Jump Suspended, Wall & Cantilever 1 cct. LED Wiring Options 120V or 277V All luminaires are pre-wired to ends with quick-wire connectors or quick-connect plugs. Each circuit has its own neutral conductor supplied. All circuits are clearly labeled at each end. All wiring options can be ordered with 1 or 2 circuit thru wiring to fixture ends. Dimming can be supplied for all fixtures. 1 Circuit 12' section: 1 board, 1cct. 12' section: 1 board, 1cct. 1 1 1 1 1 1 All lamps wired on one circuit. 12' section: 1 board, 2cct. with A/B switching (module to module) 12' section: 1 board, 2cct. with A/B switching (module to module) 1 1 1 Circuit with Emergency / Night Light (EM/NL) 2 2 1 1 1 1 EM/NL EM/NL 12' section: 1 board, 1cct. with EM/NL 12' section: 1 board, 1cct. with EM/NL 1 1 One 4ft module in a one circuit fixture to be wired on a separate circuit. All LED in EM/NL to be wired together. Leads to formodule) normal circuit wired to both fixture ends. 12'boards section: 1 board,module 2cct. with A/B switching (module & EM/NL Leads 12' for section: EM/NL circuit exit2cct. at EM/NL section only. (module to module) & EM/NL 1 board, with A/B switching 1 1 ©2013 Philips Ledalite Phone: 604-888-6811 Toll Free Fax: 1-800-665-LEDA (5332) EM/NL EM/NL 2 2 Fax: 604-888-2003 ledalite.com Some combinations and exceptions may not be shown. For the most up to date information, especially for projects involving dimming, step-dimming or customer-specified driver, please consult factory. WD_susp_wall_LED-12 0313 Jump Suspended, Wall & Cantilever 2 cct. LED Wiring Options 120V or 277V All luminaires are pre-wired to ends with quick-wire connectors or quick-connect plugs. Each circuit has its own neutral conductor supplied. All circuits are clearly labeled at each end. All wiring options can be ordered with 1 or 2 circuit thru wiring to fixture ends. Dimming can be supplied for all fixtures. 12' section: 1 board, 1cct. 1 1 2 Circuit A/B Switching (module to module) 1 12' section: 1 board, 2cct. with A/B switching (module to module) 2 1 1 Fixture wired for two circuits. Lamps wired in alternating 4ft modules. 12' section: 1 board, 1cct. with EM/NL 1 EM/NL 1 2 Circuit A/B Switching (module to module) with Emergency / Night Light (EM/NL) 12' section: 1 board, 2cct. with A/B switching (module to module) & EM/NL 1 EM/NL 2 One 4ft module in a two circuit fixture (A/B switching) to be wired on a separate thru circuit. Leads for both normal circuits and EM/NL circuit wired to fixture ends. All lamps in EM module to be wired together. Some combinations and exceptions may not be shown. For the most up to date information, especially for projects involving dimming, step-dimming or customer-specified driver, please consult factory. ©2013 Philips Ledalite Phone: 604-888-6811 Toll Free Fax: 1-800-665-LEDA (5332) Fax: 604-888-2003 ledalite.com WD_susp_wall_LED-12 0313 Jump Suspended Power Feeds / Connections 120V, 277V or 347V LED Wiring Options All luminaires are pre-wired to ends with quick-wire connectors. All power cord jackets are factory pre-stripped. Power Cords (for aircraft cable) 4 Conductor 5 Conductor • Max. 10 amps in a 1 circuit application • Max. 5 amps per circuit in a 2 circuit application with shared neutral • Max. 600V • Good for 2 circuit feeds or a 1 circuit feed with a battery pack hot lead • 120V, 277V or 347V applications 7 Conductor • Max. 10 amps in a 1 circuit application • Max. 5 amps per circuit in a 2 circuit application • Max. 600V • Good for 1 circuit feed with dimming or 2 circuit feeds • 120V, 277V or 347V applications • Max. 10 amps in a 1 circuit application • Max. 5 amps per circuit in a 2 circuit application • Max. 600V • Good for 3 circuit feeds or 2 circuit feeds with a battery pack hot lead • 120V, 277V or 347V applications Pendant Pipe • Max. 3 circuits 14 gauge wire (supplied by others) • Not available for all products. Please consult factory for availability. Electrical Connections (standard with all products) Quick-wire connectors - Installed at one end of each fixture INSTALLED VIEW ©2013 Philips Ledalite Phone: 604-888-6811 Toll Free Fax: 1-800-665-LEDA (5332) Fax: 604.888-2003 ledalite.com WD_susp_wall_LED-12 0313