Thermal Overload Relays Thermal Overload Relays The thermal overload relay is a thermal-type overload-protection relay that takes advantage of the heating-bimetal-results-in-bending property. Mounted on appropriate contactors, they provide overload protection and phase-loss protection in order to prevent motors from burning out. On a standalone basis, they can also be used as a over-current relay. Kasuga thermal overload relays includes models with 3 thermal elements, and models featuring Phase-Loss HRD 010 D Protection (2E), for your various motor-protecting needs. HRD 018 D Structure and Characteristics Terminal on the power side Current adjustment dial ・Overload protection can be ensured by just adjusting this to the rated current of the motor. It is possible to adjust it within plus or minus 20%, and it is set in the middle before shipment. Trip indication lever ・This lever falls right and disappears when tripped. Or if you push down this lever down to the right with a small screw driver, you can intentionally break and check the circuit. Terminal on the load side ・The HRE75 type and with lower numbers are terminals with a wire-press. It is possible to just insert the wire for connection without a crimp contact. Reset button ・This will reset and make ready for operation again. Control circuit terminal ・This contact sets apart the electromagnetic contactors when tripped, or gives warnings. Automatic/Manual switch tab ・The automatic reset and manual reset can be selected with this tab. When it is set to the automatic restoration mode, the bimetal will cool off after tripped and bend back, and automatically reset. It is in the manual reset position before shipment. Mounting bracket ・We have special brackets available in case the electromagnetic switch is assembled with electromagnetic contactors. *This is a photo of the HRE 35 DG. The structure and characteristics vary depending on the model. Selection map Standalone Type Mount Type Standard Type 2Thermal Elements 3Thermal Elements Phase-Loss Protection (2E) Featured 2Thermal Elements 3Thermal Elements Phase-Loss Protection (2E) Featured HRD010 HRD010B − − HRD010D − − HRD018 HRD018B HRD018BF − HRD018D HRD018DF − 2A 0.5A 0.5A 0.3A Manual 1.2VA MUD5 MUF7 MUF10-4 MUF10-5 HMUF10 MUK12 Auxiliary Contact Open-Circuit Thermal Current Rated Operational 110V Current (AC-15) 220V 440V Resetting Power Consumption (per thermal element) Corresponding Contactors to Mount [ ]Models in square brackets : Applicable in combination with CT 4A 3A 2A 1A Manual 1.2VA MUF18 HMU18 MUF20 [MUF300] [MUF400] 7 to 10 to 12 to 18 to 24 to 9 12 15 22 30 to 11* to 14* to 18* to 26 to 36 4A 3A 2A 1A Automatic-Manual 3.2VA MUF25 MUF35 HRE150 − − − HRE150DG HRE150DF HRE150DE HRE180 − − − HRE180DG HRE180DF HRE180DE 12 to 15 to 18* 18 to 22 to 26* 24 to 30 to 36* 34 to 42 to 50 45 to 56 to 67 54 to 67 to 80 34 to 42 to 50* 45 to 56 to 67* 54 to 67 to 80* 65 to 80 to 95 90 to 110 to 130 65 to 80 to 95* 90 to 110 to 130* 105 to 130 to 155 125 to 155 to 185 4A 3A 2A 1A Automatic-Manual 4.2VA MUF50 MUF65 MUE80 4A 3A 2A 1A Automatic-Manual 4.8VA MUE100 MUE125 4A 3A 2A 1A Automatic-Manual 5.5VA MUE150 MUE180 Auxiliary Contact Units・ Applications Safety Covers 0.24 to 0.32 to 0.4* 0.24 to 0.32 to 0.4* 0.5 to 0.6 to 0.7 0.5 to 0.6 to 0.7 1.0 to 1.2 to 1.4 1 to 1.2 to 1.4 1.4 to 1.7 to 2* 1.4 to 1.7 to 2* 1.7 to 2.2 to 2.7 1.7 to 2.2 to 2.7 2.4 to 3 to 3.6* 2.4 to 3 to 3.6* 2.9 to 3.6 to 4.3 2.9 to 3.6 to 4.3 4 to 5 to 6 4 to 5 to 6 5.4 to 6.7 to 8 5.4 to 6.7 to 8 7 to 9 to 11 7 to 9 to 11 10 to 12 to 14 10 to 12 to 14 12 to 15 to 18 16 to 20 to 24* HRE75 − − − HRE75DG HRE75DF HRE75DE Industrial Relays Adjustable Current Range (Rated) Minimum−Median−Maximum *Production on Order HRE35 − − − HRE35DG HRE35DF HRE35DE Star Delta Automatic Starters Frame Reversible Electromagnetic Switches/ Contactors・ Electromagnetic Switches with ON-OFF Push-buttons・ Electromagnetic Swithes with Special Enclosures ・The mount type has a terminal plate that can be directly installed onto electromagnetic contactors. The standalone type has the dedicated connection band that makes for easy connection to the electromagnetic contactors. Line-up Electromagnetic Electromagnetic Thermal Overload Switches Contactors Relays Thermal Overload Relays 30 Thermal Overload Relays Line-up Electromagnetic Electromagnetic Thermal Overload Switches Contactors Relays Thermal Overload Relays (2 elements) Mounting Direct mount type Rated current center value(A) Reversible Electromagnetic Switches/ Contactors・ Electromagnetic Switches with ON-OFF Push-buttons・ Electromagnetic Swithes with Special Enclosures 0.6 1.2 1.7 2.2 3 3.6 5 6.7 9 12 1.2 1.7 2.2 3 3.6 5 6.7 9 12 15 Type name HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD HRD 010 010 010 010 010 010 010 010 010 010 018 018 018 018 018 018 018 018 018 018 B B B B B B B B B B B B B B B B B B B B 0006 0012 0017 0022 0030 0036 0050 0067 0090 0120 0012 0017 0022 0030 0036 0050 0067 0090 0120 0150 General mass (kg) 0.07 0.11 Independent type Rated current center value(A) 0.6 - 12 1.2 - 15 9 12 15 22 30 15 22 30 42 56 67 42 56 67 80 110 80 110 130 155 Type name HRD 010 HRD 018 HRE 35 HRE 35 HRE 35 HRE 35 HRE 35 HRE 75 HRE 75 HRE 75 HRE 75 HRE 75 HRE 75 HRE 150 HRE 150 HRE 150 HRE 150 HRE 150 HRE 180 HRE 180 HRE 180 HRE 180 D D DG DG DG DG DG DG DG DG DG DG DG DG DG DG DG DG DG DG DG DG □ □ 0090 0120 0150 0220 0300 0150 0220 0300 0420 0560 0670 0420 0560 0670 0800 1100 0800 1100 1300 1550 General mass (kg) 0.12 0.18 0.17 0.33 0.55 0.76 Remarks : 1. Put the rated capacity symbol in the square of the type name column. 2. Output contacts are 1c for HRD and HRE series and 1NO+1NC for HRG series. Star Delta Automatic Starters HRD 010 B HRE 35 DG HRE 150 DG Thermal Overload Relays (3 elements with open phase protector (2E)) 3 elements Industrial Relays Auxiliary Contact Units・ Applications Safety Covers 31 Mounting Mounting Direct mount type Independent type Rated current center value(A) With open phase protector (2E) Type name General mass (kg) Mounting Direct mount type 1.2 - 15 HRD 018 BF □ 0.11 1.2 - 15 9 - 30 15 - 67 42 - 110 80 - 155 HRD 018 HRE 35 HRE 75 HRE 150 HRE 180 0.18 0.17 0.33 0.55 0.76 DF DF DF DF DF □ □ □ □ □ Independent type Remarks : 1. Put the rated capacity symbol in the square of the type name column. 2. Output contacts are 1c for HRD and HRE series and 1NO+1NC for HRG series. Rated current center value(A) Type name − − 9 - 30 15 - 67 42 - 110 80 - 155 HRE HRE HRE HRE General mass (kg) − 35 75 150 180 DE DE DE DE □ □ □ □ 0.17 0.33 0.55 0.76 Thermal Overload Relays Accessories Thermal Overload Relays HRD 010B HRD 018B HRD 018D Mounting bracket − HREK 10 A HREK 10 B HRDK 10 C HREK 18 A HRDK 18 B HREK 20 A − Applicable electromagnetic contactor Thermal Overload Relays MUD 5 MUF 7, 10-4, 10-5 HMUF 10 MUK 12 MUF 18 HMU 18 MUF 20 MUF 300, 400 HRF 18 D HRE 35 D HRE 75 D HRE 150 D HRE 180 D Mounting bracket − HREK 35 HREK 75 A HREK 75 B HREK 150 HREK 180 HREK 180 Connecting band − HREJ 35 HREJ 50 HREJ 80 HREJ 100 HREJ 180 HREJ 180 Applicable electromagnetic contactor MUF 300, 400 MUF 25, 35 MUF 50, 65 MUE 80 MUE 100 MUE 125, 150 MUE 180 Remark : Contact us for fitting and connecting band. Application and selection to motor protection Frame HRD010 HRD018 HRE35 HRE75 HRE150 HRE180 HRD018 (With CT) The performance characteristics of the thermal relay comply with the Electrical Appliance and Material Safety Law. ● Cold start: This applies to the time when the motor starts under the condition that the thermal relay receives an overload current when it is not under the influence of current-oriented heat. ● Hot start: This applies to the time when the motor starts or restarts under the condition that the thermal relay receives an overload current when the rated current runs with a constant temperature rise. Auxiliary Contact Units・ Applications Safety Covers ● Ones with an applicable motor capacity indicated must comply with the below when the ambient temperature is 40˚C plus or minus 2˚C. (1)When the electric current equivalent to 500% of the rated current of the over-current trip equipment runs, it must open circuit in more than 3 seconds and less than 45 seconds. (2)After the electric current equivalent to the rated current of the over-current trip equipment flows until the temperature rise in each part are almost constant, and when the electric current equivalent to 200% of the rated current of the over-current trip equipment is run, it must open circuit in less than 4 minutes. (3)After the electric current equivalent to the rated current of the over-current trip equipment flows until the temperature rise in each part are almost constant, and when the electric current equivalent to 125% of the rated current of the over-current trip equipment is run, it must open circuit in less than 60 minutes. Industrial Relays Performance Characteristics Star Delta Automatic Starters Rated current Adjusting range(A) Heat name 0.5 to 0.6 to 0.7 0006 1 to 1.2 to 1.4 0012 1.4 to 1.7 to 2 0017 1.7 to 2.2 to 2.7 0022 2.4 to 3 to 3.6 0030 2.9 to 3.6 to 4.3 0036 4 to 5 to 6 0050 5.4 to 6.7 to 8 0067 7 to 9 to 11 0090 10 to 12 to 14 0120 12 to 15 to 18 0150 18 to 22 to 26 0220 24 to 30 to 36 0300 34 to 42 to 50 0420 45 to 56 to 67 0560 54 to 67 to 80 0670 65 to 80 to 95 0800 90 to 110 to 130 1100 105 to 130 to 155 1300 125 to 155 to 185 1550 2.25 to 3 to 3.75 003T (CT400/5) 3 to 4 to 5 004T (CT400/5) Reversible Electromagnetic Switches/ Contactors・ Electromagnetic Switches with ON-OFF Push-buttons・ Electromagnetic Swithes with Special Enclosures Applicable motor capacity(kW) 3φ 220V 3φ 440V 1φ 110V 1φ 220V 0.1 0.2 − − 0.2 0.4 − − − 0.75 − − 0.4 − − − − − − − 0.75 1.5 − − 1.1 2.2 0.2 0.4 − − 1.5 3.7 0.4 0.75 2.2 − − − 2.7 5.5 0.75 1.5 3.7 7.5 1.1 − 5.5 11 1.5 − 7.5 15 − − 11 22 − − 15 30 − − 19 37 − − 22 45 − − 30 55 − − 37 75 − − 45 90 − − 55 110 − − 75 150 − − 90 180 − − 110 200 Line-up Electromagnetic Electromagnetic Thermal Overload Switches Contactors Relays Thermal Overload Relays 32 Thermal Overload Relays Line-up Electromagnetic Electromagnetic Thermal Overload Switches Contactors Relays Thermal Overload Relays Dimensions (Unit : mm) HRD 010 ● HRD010B(Direct type) Reversible Electromagnetic Switches/ Contactors・ Electromagnetic Switches with ON-OFF Push-buttons・ Electromagnetic Swithes with Special Enclosures HRD010D(Independent type) IEC 35mm IEC Rail Main Terminal Conditions) (Main Terminal Position) Auxiliary Terminal (Main Terminal Position) Hole Pitches (In Case with a 7.5mmHeight Rail Mounted) Main Terminal (Main Terminal Position) Conditions) General mass:0.07kg General mass:0.12kg HRD 018 ● HRD018B(Direct type) ● HRD018D(Independent type) Terminal Conditions) 31 32 31 Auxiliary Terminal Terminal Conditions) (Main Terminal Position) 33 32 33 (Main Terminal Position) Star Delta Automatic Starters Industrial Relays Auxiliary Contact Units・ Applications Safety Covers 33 ● Hole Pitches (Main Terminal Position) General mass:0.11kg General mass:0.18kg HRE 35 ● HRE35D□ (Manual Reset) (Automatic Reset) (Main Terminal Position) Main Terminal Auxiliary Terminal (Main Terminal Position) Hole Pitches General mass:0.17kg Thermal Overload Relays HRE 75 ● HRE75D□ (Manual Reset) (Automatic Reset) (Main Terminal Position) Main Terminal Auxiliary Terminal (Main Terminal Position) Hole Pitches General mass:0.33kg Reversible Electromagnetic Switches/ Contactors・ Electromagnetic Switches with ON-OFF Push-buttons・ Electromagnetic Swithes with Special Enclosures HRE 150 ● HRE150D□ (Main Terminal Position) (Manual Reset) (Automatic Reset) Hole Pitches Auxiliary Terminal (Main Terminal Position) General mass:0.55kg Industrial Relays HRE 180 ● Star Delta Automatic Starters Main Terminal Line-up Electromagnetic Electromagnetic Thermal Overload Switches Contactors Relays Thermal Overload Relays HRE180D□ (Manual Reset) Terminal (Automatic Reset) Position) Auxiliary Terminal Hole Pitches Main Terminal M1 (Load Position) (Main Terminal Position) General mass:0.76kg Auxiliary Contact Units・ Applications Safety Covers (Main Terminal Position) 34 Thermal Overload Relays Line-up Electromagnetic Electromagnetic Thermal Overload Switches Contactors Relays Reversible Electromagnetic Switches/ Contactors・ Electromagnetic Switches with ON-OFF Push-buttons・ Electromagnetic Swithes with Special Enclosures Star Delta Automatic Starters Industrial Relays Auxiliary Contact Units・ Applications Safety Covers 35 Thermal Overload Relays Internal connection diagram HRD 010 With 2 Thermal Elements (Standard) Notes : 1. This model cannot obtain With 3 Thermal Elements and Phase-Loss Protection. 2. Automatic reset system is not featured in this model. 3. Terminal 8 is not included as standard. HRD 018 With 2 Thermal Elements (Standard) Notes : 1. This model cannot obtain Phase-Loss Protection. 2. Automatic reset system is not featured in this model. 3. Terminal 8 is not included as standard. With 3 Thermal Elements HRE 35, HRE75, HRE150, HRE180 With 2 Thermal Elements (Standard) With 3 Thermal Elements, Phase-Loss Protection Featured