Influence of ambient temperature

advertisement
Complementary
technical information
Influence of ambient
temperature
,QÀXHQFHRIWHPSHUDWXUHRQWKHRSHUDWLRQ
Devices
DPN, C60H-DC, C60, C120, NG125,
C60PV-DC circuit breakers
iK60 circuit breakers
iC60a/N/H/L circuit breakers
Circuit breakers
With Vigi (AC)
With Vigi (A, SI)
5HÀH[L&
C60H RCBO, C60H2 RCBO
C60NA-DC, SW60PV-DC, C120NA-DC
switch-disconnectors
iID K residual current circuit breakers
iID residual current AC
circuit breakers
A, SI
Switches
iSW
iSW-NA
Protection auxiliaries
RCA, ARA control auxiliaries
iCT contactors
iTL impulse relays
iCT, iTL auxiliaries
Linergy DX
Linergy FM
Characteristics
LQÀXHQFHGE\
temperature
Temperature
Min.
Max.
Tripping on overload
-30°C
+70°C
Tripping on overload
Tripping on overload
Tripping on overload
-25°C
-35°C
-5°C
-25°C
-25°C
-15°C
-25°C
+60°C
+70°C
+60°C
+60°C
+60°C
+60°C
+70°C
-5°C
-5°C
-25°C
-20°C
-35°C
-35°C
-25°C
-5°C
-20°C
-20°C
-25°C
-25°C
+60°C
+60°C
+60°C
+50°C
+70°C
+70°C
+60°C
+60°C
+50°C
+50°C
+60°C
+60°C
Tripping on overload
Tripping on overload
Maximum operating current
Maximum operating current
Maximum operating current
Maximum operating current
None
None
Installation conditions
None
None
Maximum operating current
Maximum operating current
Note: the temperature considered is the temperature viewed through the device.
Circuit breakers
High temperatures
b A rise in temperature causes lowering of the thermal threshold
(tripping on overload).
b Protection is still ensured: the tripping threshold remains lower than the current
acceptable by the cable (Iz)
b To prevent nuisance tripping, it should be checked that this threshold remains
higher than the maximum operating current (IBRIWKHFLUFXLWGH¿QHGE\
v the rated load currents,
v WKHFRHI¿FLHQWVRIH[SDQVLRQDQGVLPXOWDQHLW\RIXVH
,IWKHWHPSHUDWXUHLVVXI¿FLHQWO\KLJKIRUWKHWULSSLQJWKUHVKROGWREHFRPHORZHUWKDQ
the operating current IB, switchboard ventilation should be provided for.
Low temperatures
b A fall in temperature increases the thermal tripping threshold of the circuit breaker.
b There is no risk of nuisance tripping: the threshold remains higher than the
maximum operating current of the circuit (IB) demanded by the loads.
b It should be checked that the cable remains suitably protected, i.e. that its
acceptable current (Iz) is higher than the values shown in the following tables
(in amperes).
When the ambient temperature could vary within a broad range, both these aspects
must be taken into account:
b the difference between the maximum operating current of the circuit (IB) and the
tripping threshold of the circuit breaker for the minimum ambient temperature,
b the difference between the strength of the cable (IZ) and the maximum tripping
threshold of the circuit breaker for the maximum ambient temperature.
462
Version : 2.7
25/09/2013
CA908007E
Complementary
technical information
Influence of ambient
temperature (cont.)
Maximum permissible current
b 7KHPD[LPXPFXUUHQWDOORZHGWRÀRZWKURXJKWKHGHYLFHGHSHQGVRQWKHDPELHQW
temperature in which it is placed.
b The ambient temperature is the temperature inside the enclosure or switchboard
in which the devices are installed.
b The reference temperature is in a halftone colour for the different devices.
b When several devices operating simultaneously are mounted side by side in a
small enclosure, a temperature rise in the enclosure results in a reduction in the
RSHUDWLQJFXUUHQW$UHGXFWLRQFRHI¿FLHQWRIZLOOWKHQKDYHWREHDVVLJQHGWRWKH
rating (already derated, if applicable, depending on the ambient temperature).
b Example:
Depending on the ambient temperature and the method of installation, the table
below shows how to determine, for an iC60, the operating currents not to be
exceeded for ratings 25 A, 32 A and 40 A (reference temperature 50°C).
Operating current not to be exceeded (A)
Installation
iC60 alone
conditions (IEC
60947-2)
CA908007E
Ambient
temperature (°C)
35°C
Type Nominal
rating (A)
Actual rating (A)
iC60
26.35
34
42.5
25
32
40
Version : 2.7
50°C
Several iC60 in the same enclosure
FDOFXODWHZLWKWKHUHGXFWLRQFRHI¿FLHQW
indicated below)
25
32
40
65°C
23.57
29.9
37.34
25/09/2013
35°C
50°C
65°C
26.35 x 0.8 = 21 25 x 0.8 = 20
23.57 x 0.8 = 19
34 x 0.8 = 27
32 x 0.8 = 25.6 29.9 x 0.8 = 24
42.5 x 0.8 = 34 40 x 0.8 = 32
37.34 x 0.8 = 30
463
Complementary
technical information
Influence of ambient
temperature (cont.)
Household (IEC 60898-1)
DPN derating table (IEC 60898-1)
DPN
Rating
1A
2A
3A
4A
6A
10 A
10 A
13 A
13 A
16 A
16 A
20 A
20 A
25 A
32 A
40 A
Ambient temperature (°C)
Curve
-30
B, C, D 1.55
B, C, D 2.51
B, C, D 3.8
B, C, D 4.97
B, C, D 7.13
B
11.9
C, D
12.3
B
15.6
C, D
15.7
B, C
19
D
19.1
B
23.7
C, D
23.9
B, C, D 29.6
B, C, D 38.3
B, C, D 48.3
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
1.51
2.47
3.74
4.9
7.04
11.7
12.1
15.4
15.5
18.8
18.9
23.4
23.6
29.2
37.8
47.7
1.47
2.43
3.68
4.82
6.95
11.6
12
15.2
15.3
18.5
18.6
23.1
23.3
28.8
37.3
47
1.43
2.39
3.62
4.75
6.86
11.4
11.8
15
15.1
18.3
18.4
22.8
23
28.5
36.8
46.4
1.39
2.35
3.55
4.67
6.77
11.3
11.6
14.8
14.9
18.1
18.1
22.5
22.7
28.1
36.3
45.7
1.35
2.31
3.49
4.59
6.68
11.1
11.4
14.6
14.6
17.8
17.9
22.2
22.4
27.8
35.8
45
1.3
2.27
3.42
4.51
6.59
11
11.2
14.4
14.4
17.6
17.6
21.9
22
27.4
35.3
44.3
1.26
2.23
3.36
4.43
6.49
10.8
11
14.1
14.2
17.3
17.4
21.6
21.7
27
34.7
43.7
1.21
2.18
3.29
4.35
6.4
10.7
10.8
13.9
14
17.1
17.1
21.3
21.4
26.6
34.2
43
1.16
2.14
3.22
4.26
6.3
10.5
10.6
13.7
13.7
16.8
16.8
21
21
26.2
33.7
42.2
1.11
2.09
3.15
4.18
6.2
10.3
10.4
13.5
13.5
16.5
16.6
20.7
20.7
25.8
33.1
41.5
1.06
2.05
3.07
4.09
6.1
10.2
10.2
13.2
13.3
16.3
16.3
20.3
20.4
25.4
32.6
40.8
1
2
3
4
6
10
10
13
13
16
16
20
20
25
32
40
0.94
1.95
2.92
3.91
5.9
9.8
9.8
12.8
12.8
15.7
15.7
19.7
19.6
24.6
31.4
39.2
0.88
1.9
2.85
3.81
5.79
9.7
9.6
12.5
12.5
15.4
15.4
19.3
19.3
24.2
30.8
38.4
0.81
1.85
2.76
3.72
5.68
9.5
9.3
12.3
12.2
15.2
15.1
19
18.9
23.7
30.2
37.6
0.73
1.8
2.68
3.62
5.57
9.3
9.1
12
12
14.9
14.8
18.6
18.5
23.3
29.6
36.8
0.65
1.74
2.6
3.52
5.46
9.1
8.9
11.8
11.7
14.6
14.5
18.3
18.1
22.8
29
36
0.55
1.69
2.51
3.41
5.35
8.9
8.6
11.5
11.4
14.3
14.2
17.9
17.7
22.4
28.4
35.1
0.43
1.63
2.42
3.3
5.23
8.7
8.4
11.2
11.1
14
13.9
17.5
17.3
21.9
27.7
34.2
0.27
1.57
2.32
3.19
5.11
8.5
8.1
11
10.8
13.6
13.5
17.1
16.9
21.4
27
33.3
iK60 derating table. B curve (IEC 60898-1)
iK60
Ambient temperature (°C)
Rating -25
1A
2A
3A
4A
6A
10 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
1.19
2.45
3.69
4.92
7.44
11.9
19
23.5
29.1
37.9
47.4
59.9
76.4
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
1.17
2.41
3.63
4.84
7.32
11.8
18.7
23.2
28.8
37.4
46.7
59.1
75.3
1.15
2.37
3.57
4.77
7.2
11.6
18.5
22.9
28.4
36.9
46.1
58.2
74.1
1.14
2.34
3.51
4.69
7.07
11.4
18.2
22.6
28
36.4
45.5
57.4
73
1.12
2.3
3.45
4.61
6.95
11.3
18
22.3
27.7
35.9
44.8
56.5
71.8
1.11
2.26
3.39
4.53
6.82
11.1
17.7
22
27.3
35.3
44.2
55.6
70.6
1.09
2.22
3.33
4.44
6.69
10.9
17.4
21.7
26.9
34.8
43.5
54.7
69.4
1.07
2.17
3.27
4.36
6.56
10.8
17.1
21.4
26.6
34.3
42.8
53.8
68.2
1.05
2.13
3.2
4.27
6.42
10.6
16.9
21
26.2
33.7
42.1
52.9
66.9
1.04
2.09
3.14
4.18
6.29
10.4
16.6
20.7
25.8
33.2
41.4
52
65.6
1.02
2.04
3.07
4.09
6.14
10.2
16.3
20.4
25.4
32.6
40.7
51
64.3
1
2
3
4
6
10
16
20
25
32
40
50
63
0.98
1.95
2.93
3.91
5.85
9.8
15.7
19.7
24.6
31.4
39.3
49
61.6
0.96
1.91
2.86
3.81
5.7
9.6
15.4
19.3
24.2
30.8
38.5
48
60.3
0.94
1.86
2.78
3.71
5.54
9.4
15.1
18.9
23.8
30.2
37.7
46.9
58.8
0.92
1.81
2.71
3.61
5.38
9.2
14.8
18.6
23.3
29.6
37
45.9
57.4
0.9
1.76
2.63
3.5
5.22
9
14.5
18.2
22.9
28.9
36.2
44.8
55.9
0.88
1.71
2.55
3.39
5.04
8.8
14.1
17.8
22.5
28.3
35.3
43.6
54.3
iK60 derating table. C curve (IEC 60898-1)
iK60
Ambient temperature (°C)
Rating -25
1A
2A
3A
4A
6A
10 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
464
1.2
2.4
3.7
4.9
7.4
12.4
19.4
24
30
38.8
47.4
59.9
76.4
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
1.2
2.4
3.6
4.8
7.3
12.2
19.1
23.6
29.5
38.2
46.7
59.1
75.3
1.2
2.4
3.6
4.8
7.2
12
18.8
23.3
29.1
37.7
46.1
58.2
74.1
1.1
2.3
3.5
4.7
7.1
11.8
18.5
23
28.7
37.1
45.5
57.4
73
1.1
2.3
3.5
4.6
6.9
11.6
18.2
22.6
28.3
36.5
44.8
56.5
71.8
1.1
2.3
3.4
4.5
6.8
11.4
17.9
22.3
27.8
35.9
44.2
55.6
70.6
1.1
2.2
3.3
4.4
6.7
11.2
17.6
21.9
27.4
35.3
43.5
54.7
69.4
1.1
2.2
3.3
4.4
6.6
10.9
17.3
21.5
26.9
34.6
42.8
53.8
68.2
1.1
2.1
3.2
4.3
6.4
10.7
17
21.2
26.4
34
42.1
52.9
66.9
1
2.1
3.1
4.2
6.3
10.5
16.7
20.8
26
33.3
41.4
51.9
65.6
1
2
3.1
4.1
6.1
10.2
16.3
20.4
25.5
32.7
40.7
51
64.3
1
2
3
4
6
10
16
20
25
32
40
50
63
0.98
1.95
2.93
3.91
5.85
9.8
15.7
19.6
24.5
31.3
39.3
49
61.6
0.96
1.91
2.86
3.81
5.7
9.5
15.3
19.2
24
30.6
38.5
48
60.3
0.94
1.86
2.78
3.71
5.54
9.2
14.9
18.8
23.5
29.9
37.7
46.9
58.8
0.92
1.81
2.71
3.61
5.38
9
14.6
18.3
22.9
29.1
37
45.9
57.4
0.9
1.76
2.63
3.5
5.22
8.7
14.2
17.9
22.4
28.4
36.2
44.8
55.9
0.88
1.71
2.55
3.39
5.04
8.4
13.8
17.5
21.8
27.6
35.3
43.6
54.3
Version : 2.7
25/09/2013
CA908007E
Complementary
technical information
Influence of ambient
temperature (cont.)
Household (IEC 60898-1) (cont.)
iC60 derating table (IEC 60898-1)
iC60
Ambient temperature (°C)
Rating
-35
-30
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
0.61
1.22
2.52
3.8
5.07
7.67
12.3
15.8
19.5
24.1
29.8
38.9
48.6
61.6
78.6
0.6
1.2
2.49
3.74
5
7.55
12.1
15.6
19.2
23.8
29.4
38.4
48
60.7
77.5
0.59
1.19
2.45
3.69
4.92
7.44
11.9
15.4
19
23.5
29.1
37.9
47.4
59.9
76.4
0.59
1.17
2.41
3.63
4.84
7.32
11.8
15.2
18.7
23.2
28.8
37.4
46.7
59.1
75.3
0.58
1.15
2.37
3.57
4.77
7.2
11.6
15
18.5
22.9
28.4
36.9
46.1
58.2
74.1
0.57
1.14
2.34
3.51
4.69
7.07
11.4
14.8
18.2
22.6
28
36.4
45.5
57.4
73
0.56
1.12
2.3
3.45
4.61
6.95
11.3
14.6
18
22.3
27.7
35.9
44.8
56.5
71.8
0.55
1.11
2.26
3.39
4.53
6.82
11.1
14.4
17.7
22
27.3
35.3
44.2
55.6
70.6
0.54
1.09
2.22
3.33
4.44
6.69
10.9
14.1
17.4
21.7
26.9
34.8
43.5
54.7
69.4
0.54
1.07
2.17
3.27
4.36
6.56
10.8
13.9
17.1
21.4
26.6
34.3
42.8
53.8
68.2
0.53
1.05
2.13
3.2
4.27
6.42
10.6
13.7
16.9
21
26.2
33.7
42.1
52.9
66.9
0.52
1.04
2.09
3.14
4.18
6.29
10.4
13.5
16.6
20.7
25.8
33.2
41.4
52
65.6
0.51
1.02
2.04
3.07
4.09
6.14
10.2
13.2
16.3
20.4
25.4
32.6
40.7
51
64.3
0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63
0.49
0.98
1.95
2.93
3.91
5.85
9.8
12.8
15.7
19.7
24.6
31.4
39.3
49
61.6
0.48
0.96
1.91
2.86
3.81
5.7
9.6
12.5
15.4
19.3
24.2
30.8
38.5
48
60.3
0.47
0.94
1.86
2.78
3.71
5.54
9.4
12.3
15.1
18.9
23.8
30.2
37.7
46.9
58.8
0.46
0.92
1.81
2.71
3.61
5.38
9.2
12
14.8
18.6
23.3
29.6
37
45.9
57.4
0.45
0.9
1.76
2.63
3.5
5.22
9
11.8
14.5
18.2
22.9
28.9
36.2
44.8
55.9
0.44
0.88
1.71
2.55
3.39
5.04
8.8
11.5
14.1
17.8
22.5
28.3
35.3
43.6
54.3
0.43
0.86
1.65
2.47
3.28
4.87
8.5
11.2
13.8
17.4
22
27.6
34.5
42.5
52.8
0.42
0.84
1.59
2.38
3.17
4.68
8.3
10.9
13.4
17
21.5
26.9
33.6
41.3
51.1
0.5 A
1A
2A
3A
4A
6A
10 A
13 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
C60 derating table (IEC 60898-1)
C60
Ambient temperature (°C)
Rating
-30
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
0.65
0.98
1.2
2.36
3.53
4.59
8.68
10.18
12.1
15.7
18.6
24.4
30
40.7
51.1
58.5
64.2
82.3
0.64
0.96
1.19
2.33
3.49
4.54
8.49
10.01
11.96
15.5
18.4
24.1
29.6
39.8
50.1
57.4
63
80.7
0.63
0.94
1.17
2.3
3.44
4.5
8.29
9.85
11.8
15.3
18.2
23.7
29.2
39.2
49.2
56.4
61.9
79.2
0.62
0.92
1.16
2.27
3.4
4.45
8.09
9.68
11.6
15.1
18
23.4
28.8
38.5
48.4
55.3
60.8
77.8
0.6
0.9
1.14
2.24
3.36
4.4
7.89
9.51
11.5
14.9
17.8
23
28.4
37.9
47.5
54.3
59.7
76.3
0.59
0.89
1.12
2.22
3.32
4.35
7.68
9.33
11.3
14.6
17.6
22.7
28
37.2
46.7
53.2
58.6
74.7
0.58
0.87
1.11
2.19
3.27
4.3
7.46
9.15
11.1
14.4
17.4
22.3
27.6
36.5
45.8
52.1
57.4
73.2
0.57
0.85
1.09
2.16
3.23
4.26
7.24
8.97
10.9
14.2
17.1
22
27.2
35.8
44.9
51
56.3
71.6
0.55
0.83
1.07
2.13
3.19
4.21
7.01
8.79
10.8
14
16.9
21.6
26.8
35.1
43.9
49.9
55.1
69.9
0.54
0.81
1.05
2.1
3.14
4.15
6.77
8.6
10.6
13.7
16.7
21.2
26.3
34.3
43
48.7
53.8
68.3
0.53
0.79
1.04
2.06
3.09
4.10
6.52
8.4
10.4
13.5
16.5
20.8
25.9
33.6
42
47.5
52.6
66.6
0.51
0.77
1.02
2.03
3.05
4.05
6.27
8.2
10.2
13.2
16.2
20.4
25.5
32.8
41
46.3
51.3
64.8
0.5
0.75
1
2
3
4
6
8
10
13
16
20
25
32
40
45
50
63
0.49
0.73
0.98
1.97
2.95
3.95
5.72
7.79
9.8
12.7
15.8
19.6
24.5
31.2
39
43.7
48.7
61.1
0.47
0.71
0.96
1.93
2.9
3.89
5.43
7.58
9.6
12.5
15.5
19.2
24.1
30.4
37.9
42.4
47.3
59.2
0.45
0.68
0.94
1.9
2.85
3.84
5.12
7.36
9.4
12.2
15.3
18.7
23.6
29.5
36.8
41
45.8
57.2
0.44
0.66
0.92
1.87
2.8
3.78
4.79
7.13
9.2
12
15
18.3
23.1
28.6
35.6
39.6
44.4
55.2
0.42
0.63
0.9
1.83
2.75
3.73
4.43
6.89
9
11.7
14.8
17.8
22.6
27.7
34.5
38.1
42.8
53.1
0.4
0.61
0.88
1.79
2.7
3.67
4.05
6.65
8.8
11.4
14.5
17.4
22.1
26.8
33.2
36.5
41.3
50.8
0.38
0.59
0.86
1.76
2.64
3.61
3.62
6.4
8.5
11.1
14.2
16.9
21.6
25.6
31.8
35
39.5
48.7
0.36
0.57
0.84
1.72
2.59
3.55
3.13
6.13
8.3
10.8
14
16.4
21
24.6
30.5
33.5
37.9
46.6
0.5 A
0.75 A
1A
2A
3A
4A
6A
8A
10 A
13 A
16 A
20 A
25 A
32 A
40 A
45 A
50 A
63 A
C120 derating table (IEC 60898-1)
C120 Ambient temperature (°C)
Rating -30
10 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
80 A
100 A
125 A
12.9
19.4
24.6
30.9
38.9
49.8
62.2
78.6
98.4
124.5
157
CA908007E
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30 +35
+40
+45
+50
+55
+60
+65
+70
12.7
19.1
24.2
30.5
38.4
49.1
61.3
77.5
97
122.6
154.6
12.5
18.8
23.9
30
37.9
48.3
60.4
76.3
95.6
120.7
152.2
12.2
18.6
23.5
29.5
37.3
47.6
59.4
75
94.2
118.8
149.7
12
18.3
23.2
29.1
36.8
46.8
58.4
73.8
92.7
116.9
147.1
11.8
18
22.8
28.6
36.2
46
57.5
72.5
91.2
114.9
144.6
11.5
17.8
22.4
28.1
35.6
45.2
56.5
71.3
89.7
112.9
141.9
11.3
17.5
22
27.6
35
44.4
55.4
69.9
88.1
110.9
139.2
11
17.2
21.6
27.1
34.5
43.5
54.4
68.6
86.6
108.8
136.5
10.8
16.9
21.2
26.6
33.9
42.7
53.3
67.3
85
106.6
133.7
10.5
16.6
20.8
26.1
33.3
41.8
52.2
65.9
83.4
104.5
130.9
10.3
16.3
20.4
25.5
32.6
40.9
51.1
64.5
81.7
102.3
128
10
16
20
25
32
40
50
63
80
100
125
9.4
15.4
19.1
23.9
30.7
38.1
47.7
60
76.5
95.3
118.8
9.1
15.1
18.7
23.3
30
37.1
46.4
58.4
74.7
92.9
115.6
8.8
14.7
18.2
22.7
29.3
36.1
45.2
56.8
72.8
90.4
112.3
8.5
14.4
17.7
22.1
28.6
35.1
43.9
55.2
70.9
87.8
108.9
8.2
14
17.3
21.5
27.9
34.1
42.6
53.5
69
85.2
105.4
7.9
13.7
16.8
20.8
27.2
33
41.2
51.7
67
82.5
101.8
7.5
13.3
16.2
20.1
26.4
31.8
39.8
49.9
64.9
79.6
98
Version : 2.7
9.7
15.7
19.6
24.4
31.4
39.1
48.8
61.5
78.3
97.7
122
25/09/2013
465
Complementary
technical information
Influence of ambient
temperature (cont.)
Tertiary/Industry (IEC 60947-2)
DPN derating table (IEC 60947-2)
DPN
Rating
1A
2A
3A
4A
6A
10 A
10 A
13 A
13 A
16 A
16 A
20 A
20 A
25 A
32 A
40 A
Ambient temperature (°C)
Curve
-30
B, C, D 1.69
B, C, D 2.68
B, C, D 4.03
B, C, D 5.26
B, C, D 7.51
B
12.5
C, D
13
B
17
C, D
17.2
B, C
20.6
D
20.8
B
25.7
C, D
26
B, C, D 32
B, C, D 41.6
B, C, D 52.7
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
1.66
2.64
3.97
5.19
7.42
12.3
12.9
16.7
16.9
20.4
20.5
25.3
25.7
31.6
41.1
52
1.62
2.6
3.91
5.12
7.34
12.2
12.7
16.5
16.7
20.1
20.2
25
25.3
31.2
40.5
51.3
1.59
2.56
3.86
5.05
7.25
12.1
12.5
16.3
16.5
19.8
20
24.7
25
30.8
40
50.6
1.55
2.52
3.8
4.98
7.16
11.9
12.3
16.1
16.2
19.6
19.7
24.4
24.6
30.4
39.4
49.8
1.51
2.48
3.74
4.9
7.07
11.8
12.2
15.8
16
19.3
19.4
24
24.3
30
38.9
49.1
1.47
2.44
3.68
4.83
6.98
11.6
12
15.6
15.7
19
19.1
23.7
23.9
29.6
38.3
48.3
1.43
2.4
3.61
4.75
6.89
11.5
11.8
15.4
15.5
18.7
18.8
23.4
23.6
29.2
37.7
47.6
1.39
2.36
3.55
4.67
6.8
11.3
11.6
15.1
15.2
18.5
18.5
23
23.2
28.7
37.1
46.8
1.35
2.32
3.49
4.6
6.7
11.2
11.4
14.9
15
18.2
18.2
22.7
22.8
28.3
36.5
46
1.3
2.28
3.42
4.52
6.61
11
11.2
14.6
14.7
17.9
17.9
22.3
22.4
27.8
35.9
45.2
1.26
2.23
3.36
4.43
6.51
10.8
11
14.4
14.4
17.6
17.6
21.9
22
27.4
35.3
44.4
1.21
2.19
3.29
4.35
6.41
10.7
10.8
14.1
14.2
17.3
17.3
21.6
21.7
26.9
34.7
43.5
1.16
2.14
3.22
4.27
6.31
10.5
10.6
13.8
13.9
17
17
21.2
21.3
26.5
34
42.7
1.11
2.1
3.15
4.18
6.21
10.3
10.4
13.6
13.6
16.7
16.7
20.8
20.8
26
33.4
41.8
1.06
2.05
3.07
4.09
6.11
10.2
10.2
13.3
13.3
16.3
16.3
20.4
20.4
25.5
32.7
40.9
1
2
3
4
6
10
10
13
13
16
16
20
20
25
32
40
0.94
1.95
2.92
3.91
5.89
9.8
9.8
12.7
12.7
15.7
15.7
19.6
19.6
24.5
31.3
39.1
0.88
1.9
2.85
3.81
5.78
9.7
9.6
12.4
12.4
15.3
15.3
19.2
19.1
24
30.6
38.1
0.81
1.85
2.77
3.72
5.67
9.5
9.3
12.1
12.1
15
14.9
18.8
18.7
23.5
29.9
37.1
0.73
1.79
2.68
3.62
5.56
9.3
9.1
11.8
11.7
14.6
14.6
18.3
18.2
22.9
29.1
36.1
L&5HÀH[L&GHUDWLQJWDEOH,(&
iC60
Ambient temperature (°C)
Rating
-35
-30
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
0.66
1.32
2.79
4.21
5.62
8.55
13.3
17.1
21.1
26
31.9
42
52.6
67.1
86.3
0.65
1.3
2.75
4.15
5.54
8.42
13.2
16.9
20.8
25.7
31.6
41.5
51.9
66.3
85.1
0.64
1.28
2.71
4.08
5.46
8.29
13
16.7
20.6
25.4
31.2
41
51.3
65.4
83.9
0.63
1.27
2.67
4.02
5.37
8.16
12.8
16.4
20.3
25
30.8
40.5
50.6
64.5
82.7
0.63
1.25
2.63
3.96
5.29
8.03
12.6
16.2
20
24.7
30.4
39.9
49.9
63.5
81.4
0.62
1.23
2.58
3.89
5.2
7.89
12.5
16
19.7
24.4
30.1
39.4
49.2
62.6
80.1
0.61
1.21
2.54
3.83
5.11
7.75
12.3
15.8
19.5
24.1
29.7
38.8
48.5
61.6
78.9
0.6
1.2
2.5
3.76
5.02
7.61
12.1
15.5
19.2
23.7
29.3
38.2
47.8
60.7
77.6
0.59
1.18
2.45
3.69
4.93
7.46
11.9
15.3
18.9
23.4
28.9
37.7
47.1
59.7
76.2
0.58
1.16
2.4
3.62
4.83
7.31
11.7
15.1
18.6
23
28.5
37.1
46.4
58.7
74.9
0.57
1.14
2.36
3.55
4.74
7.16
11.5
14.8
18.3
22.7
28.1
36.5
45.6
57.7
73.5
0.56
1.12
2.31
3.48
4.64
7.01
11.3
14.6
18
22.3
27.6
35.9
44.9
56.7
72.1
0.55
1.1
2.26
3.4
4.54
6.85
11.1
14.3
17.7
21.9
27.2
35.3
44.1
55.6
70.7
0.54
1.08
2.21
3.32
4.44
6.69
10.9
14.1
17.3
21.6
26.8
34.6
43.3
54.5
69.2
0.53
1.06
2.16
3.25
4.33
6.52
10.7
13.8
17
21.2
26.4
34
42.5
53.4
67.7
0.52
1.04
2.11
3.17
4.22
6.35
10.5
13.6
16.7
20.8
25.9
33.3
41.7
52.3
66.2
0.51
1.02
2.05
3.08
4.11
6.18
10.2
13.3
16.3
20.4
25.5
32.7
40.9
51.2
64.6
0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63
0.49
0.98
1.94
2.91
3.88
5.81
9.8
12.7
15.7
19.6
24.5
31.3
39.1
48.8
61.4
0.48
0.96
1.89
2.82
3.76
5.62
9.5
12.4
15.3
19.2
24.1
30.6
38.2
47.6
59.7
0.47
0.93
1.83
2.73
3.64
5.43
9.3
12.1
14.9
18.7
23.6
29.9
37.3
46.3
57.9
0.45
0.91
1.76
2.64
3.51
5.22
9
11.8
14.5
18.3
23.1
29.1
36.4
45
56.1
0.5 A
1A
2A
3A
4A
6A
10 A
13 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
5HÀH[L&
C60 derating table (IEC 60947-2)
C60
Ambient temperature (°C)
Rating
-30
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
0.68
0.93
1.31
2.55
3.81
4.9
7.93
10.37
13.3
17
20
26.9
32.9
41.5
53.7
60.8
65
85.5
0.67
0.92
1.3
2.59
4.04
4.86
7.82
10.23
13.2
16.9
19.8
26.6
32.5
41.1
52.9
60.1
64.3
84.6
0.66
0.91
1.28
2.56
3.98
4.81
7.71
10.09
13
16.6
19.5
26.2
32.1
40.5
52.2
59.2
63.5
83.3
0.65
0.9
1.27
2.52
3.92
4.76
7.6
9.96
12.8
16.4
19.3
25.8
31.6
40
51.4
58.3
62.6
82
0.64
0.89
1.25
2.49
3.85
4.7
7.49
9.82
12.6
16.2
19.1
25.4
31.1
39.4
50.6
57.4
61.7
80.7
0.63
0.88
1.23
2.45
3.79
4.65
7.38
9.68
12.4
15.9
18.8
25
30.7
38.9
49.8
56.5
60.8
79.4
0.62
0.87
1.21
2.41
3.73
4.59
7.27
9.54
12.2
15.7
18.6
24.6
30.2
38.3
49
55.5
59.9
78
0.61
0.86
1.19
2.37
3.66
4.54
7.15
9.4
12
15.4
18.4
24.2
29.7
37.7
48.2
54.6
59
76.7
0.6
0.85
1.17
2.34
3.59
4.48
7.03
9.25
11.8
15.2
18.1
23.7
29.2
37.1
47.3
53.6
58.1
75.3
0.59
0.83
1.15
2.3
3.52
4.42
6.91
9.11
11.6
14.9
17.9
23.3
28.7
36.5
46.5
52.6
57.1
73.9
0.58
0.82
1.13
2.26
3.45
4.37
6.79
8.96
11.4
14.7
17.6
22.9
28.2
35.9
45.6
51.6
56.2
72.4
0.56
0.81
1.11
2.22
3.38
4.31
6.66
8.81
11.2
14.4
17.3
22.4
27.7
35.3
44.7
50.5
55.2
70.9
0.55
0.8
1.09
2.17
3.31
4.25
6.54
8.65
10.9
14.1
17.1
22
27.2
34.7
43.8
49.5
54.2
69.4
0.54
0.79
1.07
2.13
3.23
4.19
6.41
8.49
10.7
13.9
16.8
21.5
26.7
34
42.9
48.4
53.2
67.9
0.53
0.78
1.05
2.09
3.16
4.13
6.27
8.33
10.5
13.6
16.6
21
26.1
33.4
42
47.3
52.1
66.3
0.51
0.76
1.02
2.04
3.08
4.06
6.14
8.17
10.2
13.3
16.3
20.5
25.6
32.7
41
46.2
51.1
64.7
0.5
0.75
1
2
3
4
6
8
10
13
16
20
25
32
40
45
50
63
0.49
0.74
0.98
1.95
2.92
3.94
5.86
7.83
9.8
12.7
15.7
19.5
24.4
31.3
39
43.8
48.9
61.3
0.47
0.72
0.95
1.91
2.83
3.87
5.71
7.65
9.5
12.4
15.4
18.9
23.8
30.6
37.9
42.6
47.8
59.5
0.46
0.7
0.93
1.88
2.82
3.81
5.56
7.47
9.2
12.1
15.1
18.4
23.2
29.9
36.9
41.4
46.7
57.8
0.44
0.68
0.91
1.84
2.76
3.74
5.42
7.31
9
11.8
14.8
17.9
22.6
29.1
35.8
40.1
45.5
56
0.5 A
0.75 A
1A
2A
3A
4A
6A
8A
10 A
13 A
16 A
20 A
25 A
32 A
40 A
45 A
50 A
63 A
466
Version : 2.7
25/09/2013
CA908007E
Complementary
technical information
Influence of ambient
temperature (cont.)
Tertiary/Industry (IEC 60947-2) (cont.)
C60H-DC derating table (IEC 60947-2)
C60H-DC
Ambient temperature (°C)
Rating
-30
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
0.5 A
1A
2A
3A
4A
5A
6A
10 A
13 A
15 A
16 A
20 A
25 A
30 A
32 A
40 A
50 A
63 A
0.63
1.18
2.54
3.78
5.08
6
7.26
12.6
15.5
18.6
19.4
24.1
30.4
37.4
38.5
48.9
59.9
78.2
0.62
1.17
2.5
3.71
4.99
5.92
7.15
12.4
15.3
18.3
19.1
23.7
29.9
36.7
37.9
48.2
59.1
76.9
0.61
1.15
2.45
3.65
4.9
5.83
7.04
12.2
15.1
18
18.9
23.4
29.5
36.1
37.4
47.4
58.3
75.6
0.6
1.14
2.41
3.58
4.81
5.74
6.94
11.9
14.9
17.7
18.6
23
29
35.5
36.8
46.7
57.4
74.3
0.59
1.12
2.36
3.51
4.71
5.66
6.83
11.7
14.6
17.4
18.3
22.7
28.5
34.9
36.2
45.9
56.5
73
0.58
1.1
2.31
3.45
4.62
5.57
6.71
11.5
14.4
17.1
18
22.3
28.1
34.2
35.7
45.1
55.6
71.7
0.56
1.09
2.26
3.38
4.52
5.48
6.6
11.3
14.2
16.7
17.6
21.9
27.6
33.5
35.1
44.3
54.7
70.3
0.55
1.07
2.21
3.3
4.42
5.39
6.48
11
14
16.4
17.3
21.6
27.1
32.9
34.5
43.5
53.8
68.9
0.54
1.05
2.16
3.23
4.32
5.29
6.37
10.8
13.7
16.1
17
21.2
26.6
32.2
33.9
42.6
52.9
67.5
0.53
1.04
2.11
3.16
4.22
5.2
6.25
10.5
13.5
15.7
16.7
20.8
26.1
31.5
33.3
41.8
52
66
0.51
1.02
2.06
3.08
4.11
5.1
6.12
10.3
13.3
15.4
16.3
20.4
25.5
30.7
32.6
40.9
51
64.5
0.5
1
2
3
4
5
6
10
13
15
16
20
25
30
32
40
50
63
0.49
0.98
1.94
2.92
3.89
4.9
5.87
9.7
12.8
14.6
15.7
19.6
24.5
29.2
31.4
39.1
49
61.4
0.47
0.96
1.88
2.84
3.77
4.8
5.74
9.5
12.5
14.3
15.3
19.2
23.9
28.5
30.7
38.2
48
59.8
0.46
0.94
1.82
2.75
3.65
4.69
5.61
9.2
12.2
13.9
14.9
18.7
23.3
27.7
30
37.2
46.9
58.2
0.44
0.92
1.76
2.66
3.53
4.58
5.47
8.9
12
13.5
14.6
18.3
22.7
26.8
29.3
36.2
45.9
56.5
0.43
0.9
1.7
2.57
3.4
4.47
5.33
8.6
11.7
13
14.2
17.9
22.1
26
28.6
35.2
44.8
54.7
0.41
0.88
1.63
2.48
3.27
4.36
5.19
8.3
11.4
12.6
13.8
17.4
21.5
25.1
27.9
34.2
43.6
52.9
0.39
0.86
1.56
2.38
3.13
4.24
5.04
7.9
11.1
12.2
13.4
16.9
20.9
24.2
27.1
33.1
42.5
51.1
0.38
0.84
1.48
2.27
2.98
4.12
4.89
7.6
10.8
11.7
13
16.4
20.2
23.2
26.3
32
41.3
49.1
0.36
0.82
1.41
2.17
2.83
4
4.73
7.2
10.5
11.2
12.5
15.9
19.6
22.3
25.5
30.8
40.1
47.1
C60PV-DC derating table (IEC 60947-2)
C60PV-DC Ambient temperature (°C)
Rating
1A
2A
3A
5A
8A
10 A
13 A
15 A
16 A
20 A
25 A
-30
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
1.18
2.54
3.78
6
9.64
12.6
15.5
18.6
19.4
24.1
30.4
1.17
2.5
3.71
5.92
9.5
12.4
15.3
18.3
19.1
23.7
29.9
1.15
2.45
3.65
5.83
9.36
12.2
15.1
18
18.9
23.4
29.5
1.14
2.41
3.58
5.74
9.22
11.9
14.8
17.7
18.6
23
29
1.12
2.36
3.51
5.66
9.08
11.7
14.6
17.4
18.3
22.7
28.5
1.1
2.31
3.45
5.57
8.93
11.5
14.4
17.1
18
22.3
28.1
1.09
2.26
3.38
5.48
8.78
11.2
14.2
16.7
17.6
21.9
27.6
1.07
2.21
3.3
5.39
8.63
11
14
16.4
17.3
21.6
27.1
1.05
2.16
3.23
5.29
8.48
10.8
13.7
16.1
17
21.2
26.6
1.04
2.11
3.16
5.2
8.32
10.5
13.5
15.7
16.7
20.8
26.1
1.02
2.06
3.08
5.1
8.16
10.3
13.2
15.4
16.3
20.4
25.5
1
2
3
5
8
10
13
15
16
20
25
0.98
1.94
2.92
4.9
7.83
9.7
12.7
14.6
15.7
19.6
24.5
0.96
1.88
2.84
4.8
7.67
9.4
12.5
14.3
15.3
19.2
23.9
0.94
1.82
2.75
4.69
7.49
9.2
12.2
13.9
14.9
18.7
23.3
0.92
1.76
2.66
4.58
7.31
8.9
12
13.5
14.6
18.3
22.7
0.9
1.7
2.57
4.47
7.13
8.6
11.7
13
14.2
17.9
22.1
0.88
1.63
2.48
4.36
6.95
8.2
11.4
12.6
13.8
17.4
21.5
0.86
1.56
2.38
4.24
6.76
7.9
11.1
12.2
13.4
16.9
20.9
0.84
1.48
2.27
4.12
6.56
7.6
10.8
11.7
13
16.4
20.2
0.82
1.41
2.17
4
6.36
7.2
10.5
11.2
12.5
15.9
19.6
C120 derating table (IEC 60947-2)
C120 Ambient temperature (°C)
Rating -30
10 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
80 A
100 A
125 A
14.5
21.2
27
33.7
42.7
54.8
69.1
87.1
103.7
137.6
174.6
CA908007E
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50 +55
+60
+65
+70
14.3
21
26.6
33.3
42.1
54
68.1
85.8
102.4
135.5
171.9
14
20.7
26.3
32.8
41.5
53.2
67
84.5
101
133.5
169.2
13.8
20.4
25.9
32.3
40.9
52.4
65.9
83.1
99.7
131.4
166.4
13.5
20.1
25.5
31.8
40.3
51.5
64.8
81.8
98.3
129.2
163.6
13.3
19.8
25
31.3
39.7
50.7
63.7
80.4
96.9
127.1
160.7
13
19.4
24.6
30.8
39
49.8
62.6
78.9
95.5
124.8
157.8
12.7
19.1
24.2
30.2
38.4
48.9
61.5
77.5
94.1
122.6
154.9
12.5
18.8
23.8
29.7
37.7
48
60.3
76
92.6
120.3
151.8
12.2
18.5
23.3
29.1
37.1
47.1
59.1
74.5
91.1
118
148.7
11.9
18.2
22.9
28.6
36.4
46.1
57.9
73
89.6
115.6
145.6
11.6
17.8
22.4
28
35.7
45.2
56.7
71.4
88.1
113.1
142.4
11.3
17.5
22
27.5
35
44.2
55.4
69.8
86.5
110.6
139.1
11
17.1
21.5
26.9
34.3
43.2
54.1
68.2
84.9
108.1
135.7
10.7
16.8
21
26.3
33.5
42.1
52.8
66.5
83.3
105.5
132.2
10.3
16.4
20.5
25.6
32.8
41.1
51.4
64.8
81.7
102.8
128.7
10
16
20
25
32
40
50
63
80
100
125
9.3
15.2
18.9
23.7
30.4
37.7
47.1
59.3
76.5
94.2
117.3
8.9
14.8
18.4
23
29.6
36.6
45.5
57.4
74.7
91.2
113.3
8.5
14.4
17.8
22.3
28.7
35.3
43.9
55.4
72.9
88.1
109.1
Version : 2.7
25/09/2013
9.7
15.6
19.5
24.4
31.2
38.9
48.6
61.2
78.3
97.2
121.2
467
Complementary
technical information
Influence of ambient
temperature (cont.)
Tertiary/Industry (IEC 60947-2) (cont.)
NG125 derating table (IEC 60947-2)
NG125 Ambient temperature (°C)
Rating -30
10 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
80 A
100 A
125 A
13.7
20.3
26
33.8
41.2
53.5
66.3
83.4
100.4
133.4
165.2
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
13.5
20.1
25.6
33.2
40.6
52.7
65.2
82.1
99.1
131.3
162.7
13.2
19.8
25.3
32.7
40
51.8
64.2
80.8
97.8
129.1
160.1
13
19.5
24.9
32.1
39.4
51
63.1
79.5
96.4
127
157.5
12.8
19.2
24.5
31.5
38.8
50.1
62.1
78.1
95
124.8
154.8
12.5
18.9
24
30.9
38.2
49.1
61
76.8
93.6
122.5
152.1
12.3
18.6
23.6
30.3
37.5
48.2
59.8
75.4
92.2
120.2
149.3
12
18.3
23.2
29.7
36.9
47.3
58.7
73.9
90.8
117.9
146.5
11.7
18
22.8
29.1
36.2
46.3
57.5
72.5
89.3
115.5
143.6
11.5
17.7
22.3
28.4
35.6
45.3
56.4
71
87.8
113.1
140.7
11.2
17.4
21.9
27.8
34.9
44.3
55.1
69.5
86.3
110.6
137.7
10.9
17
21.4
27.1
34.2
43.3
53.9
67.9
84.8
108
134.6
10.6
16.7
21
26.4
33.5
42.2
52.6
66.3
83.2
105.4
131.5
10.3
16.4
20.5
25.7
32.7
41.1
51.3
64.7
81.6
102.7
128.3
10
16
20
25
32
40
50
63
80
100
125
9.7
15.7
19.5
24.3
31.2
38.9
48.6
61.3
78.3
97.2
121.6
9.4
15.3
19
23.5
30.5
37.7
47.2
59.5
76.6
94.3
118.1
9
14.9
18.5
22.7
29.7
36.5
45.8
57.7
74.9
91.3
114.6
8.7
14.5
17.9
21.9
28.8
35.2
44.3
55.8
73.1
88.2
110.9
8.3
14.1
17.4
21
28
33.9
42.7
53.9
71.3
85
107
7.9
13.7
16.8
20.1
27.1
32.5
41.1
51.8
69.4
81.6
103.1
Tertiaire/Industrie (IEC 60947-3)
SW60-DC derating table (IEC 60947-3)
SW60PV-DC Ambient temperature (°C)
Rating
50 A
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+60
+70
63
61
60
58
56
54
52
50
48
46
41
35
C60NA-DC derating table (IEC 60947-3)
C60NA-DC
Ambient temperature (°C)
Rating
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+60
+70
63
61
60
58
56
54
52
50
48
46
41
35
50 A
C120NA-DC derating table (IEC 60947-3)
C120NA-DC Ambient temperature (°C)
Rating
100 A
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+60
+70
113
111
110
108
106
104
102
100
98
96
91
85
Tertiary/Industry (IEC 61009-1)
C60H2 RCBO derating table (IEC 61009-1)
C60H2
RCBO
Ambient temperature (°C)
Rating
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
12.3
19.6
24.9
30.2
37.9
12.2
19.4
24.6
29.8
37.5
12
19.1
24.2
29.5
37.1
11.8
18.8
23.9
29.1
36.7
11.7
18.6
23.5
28.7
36.2
11.5
18.3
23.2
28.3
35.8
11.3
18
22.8
27.9
35.3
11.1
17.8
22.4
27.5
34.9
11
17.5
22
27.1
34.4
10.8
17.2
21.6
26.7
33.9
10.6
16.9
21.2
26.3
33.5
10.4
16.6
20.8
25.9
33
10.2
16.3
20.4
25.4
32.5
10
16
20
25
32
9.8
15.7
19.6
24.6
31.5
9.6
15.4
19.1
24.1
31
10 A
16 A
20 A
25 A
32 A
C60N/H RCBO derating table (IEC 61009-1)
C60H
RCBO
Ambient temperature (°C)
Rating
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
8.3
12.9
20.9
26.3
31.5
39.2
50.2
55.5
8.15
12.7
20.6
25.9
31
38.7
49.5
54.7
7.99
12.5
20.3
25.4
30.6
38.2
48.8
54
7.83
12.3
19.9
25
30.1
37.7
48
53.2
7.67
12.1
19.6
24.5
29.6
37.2
47.3
52.5
7.50
11.9
19.2
24.1
29.2
36.6
46.5
51.7
7.33
11.6
18.8
23.6
28.7
36.1
45.8
50.9
7.16
11.4
18.4
23.1
28.2
35.5
45
50.1
6.98
11.2
18.1
22.6
27.7
35
44.2
49.3
6.79
11
17.7
22.1
27.2
34.4
43.4
48.5
6.6
10.7
17.3
21.6
26.6
33.8
42.6
47.6
6.41
10.5
16.9
21.1
26.1
33.2
41.7
46.8
6.21
10.3
16.4
20.6
25.6
32.6
40.9
45.9
6
10
16
20
25
32
40
45
5.78
9.7
15.6
19.4
24.4
31.4
39.1
41.9
5.56
9.5
15.1
18.8
23.8
30.7
38.2
41
6A
10 A
16 A
20 A
25 A
32 A
40 A
45 A
468
Version : 2.7
25/09/2013
CA908007E
Complementary
technical information
Influence of ambient
temperature (cont.)
Switches
b In all cases, the switches are correctly protected against overloads by a circuit
breaker with a lower or equal rating, operating at the same ambient temperature.
iCT contactors
DB123331
In the case of contactor mounting in an enclosure for which the interior temperature
is in a range between 50°C and 60°C, it is necessary to use a spacer,
cat. no. A9A27062, between each contactor.
Spacer cat. no. A9A27062
CA908007E
Splitter blocks
In the event of a temperature higher than 40°C, the maximum acceptable current is
limited to the values in the table below:
Type
Temperature
Linergy FM 80 A
Linergy DX 63 A
40°C
80
63
Version : 2.7
45°C
76
60
25/09/2013
50°C
73
58
55°C
69
55
60°C
66
53
469