ I I a ⎡ Ia ⎤ ⎢ +⎥ ⎢ +⎥ ⎢ ⎥ Then I = I b = A ⎢ I a ⎥ = A ⎢ I ⎥ = A I s ⎢ ⎥ ⎢ −⎥ ⎢ −⎥ ⎢⎣ I c ⎥⎦ ⎢⎣ I a ⎥⎦ ⎢⎣ I ⎥⎦ ELE B7 Slide # 9 Conversion Phase to Sequence By taking the inverse we can convert from the phase values to the sequence values I s = A −1I 1⎤ ⎡1 1 −1 1 ⎢ 2⎥ with A = ⎢1 α α ⎥ 3 ⎢1 α 2 α ⎥ ⎣ ⎦ Sequence sets can be used with voltages as well as with currents ELE B7 Slide # 10 Example If the values of the fault currents in a three phase system are: I A = 150 ∠45 I B = 250 ∠150 I C = 100 ∠300 Find the symmetrical components? Solution: VO ELE B7 Slide # 11 Example If the values of the sequence voltages in a three phase system are: Vo = 100 V+ = 200 ∠60 V− = 100 ∠120 Find the three phase voltages Solution: V A = 200 ∠60 + 100 ∠120 + 100 V A = 300 ∠60 V B = 1∠ 240( 200 ∠60 ) + 1∠120( 100 ∠120 ) + 100 V B = 300 ∠ − 60 VC = 1∠120( 200 ∠60 ) + 1∠ 240( 100 ∠120 ) + 100 VC = 0 ELE B7 Slide # 12 Use of Symmetrical Components Consider the following wye-connected load: I n = I a + Ib + I c Vag = I a Z y + I n Z n Vag = ( ZY + Z n ) I a + Z n I b + Z n I c Vbg = Z n I a + ( ZY + Z n ) I b + Z n I c Vcg = Z n I a + Z n I b + ( ZY + Z n ) I c ELE B7 ⎡Vag ⎤ ⎡Z y + Zn ⎢ ⎥ ⎢ ⎢Vbg ⎥ = ⎢ Z n ⎢V ⎥ ⎢ Z n ⎣ cg ⎦ ⎣ Zn Z y + Zn Zn ⎤ ⎡ Ia ⎤ ⎥⎢ ⎥ Z n ⎥ Ib ⎢ ⎥ Z y + Z n ⎥⎦ ⎢⎣ I c ⎥⎦ Zn Slide # 13 Use of Symmetrical Components ⎡Vag ⎤ ⎡Z y + Zn Zn ⎢ ⎥ ⎢ Z y + Zn ⎢Vbg ⎥ = ⎢ Z n ⎢V ⎥ ⎢ Z Zn n ⎣ cg ⎦ ⎣ = Z I V = A Vs V A Vs = Z A I s → ⎡ Z y + 3Z n ⎢ −1 A ZA = ⎢ 0 ⎢ 0 ⎣ ELE B7 ⎤ ⎡ Ia ⎤ ⎥⎢ ⎥ Z n ⎥ Ib ⎢ ⎥ Z y + Z n ⎥⎦ ⎢⎣ I c ⎥⎦ I = A Is Zn Vs = A −1 Z A I s 0 Zy 0 0⎤ ⎥ 0⎥ Z y ⎥⎦ Slide # 14 Networks are Now Decoupled ⎡V 0 ⎤ ⎡ Z y + 3Z n 0 ⎢ +⎥ ⎢ 0 Zy ⎢V ⎥ = ⎢ ⎢ −⎥ ⎢ 0 0 ⎢⎣V ⎥⎦ ⎣ Systems are decoupled V 0 = ( Z y + 3Z n ) I 0 − V = Zy I ELE B7 0⎤ ⎡ I 0⎤ ⎥⎢ +⎥ 0 ⎥ ⎢I ⎥ ⎢ −⎥ ⎥ Z y ⎦ ⎢I ⎥ ⎣ ⎦ V+ = Zy I+ − Slide # 15 Grounding z z z ELE B7 When studying unbalanced system operation how a system is grounded can have a major impact on the fault flows Ground current only impacts zero sequence system In previous example if load was ungrounded the zero sequence network is (with Zn equal infinity): Slide # 16 Sequence diagrams for lines z z ELE B7 Similar to what we did for loads, we can develop sequence models for other power system devices, such as lines, transformers and generators For transmission lines, assume we have the following, with mutual impedances Slide # 17 Sequence diagrams for lines, cont’d Assume the phase relationships are ⎡ ΔVa ⎤ ⎡ Zs Zm Zm ⎤ ⎡ Ia ⎤ ⎢ ΔV ⎥ = ⎢ Z ⎥ ⎢I ⎥ Z Z s m⎥⎢ b⎥ ⎢ b⎥ ⎢ m ⎢⎣ ΔVc ⎥⎦ ⎢⎣ Z m Z m Z s ⎥⎦ ⎢⎣ I c ⎥⎦ where Z s = self impedance of the phase Zm = mutual impedance between the phases Writing in matrix form we have ΔV = Z I ELE B7 Slide # 18 Sequence diagrams for lines, cont’d Similar to what we did for the loads, we can convert these relationships to a sequence representation ΔV = Z I ΔV = A ΔVs I = A Is A ΔVs = Z A Is → ΔVs = A −1 Z A I s 0 0 ⎤ ⎡ Z s + 2Z m A −1 Z A = ⎢ Zs − Zm 0 0 ⎥ ⎢ ⎥ Z s − Z m ⎥⎦ 0 0 ⎢⎣ Thus the system is again decoupled. A rule of thumb is that Z+ = Z − and Z0 is approximate 3 times Z+ . ELE B7 Slide # 19 Sequence diagrams for generators z Key point: generators only produce positive sequence voltages; therefore only the positive sequence has a voltage source During a fault Z+ ≈ Z− ≈ Xd”. The zero sequence impedance is usually substantially smaller. The value of Zn depends on whether the generator is grounded ELE B7 Slide # 20 Sequence diagrams for Transformers z z ELE B7 The positive and negative sequence diagrams for transformers are similar to those for transmission lines. The zero sequence network depends upon both how the transformer is grounded and its type of connection. The easiest to understand is a double grounded wye-wye Slide # 21 Transformer Sequence Diagrams ELE B7 Slide # 22 Unbalanced Fault Analysis z z The first step in the analysis of unbalanced faults is to assemble the three sequence networks. Consider the following example VT =1.05 T1 G1 T2 Transmission Line fault Δ Δ ELE B7 VT =1.05 MVA Voltage X+ G1 100 11 kV 0.15 0.17 0.05 G2 100 11 kV 0.20 0.21 0.1 T1 100 11/220kV 0. 1 0.1 0.1 T2 100 11/220kV 0.1 0.1 0.1 Line 100 220kV 0.105 0.105 0.315 X- Xo G2 J0.0 5 Slide # 23 Sequence Diagrams for Example Positive Sequence Network J0.15 J0.1 J0.105 J0.1 1.05∠0o J0.2 1.05∠0o Negative Sequence Network J0.17 ELE B7 J0.1 J0.105 J0.1 J0.21 Slide # 24 Sequence Diagrams for Example Zero Sequence Network J0.05 J0.1 J0.315 J0.1 J0.1 J0.15 ELE B7 Slide # 25 Create Thevenin Equivalents z Second is to calculate the Thevenin equivalents as seen from the fault location. In this example the fault is at the terminal of the right machine so the Thevenin equivalents are: j 0 . 1389 1 .05 ∠ 0 0 E I a+ I a− ++ Va I a0 + j 0 .1456 - V a− j 0 . 25 V a0 - Zth+ = j 0.2 in parallel with j0.455 Zth− = j 0.21 in parallel with j0.475 ELE B7 Slide # 26 Single Line-to-Ground (SLG) Faults z z ELE B7 Unbalanced faults unbalance the network, but only at the fault location. This causes a coupling of the sequence networks. How the sequence networks are coupled depends upon the fault type. We’ll derive these relationships for several common faults. With a SLG fault only one phase has non-zero fault current -- we’ll assume it is phase A. Slide # 27 SLG Faults, cont’d Ignoring prefault currents, the SLG fault can be described by the following voltage and current relationships: Ib = 0 Ic = 0 & Ia Va Zf Ic Ib Vb Vc Va = I a Z f The terminal unbalance currents at the fault point can be transferred into their sequence components as follows: ⎡1 ⎡ I a0 ⎤ ⎢ ⎢ ⎥ ⎢ ⎥ 1⎢ ⎢ I + ⎥ = ⎢1 3⎢ ⎢ a⎥ ⎢ ⎢ ⎥ ⎢⎣1 ⎢ −⎥ I ⎢ a ⎦⎥ ELE B7 ⎣ 1 α α2 1 ⎤ ⎡I a ⎤ ⎥ ⎢ ⎥ ⎥ ⎢ ⎥ 2 α ⎥ ⎢0 ⎥ ⎥ ⎢ ⎥ ⎥ ⎢ ⎥ α ⎥⎦ ⎢0 ⎥ ⎣ ⎦ → I a0 = I a+ = I a− = Ia 3 Slide # 28 SLG Faults, cont’d During fault, Ia = Va Zf and I ao = Va 3Z f The terminal voltage at phase “a” can be transferred into its sequence components as: Va = Va0 + Va+ + Va− 0 + − V V V V + + a a I a0 = a = a 3Z f 3Z f ELE B7 Slide # 29 SLG Faults, cont’d The only way that these two constraint can be satisfied is by coupling the sequence networks in series I ao Zero Sequence Circuit Ia Va Zf Vb Vc Zero Sequence Circuit I a+ Ic Ib Vao I ao Positive Sequence Circuit Va + + a I = I = I − a Negative Sequence Circuit Va − Vao Zo Ia+ Positive Sequence Circuit I a− 0 a I ao Va + Ia+ 3Z f 1 ∠0 Z+ E Va − Va + 3Z f Ia− Ia− Negative Sequence Circuit Vao Z− Va − Va Va0 + Va+ + Va− = I = 3Z f 3Z f 0 a ELE B7 Slide # 30 Example: z Consider the following system VT =1.05 T1 T2 Transmission Line G1 Δ Δ z ELE B7 fault G2 J0.05 Its Thevenin equivalents as seen from the fault location are: j 0 . 1389 1 .05 ∠ 0 0 VT =1.05 E I a+ I a− ++ Vf - I a0 + j 0 .1456 V f− j 0 . 25 V f0 - Slide # 31 Example, cont’d I j 0 . 1389 E With the sequence networks in series, we can solve for the fault currents 1 . 05 ∠ 0 + a V 0 I − a + + a + V j 0 . 1456 − a - I j 0 . 25 0 1 . 05 ∠ 0 I a+ = I a− = I a0 = = − j1.964 j (0.1389 + 0.1456 + 0.25) 0 a V 0 a I = AI s → I a = − j 5.8 (of course, I b = I c = 0) NOTE 1: These are the currents at the SLG fault point. The currents in the system during the SLG fault should be computed by analyzing the sequence circuits. ELE B7 Slide # 32 Example, cont’d From the sequence currents we can find the sequence voltages as follows: Va+ = 1.05∠00 − I a+ Z + , Va− = − I a− Z − , Va0 = − I ao Z o V = AVs → Va = 0, Vb = 1.166 − j 0.178 , Vc = 1.166 + j 0.178 NOTE 2: These are the voltages at the SLG fault point. The voltages at other locations in the system (during the SLG fault) should be computed by analyzing the sequence circuits. ELE B7 Slide # 33 Line-to-Line (LL) Faults z The second most common fault is line-to-line, which occurs when two of the conductors come in contact with each other. With out loss of generality we'll assume phases b and c. Ia Va Ib Ic Vb Z f Vc Ib = − Ic & Current relationships: I a = 0 Voltage relationships: Vb = Vc + I b Z f ELE B7 Slide # 34 LL Faults, cont'd Using the current relationships, we get ⎡ I a0 ⎤ ⎢ ⎥ ⎢ ⎥ ⎢I + ⎥ ⎢ a⎥ ⎢ ⎥ ⎢ −⎥ ⎢⎣ I a ⎥⎦ ⎡1 ⎢ 1⎢ ⎢1 = 3⎢ ⎢ ⎢1 ⎣ 1 α α2 1 ⎤ ⎥ ⎥ 2⎥ α ⎥ ⎥ α ⎥⎦ ⎡ 0 ⎤ ⎢ ⎥ ⎢ ⎥ ⎢ Ib ⎥ ⎢ ⎥ ⎢ ⎥ ⎢− I ⎥ ⎣ b⎦ NOTE Therefore, I =0 0 a 1 I = (α − α 2 ) I b 3 1 2 − I a = (α − α ) I b 3 + a Hence ELE B7 I a− = − I a+ α = 1∠120 α = −0.5 + j 0.866 α 2 = 1∠240 α 2 = −0.5 − j 0.866 α 2 −α = − j 3 α −α 2 = j 3 Slide # 35 LL Faults, con'td Therefore, it is obvious that, during a LL Faults there is no zero sequence components in the sequence circuit that represents this fault. During LL fault, we have: I =0 Vb = Vc + I b Z f Using the symmetrical components, then: Vb = Va0 + α 2Va+ + α Va− Vao = 0 Zo I a0 = 0 Va0 = − I a0 Z 0 = 0 0 a Vc = Va0 + α Va+ + α 2Va− I b Z f = Z f ( I a0 + α 2 I a+ + α I a− ) ELE B7 Ia Ib + Zf + Va + Vb Vc _ _ _ Slide # 36 LL Faults, con'td Therefore, Va0 + α 2Va+ + α Va− = Va0 + αVa+ + α 2Va− + Z f ( I a0 + α 2 I a+ + α I a− ) I a+ = − I a− Substitute for I a0 = 0 Va0 = − I a0 Z 0 = 0 (α 2 − α )Va+ = (α 2 − α )Va− + (α 2 − α ) I a+ Z f Then, Va+ = Va− + I a+ Z f To satisfy I a− = − I a+ , Va+ = Va− + I a+ Z f and I a0 = 0 , the positive and negative sequence networks must be connected in parallel I ao Zero Sequence Circuit I =0 0 a V ao Ia+ I a+ = − I a− Ia Va ELE B7 Ib Positive Sequence Circuit Ia− Ic Vb Z f Vc Va+ + a − a + a V =V + I Zf Negative Sequence Circuit Va− I ao Zero Sequence Circuit Ia+ 1∠0 Vao Ia+ Positive Sequence Circuit Va + Ia− Va + Ia− Negative Sequence Circuit Z+ E Zf Z− Zf Va − Va − Slide # 37 LL Faults-Example In the previous example, assume a phase-b-to-phase-c fault occurs at the busbar of generator 2 (G2) j 0 .1389 1.05∠00 I a+ j 0 . 1389 Va+ E I j 0.1456 Zf − a Va− Va0 Note: Zf = 0 ELE B7 Va+ E Zf I a− Va− j 0 . 1456 Solving the network for the currents, we get I a0 j0.25 1 .05 ∠ 0 0 I a+ 1.05∠00 = 3.691∠ − 900 I = j (0.1389 + 0.1456) + a ⎡I a ⎤ ⎡1 ⎢ ⎥ ⎢ ⎢ ⎥ 1⎢ ⎢I ⎥ ⎢ b ⎥ = 3 ⎢1 ⎢ ⎢ ⎥ ⎢ ⎢ ⎥ ⎢⎣1 ⎢⎣ I c ⎥⎦ 1 α α2 1⎤ ⎡ 0 ⎤ ⎡ 0 ⎤ ⎥ ⎢ ⎥ ⎢ ⎥ ⎥ ⎢ ⎥ ⎢ ⎥ 0⎥ 2 ⎢ α ⎥ 3.691∠ − 90 = ⎢ − 6.39 ⎥ ⎥ ⎢ ⎥ ⎥ ⎢⎢ ⎥ ⎢ ⎥ ⎥ ⎢ 0 ⎥ ⎢ 6.39⎥⎦ 3.691∠90 ⎣ ⎣ ⎦ ⎥ α ⎦ Slide # 38 LL Faults-Example, cont'd Solving the network for the voltages we get + V fa V fa− = 1.05∠0° − j 0.1389 × 3.691∠ − 90° = 0.537∠0° = − j 0.1452 × 3.691∠90° = 0.537∠0° ⎡Vaf ⎤ 1 ⎤ ⎡ 0 ⎤ ⎡ 1.074 ⎤ ⎡1 1 ⎢ f⎥ ⎢ ⎥⎢ 2 α ⎥ 0.537 ⎥ = ⎢ −0.537 ⎥ ⎢Vb ⎥ = ⎢1 α ⎥ ⎢ ⎥ ⎢ ⎢ f⎥ ⎢1 α α 2 ⎥ ⎢⎣0.537 ⎥⎦ ⎢⎣ −0.537 ⎥⎦ V ⎣ ⎦ ⎢⎣ c ⎥⎦ ELE B7 Slide # 39 Double Line-to-Ground Faults z With a double line-to-ground (DLG) fault two line conductors come in contact both with each other and ground. We'll assume these are phases b and c. The voltage and the current relationships are: Vb = Vc Vb = Vc = ( I b + I c ) Z f Ia = 0 + a Ia − a Ia = I + I + I = 0 0 a Va Ib Vb Ic Vc Zf Note, because of the path to ground the zero sequence current is no longer zero. ELE B7 Slide # 40 DLG Faults, cont'd Using the symmetrical components, the terminal voltages are: 0 + − Vb = Vb + Vb + Vb Vb = Va0 + α 2Va+ + α Va− Vc = Va0 + α Va+ + α 2Va− Vb = Vc Va0 + α 2Va+ + α Va− = Va0 + α Va+ + α 2Va− (α 2 − α )Va+ = (α 2 − α )Va− Va+ = Va− ELE B7 Slide # 41 DLG Faults, cont'd Using the symmetrical components, the terminal currents are: I b = I a0 + α 2 I a+ + α I a− I c = I a0 + α I a+ + α 2 I a− The voltage between fault terminal and ground is: Vb = Vc = ( I b + I c ) Z f Express the above equation in terms of its symmetrical components: Va0 + α 2Va+ + α Va− = ( I a0 + α 2 I a+ + α I a− + I a0 + α I a+ + α 2 I a− ) Z f Using Va+ = Va− , 1 + α + α 2 = 0 & Then Va0 − Va+ = 3I a0 Z f ELE B7 I a = I a0 + I a+ + I a− = 0 Slide # 42 DLG Faults, cont'd To satisfy I a = I a0 + I a+ + I a− = 0 , Va+ = Va− & the three symmetrical circuits, during a double line to ground fault, are connected as follows: I ao I ao I ao Zero Sequence Circuit Vao Zero Sequence Circuit Ia+ I a+ Ia Va Ib Ic Positive Sequence Circuit Va + Ia− Vb Vc Zf I a = I a0 + I a+ + I a− = 0 Va0 − Va+ = 3I a0 Z f Negative Sequence Circuit Va − Vao Positive Sequence Circuit Va + Zo 3Z f Va − 3Z f Ia+ 1 ∠0 Z+ E Va+ = Va− Va + Ia− Ia− Negative Sequence Circuit Vao Z− Va − Va0 − Va+ = 3I a0 Z f ELE B7 Slide # 43 DLG Faults-Example In previous example, assume DLG fault occurred at G2 bus. I a0 V a0 j 0 . 25 I a+ 1 . 05 ∠ 0 0 E j 0 . 1389 3Z f I a− I a+ j 0 . 1389 V a+ V + a V − a 1 . 05 ∠ 0 0 V a− V a0 j 0 . 25 E I a− j 0 . 1456 j 0 . 1456 I a0 3Z f Assuming Zf=0, then + 0 V 1 . 05 ∠ 0 a = I a+ = + − 0 Z + Z //( Z + 3Z f ) j (0.1389 + j 0.092) = 4.547∠ − 900 ELE B7 Slide # 44 DLG Faults, cont'd I a− I a+ j 0 . 1389 V a+ 1 . 05 ∠ 0 0 I a0 j 0 . 1456 V a− V a0 j 0 . 25 E 3Z f V fa+ = 1.05 − 4.547∠ − 90° × j 0.1389 = 0.4184 I −fa = −0.4184 / j 0.1456 = j 2.874 I 0fa = − I +fa − I −fa = j 4.547 − j 2.874 = j1.673 Converting to phase: I bf = −1.04 + j 6.82 I cf = 1.04 + j 6.82 ELE B7 Slide # 45 Unbalanced Fault Summary z z z ELE B7 SLG: Sequence networks are connected in series, parallel to three times the fault impedance LL: Positive and negative sequence networks are connected in parallel; zero sequence network is not included since there is no path to ground DLG: Positive, negative and zero sequence networks are connected in parallel, with the zero sequence network including three times the fault impedance Slide # 46 Generalized System Solution z z 1. 2. 3. ELE B7 Assume we know the pre-fault voltages The general procedure is then Calculate Zbus for each sequence For a fault at bus i, the Zii values are the Thevenin equivalent impedances; the pre-fault voltage is the positive sequence Thevenin voltage Connect and solve the Thevenin equivalent sequence networks to determine the fault current; how the sequence networks are interconnected depends upon the fault type Slide # 47 Generalized System Solution, cont’d 4. Sequence voltages throughout the system are given by ⎡ 0 ⎤ ⎢ M ⎥ This is solved ⎢ ⎥ ⎢ 0 ⎥ for each ⎢ ⎥ sequence V = V prefault + Z ⎢ − I f ⎥ network! ⎢ 0 ⎥ ⎢ ⎥ ⎢ M ⎥ ⎢⎣ 0 ⎥⎦ 5. Phase values are determined from the sequence values ELE B7 Slide # 48 Unbalanced System Example Bus 1 Bus 2 G1 Δ G2 fault Bus 3 For the generators assume Z+ = Z− = j0.2; Z0 = j0.05 For the transformers assume Z+ = Z− =Z0 = j0.05 For the lines assume Z+ = Z− = j0.1; Z0 = j0.3 Assume unloaded pre-fault, with voltages =1.0 p.u. ELE B7 Slide # 49 Positive/Negative Sequence Network Bus 1 j0.2 j0.05 Bus 2 j0.3 j0.05 1.0∠0o j0.2 1.0∠0o j0.3 fault j0.3 Bus 3 ⎡−24 10 10 ⎤ ⎡0.1397 0.1103 0.125⎤ + + Ybus = j ⎢ 10 −24 10 ⎥ Zbus = ⎢0.1103 0.1397 0.125⎥ ⎢ ⎥ ⎢ ⎥ ⎢⎣ 10 10 −20⎥⎦ ⎢⎣0.1250 0.1250 0.175⎥⎦ Negative sequence is identical to positive sequence ELE B7 Slide # 50 Zero Sequence Network Bus 1 j0.05 j0.05 Bus 2 j0.3 j0.3 fault j0.05 j0.05 j0.3 Bus 3 ⎡−16.66 3.33 3.33 ⎤ ⎡0.0732 0.0148 0.0440 ⎤ 0 0 = ⎢ 0.0148 0.0435 0.0.292 ⎥ Ybus = j ⎢ 3.33 −26.66 3.33 ⎥ Zbus ⎢ ⎥ ⎢ ⎥ ⎢⎣0.0440 0.0292 0.1866 ⎥⎦ 3.33 −6.66⎥⎦ ⎢⎣ 3.33 ELE B7 Slide # 51 For a SLG Fault at Bus 3 The sequence networks are created using the pre-fault voltage for the positive sequence thevenin voltage, and the Zbus diagonals for the thevenin impedances j 0 . 1750 1 .0 ∠ 0 0 E Positive Seq. j 0 .1750 Negative Seq. j 0 . 1866 Zero Seq. The fault type then determines how the networks are interconnected ELE B7 Slide # 52 Bus 3 SLG Fault, cont’d I +f + If V+ V− ELE B7 1.0∠0° = = − j1.863 j (0.1750 + 0.1750 + 0.1866) = − If = 0 If = − j1.863 ⎡1.0∠0°⎤ ⎡ 0 ⎤ ⎡ 0.7671⎤ + ⎢ = ⎢1.0∠0°⎥ + Zbus 0 ⎥ = ⎢ 0.7671⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢⎣1.0∠0°⎥⎦ ⎢⎣ j1.863⎥⎦ ⎢⎣ 0.6740 ⎥⎦ ⎡ 0 ⎤ ⎡ −0.2329 ⎤ − ⎢ = Zbus 0 ⎥ = ⎢ −0.2329 ⎥ ⎥ ⎢ ⎥ ⎢ ⎢⎣ j1.863⎥⎦ ⎢⎣ −0.3260 ⎦⎥ Slide # 53 Bus 3 SLG Fault, cont’d ⎡ 0 ⎤ ⎡ − 0.0820 ⎤ 0 ⎢ 0 ⎥ = ⎢ − 0.0544 ⎥ V 0 = Z bus ⎢ ⎥ ⎢ ⎥ ⎢⎣ j1.863 ⎥⎦ ⎢⎣ − 0.3479 ⎥⎦ We can then calculate the phase voltages at any bus 0 ⎡ − 0.3479 ⎤ ⎡ ⎤ V3 = A × ⎢ 0.6740 ⎥ = ⎢ − 0.522 − j 0.866 ⎥ ⎢ ⎥ ⎢ ⎥ ⎢⎣ − 0.3260 ⎥⎦ ⎢⎣ − 0.522 + j 0.866 ⎥⎦ 0.4522 ⎡ − 0.0820 ⎤ ⎡ ⎤ V1 = A × ⎢ 0.7671 ⎥ = ⎢ − 0.3491 − j 0.866 ⎥ ⎢ ⎥ ⎢ ⎥ ⎢⎣ − 0.2329 ⎥⎦ ⎢⎣ − 0.3491 + j 0.866 ⎥⎦ ELE B7 Slide # 54 Faults on Lines z z ELE B7 The previous analysis has assumed that the fault is at a bus. Most faults occur on transmission lines, not at the buses For analysis these faults are treated by including a dummy bus at the fault location. How the impedance of the transmission line is then split depends upon the fault location Slide # 55 Line Fault Example Assume a SLG fault occurs on the previous system on the line from bus 1 to bus 3, one third of the way from bus 1 to bus 3. To solve the system we add a dummy bus, bus 4, at the fault location Bus 1 Bus 2 j0.1 j0.25 1.0∠0o j0.25 j0.0333 1.0∠0o j0.1 j0.0677 Dummy fault bus Bus 3 Bus 4 ELE B7 Slide # 56 Line Fault Example, cont’d 0 30 ⎤ ⎡−44 10 The Ybus ⎢ 10 −24 10 ⎥ 0 + now has ⎥ Ybus = j⎢ 4 buses ⎢ 0 10 −25 15 ⎥ ⎢ 30 ⎥ 0 15 −45⎦ ⎣ Adding the dummy bus only changes the new row/column entries associated with the dummy bus ELE B7 ⎡0.1397 ⎢0.1103 + = j⎢ Zbus ⎢0.1250 ⎢0.1348 ⎣ 0.1103 0.1397 0.1250 0.1152 0.1250 0.1250 0.1750 0.1417 0.1348⎤ 0.1152⎥ ⎥ 0.1417⎥ 0.1593⎥⎦ Slide # 57