Overload relays 1 E Line thermal overload relay 1.1 1.2 E Line thermal overload relay Thermal overload relays XTOD / XTOG ............................................................................... 2 xStart series overload relays Bimetal relay ZE, ZB, Z5 .................................................................................................... 9 Overload relay ZW7 ............................................................................................................ 9 Electronic overload relays ZEB ............................................................................................ 11 EMT6 thermistor overload relay for machine protection .................................................... 11 C441 Overload and monitoring relay ................................................................................. 44 xStart series overload relay AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Thermal overload relays XTOD/XTOG Contents 1.1 Contents Thermal overload relays XTOD/XTOG 1 Description Page Thermal overload relays XTOD/XTOG System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 3 5 6 Thermal overload relays XTOD/XTOG Product description Features System overview Standards and certifications XTOD/XTOG thermal overload relays offer precision motor protection with phase loss protection and ambient temperature compensation. The seperate mount design allows for flexibility and the units can be mounted on DIN rail or directly on the panel adjacent the motor contactor. • Precision motor protection up to 97A • Integral 1NO/1NC contact for contactor control and alarm signal • Phase loss protection • Ambient temperature compensation • DIN rail or panel mount options Thermal overload relays provide protective features for 1 or 3 phase motors. The relay monitors the operating current of the motor and switched the contactor off in the event of an overload situation. It also protects the motor from damage during phase loss. • • • • GB 14048 IEC/EN 60947 CCC CE XTOD... is for separate mounting; XTOG is for direct mounting. AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 2 1.1 Thermal overload relays XTOD/XTOG Product selection Thermal overload relays 1 For use with XTOD..CC1S XTCG007 XTCG009 XTCG012 XTCG018 XTCG025 XTCG032 XTCG038 Setting range of overload releases Ir (A) Seperate mounting Circuit symbol 97 95 0.3~0.45 Seperate mounting Seperate mounting 4 6 Standard package 0.45 ~0.67 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 XTODP45CC1S 167952 1 piece 1 N/O 1 N/C XTODP67CC1S 167953 1 piece 1 N/O 1 N/C XTOD001CC1S 167954 1 piece 1 N/O 1 N/C XTOD1P5CC1S 167955 1 piece 1 N/O 1 N/C XTOD2P2CC1S 167956 1 piece 1 N/O 1 N/C XTOD2P7CC1S 167957 1 piece 1 N/O 1 N/C XTOD3P6CC1S 167958 1 piece 1 N/O 1 N/C XTOD005CC1S 167959 1 piece 1 N/O 1 N/C XTOD006CC1S 167960 1 piece 1 N/O 1 N/C XTOD8P5CC1S 167961 1 piece 1 N/O 1 N/C XTOD013CC1S 167962 1 piece 1 N/O 1 N/C XTOD018CC1S 167963 1 piece 1 N/O 1 N/C XTOD024CC1S 167964 1 piece 1 N/O 1 N/C XTOD030CC1S 167965 1 piece 1 N/O 1 N/C XTOGP16BC1 173679 1 piece 1 N/O 1 N/C XTOGP24BC1 173680 1 piece 1 N/O 1 N/C XTOGP40BC1 173681 1 piece 1 N/O 1 N/C XTOGP60BC1 173682 1 piece 1 N/O 1 N/C XTOG001BC1 173683 1 piece 1 N/O 1 N/C XTOG1P6BC1 173684 1 piece 1 N/O 1 N/C XTOG2P4BC1 173685 1 piece 1 N/O 1 N/C XTOG004BC1 173686 1 piece 1 N/O 1 N/C XTOG006BC1 173687 1 piece 1 N/O 1 N/C XTOG010BC1 173688 1 piece 1 N/O 1 N/C XTOG012BC1 173689 1 piece 1 N/O 1 N/C XTOG016CC1 173690 1 piece 1 N/O 1 N/C XTOG024CC1 173691 1 piece 1 N/O 1 N/C XTOG032CC1 173692 1 piece 98 96 97 95 1.0 ~1.5 1 N/C 98 96 97 95 0.67~1.0 1 N/O 98 96 97 95 2 Seperate mounting Part no. Article no. N/O =Normally open N/C =Normally closed 2 Seperate mounting Auxiliary contact 98 96 97 95 1.4 ~2.1 98 96 97 95 Seperate mounting 1.8~2.7 98 96 97 95 Seperate mounting Seperate mounting Seperate mounting Seperate mounting Seperate mounting Seperate mounting Seperate mounting Seperate mounting 2.4~3.6 97 95 3.5~5.0 XTCG007 XTCG009 XTCG012 XTCG018 XTCG025 XTCG032 XTCG038 Direct mounting Direct mounting Direct mounting Direct mounting Direct mounting 97 95 22~30 Direct mounting 3 98 96 97 95 4 6 2 4 6 2 4 6 2 4 6 98 96 97 95 0.16~0.24 98 96 97 95 0.24~0.4 98 96 97 95 0.4~0.6 98 96 97 95 0.6~1 4 6 98 96 97 95 1~1.6 4 6 98 96 97 95 1.6~2.4 4 6 98 96 97 95 2.4~4 4 6 98 96 97 95 4~6 4 6 98 96 97 95 6~10 4 6 98 96 97 95 9-12 4 6 98 96 97 95 12~16 2 Direct mounting 6 2 2 Direct mounting 4 0.1~0.16 2 Direct mounting 98 96 97 95 2 Direct mounting 98 96 97 95 17~24 2 Direct mounting 98 96 97 95 12.5~18 2 Direct mounting 98 96 97 95 8.5~12.5 2 Direct mounting 98 96 97 95 5.5~8.5 2 Direct mounting 98 96 4.0~6.0 2 XTOG... 98 96 4 6 98 96 97 95 16~24 2 4 6 2 4 6 98 96 97 95 24~32 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 98 96 Thermal overload relays XTOD/XTOG Product selection 1.1 Thermal overload relays For use with XTOG... XTCG040 XTCG050 XTCG065 XTCG080 XTCG095 1 Setting range of overload releases Ir (A) Direct mounting Direct mounting Direct mounting Circuit symbol 97 95 17~25 2 4 6 2 4 6 Standard package 4 6 4 6 48~65 4 6 1 piece 1 N/O 1 N/C XTOG032DC1 173694 1 piece 1 N/O 1 N/C XTOG040DC1 173695 1 piece 1 N/O 1 N/C XTOG050DC1 173696 1 piece 1 N/O 1 N/C XTOG065DC1 173697 1 piece 1 N/O 1 N/C XTOG050EC1 173698 1 piece 1 N/O 1 N/C XTOG065EC1 173699 1 piece 1 N/O 1 N/C XTOG080EC1 173700 1 piece 1 N/O 1 N/C XTOG097EC1 173701 1 piece 98 96 97 95 2 XTOG025DC1 173693 98 96 97 95 37~50 1 N/C 98 96 97 95 30~40 1 N/O 98 96 97 95 23~32 2 Direct mounting Part no. Article no. N/O =Normally open N/C =Normally closed 2 Direct mounting Auxiliary contact 98 96 97 95 Direct mounting 37~50 2 4 6 98 96 97 95 Direct mounting 48~65 2 Direct mounting Direct mounting 4 6 98 96 97 95 63~80 2 4 6 2 4 6 98 96 97 95 77~97 98 96 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 4 Thermal overload relays XTOD/XTOG 1.1 1 Technical data General XTOD/XTOG Standards Climatic Proofing IEC/EN 60947, GB 14048 Damp heat, constant, to IEC60068-2-78 Damp heat, cyclic, to IEC60068-2-30 Ambient temperature Open Enclosed Temperature compensation °C °C °C kg Weight Protection type -25~55 -25~40 -5~40 0.15 IP20 XTOD/XTOG Main contacts Uimp VAC 6000 III/3 Ui Overload release setting range VAC VAC A 690 690 0.1-97 Terminal capacity Solid mm2 1 x (1-6) 2 x (1-6) Flexible with ferrule mm2 1 x (1-6) 2 x (1-6) Solid/stranded Terminal screw Tightening torque AWG Rated impulse withstand voltage Overvoltage category/pollution degree Rated insulation voltage AC Rated operational voltage Ue Nm M4 1.2 XTOD/XTOG Auxiliary and control circuits Uimp V 6000 III/3 Terminal capacity Solid mm2 1 x (1-6) 2 x (1-6) Flexible with ferrule mm2 1 x (1-6) 2 x (1-6) Solid/stranded Terminal screw Tightening torque Rated insulation voltage Rated operational voltage AWG Rated impulse withstand voltage Overvoltage category/pollution degree Conventional thermal current Rated operational current AC-15 120V 220/240V 380V 480V 500V 600V DC-13 125V 250V 5 Ui Nm VAC M3.5 0.8 690 Ue Ith VAC A 690 10 Ie A 6 Ie Ie Ie Ie Ie A A A A A 3 1.9 1.5 1.4 1.2 Ie Ie A A 0.55 0.27 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Thermal overload relays XTOD/XTOG Dimensions 1.1 Dimensions 1 Thermal overload relay + mounting adapter XTOD..CC1S Thermal overload relays XTOG 17-65A 37-97A AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 6 1.2 Overload relays 1 Overload relay Motor protection is a central task of electrical equipment for machinery. From cost-effective bimetal solutions to demanding full motor protection with cross-linkage we offer the right solution for each application. ATEX Bimetal relay - overload relay up to 630 A • Direct mounting on contactor saves mounting time. • ATEX approval for the protection of EEx e motors up to 250 A. • Comprehensive motor protection through phase failure sensitivity. Page 13. • Integrated test pushbutton facilitates high safety ZEB electronic overload relay - overload relay up to 1500 A • ATEX approval for protection of EEx e motors up to 1500 A. • Adjustable tripping classes. • Phase failure and unbalance protection. • Optional earth fault detection. Page 21. • Additional current setting range (5:1) EMT6 thermistor overload relay for machine protection • Overload protection through direct evaluation of winding temperature. • Quick detection of operating state through LED display. • Suitable for overload monitoring of motors in EEx e range. • Wide range power supply reduces amount of types Page 26. 7 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Overload relays Contents Overload relay 1.2 Contents Description 1 Page Technical overview Bimetal relay ZE, ZB, Z5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overload relay ZW7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electronic overload relays ZEB . . . . . . . . . . . . . . . . . . . . . . . . EMT6 thermistor overload relay for machine protection . . . . Ordering Bimetal relays for mini-contactor relays . . . . . . . . . . . . . . . . . Bimetal relays up to 150A . . . . . . . . . . . . . . . . . . . . . . . . . . . Bimetal relay greater than 150 A . . . . . . . . . . . . . . . . . . . . . . Overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bimetal relay accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . ZEB Electronic overload relay . . . . . . . . . . . . . . . . . . . . . . . . . Ordering EMT6 thermistor overload relay for machine protection . . . . Engineering EMT6 thermistor overload relay for machine protection . . . . Selection criteria ZE, ZB, Z5, ZW7 . . . . . . . . . . . . . . . . . . . . . Characteristic curve ZB, Z5, ZW7 . . . . . . . . . . . . . . . . . . . . . . UL/CSA short-circuit strength ZE, ZB, Z5 . . . . . . . . . . . . . . . . Technical data Bimetal relay for mini-contactor relays . . . . . . . . . . . . . . . . . . Bimetal relays up to 150A . . . . . . . . . . . . . . . . . . . . . . . . . . . Overload relays greater than 150 A . . . . . . . . . . . . . . . . . . . . Overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ZEB electronic overload relay . . . . . . . . . . . . . . . . . . . . . . . . . EMT6 thermistor overload relay for machine protection . . . . Dimensions Bimetal relays for mini-contactor relays . . . . . . . . . . . . . . . . . Bimetal relays up to 150A . . . . . . . . . . . . . . . . . . . . . . . . . . . Bimetal relays greater than 150 A . . . . . . . . . . . . . . . . . . . . . Overload relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ZEB electronic overload relay . . . . . . . . . . . . . . . . . . . . . . . . . EMT6 thermistor overload relay for machine protection . . . . AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 9 9 11 11 13 15 19 19 28 31 26 27 30 30 31 32 32 33 33 35 36 37 37 39 39 40 42 8 1.2 1 Overload relays Overload relays, CT-operated overload relays Technical overview Overload relays, CT-operated overload relays Electronic overload relays, thermistor overload relay for machine protection Setting ranges (A) (note max. current of the contactor) DILEM DILM7 DILM12 DILM9 DILM15 DILM17 DILM32 DILM25 DILM38 Overload relays ZE 0.1-12 ZB12 0.1-16 ZB32 0.1-38 ZB65 6-75 ZB150 35-175 Z5-.../FF225A 70-250 Z5-.../FF250 50-300 Current transformer-operated overload relay ZW7-... 42-630 9 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical DILM40 DILM65 DILM50 DILM72 DILM80 DILM150 DILM95 DILM170 DILM115 Overload relays Overload relays, CT-operated overload relays 1.2 1 DILM185A DILM225A DILM250 DILM300 DILM400 DILM580 DILM500 DILM650 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 10 1.2 1 Overload relays Electronic overload relays, thermistor overload relay for machine protection Electronic overload relays, thermistor overload relay for machine protection Setting ranges (A) (note max. current of the contactor) DILEM DILM7 DILM12 DILM9 DILM15 DILM17 DILM32 DILM25 DILM38 Electronic overload relays ZEB12 0.33-20 ZEB32 0.33-45 ZEB65 9-100 ZEB150 20-100 ZEB32-5-(GF)/KK combined with ZEB-XCT300 60-300 ZEB-XCT600 120-600 ZEB-XCT1000 200-1000 ZEB-XCT1500 300-1500 Thermistor overload relay for machine protection EMT6((DB)K) 11 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical DILM40 DILM65 DILM50 DILM72 DILM80 DILM150 DILM95 DILM170 DILM115 Overload relays Electronic overload relays, thermistor overload relay for machine protection 1.2 1 DILM185A DILM225A DILM250 DILM300 DILM400 DILM580 DILM500 DILM650 DILM750 DILM820 DILM1000 DILM1600 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 12 1.2 1 Overload relays Bimetal relays for mini-contactor relays Ordering ZE overload relays for mini contactor relays • • • • • Phase failure sensitivity to IEC/EN 60947, VDE 0660 Part 102 Test/off pushbutton Reset pushbutton manual/auto Trip-free release Direct mounting Setting range of overload releases Circuit symbol Auxiliary contact For use with N/O = normally open contact NC = normally closed contact Ir Type “1” coordination gG/gL Type “2” coordination gG/gL A A A 20 0.5 20 1 1 N/O 1 NC 1 N/O 1 NC 0.24 – 0.4 1 N/O 1 NC 20 2 0.4 – 0.6 1 N/O 1 NC 20 2 0.6 – 1 1 N/O 1 NC 20 4 1 – 1.6 1 N/O 1 NC 20 6 1.6 – 2.4 1 N/O 1 NC 20 6 2.4 – 4 1 N/O 1 NC 20 10 4–6 1 N/O 1 NC 20 10 6–9 1 N/O 1 NC 20 10 9 – 12 1 N/O 1 NC 20 10 0.1 – 0.16 0.16 – 0.24 97 95 2 4 6 98 96 DILEM DIULEM/21/MV SDAINLEM Information relevant for export to North America Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Max. Voltage Rating Degree of Protection See also 13 Short-circuit protection UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking E29184 NKCR 12528 3211-03 UL Listed, CSA certified Branch circuits 600 V AC IEC: IP20, UL/CSA Type: Page 31 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Overload relays Bimetal relays for mini-contactor relays 1.2 1 Part no. Article no. ZE-0.16 014263 ZE-0.24 014285 ZE-0.4 014300 ZE-0.6 014333 ZE-1.0 014376 ZE-1.6 014432 ZE-2.4 014479 ZE-4 014518 ZE-6 014565 ZE-9 014708 ZE-12 014752 Price See price list Std. pack Notes 1 Off Overload release: tripping class 10 A Short-circuit protection: With direct mounting, observe the maximum permissible fuse of the contactor. With side-by-side mounting, there must be a minimum clearance of 5 mm between overload relays. Suitable for protection of EEx e motors 1 II (2) GD PTB 01 ATEX 3331 Observe manual AWB2300-1425D/GB. 1 Contactor Chapter 5 Accessories Page 28 Manual Page 28 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 14 1.2 Overload relays Overload relays up to 150A ZB12, ZB32 1 Setting range of overload releases ZB12 overload relay Circuit symbol For use with N/O = normally open contact NC = normally closed contact Contactors Short-circuit protection Ir Type “1” coordination gG/gL Type “2” coordination gG/gL A A A – 25 0.5 – 25 1 – 25 2 – 25 4 0.1 – 0.16 DILM7, DILM9, DILM12, DILM15, DIULM7, DIULM9, DIULM12, SDAINLM12, SDAINLM16, SDAINLM22 Soft starters 1 N/O 1 NC 1 N/O 1 NC 0.24 – 0.4 1 N/O 1 NC 0.4 – 0.6 1 N/O 1 NC 0.6 – 1 1 N/O 1 NC – 25 4 1 – 1.6 1 N/O 1 NC – 25 6 1.6 – 2.4 1 N/O 1 NC – 25 10 2.4 – 4 1 N/O 1 NC DS7-34…SX004… 25 16 4–6 1 N/O 1 NC DS7-34…SX005… 25 20 6 – 10 1 N/O 1 NC 50 25 9 – 12 1 N/O 1 NC DS7-34…SX007… DS7-34…SX009… DS7-34…SX012… 50 25 12 – 16 1 N/O 1 NC – 50 25 1 N/O 1 NC – 25 0.5 1 N/O 1 NC – 25 1 0.24 – 0.4 1 N/O 1 NC – 25 2 0.4 – 0.6 1 N/O 1 NC – 25 4 0.6 – 1 1 N/O 1 NC – 25 4 1 – 1.6 1 N/O 1 NC – 25 6 1.6 – 2.4 1 N/O 1 NC – 25 10 2.4 – 4 1 N/O 1 NC – 25 16 4–6 1 N/O 1 NC – 25 20 6 – 10 1 N/O 1 NC – 50 25 10 – 16 1 N/O 1 NC DS7-34...SX016... 63 35 16 – 24 1 N/O 1 NC DS7-34...SX024... 100 35 24 – 32 1 N/O 1 NC DS7-34...SX032... 125 63 32 – 38 1 N/O 1 NC – 125 63 97 95 0.16 – 0.24 2 ZB32 overload relay Auxiliary contact 4 6 0.1 – 0.16 98 96 A2 14/ 22 97 95 0.16 – 0.24 2 4 6 98 96 14/ 22 DILM17, DILM25, DILM32, DILM38, DILMF8, DILMF11, DILMF14, DILMF17, DILMF25, DILMF32, DIULM17, DIULM25, DIULM32, SDAINLM30, SDAINLM45, SDAINLM55 Information relevant for export to North America Product Standards UL File No. UL CCN CSA File No. CSA Class No. 15 UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking E29184 NKCR 12528 3211-03 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical NA Certification Suitable for Max. Voltage Rating Degree of Protection See also UL Listed, CSA certified Branch circuits 600 V AC IEC: IP20, UL/CSA Type: Page 31 Overload relays Overload relays up to 150A 1.2 1 Part no. Article no. ZB12-0,16 278431 ZB12-0,24 278432 ZB12-0,4 278433 ZB12-0,6 278434 ZB12-1 278435 ZB12-1,6 278436 ZB12-2,4 278437 ZB12-4 278438 ZB12-6 278439 ZB12-10 278440 ZB12-12 278441 ZB12-16 290168 ZB32-0,16 278442 ZB32-0,24 278443 ZB32-0,4 278444 ZB32-0,6 278445 ZB32-1 278446 ZB32-1,6 278447 ZB32-2,4 278448 ZB32-4 278449 ZB32-6 278450 ZB32-10 278451 ZB32-16 278452 ZB32-24 278453 ZB32-32 278454 ZB32-38 112474 Price See price list Std. pack Notes 1 Off Overload release: tripping class 10 A Short-circuit protection: With direct mounting, observe the maximum permissible fuse of the contactor. Fitted directly to the contactor 1 Suitable for protection of EEx e motors. II (2) GD PTB 04 ATEX 3022 Observe manual AWB2300-1527D/GB. • Phase failure sensitivity to IEC/EN 60947, VDE 0660 Part 102 • Test/off pushbutton • Reset pushbutton manual/auto • Trip-free release • Direct mounting 1 Off Overload release: tripping class 10 A Short-circuit protection: With direct mounting, observe the maximum permissible fuse of the contactor. 1 Contactor Chapter 5 Accessories Page 28 Manual Page 28 Fitted directly to the contactor Separate mounting 1 1 Suitable for protection of EEx e motors. II (2) GD PTB 04 ATEX 3022 Observe manual AWB2300-1527D/GB. • Phase failure sensitivity to IEC/EN 60947, VDE 0660 Part 102 • Test/off pushbutton • Reset pushbutton manual/auto • Trip-free release • Direct mounting 2 1 Contactor Chapter 5 2 Base Page 28 Manual Page 28 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 16 1.2 Overload relays Overload relays up to 150A ZB65, ZB150 1 Setting range of overload releases Circuit symbol Auxiliary contact For use with N/O = normally open contact NC = normally closed contact Ir A ZB65 overload relay • Phase failure sensitivity to IEC/EN 60947, VDE 0660 Part 102 • Test/off pushbutton • Reset pushbutton manual/auto • Trip-free release • Direct mounting ZB150 overload relay • Phase failure sensitivity to IEC/EN 60947, VDE 0660 Part 102 • Test/off pushbutton • Reset pushbutton manual/auto • Trip-free release • Direct mounting ZB150 overload relay • Phase failure sensitivity to IEC/EN 60947, VDE 0660 Part 102 • Test/off pushbutton • Reset pushbutton manual/auto • Trip-free release • Separate mounting 6 – 10 DILM40, DILM50, DILM65, DILM72, DILMF40, DILMF50, DILMF65, DIULM40, DIULM50, DIULM65, SDAINLM70, SDAINLM90, SDAINLM115 Type “1” coordination gG/gL A Type “2” coordination gG/gL A 50 25 63 35 63 50 125 63 160 80 1 N/O 1 NC 1 N/O 1 NC 16 – 24 1 N/O 1 NC 24 – 40 1 N/O 1 NC 40 – 57 1 N/O 1 NC 50 – 65 1 N/O 1 NC 160 100 65 – 75 1 N/O 1 NC 250 160 1 N/O 1 NC 160 125 1 N/O 1 NC 250 160 70 – 100 1 N/O 1 NC 315 200 95 – 125 1 N/O 1 NC 315 250 120 – 150 1 N/O 1 NC 315 250 145 – 175 1 N/O 1 NC DILM80, DILM95, DILM115, DILM150, DILM170 DILMF80, DILMF95, DILMF115, DILMF150, DIULM80, DIULM95, DIULM115, DIULM150, SDAINLM140, SDAINLM165, SDAINLM200, SDAINLM260 315 250 1 N/O 1 NC 160 125 1 N/O 1 NC 250 160 70 – 100 1 N/O 1 NC 315 200 95 – 125 1 N/O 1 NC 315 250 120 – 150 1 N/O 1 NC 315 250 145 – 175 1 N/O 1 NC DILM80, DILM95, DILM115, DILM150, DILM170 DILMF80, DILMF95, DILMF115, DILMF150, DIULM80, DIULM95, DIULM115, DIULM150, SDAINLM140, SDAINLM165, SDAINLM200, SDAINLM260 400 315 10 – 16 97 95 2 4 6 35 – 50 98 96 97 95 50 – 70 2 4 6 35 – 50 50 – 70 98 96 97 95 2 4 6 98 96 Information relevant for export to North America Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Max. Voltage Rating Degree of Protection See also 17 Short-circuit protection UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking E29184 NKCR 12528 3211-03 UL Listed, CSA certified Branch circuits 600 V AC IEC: IP00, UL/CSA Type: Page 31 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Overload relays Overload relays up to 150A 1.2 1 Part no. Article no. Price See price list Std. pack Notes ZB65-10 278455 ZB65-16 278456 ZB65-24 278457 ZB65-40 278458 ZB65-57 278459 ZB65-65 278460 ZB65-75 108792 ZB150-50 278462 ZB150-70 278463 ZB150-100 278464 ZB150-125 278465 ZB150-150 278466 ZB150-175 107316 1 Off Overload release: tripping class 10 A Short-circuit protection: With direct mounting, observe the maximum permissible fuse of the contactor. ZB150-50/KK 278468 ZB150-70/KK 278469 ZB150-100/KK 278470 ZB150-125/KK 278471 ZB150-150/KK 278472 ZB150-175/KK 107317 1 Off Fitted directly to the contactor Separate mounting Suitable for protection of EExe motors. 1 II (2) GD PTB 04 ATEX 3022 1 Observe manual AWB2300-1545D/GB. 1 Off Overload release: tripping class 10 A Short-circuit protection: With direct mounting, observe the maximum permissible fuse of the contactor. 2 Suitable for protection of EEx e motors. II (2) GD PTB 04 ATEX 3022 Observe manual AWB2300-1545D/GB. Overload release: tripping class 10 A Short-circuit protection: With direct mounting, observe the maximum permissible fuse of the contactor. 1 Contactor Chapter 5 2 Base Page 28 Manual Page 28 Suitable for protection of EEx e motors. II (2) GD PTB 04 ATEX 3022 Observe manual AWB2300-1545D/GB. AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 18 1.2 Overload relays Overload relays greater than 150 A, CT-operated overload relays Z5, ZW7 1 Setting range of of overload releases Circuit symbol Auxiliary contacts For use with N/O = normally open contact NC = normally closed contact Short-circuit protection Type “1” coordination gG/gL Type “2” coordination gG/gL A A 250 250 315 315 160 160 200 200 Ir A Z5 overload relays greater than 150A • Phase failure sensitivity to IEC/EN 60947, VDE 0660 Part 102 • Test/off pushbutton • Reset pushbutton manual/auto • Trip-free release Direct mounting Z5 overload relays greater than 150A • Phase failure sensitivity to IEC/EN 60947, VDE 0660 Part 102 • Test/off pushbutton • Reset pushbutton manual/auto • Trip-free release Separate mounting ZW7 current transformer-operated overload relays • Test/off button • Reset pushbutton manual/auto • Trip-free release • Protection with heavy starting duty Separate mounting 19 50 – 70 DILM185A DILM225A 1 N/O 1 NC 1 N/O 1 NC 95 – 125 1 N/O 1 NC 315 315 250 250 120 – 160 1 N/O 1 NC 400 400 250 250 160 – 220 1 N/O 1 NC 400 500 315 400 200 – 250 1 N/O 1 NC 400 500 315 400 50 – 70 1 N/O 1 NC 250 250 160 160 70 – 100 1 N/O 1 NC 95 – 125 1 N/O 1 NC 315 315 315 315 200 200 250 250 120 – 160 1 N/O 1 NC 400 400 250 250 160 – 220 1 N/O 1 NC 200 – 250 1 N/O 1 NC 250 – 300 1 N/O 1 NC DILM300A 400 500 400 500 500 500 315 400 315 400 400 400 1 N/O 1 NC – – – 1 N/O 1 NC – – – 1 N/O 1 NC – – – 110 – 160 1 N/O 1 NC – – – 160 – 240 1 N/O 1 NC – – – 190 – 290 1 N/O 1 NC – – – 270 – 400 1 N/O 1 NC – – – 360 – 540 1 N/O 1 NC – – – 420 – 630 1 N/O 1 NC – – – 1 3 5 97 95 2 4 6 98 96 70 – 100 42 – 63 DILM250 97 95 60 – 90 85 – 125 98 96 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Overload relays Overload relays greater than 150 A, CT-operated overload relays 1.2 1 Part no. Article no. Z5-70/FF225A 139572 Z5-100/FF225A 139573 Z5-125/FF225A 139574 Z5-160/FF225A 139575 Price See price list Std. pack Notes Information relevant for export to North America 1 Off Overload release: tripping class 10 A Short-circuit protection: With direct mounting, observe the maximum permissible fuse of the contactor. Product Standards Z5-…/FF225A for protecting EEx electric motors in preparation. NA Certification Suitable for Max. Voltage Rating Degree of Protection See also Fitted directly to the contactor Z5-220/FF225A 139576 Z5-250/FF225A 139577 1 Z5-70/FF250 210070 Product Standards Z5-100/FF250 210071 Z5-125/FF250 210072 Z5-160/FF250 210073 UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Max. Voltage Rating Degree of Protection See also 1 Contactor Accessories Z5-220/FF250 210074 Chapter 5 Page 29 Z5-250/FF250 210075 Z5-300/FF250 139578 Product Standards NA Certification Suitable for Max. Voltage Rating Degree of Protection ZW7-63 000245 ZW7-90 002618 UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking Request filed for UL and CSA Branch circuits 600 V AC IEC: IP00, UL/CSA Type: Page 31 1 Off ZW7-125 004991 ZW7-160 007364 ZW7-240 009737 The main current characteristic values are defined by the main current wiring being used. Adjustment for smaller rated motor currents Page 30 Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Max. Voltage Rating Degree of Protection UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking E29184 NKCR 12528 3211-03 UL Listed, CSA certified Branch circuits 600 V AC IEC: IP00, UL/CSA Type: Page 31 UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking Request filed for UL and CSA Branch circuits 600 V AC IEC: IP00, UL/CSA Type: UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking E29184 NKCR 12528 3211-03 UL Listed, CSA certified Branch circuits 600 V AC IEC: IP00, UL/CSA Type: - ZW7-290 052448 ZW7-400 045329 ZW7-540 047702 ZW7-630 050075 1 O ff – AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 20 1.2 Electronic overload relays to 1500 A Basic devices ZEB12, ZEB32 1 Ground fault detection ZEB12 electronic overload relay • Phase-failure sensitivity • Test/off pushbutton • Reset button • Manual/Auto reset selectable • Protection with heavy starting duty (Class 10A-30) Direct mounting ZEB32 electronic overload relay • Phase-failure sensitivity • Test/off pushbutton • Reset button • Manual/Auto reset selectable • Protection with heavy starting duty (Class 10A-30) Direct mounting ZEB32 electronic overload relay • Phase-failure sensitivity • Test/off pushbutton • Reset button • Manual/Auto reset selectable • Protection with heavy starting duty (Class 10A-30) Separate mounting Setting range of overload releases Ir A Without 0.33 – 1.65 Without 1–5 Circuit symbol For use with N/O = normally open contact NC = normally closed contact 97 95 2 4 6 1 N/O 1 NC 1 N/O 1 NC 98 96 Without 4 – 20 1 N/O 1 NC With 0.33 – 1.65 1 N/O 1 NC With 1–5 1 N/O 1 NC With 4 – 20 1 N/O 1 NC Without 0.33 – 1.65 1 N/O 1 NC Without 1–5 1 N/O 1 NC Without 4 – 20 1 N/O 1 NC Without 9 – 45 1 N/O 1 NC With 0.33 – 1.65 1 N/O 1 NC With 1–5 1 N/O 1 NC With 4 – 20 1 N/O 1 NC With 9 – 45 1 N/O 1 NC Without 0.33 – 1.65 1 N/O 1 NC Without 1–5 1 N/O 1 NC Without 4 – 20 1 N/O 1 NC Without 9 – 45 1 N/O 1 NC With 0.33 – 1.65 1 N/O 1 NC With 1–5 1 N/O 1 NC With 4 – 20 1 N/O 1 NC With 9 – 45 1 N/O 1 NC 97 95 2 4 6 98 96 1 3 5 97 95 2 4 6 98 96 Information relevant for export to North America Product Standards NA Certification Suitable for Max. Voltage Rating Degree of Protection 21 Auxiliary contact UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking Request filed for UL and CSA Branch circuits 600 V AC IEC: IP20, UL/CSA Type: - AUTOMATION AND CONTROL www.eaton.com/seasia-electrical DILM7 DILM9 DILM12 DILM15 DIULM7 DIULM9 DIULM12 SDAINLM12 SDAINLM16 SDAINLM22 DILM17 DILM25 DILM32 DILM38 DIULM17 DIULM25 DIULM32 SDAINLM30 SDAINLM45 SDAINLM55 DILM17 DILM25 DILM32 DILM38 DIULM17 DIULM25 DIULM32 SDAINLM30 SDAINLM45 SDAINLM55 Electronic overload relays to 1500 A Basic devices 1.2 1 Part no. Article no. ZEB12-1,65 136480 ZEB12-5 136481 Price See price list Std. pack Notes 1 Off Suitable for protection of EEx e motors. Fitted directly to the contactor II (2) GD PTB ATEX starting 08/2010 ZEB12-20 136482 ZEB12-1,65-GF 136483 1 Observe manual AWB2320-1633D/GB. Switchgear and cable dimensioning according to CLASS Page 25 ZEB12-5-GF 136484 ZEB12-20-GF 136485 1 Contactor Accessories ZEB32-1.65 136486 1 Off Suitable for protection of EEx e motors. ZEB32-5 136487 II (2) GD PTB ATEX starting 08/2010 ZEB32-20 136488 ZEB32-45 136489 ZEB32-1,65-GF 136490 Observe manual AWB2320-1633D/GB. Chapter 5 Page 25 Fitted directly to the contactor 1 Switchgear and cable dimensioning according to CLASS Page 25 ZEB32-5-GF 136491 ZEB32-20-GF 136492 ZEB32-45-GF 136493 ZEB32-1,65/KK 136494 ZEB32-5/KK 136495 ZEB32-20/KK 136496 ZEB32-45/KK 136497 ZEB32-1,65-GF/KK 136498 ZEB32-5-GF/KK 136499 ZEB32-20-GF/KK 136500 1 Off Suitable for protection of EEx e motors. 1 Contactor Accessories II (2) GD PTB ATEX starting 08/2010 Chapter 5 Page 25 Observe manual AWB2320-1633D/GB. Switchgear and cable dimensioning according to CLASS Page 25 ZEB32-45-GF/KK 136501 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 22 1.2 Electronic overload relays to 1500 A Basic devices ZEB65, ZEB150 1 Ground fault detection Setting range of overload releases Ir A ZEB65 electronic overload relay • Phase-failure sensitivity • Test/off pushbutton • Reset button • Manual/Auto reset selectable • Protection with heavy starting duty (Class 10A-30) Direct mounting Without 9 – 45 With 9 – 45 Without ZEB150 electronic overload relay • Phase-failure sensitivity • Test/off pushbutton • Reset button • Manual/Auto reset selectable • Protection with heavy starting duty (Class 10A-30) Direct mounting ZEB150 electronic overload relay • Phase-failure sensitivity • Test/off pushbutton • Reset button • Manual/Auto reset selectable • Protection with heavy starting duty (Class 10A-30) Separate mounting Circuit symbol For use with N/O = normally open contact NC = normally closed contact 1 N/O 1 NC 1 N/O 1 NC 20 – 100 1 N/O 1 NC With 20 – 100 1 N/O 1 NC Without 20 – 100 1 N/O 1 NC With 20 – 100 1 N/O 1 NC 1 N/O 1 NC 1 N/O 1 NC Without 20 – 100 With 20 – 100 97 95 2 4 6 98 96 97 95 2 4 6 98 96 1 3 5 97 95 2 4 6 98 96 Information relevant for export to North America Product Standards NA Certification Suitable for Max. Voltage Rating Degree of Protection 23 Auxiliary contact UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking Request filed for UL and CSA Branch circuits 600 V AC IEC: IP20, UL/CSA Type: - AUTOMATION AND CONTROL www.eaton.com/seasia-electrical DILM40 DILM50 DILM65 DILM72 DIULM40 DIULM50 DIULM65 SDAINLM70 SDAINLM90 SDAINLM115 DILM80 DILM95 DILM115 DILM150 DIULM80 DIULM95 DIULM115 DIULM150 SDAINLM140 SDAINLM165 SDAINLM200 SDAINLM260 DILM80 DILM95 DILM115 DILM150 DIULM80 DIULM95 DIULM115 DIULM150 SDAINLM140 SDAINLM165 SDAINLM200 SDAINLM260 Electronic overload relays to 1500 A Basic devices 1.2 1 Part no. Article no. ZEB65-45 136502 ZEB65-45-GF 136503 Price See price list Std. pack Notes 1 Off Suitable for protection of EEx e motors. Fitted directly to the contactor II (2) GD PTB ATEX starting 08/2010 ZEB65-100 136504 ZEB65-100-GF 136505 1 Observe manual AWB2320-1633D/GB. Switchgear and cable dimensioning according to CLASS Page 25 1 Contactor Accessories ZEB150-100 136506 1 Off Suitable for protection of EEx e motors. Chapter 5 Page 25 Fitted directly to the contactor II (2) GD PTB ATEX starting 08/2010 ZEB150-100-GF 136507 1 Observe manual AWB2320-1633D/GB. Switchgear and cable dimensioning according to CLASS Page 25 ZEB150-100/KK 136508 ZEB150-100-GF/KK 136509 1 Off Suitable for protection of EEx e motors. II (2) GD PTB ATEX starting 08/2010 Observe manual AWB2320-1633D/GB. 1 Contactor Accessories Chapter 5 Page 25 Switchgear and cable dimensioning according to CLASS Page 25 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 24 1.2 1 Electronic overload relays to 1500 A Accessories ZEB-XCT… Setting range of overload releases Language Can be used with Part no. Article no. Price See price list Std. pack 60 – 300 – ZEB32-5-GF/KK ZEB32-5/KK ZEB-XCT3001) 136511 1off 120 – 600 – ZEB32-5-GF/KK ZEB32-5/KK ZEB-XCT6001) 136512 1off 200 – 1000 – ZEB32-5-GF/KK ZEB32-5/KK ZEB-XCT10001) 136517 1off 300 – 1500 – ZEB-XCT15001) 136513 1off – – – ZEB-XSC2) 136514 1 off – – – ZEB-XRB2) 136515 1 off – Deutsch English ZEB12 ZEB32 ZEB65 ZEB150 AWB2320-1633DE/EN 136516 1 off Ir A Current sensors Sealable shroud Cover to prevent adjustment of motor current (tamper-proof) Reset adapter Cover to prevent adjustment of motor current (tamper-proof) Documentation ZEB electronic overload relay Overload monitoring of EEx e motors 1) 2) Information relevant for export to North America Information relevant for export to North America Product Standards Product Standards NA Certification Suitable for Max. Voltage Rating Degree of Protection UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking Request filed for UL and CSA Branch circuits 600 V AC IEC: IP00, UL/CSA Type: - NA Certification Max. Voltage Rating Degree of Protection UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking Request filed for UL and CSA 600 V AC IEC: IP20, UL/CSA Type: - Switchgear and cable sizing corresponding to the respective starting inertia (CLASS) for ZEB Switchgear is designed according to "CLASS 10" requirements for both normal and overload operation conditions. In order for the switchgear (circuit-breaker and contactor) and the cables not to be overloaded with long tripping times, they must be overdimensioned accordingly. The rated operational current, Ie, for switchgear and cables can be calculated with the following current factor taking the tripping class into account: Trippling class Class 5 Class 10 Class 15 Class 20 Class 25 Class 30 Class 35 Class 40 Current factor of rated operational current Ie 1.00 1.00 1.22 1.41 1.58 1.73 1.89 2.00 25 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Overload relays for machine protection 1.2 Basic devices, accessories Ordering 1 EMT6 Function Rated operational current Conventional thermal AC-15 AC-14 current 240 V 400 V Rated control voltage Part no. Article no. Ie Ie I th Us A A A V 6 24 - 240 V 50/60 Hz, EMT61) 2) 066166 24 - 240 V DC 230 V 50/60 Hz EMT6(230V)1) 2) 066400 Price See price list Std. pack Notes EMT6 thermistor machine protection overload relays Without automatic reset Mains and fault LED display 3 3 Without automatic reset Mains and fault LED display Tripped in the event of a short-circuit in the sensor-cable 3 Selector switch with/without automatic reset For manual or remote resetting Test button Mains and fault LED display 3 Selector switch with/without automatic reset For manual or remote resetting Test button Mains and fault LED display Trip with short-circuit in the sensor cable 3 3 6 24 - 240 V 50/60 Hz, EMT6-KDB 2) 24 - 240 V DC 269471 All-in-one device Selector switch with/without automatic reset Trip with short-circuit in the sensor cable Zero-voltage safe For manual or remote resetting Test button Short-circuit detection and retention can be deactivated Mains and fault LED display 3 3 6 24 - 240 V 50/60 Hz, EMT6-DBK 2) 24 - 240 V DC 066168 3 3 1 off II (2) G II (2) GD only for EMT6-K 24 - 240 V 50/60 Hz, EMT6-K 2) 24 - 240 V DC 269470 6 PTB 02 ATEX 3162 Observe the manual AWB 2327-1446 Page 26 Can be snap fitted on a top-hat rail to IEC/EN 60715. Device clearance ≧ 3 mm. 24 - 240 V 50/60 Hz, EMT6-DB1) 2) 24 - 240 V DC 066167 6 230 V 50/60 Hz EMT6-DB(230V)1) 2) 066401 Accessories Screw adapters for screw fixing Documentation EMT6 thermistor overload relay Overload monitoring of machines in the EEx e area German English CS-TE 3) 095853 10 off AWB2327-1446D 264853 AWB2327-1446GB 267010 1 off 1 off 1) For EMT6, EMT6(230V), EMT6-DB and EMT6-DB(230V) applies: Provide additional short-circuit protection in the sensor circuit with a current monitoring relay. Notes 2) 3) Information relevant for export to North America Information relevant for export to North America Product Standards UL/CSA certification not required UL File No. UL CCN CSA File No. CSA Class No. NA Certification Max. Voltage Rating Degree of Protection – UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking E29184 NKCR 12528 3211-03 UL Listed, CSA certified 600 V AC IEC: IP20, UL/CSA Type: - AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 26 1.2 Selection aid Engineering Terminal marking according to EN 50005 EMT6(-K), EMT6-(K)DB, EMT6-DBK Auto EMT6-(K)DB, EMT6-DBK Manual ~ L+ ~ L+ A1/A2 A1/A2 T1/T2 21 A1 Power 3.6 K 1.6 K 0 T1/T2 Y1 Y2 A1 13 Power Tripped 21 13 22 1.6 k 0 Y1/Y2, RESET US Tripped LED T1 T2 A2 3.6 K Tripped 13–14, 21–22 US 13–14, 21–22 22 14 T1 T2 A2 14 Tripped LED PTC PTC N~ N~ EMT6-DBK Zero-voltage safe operation LED display ~ L+ A1/A2 T1/T2 Y1 Y2 A1 Power Y3 Y4 21 13 Supply voltage present 3.6 K 1.6 K 0 Device has tripped Tripped Device has tripped/short-circuit in the sensor circuit Y1/Y2, RESET US 13–14, 21–22 T1 T2 A2 22 14 Tripped LED Short-circuit PTC N ~– Sensor circuit At R K ≦ 250 Ω per sensor: 6 sensors, at RK≦100 Ω per sensor: 9 sensors in the winding (provided by user), max. cable length to sensor 250 m (not shielded); Total PTC thermistor resistance ∑ R K≦1500 Ω Sensor circuit characteristic values at Us and +20 °C 12000 R T1-T2 EMT6… U T1-T2 V DC max. I T1-T2 mA max. T1, T2 short-circuited 4 kΩ T1-T2 open 3 5.1 1.9 0.8 - Resistance [ ] 1 Overload relays for machine protection 4000 3600 IECTripping range 1650 Resetting range 1600 Disconnection by link Short-circuit monitoring Zero-voltage safety Y1 - Y 3 Y1 - Y 4 27 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Reset 750 Tolerance limits Temperature [°C] Functions that can be disconnected on the EMT6-DBK: Function Tripping 60 NAT NAT –20° –5° NAT NAT NAT +5° +15° Overload relays Accessories 1.2 Ordering 1 ZB, Z5, ZW7 For use with Part no. Article no. Std. pack Notes AWB2300-1425D 258704 AWB2300-1527D/GB 284910 AWB2300-1545D/GB 102065 1 off German 1 off German/English 1 off German/English ZB32 ZB32-XEZ 278473 5 off Product Standards ZB65 ZB65-XEZ 278474 2 off Can be snap fitted on a top-hat rail to IEC/EN 60715 or can be screw fitted. For ZB32-38, use BK25/3-PKZ0 additionally. ZW7... ZE Z5 ZB12 ZB32 ZB65 ZB150 M22-DZ-B 254833 10 off Button plate, blue Product Standards ZW7... ZE Z5 ZB12 ZB32 ZB65 ZB150 M22-DZ-B-GB14 254834 10 off Button plate, blue RESET Pushbuttons For enclosed Overload relay Mounting diameter: 22.3 mm Off button, IP65 ZW7... ZE Z5 ZB12 ZB32 ZB65 ZB150 M22-DZ-X 254835 10 off Without button plate, add button plate. Pushbuttons For enclosed Overload relay Mounting diameter: 22.3 mm Button plates M22-DZ-X M22-XD-R 216423 M22-XD-R-X0 218153 Documentation Overload relays Overload monitoring of EEx e motors Bases For separate mounting Pushbuttons For enclosed Overload relay Mounting diameter: 22.3 mm External reset button, IP65 ZE… ZB12… ZB32… ZB65… ZB150… M22-DZ-X M22-DZ-X Price See price list Information relevant for export to North America UL File No. UL CCN CSA File No. CSA Class No. NA Certification Max. Voltage Rating Degree of Protection UL File No. UL CCN CSA File No. CSA Class No. NA Certification Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification M22-XD-R-GB0 218194 10 off Button plate, red UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking E29184 NKCR 12528 3211-03 UL Listed, CSA certified 600 V AC IEC: IP00, UL/CSA Type: UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking E29184 NKCR 12528 3211-03 UL Listed, CSA certified UL 508; CSA-C22.2 No.14; IEC/EN 60947-4-1; CE marking E29184 NKCR 12528 3211-03 UL Listed, CSA certified UL/CSA certification not required Red button plate with white circle Button plate red STOP AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 28 1.2 Overload relays Accessories Z5..., K-B..., KS-B... 1 Covers For use with Part no. Article no. Direct mounting Z5-…/FF225 to DILM185A DILM225A Z5/FF225A-XHB-Z 139579 Price See price list Std. pack Notes 1 off Fitted directly to the contactor DILM400 -XHB DILM185A/ 225A Z5/FF225A -XHB-Z Z5-.../FF225A Z5/FF250 -XHB Z5-…/FF225A Z5-…/FF250 Covers Z5/FF250-XHB 215217 1 off Separate mounting Z5/FF250 -XHB Z5-.../FF250/ FF225A Z5/FF250 -XHB Direct mounting Z5-…/FF250 to DILM250 DILM300A Covers Z5/FF250-XHB-Z 215218 1 off Fitted directly to the contactor DILM400 -XHB DILM400 -XHB DILM250/ 300A DILM185A/ 225A Z5/FF250 -XHB-Z Z5/FF225A -XHB-Z Z5-.../FF250 Z5-.../FF225A Z5/FF250 -XHB Z5/FF250 -XHB Fitted directly to the contactor DILM400 -XHB DILM250/ 300A Z5/FF250 -XHB-Z Z5-.../FF250 Z5/FF250 -XHB Box terminals kit Consisting of 3 individual clamps For use with For connection of copper flat strip max. W×H mm Part no. Article no. With protective cover Z5-…/FF250 24 × 26 With control circuit terminal and protective cover Z5-…/FF250 24 × 26 29 Price See price list Std. pack Notes K-B-DIL6AM 064062 1 off When using box terminals the protective covers must be used. KS-B-DIL6AM 064063 1 off When using box terminals the protective covers must be used. AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Fitted directly to the contactor Overload relays 1.2 Selection criteria for North America 1 Engineering Protection of single-phase and DC current motors: Mounting position: 1 pole ZE 2 pole ZB12, ZB32, ZB65, ZB150, Z5 Tripping characteristics These tripping characteristics are mean values of the spread at 20 °C ambient temperature in a cold state. They show the tripping times in relation to the response current. When the devices are at operational temperature the tripping time of the overload relay drops to approx. 25% of the value shown. Specific characteristics for each individual setting range can be found in the manual on Page 28 1 1.5 2 3 4 6 8 10 15 20 x Setting current Minutes 3-phase 2-phase 1 1.5 2 3 4 6 8 10 15 20 x Setting current 2h 100 60 40 20 10 6 4 2 1 40 20 10 6 4 2 1 0.6 Z5 Minutes ZW7 Maximum 3 phase Seconds 2-phase 2h 100 60 40 20 10 6 4 2 1 40 20 10 6 4 2 1 0.6 ZB150 Minimum Seconds 3-phase Seconds Seconds 2h 100 60 40 20 10 6 4 2 1 40 20 10 6 4 2 1 0.6 Minutes ZB12, ZB32, ZB65, ZE Minutes 2h 100 60 40 20 10 6 4 2 1 40 20 10 6 4 2 1 0.6 1 1.5 2 3 4 6 8 10 15 20 x Setting current 2 phase 1 1.5 2 3 4 6 8 10 15 20 x Setting current Adaption of ZW7 to smaller rated motor currents Number of loops ZW7 -63 1 2 3 4 5 Rated motor current IN [A] 42-63 60-90 21-31,5 30-45 14-21 20-30 10.5-15,8 15-22,5 8.4-12,6 12-18 -90 -125 -160 -240 -290 -400 -540 -630 85-125 42.5-62,5 28.3-41,7 21.3-31,3 17-25 110-160 55-80 36.7-53,3 27.5-40 22-32 160-240 80-120 53.3-80 40-60 32-48 190-290 95-145 63.3-96,7 47.5-72,5 38-58 270-400 135-200 90-133,3 67.5-100 54-80 360-540 180-270 120-180 90-135 72-108 420-630 210-315 140-210 105-157,5 84-126 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 30 1.2 1 Overload relays UL/CSA-short-circuit strength For North America ZE, ZB, Z5 Overload relay short-circuit strength UL508, CSA-C22,2 No. 14/SCCR values ZE-0,16 ZE-0.24 ZE-0.4 ZE-0.6 ZE-1,0 ZE-1.6 ZE-2.4 ZE-4 ZE-6 ZE-9 ZE-12 ZB12(32)-0,16 ZB12(32)-0,24 ZB12(32)-0,4 ZB12(32)-0,6 ZB-12(32)-1,0 ZB-12(32)-1,6 ZB-12(32)-2,4 ZB-12(32)-4 ZB-12(32)-6 ZB-12(32)-10 ZB12-12 ZB12-16 ZB32-16 ZB32-24 ZB32-32 ZB65-10 ZB65-16 ZB65-24 ZB65-40 ZB65-57 ZB65-65 ZB65-75 31 Fuse acc. to NEC, CEC A kA CB A kA 600V AC 1 1 1 1 3 6 6 15 20 35 45 600V AC 1 CLASS J/CC 1 CLASS J/CC 1 CLASS J/CC 1 CLASS J/CC 1 CLASS J/CC 3 CLASS J/CC 3 CLASS J/CC 6 CLASS J/CC 10 CLASS J/CC 15 CLASS J/CC 15 CLASS J/CC 30 CLASS J/CC 35 CLASS J 45 CLASS J 60 CLASS J 600V AC 15 CLASS J 35 CLASS J 45 CLASS J 60 CLASS J 110 CLASS J 125 CLASS J 125 CLASS J 480V AC 15 15 15 15 15 15 15 15 15 15 - 5 5 5 5 5 5 5 5 5 5 - 5 5 5 5 5 5 5 5 5 5 5 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 600V AC 40 60 90 125 150 150 150 - ZB150-50 ZB150-70 ZB150-100 ZB150-125 ZB150-150 ZB150-175 ZB150-50(KK) ZB150-70(KK) ZB150-100(KK) ZB150-125(KK) ZB150-150(KK) ZB150-175(KK) Z5-70/... Z5-100/... Z5-125/... Z5-160/... Z5-220/... Z5-250/... Z5-70/... Z5-100/... Z5-125/... Z5-160/... 5 5 5 5 10 10 10 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Fuse acc. to NEC, CEC A kA CB A 600V AC 225 250 400 CLASS J 500 CLASS J 600 CLASS J 600 CLASS J 110 CLASS J 125 CLASS J 200 CLASS J 250 CLASS J 300 CLASS J 300 CLASS J 600V AC 250 400 CLASS J 500 CLASS J 600 CLASS J 800 CLASS J 700 CLASS J 125 CLASS J 200 CLASS J 250 CLASS J 300 CLASS J 600 V AC 200 250 400 500 600 600 200 250 400 500 600 600 600V AC 250 400 500 600 800 600 - 5 10 10 10 10 10 100 100 100 100 100 100 10 10 10 10 10 10 100 100 100 100 kA 5 10 10 10 10 10 5 10 10 10 10 10 10 10 10 10 10 10 - Overload relays 1.2 Overload relays Technical data 1 ZE, ZB ZE General Standards Climatic proofing ZB12, ZB32 ZB65 ZB150(KK) IEC/EN 60947, VDE 0660, UL, CSA Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature Open 1) Enclosed 1) Temperature compensation °C -25…50 -25…55 -25…55 -25…55 °C -25…40 Continuous -25…40 -25…40 -25…40 kg g 0.07 10 0.15 10 0.25 10 1.64 10 IP20 IP20 IP00 IP00 Mounting position Page 30 Weight Mechanical shock resistance half-sinusoidal shock, 10 ms to IEC 60068-2-27 Protection type Protection against direct contact when actuated from front (EN 50274) Main contacts Rated impulse withstand voltage Finger- and back-of-hand proof U imp V AC Overvoltage category/pollution degree Rated insulation voltage AC Rated operating voltage Safe isolation according to EN 61140 6000 6000 6000 8000 III/3 III/3 III/3 III/3 Ui V AC 690 690 690 1000 Ue V AC 690 690 690 1000 V AC V AC 300 300 440 440 440 440 440 440 Between auxiliary contacts and main contacts Between the main contacts Overload relay setting range A 0.1…12 0.1…38 6…75 25…175 Temperature compensation residual error > 40 ºC Short-circuit protection rating maximum fuse %/K ≦0.25 Page 13 ≦0.25 Page 15 ≦0.25 Page 17 ≦0.25 Page 17 W W 2.5 6 2.5 6 3 7.5 16 18 Solid Flexible with ferrule mm² mm² 2 × (0.75 - 2.5) 2 × (0.5 - 1.5) Stranded mm² – 2 × (1 - 6) 5) 2 × (1 - 4) 5) 2 × (1 - 6) 3) – 2 × (1 - 16) 4) 1 × (1…25) 2 × (1…10) 2) 1 × (16…25) 14 - 2 2 × (4 - 16) 1 × (4 - 70) 2 × (4 - 50) 1 × (16…50) 2 × (16…50) 3/0 Current heat loss (3 conductors) Lower value of setting range Upper value of setting range Terminal capacity AWG 18 - 14 14 - 8 5) mm – – – – Terminal screw Tightening torque Nm M3.5 1.2 M4 1.85) M6 3.5 M10 10 Tools Pozidriv screwdriver Size 2 2 2 – mm 0.8 × 5.5 1×6 1×6 – mm – – – 5 Solid or stranded Busbar Width Flat-blade sc rewdriver Hexagon soc ket Notes SW 1) Ambient temperature: Operating range to IEC/EN 60947, PTB: -5°C to +55°C Use identical cross-section when using two conductors 6 mm flexible with ferrules to DIN 46228 4) With ZB65-XEZ max 1 × (1… 16) 5) ZB32-38: solid and flexible with ferrule, 2.5 - 25 mm², 3 Nm tightening torque. AWG10-b, 27 lb-in tightening torque for solid or stranded conductors. 2) 3) AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 32 1.2 1 Overload relays Overload relays, CT-operated overload relays Z5, ZW7 Z5-…/FF225A(250) ZW7 IEC/EN 60947, VDE 0660, UL, CSA Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 IEC/EN 60947, VDE 0660, UL, CSA °C -25…50 -25…50 °C -25…40 Continuous -25…40 Continuous General Standards Climatic proofing Ambient temperature Open 1) Enclosed 1) Temperature compensation Mounting position Weight kg Page 30 1.55 Any 0.8 Mechanical shock resistance half-sinusoidal shock, 10 ms g 10 10 IP00 IP00 With terminal cover Finger- and back-of-hand proof to IEC 60068-2-27 Protection type Protection against direct contact when actuated from front (EN 50274) Main contacts U imp V AC 8000 III/3 6000 III/3 Ui V AC 1000 690 Ue V AC 1000 690 V AC V AC 440 440 440 440 Overload relay setting range A 50…300 42…630 Temperature compensation residual error > 40 ºC %/K ≦ 0.25 Rated impulse withstand voltage Overvoltage category/pollution degree Rated insulation voltage AC Rated operating voltage Safe isolation according to EN 61140 Between auxiliary contacts and main contacts Between the main contacts Short-circuit protection rating maximum fuse Page 19 – With overload relay in conjunction with a transformer as required for the contactor Current heat loss (3 conductors) Lower value of setting range W 16 3 Upper value of setting range W 28 10 mm² mm² 95 120 – – Terminal capacity Flexible with ferrule Stranded with ferrule Solid or stranded Flat conductor. Busbar Push-through opening AWG 250 MCM – Number of segments × width × thickness mm 6 × 16 × 0.82) – Width mm mm 20 × 3 – – 27 Nm M8 × 25 24 – – mm 13 – Terminal screw Tightening torque Tools Hexagonal socket Notes 33 SW 1) Ambient temperature: Operating range to IEC/EN 60947, PTB: -5°C to +50°C 2) Fixing with box terminals AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Overload relays 1.2 Overload relays, CT-operated overload relays ZE, ZB, Z5, ZW7 1 ZE Auxiliary and control circuits Rated impulse withstand voltage U imp V Overvoltage category/Pollution degree ZB12, ZB32 ZB65 ZB150(KK) Z5-.../FF225 Z5-.../FF250 ZW7 6000 6000 6000 6000 6000 6000 III/3 III/3 III/3 III/3 III/3 III/3 Terminal capacity Solid mm² 2 × (0.75 - 2.5) 2 × (0.75 - 4) 2 × (0.75 - 4) 2 × (0.75 - 4) 2 × (0.75 - 4) 2 × (0.75 - 4) Flexible with ferrule mm² 2 × (0.5 - 1.5) 2 × (0.75 - 2.5) 2 × (0.75 - 2.5) 2 × (0.75 - 2.5) 2 × (0.75 - 2.5) 2 × (0.75 - 2.5) Solid or stranded Terminal screw AWG 2 × (18 - 12) M3.5 2 × (18 - 12) M3.5 2 × (18 - 12) M3.5 2 × (18 - 12) M3.5 2 × (18 - 12) M3.5 2 × (18 - 12) M3.5 Tightening torque Nm 0.8 - 1.2 0.8 - 1.2 0.8 - 1.2 0.8 - 1.2 0.8 - 1.2 0.8 - 1.2 Size 2 2 2 2 2 2 Ui Ue mm V AC V AC 0.8 × 5.5 690 500 1×6 500 500 1×6 500 500 1×6 500 500 1×6 500 500 1×6 500 500 V AC 300 240 240 240 240 240 I th A 6 6 6 6 6 6 Tools Pozidriv screwdriver Flat-blade screwdriver Auxiliary circuit rated insulation voltage Rated operating voltage Safe isolation according to EN 61140 Between the auxiliary contacts Conventional thermal current Rated operational current AC-15 N/O 120 V Ie A 1.5 1.5 1.5 1.5 1.5 1.5 240 V Ie A 1.5 1.5 1.5 1.5 1.5 1.5 415 V Ie A 0.5 0.5 0.5 0.5 0.5 0.5 500 V Ie A 0.3 0.5 0.5 0.5 0.5 0.5 NC 120 V Ie A 1.5 1.5 1.5 1.5 1.5 1.5 240 V 415 V Ie Ie A A 1.5 0.7 1.5 0.9 1.5 0.9 1.5 0.9 1.5 0.9 1.5 0.9 500 V Ie A 0.5 0.8 0.8 0.8 0.8 0.8 24 V Ie A 0.9 0.9 0.9 0.9 0.9 0.9 60 V Ie A 0.75 0.753) 0.753) 0.753) 0.753) 0.753) 110 V 220 V Ie Ie A A 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 AC operated V – – – – – AC operated A – – – – – DC operated V 240 600 1.5 0.6 – – – – – – DC operated A – – – – – – AC operated D300 DC operated R300 B300 4) B600 5) R300 B300 4) B600 5) R300 B300 4) B600 5) R300 B300 4) B600 5) R300 B300 4) B600 5) R300 4 6 6 6 6 6 DC-13 L/R ≦ 15 ms 1) General Use Pilot Duty Short-circuit rating without welding Max. fuse 2) Notes A gG/gL 1) Making and breaking conditions to DC-13, time constant as stated 2) See transparent overlay "Fuses" for time/current characteristics (please enquire) 3) Rated operational current DC-13, 60 V: N/O auxiliary contact 0.6 A 4) With opposite polarity 5) With same polarity AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 34 1.2 1 Electronic overload relays to 1500 A ZEB ZEB12, ZEB32 General Standards Climatic proofing ZEB65-45 ZEB65-100 ZEB150 IEC/EN 60947, VDE 0660, UL, CSA Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature Open Enclosed Temperature compensation Mounting position Mechanical shock resistance half-sinusoidal shock, 10 ms to IEC 60068-2-27 Protection type Protection against direct contact when actuated from front (EN 50274) Main contacts Rated impulse withstand voltage Overvoltage category/pollution degree Rated insulation voltage AC Rated operating voltage Safe isolation according to EN 61140 Between auxiliary contacts and main contacts Between the main contacts Overload relay setting range Terminal capacity Solid Solid or stranded Auxiliary and control circuits Rated impulse withstand voltage Overvoltage category/pollution degree Terminal capacity Solid Flexible with ferrule Solid or stranded Terminal screw Tightening torque Tightening torque Tools Pozidriv screwdriver Flat-blade screwdriver Auxiliary circuit rated insulation voltage Rated operating voltage Safe isolation according to EN 61140 Between the auxiliary contacts Conventional thermal current Rated operational current °C °C –25…65 –25…65 Continuous Any –25…65 –25…40 Continuous Any –25…65 –25…40 Continuous Any –25…65 –25…40 Continuous Any g 15 15 15 15 IP20 IP20 Finger- and back-of-hand proof IP20 IP20 U imp V AC 6000 III / 3 6000 III / 3 6000 III / 3 6000 III / 3 Ui Ue V AC V AC 690 690 690 690 690 690 690 690 V AC V AC A 600 600 0.3…45 600 600 9…45 600 600 20…100 600 600 20…100 mm² AWG 1 × 2.5 - 16 1 × 14 - 4 1 × 2.5 - 16 1 × 14 - 4 1 × 6 - 50 1 × 10 - 1 1 × 6 - 50 1 × 10 - 1 V 6000 III / 3 6000 III / 3 6000 III / 3 6000 III / 3 mm² mm² AWG Nm 2 × (0.75 - 4) 2 × (0.75 - 2.5) 2 × (18 - 12) M3.5 0.8 - 1.2 2 × (0.75 - 4) 2 × (0.75 - 2.5) 2 × (18 - 12) M3.5 0.8 - 1.2 2 × (0.75 - 4) 2 × (0.75 - 2.5) 2 × (18 - 12) M3.5 0.8 - 1.2 2 × (0.75 - 4) 2 × (0.75 - 2.5) 2 × (18 - 12) M3.5 0.8 - 1.2 lb-in 7 - 10.6 7 - 10.6 7 - 10.6 7 - 10.6 Ui Ue Size mm V AC V AC 2 1×6 500 500 2 1×6 500 500 2 1×6 500 500 2 1x6 500 500 I th V AC A 240 5 240 5 240 5 240 5 Ie Ie Ie Ie Ie Ie Ie Ie A A A A A A A A 1.5 1.5 0.5 0.5 1.5 1.5 0.9 0.8 1.5 1.5 0.5 0.5 1.5 1.5 0.9 0.8 1.5 1.5 0.5 0.5 1.5 1.5 0.9 0.8 1.5 1.5 0.5 0.5 1.5 1.5 0.9 0.8 Ie Ie Ie Ie A A A A 0.9 0.75 0 0.2 0.9 0.75 0.4 0.2 0.9 0.75 0.4 0.2 0.9 0.75 0.4 0.2 A gG/gL 6 6 6 6 U imp AC-15 N/O NC 120 V 240 V 415 V 500 V 120 V 240 V 415 V 500 V DC-13 L/R ≦15 ms 24 V 60 V 110 V 220 V Short-circuit rating without welding Max. fuse 35 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Thermistor machine protection relays EMT6 1.2 EMT6 General Standards Climatic proofing 1 IEC/EN 60947, VDE 0660, EN 55011 Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature Open °C -25…60 Enclosed Storage Mounting position Weight °C °C -25…45 -45 - 60 Any 0.15 Shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 Protection type g kg Protection against direct contact when actuated from front (EN 50274) Safe isolation according to EN 61140 Finger- and back-of-hand proof Between the contacts Between contacts and supply voltage Auxiliary and control circuits Rated impulse withstand voltage 10 IP20 U imp V AC 250 V AC 250 V AC Overvoltage category/pollution degree Auxiliary and control circuit terminal capacity 6000 III/3 Solid mm² AWG 1 × 2.5 2 × (0.5 - 1.5) 1 × 2.5 2 × (0.5 - 1.5) 20 - 14 Flexible with ferrule mm² Terminal screw Tightening torque Solid or stranded Nm M3.5 1.2 Tools Pozidriv screwdriver Size 2 mm 1×6 Ui V 400 415 V Ie A 3 415 V Ie A 3 240 V Ie A 3 415 V Ie A 1 Ie Ie A A 3 1 gG/gL A 6 Ui V 240 Ue V x Ue 2401) 0.85 - 1.1 VA W Ω Ω 3.5 2 ≧3600 ≦1600 Flat-blade screwdriver Auxiliary circuit Rated insulation voltage Rated operational current AC-14 N/O NC AC-15 N/O NC 240 V 415 V Max. short-circuit protective device Fuse Control circuit Rated insulation voltage Rated operational voltage Voltage tolerance Power consumption AC DC Trip at approx. Reset at approx. Notes 1) EMT6(-DB)230V: Ue = 230 V AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 36 1.2 Overload relays Dimensions Overloadrelays Base ZE-… ZB32-XEZ ZB65-XEZ 5.5 49 b2 b1 b 2x d 106 5 c2 58 32 45 a1 c 16.5 a a b c c2 a1 b1 b2 d >5 = ZB32 62 27.5 136 53 120 42 34 ZB12 84 88 39 45 27.5 102 39 OFF Reset/ON 45 ZB32-38 120 136 62 42 OFF Reset/ON 25 2 1 Overload relays 27.5 102 39 45 37 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical ZB32 45 85 90.5 3.8 35 75 40.5 M4 ZB65 60 86 112 4.7 50 75 47 M5 Overload relays Overload relays 1.2 Overload relays 1 ZB65 40 172 OFF Reset/ON 35 7.5 46.5 96.5 132 60 ZB150 90 160 70 OFF Reset/ON 44 74 91 277 156 170 150 7 5 134 16.5 95 100 118 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 38 1.2 Overload relays, CT-operated overload relays Overload relays ZB150-50/KK OFF Reset/ON 100 7 121 74 7 5 63 16.5 129 95 134 99 118 Z5 overload relays greater than 150A Z5-.../FF250 OFF Reset/ON 121 110 96 144 48 25 94 169 144 74 7 111 7 5 11 16.5 128 Current transformer-operated overload relays ZW7-… 1.5 7.5 4.3 26 55 85 55 44 M4 26 44 21 8 185 33 71 185 159 172 – 250 200 65 65 71 1 Overload relays 90° 27 39 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 90° 90° Reset/ON Overload relays Electronic overload relays 1.2 Electronic overload relays 1 ZEB32 ZEB12 117 139.5 76 43 79 161 143 70 34 97.5 103 33.2 108 40.5 103 33.2 45 108 40.5 45 ZEB65-45 ZEB65-100 146.1 146.1 132.5 213.6 57.5 107 184 87 57.5 132.5 5 33.2 40.5 45 103 108 38.6 46.2 128.2 136.3 55 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 40 1.2 Electronic overload relays Electronic overload relays ZEB150-100 111.8 175 160 289.1 145.4 85 90 38.6 132.4 63.2 140.5 116 51.7 ZEB150-100/KK 104.8 1 Overload relays 41 132.4 38.6 140.5 46.1 56 41 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Overload relays 1.2 Thermistor overload relays for machine protection, electronic overload relays Thermistor overload relays for machine protection, electronic overload relays Current sensors 1 206 89.2 127 193.5 234.2 165.1 106.1 190.5 205.4 ZEB-XCT600 ZEB-XCT300 ZEB-XCT1000 ZEB-XCT1500 330.2 188.9 304.6 317 10.1 83.5 383.5 ø 73.2 108 108 EMT6 thermistor overload relays for machine protection External reset button EMT6… M22-DZ-B M22-DZ-X 100 78 19 3.2 102 24.1 22.5 _> 3 o 29.5 2.5 8 22.3 2–5 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 42 C441 Overload and monitoring relay Product description 1.2 Contents C441 Overload and monitoring relay Description 1 Page C441 Overload and monitoring relay Features and benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Catalog number selection . . . . . . . . . . . . . . . . . . . . . . . . . . . Product selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical data and specifications . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 48 49 50 55 67 C441 Overload and monitoring relay Product description Eaton’s Motor Insight, the first product in the Intelligent Power Control Solutions family, is a highly configurable motor, load and line protection device with power monitoring, diagnostics and flexible communications allowing the customer to save energy, optimize their maintenance schedules and configure greater system protection, thus reducing overall costs and downtime. Motor Insight is available in either a line-powered or 120 Vac control powered design, capable of monitoring voltages up to 660 Vac. Each of these units is available in a 1–9 amp or a 5–90 amp FLA model. With external CTs, Motor Insight can protect motors up to 540 amps FLA. Available add-on accessories include communication modules for Modbus RTU, DeviceNet, PROFIBUS, Modbus TCP, EtherNet/IP and HTTP web services all with I/O options. For ease-of-use and operator safety, Motor Insight offers a remote display that mounts easily with two 30 mm knockouts. AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 44 1.2 1 C441 Overload and monitoring relay Features and benefits Features and Benefits Benefits Features Size/Range Broad FLA range of 1–540A Selectable trip class (5–30) Four operating voltage options Line-powered from 240 Vac, 480 Vac, 600 Vac Control-powered from 120 Vac Motor Control Two output relays One B300 Form C fault relay and one B300 ground fault shunt relay Other relay configurations are available, including one Form A and one Form B SPST (fault and auxiliary relays) allowing programmable isolated relay behavior and unique voltages One external remote reset terminal Trip status indicator Motor Protection Thermal overload Jam protection Current imbalance Current phase loss Ground fault Phase reversal Line Protection Over voltage Under voltage Voltage imbalance Voltage phase loss Monitoring Capabilities Current—average and phase rms Voltage—average and phase rms Power—motor kW Power factor Frequency Thermal capacity Run hours Ground fault current Current imbalance % Voltage imbalance % Motor starts Motor run hours Options Type 1, 12 remote display Type 3R remote display kit Communication modules Modbus Modbus with I/O DeviceNet with I/O PROFIBUS with I/O Modbus TCP with I/O EtherNet/IP with I/O Reliability and Improved Uptime Advanced diagnostics allows for quick and accurate identification of the root source of a motor, pump or power quality fault; reducing troubleshooting time and the loss of productivity, reducing repeat faults due to misdiagnosis, and increasing process output and profitability Provides superior protection of motors and pumps before catastrophic failure occurs Increases profitability with greater process uptime and throughput, reduced costs per repair, reduced energy consumption and extended equipment life Adjustments to overload configuration can be made at any time Safety IP20 rated terminal blocks Terminal blocks are set back from the display to reduce operator shock hazard Remote display (optional) does not require that the operator open the panel to configure the device Load Protection Under current Low power (kW) High power (kW) Standards and Certifications cULus listed NKCR, NKCR7, 508 UL® 1053 applicable sections for ground fault detection 45 CSA® certified (Class 3211-02) CE NEMA® IEC EN 60947-4-1 RoHS CCC AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Flexibility Communications modules Offered in a variety of configurations External snap-on modules provide support for multiple communications protocols Advanced power, voltage and current monitoring capabilities Communications modules and remote display can be used simultaneously Highly configurable fault and reset characteristics for numerous applications Fully programmable isolated fault and auxiliary relays Ease of Use Bright LED display with easy-to-understand setting and references Powered from line voltage or 120 Vac control power Remote display powered from base unit Full word descriptions and units on user interface C441 Overload and monitoring relay Features and benefits 1.2 Advanced Overload Education Description 1 Motor Insight Protection Definition Source Result Overload is a condition in which current draw to a motor exceeds 115% of the full load amperage rating over a period of time for an inductive motor. An increase in the load or torque that is being driven by the motor. Increase in current draw. Current leads to heat and insulation breakdown, which can cause system failure. Additionally, an increase in current can increase power consumption and waste valuable energy. Thermal trip behavior is defined by UL, CSA and IEC standards. The motor attempts to drive the load, which has more resistive force due to the mechanical interference. In order to drive the load, the motor draws an abnormal amount of current, which can lead to insulation breakdown and system failure. Provides a configurable Jam setting that is active during “motor run state” to avoid nuisance trips. An undetected ground fault can burn through multiple insulation windings, ultimately leading to motor failure. Motor Insight has ground fault protection capability down to 0.15 amps estimated from the existing three-phase CTs using the residual current method. That is, the three-phase current signals should sum to zero unless a ground fault (GF) condition is present. In the case of a GF, Motor Insight can alarm, trip the starter, or trip an alternative relay that can be used to shunt trip a breaker or light up a warning light. GF current can also be monitored in real-time through the advanced monitoring capabilities. Motor Protection Thermal overload A low voltage supply to the motor would cause the current to go high to maintain the power needed. Trip class is settable from 5–30 by 1 Provides power factor monitoring and low voltage protection features. A poor power factor would cause above normal current draw. Jam Ground fault Jam is similar to thermal overload in that it is a current draw on the motor above normal operating conditions. A line to ground fault. Mechanical stall, interference, jam or seizure of the motor or motor load. A current leakage path to ground. Trip Threshold 150–400% of FLA. Trip Delay 1–20 seconds. Note: GF settable thresholds vary with motor FLA. 0.15 amps may not be available in all cases. Provides two protection settings that address this problem. The user can choose to set current imbalance thresholds or voltage imbalance thresholds, each of which can trip the starter. Additionally, both of these may be monitored through Motor Insight’s advanced monitoring capabilities, allowing the customer to notice in realtime when and where a condition is present. Imbalanced phases (voltage and current) Uneven voltage or currents between phases in a three-phase system. When a three-phase load is powered with Imbalanced voltage causes large a poor quality line, the voltage per phase imbalanced currents and as a result this may be imbalanced. can lead to motor stator windings being overloaded, causing excessive heating, reduced motor efficiency and reduced insulation life. Phase loss—current (single-phasing) One of the three-phase current is not present. Multiple causes, loose wire, improper wiring, grounded phase, open fuse, and so on. Phase rotation (phase-reversal) Improper wiring, leading to phases being A miswired motor. Inadvertent phaseconnected to the motor improperly. reversal by the utility. Phase-reversal can cause unwanted directional rotation of a motor. In the event that the load attached to the motor can only be driven in one direction, the result could be significant mechanical failure and/or injury to an operator. Configurable phase protection, allowing the user to define the phase sequencing intended for that application. If no phase sequence is required, the user has the ability to disable this feature. Frequency variance When line frequency is inconsistent. Variations in frequency can cause increases in losses, decreasing the efficiency of the motor. In addition, this can result in interference with synchronous devices. Advanced monitoring capabilities allow the user to monitor frequency in real-time. Malfunctioning alternator speed regulator, or poor line quality caused by an overload of a supply powered by individual sources. Fixed protective setting that takes the Single-phasing can lead to unwanted motor vibrations in addition to the results starter offline if a phase drops below 60% of the other two phases. of imbalanced phases as listed above. AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 46 1.2 1 C441 Overload and monitoring relay Features and benefits Advanced Overload Education, continued Description Motor Insight Protection Definition Source Result Under current or low power Average rms current provided to the motor falls below normal operating conditions. Under current is usually associated with a portion of the user’s load disappearing. Examples of this would be a broken belt, a dry-pump (low suction head) or a dead-headed centrifugal pump. If under current goes undetected, a mechanical failure can and has occurred. In the case of a pump, running a pump dry or running a pump in a dead-headed condition can cause excessive heating, damaging expensive seals and breaking down desired fluid properties. Motor Insight has two protection settings to detect this: under current and low power. Low power is a more consistent way of ensuring detection as power is linear with motor load, where as current is not. An unloaded motor may draw 50% of its rated current, but the power draw will be less than 10% of rated power due to a low power factor. High power The motor load is drawing more power than it should at normal operating conditions. This is typical of batch processing applications where several ingredients flow into a mixer. When a substance’s consistency changes and viscosity increases from what is expected, the motor may use more power to blend the mixture. Out-of-tolerance conditions can be detected using the High Power and Low Power settings. If a high-power fault goes undetected, the result may be a batch of material that does not meet specification. Monitors the three-phase real power. If the real power value is estimated above the set threshold for the set length of time, a fault is detected and the overload will trip the starter. Additionally, power can be monitored in real-time. Over voltage When the line voltage to the motor exceeds the specified rating. Poor line quality. An over voltage condition leads to a lower than rated current draw and a poor power factor. A trip limit of 110% of rated voltage is recommended. Over voltage can also lead to exceeding insulation ratings. Monitors the maximum rms value of the three-phase voltages. If the rms value rises above the set threshold for the set length of time, a fault is detected and the overload can trip the starter or send and display an alarm of the condition. All line-related faults have an “alarm-notrip” mode. Under voltage When the line voltage to the motor is below the specified rating. Poor line quality. An under voltage condition leads to excessive current draw. This increases the heating of the motor windings and can shorten insulation life. A trip limit set to 90% of rated voltage is recommended. Monitors the minimum rms value of the three-phase voltages. If the rms value drops below the set threshold for the set length of time, a fault is detected and the overload can trip the starter or send and display an alarm of the condition. All line-related faults have an “alarm-no-trip” mode. Power-up delay Allows for starting motors and loads in a deliberate fashion. When there is a power failure, or power cycle, multiple loads come online simultaneously. Multiple loads starting simultaneously can cause sags affecting the operation of devices that may prevent successful startup. Configurable to delay closing the fault relay on power-up. For each Motor Insight controlling a motor, a different setting can be programmed, helping to maintain the integrity of your line power. Load Protection Line Protection If power is lost to a motor driving a pump, it may be necessary to delay a restart to allow the pump to come to a complete stop to prevent starting a motor during backspin. 47 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical C441 Overload and monitoring relay Catalog number selection 1.2 Catalog Number Selection 1 Motor Insight Overload Relays C441 B A NOUI Device Type C441 = Motor Insight overload relay Overload Relay Power Source Voltage B = 240 Vac (170–264 Vac) C = 480 Vac (323–528 Vac) D = 600 Vac (487–660 Vac) Blank = 120 Vac control power (170–660 Vac) Overload Relay Current Rating A = 1–9A (1–540A refer to Page 49 ) B = 5–90A (5–90A refer to Page 49 ) 0109 = 120 Vac control power (0–660 Vac, 1–9A) 0590 = 120 Vac control power (0–660 Vac, 5–90A) Internal User Interface Blank = With user interface (line powered models) NOUI = Without user interface (120 Vac control models) Motor Insight Overload Relays—Communications Modules and Accessory Types C441 K Device Type C441 = Motor Insight overload relay Communication Module DeviceNet module 4IN/2OUT 120 Vac DeviceNet module 4IN/2OUT 24 Vdc Modbus RTU module Modbus RTU module 4IN/2OUT 120 Vac Modbus RTU module 4IN/2OUT 24 Vdc PROFIBUS module 4IN/2OUT 120 Vac Modbus TCP / EtherNet/IP module 4IN/2OUT 120 Vac S = PROFIBUS module 4IN/2OUT 24 Vdc T = Modbus TCP / EtherNet/IP module 4IN/2OUT 24 Vdc Accessory Type 1 = Type 1 and 12 remote mounted display 3 = Type 3R kit for remote display CMP1 = Conversion plate K L M N P Q R = = = = = = = AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 48 1.2 1 C441 Overload and monitoring relay Product selection Product Selection Motor Insight Motor Insight Power Source Monitoring Range Current Range Catalog Number 240 Vac (170–264) 170–264 Vac 1–9A C441BA 5–90A C441BB 1–9A C441CA 5–90A C441CB 1–9A C441DA 5–90A C441DB 1–9A C4410109NOUI 5–90A C4410590NOUI 480 Vac (323–528) 323–528 Vac 600 Vac (489–660) 489–660 Vac 120 Vac (93.5–132) 170–660 Vac Motor Insight CT Multiplier and Wire Wrap Schedule Number of Loops Number of Conductors Through CT Primary CT Multiplier Setting External CT Kit Catalog Number ② 5–22.5A 3 4 4 — 6.67–30A 2 3 3 — 10–45A 1 2 2 — 20–90A 0 1 1 — 1–5A 1 2 2 — 2–9A 0 1 1 — 60–135A 0 1 150–(150:5) C441CTKIT150 120–270A 0 1 300–(300:5) C441CTKIT300 240–540A 0 1 600–(600:5) C441CTKIT600 Motor FLA Catalog Number ① Current Range: 5–90A C441_B and C4410590NOUI Current Range: 1–9A C441_A and C4410109NOUI Notes ① Underscore indicates Operating Voltage Code required. Operating Voltage Codes: Code Voltage B 240 Vac C 480 Vac D 600 Vac <empty> 120 Vac Control Power ② 49 Any manufacturer’s CTs may be used. AUTOMATION AND CONTROL www.eaton.com/seasia-electrical C441 Overload and monitoring relay Accessories 1.2 Accessories 1 Modbus Communication Module The Motor Insight Modbus Communication Module is a side-mounted device providing Modbus communication capability to the Motor Insight overload relay. The Modbus Communication Module with I/O provides communication, monitoring and control for the Motor Insight overload relay. Features and Benefits The Modbus communication module is capable of baud rates up to 115K The Modbus address and baud rate configuration can be easily changed using the Motor Insight user interface (C441M only) Modbus address and baud rate are set via convenient DIP switches (C441N and C441P); LEDs are provided to display Modbus traffic Configuration with common Modbus configuration tools Terminals Unique locking mechanism provides for easy removal of the terminal block with the field wiring installed Each terminal is marked for ease of wiring and troubleshooting Selectable I/O assemblies 4IN/2OUT Signal types include 24 Vdc I/O and 120 Vac I/O Each I/O module is optically isolated between the field I/O and the network adapter to protect the I/O and communication circuits from possible damage due to transients and ground loops Input Module features a user-definable input debounce, which limits the effects of transients and electrical noise Output Module supports a user-definable safe state for loss of communication; hold last state, ON or OFF Modbus Communication Module Description I/O Catalog Number Modbus Module Modbus Communication Module None C441M Modbus with I/O Module Modbus Communication Module 4IN/2OUT 120 Vac C441N Modbus Communication Module 4IN/2OUT 24 Vdc C441P AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 50 1.2 1 C441 Overload and monitoring relay Accessories DeviceNet Communication Modules The DeviceNet Features and Benefits Communication Module Communication to provides monitoring and DeviceNet uses only one control for the Motor Insight DeviceNet MAC ID overload relay from a single Configuration DeviceNet node. These DeviceNet MAC ID and modules also offer convenient Baud rate are set via I/O in two voltage options, convenient DIP switches 24 Vdc and 120 Vac. with an option to set from the network Advanced configuration available using common DeviceNet tools Terminals Unique locking mechanism provides for easy removal of the terminal block with the field wiring installed Each terminal is marked for ease of wiring and troubleshooting DeviceNet Module DeviceNet Modules I/O Catalog Number DeviceNet Communication Module 120 Vac C441K DeviceNet Communication Module 24 Vdc C441L Description 51 Selectable I/O assemblies 4IN/2OUT Signal types include 24 Vdc I/O and 120 Vac I/O Each I/O module is optically isolated between the field I/O and the network adapter to protect the I/O and communication circuits from possible damage due to transients and ground loops AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Input Module features a user-definable input debounce, which limits the effects of transients and electrical noise Output Module supports a user-definable safe state for loss of communication; hold last state, ON or OFF Combined status LED C441 Overload and monitoring relay Accessories PROFIBUS Communication Module The Motor Insight PROFIBUS Communication Module is a side-mounted device providing PROFIBUS communication capability to the Motor Insight overload relay. The PROFIBUS Communication Module with I/O provides communication, monitoring and control for the Motor Insight overload relay. PROFIBUS with I/O Module 1.2 1 Features and Benefits The PROFIBUS communication module is capable of baud rates up to 12 Mb PROFIBUS address is set via convenient DIP switches (C441Q and C441S); LEDs are provided to display PROFIBUS status Intuitive configuration with common PROFIBUS configuration tools Terminals Unique locking mechanism provides for easy removal of the terminal block with the field wiring installed Each terminal is marked for ease of wiring and troubleshooting Selectable I/O assemblies 4IN/2OUT Signal types include 24 Vdc I/O and 120 Vac I/O Each I/O module is optically isolated between the field I/O and the network adapter to protect the I/O and communication circuits from possible damage due to transients and ground loops Input Module features a user-definable input debounce, which limits the effects of transients and electrical noise Output Module supports a user-definable safe state for loss of communication; hold last state, ON or OFF PROFIBUS Communication Module I/O Catalog Number PROFIBUS Communication Module 4IN/2OUT 120 Vac C441S PROFIBUS Communication Module 4IN/2OUT 24 Vdc C441Q Description AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 52 1.2 1 C441 Overload and monitoring relay Accessories Ethernet Communication Module The Motor Insight Ethernet Communication Module is a side-mounted device providing both Modbus TCP and EtherNet/IP communication capabilities with built-in HTTP web services to the Motor Insight overload relay. The Ethernet Communication Module with I/O provides communication, monitoring and control for the Motor Insight overload relay. Ethernet with I/O Module Features and Benefits Supports Modbus TCP or EtherNet/IP in a single device Contains internal embedded switch which provides two Ethernet ports allowing linear or ring network configurations Embedded web services allow for simple configuration and monitoring through Internet Explorer IP Address is set via convenient DIP Switches located on the device Ethernet Communication Module Description 53 Terminals Unique locking mechanism provides for easy removal of the terminal block with the field wiring installed Each terminal is marked for ease of wiring and troubleshooting Selectable I/O assemblies 4IN/2OUT Signal types include 24 Vdc I/O and 120 Vac I/O I/O Catalog Number Modbus TCP / EtherNet/IP Communication Module 4IN/2OUT 120 Vac C441R Modbus TCP / EtherNet/IP Communication Module 4IN/2OUT 24 Vdc C441T AUTOMATION AND CONTROL www.eaton.com/seasia-electrical Each I/O module is optically isolated between the field I/O and the network adapter to protect the I/O and communication circuits from possible damage due to transients and ground loops Input Module features a user-definable input debounce, which limits the effects of transients and electrical noise Output Module supports a user-definable safe state for loss of communication; hold last state, ON or OFF C441 Overload and monitoring relay Accessories Type 3R Kit with Remote Display Mounted Inside Features and Benefits Motor Insight offers several accessories for the Remote display unit: customer’s ease of use Same user interface as and safety: the overload relay Types 1 and 12 remote Enhanced operator display safety—operator can Type 3R remote display kit configure the overload without opening the Mounting plate adapter enclosure door 1.2 1 Type 3R kit mounts with standard 30 mm holes Mounting plate for retrofit in existing installations Type 3R Kit with Remote Display Mounted Inside Description Catalog Number C4411 Remote display Types 1 and 12 (UL 508) C4411 C4413 Type 3R kit for remote display (UL 508) C4413 Conversion plate (not shown) C441CMP1 Communication Cables The Remote Display requires a communication cable to connect to the Motor Insight overload relay: Communication Cable Lengths Length in Inches (meters) Catalog Number 9.8 (0.25) D77E-QPIP25 39.4 (1.0) D77E-QPIP100 78.7 (2.0) D77E-QPIP200 118.1 (3.0) D77E-QPIP300 Current Transformer Kits Description Catalog Number Three 150:5 CTs to be used with Motor Insight C441CTKIT150 Three 300:5 CTs to be used with Motor Insight C441CTKIT300 Three 600:5 CTs to be used with Motor Insight C441CTKIT600 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 54 1.2 1 C441 Overload and monitoring relay Technical data and specifications Technical Data and Specifications Motor Insight Description Specification C441B_ C441C_ C441D_ C441_ _ _ _NOUI Electrical Ratings Feature Range Operating voltage (threephase) and frequency 170–264 Vac 50/60 Hz 323–528 Vac 50/60 Hz 489–660 Vac 50/60 Hz 170–660 Vac 50/60 Hz Selectable Selectable Selectable Selectable C441_A and C4410109NOUI 1–9A C441_B and C4410590NOUI 5–90A Up to 540A with external CTs Refer to Page 49 for CT multiplier and wire wrap schedule. Trip Class 5–30 FLA Range Up to 540A with external CTs Refer to Page 49 for CT multiplier and wire wrap schedule. Up to 540A with external CTs Refer to Page 49 for CT multiplier and wire wrap schedule. Monitoring Capabilities Feature Value Current Per phase rms (1A, 1B, 1C), 2% accuracy Average rms, 2% accuracy Imbalance percent (0–100%) Ground fault current, 10% accuracy Per phase rms (1A, 1B, 1C), 2% accuracy Average rms, 2% accuracy Imbalance percent (0–100%) Ground fault current, 10% accuracy Per phase rms (1A, 1B, 1C), 2% accuracy Average rms, 2% accuracy Imbalance percent (0–100%) Ground fault current, 10% accuracy Per phase rms (1A, 1B, 1C), 2% accuracy Average rms, 2% accuracy Imbalance percent (0–100%) Ground fault current, 10% accuracy Voltage Per phase rms (1A, 1B, 1C), 2% accuracy Average rms, 2% accuracy Imbalance percent (0–100%) Per phase rms (1A, 1B, 1C), 2% accuracy Average rms, 2% accuracy Imbalance percent (0–100%) Per phase rms (1A, 1B, 1C), 2% accuracy Average rms, 2% accuracy Imbalance percent (0–100%) Per phase rms (1A, 1B, 1C), 2% accuracy Average rms, 2% accuracy Imbalance percent (0–100%) Power Motor kW, 5% accuracy Motor power factor, inductive 0–1.0, 1% accuracy Motor kW, 5% accuracy Motor power factor, inductive 0–1.0, 1% accuracy Motor kW, 5% accuracy Motor power factor, inductive 0–1.0, 1% accuracy Motor kW, 5% accuracy Motor power factor, inductive 0–1.0, 1% accuracy Thermal capacity 0% cold, 100% trip 0% cold, 100% trip 0% cold, 100% trip 0% cold, 100% trip Motor run hours 0–65,535 hours 0–65,535 hours 0–65,535 hours 0–65,535 hours Frequency 47–63 Hz, 1% accuracy 47–63 Hz, 1% accuracy 47–63 Hz, 1% accuracy 47–63 Hz, 1% accuracy 1.05 x FLA: Does not trip 1.15 x FLA: Overload trip 1.05 x FLA: Does not trip 1.15 x FLA: Overload trip 1.05 x FLA: Does not trip 1.15 x FLA: Overload trip 1.05 x FLA: Does not trip 1.15 x FLA: Overload trip Motor Protection Thermal overload setting Fault Delay Setting Feature Range Jam 150–400% of motor FLA, OFF 150–400% of motor FLA, OFF 150–400% of motor FLA, OFF 50–400% of motor FLA, OFF 1–20 seconds Current imbalance 1–30%, OFF 1–30%, OFF 1–30%, OFF 1–30%, OFF 1–20 seconds Current phase loss Fixed threshold 60% Fixed threshold 60% Fixed threshold 60% Fixed threshold 60% 1–20 seconds C441_A and C4410109NOUI 1–9A 0.3–2.0A with one pass through the CTs ① 0.3–2.0A with one pass through the CTs ① 0.3–2.0A with one pass through the CTs ① 0.3–2.0A with one pass through the CTs ① <150%, 1–60 seconds >150%, 2 seconds >250%, 1 second C441_B and C4410590NOUI 5–90A 3.0–20A with one pass through the CTs ① 3.0–20A with one pass through the CTs ① 3.0–20A with one pass through the CTs ① 3.0–20A with one pass through the CTs ① <150%, 1–60 seconds >150%, 2 seconds >250%, 1 second Ground fault current Phase reversal OFF = Ignore, 1 = ACB, 2 = ABC OFF = Ignore, 1 = ACB, 2 = ABC OFF = Ignore, 1 = ACB, 2 = ABC Fault reset delay 2–500 minutes, auto ② OFF = Ignore, 1 = ACB, 2 = ABC 2–500 minutes, auto ② 2–500 minutes, auto ② 2–500 minutes, auto ② Fault reset attempts 0–4 restarts allowed or automatic reset ② 0–4 restarts allowed or automatic reset ② 0–4 restarts allowed or automatic reset ② 0–4 restarts allowed or automatic reset ② Notes ① Lower levels are achievable with multiple passes. ② Motor fault reset characteristics can be programmed as a group or for motor overloads only. Reference the user manual for more detailed information. 55 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical C441 Overload and monitoring relay Technical data and specifications 1.2 Motor Insight, continued Description Specification C441B_ 1 C441C_ C441D_ C441_ _ _ _NOUI 50–90% of motor FLA 50–90% of motor FLA 50–90% of motor FLA Load Protection Feature Range Under current 50–90% of motor FLA Fault Delay Setting 1–60 seconds Low power (kW) 20–80% of rated kW 20–80% of rated kW 20–80% of rated kW 20–80% of rated kW 1–60 seconds High power (kW) 50–110% of rated kW 50–110% of rated kW 50–110% of rated kW 50–110% of rated kW 1–60 seconds Load reset delay 2–500 minutes, auto 2–500 minutes, auto 2–500 minutes, auto 2–500 minutes, auto Load reset attempts 0–4, auto 0–4, auto 0–4, auto 0–4, auto Supply Protection Feature Range Over voltage 170–264 Vac 323–528 Vac 489–660 Vac 0–660 Vac Fault Delay Setting 1–20 seconds Under voltage 170–264 Vac 323–528 Vac 489–660 Vac 0–660 Vac 1–20 seconds Voltage imbalance 1–20% imbalance 1–20% imbalance 1–20% imbalance 1–20% imbalance 1–20% imbalance Restart delay setting 1–500 seconds 1–500 seconds 1–500 seconds 1–500 seconds 1–500 seconds Radiated emissions IEC 60947-4-1—Table 15, EN 55011 (CISPIR 11) Group 1, Class A 30–1000 mHz 30–1000 mHz 30–1000 mHz 30–1000 mHz 30–1000 mHz Conducted emissions IEC 60947-4-1—Table 14, EN 55011 (CISPIR 11) Group 1, Class A 0.15–30 mHz 0.15–30 mHz 0.15–30 mHz 0.15–30 mHz 0.15–30 mHz ESD immunity IEC 60947-4-1 (Table 13) ±8 kV air, ±4 kV contact ±8 kV air, ±4 kV contact ±8 kV air, ±4 kV contact ±8 kV air, ±4 kV contact ±8 kV air, ±4 kV contact Radiated immunity IEC 60947-4-1 10 V/m 80–1000 mHz 80% amplitude modulated 1 kHz sine wave 10 V/m 80–1000 mHz 80% amplitude modulated 1 kHz sine wave 10 V/m 80–1000 mHz 80% amplitude modulated 1 kHz sine wave 10 V/m 80–1000 mHz 80% amplitude modulated 1 kHz sine wave 10 V/m 80–1000 mHz 80% amplitude modulated 1 kHz sine wave Conducted immunity IEC 60947-4-1 140 dBuV (10V rms) 150 kHz–80 mHz 140 dBuV (10V rms) 150 kHz–80 mHz 140 dBuV (10V rms) 150 kHz–80 mHz 140 dBuV (10V rms) 150 kHz–80 mHz 140 dBuV (10V rms) 150 kHz–80 mHz Fast transient immunity IEC 60947-4-1 (Table 13) IEC 61000-4-4 ±2 kV using direct method ±2 kV using direct method ±2 kV using direct method ±2 kV using direct method ±2 kV using direct method Surge immunity IEC 60947-4-1 (Table 13) IEC 61000-4-4 Three-phase power inputs: ±2 kV line-to-line (DM) ±4 kV line-to-ground (CM) Three-phase power inputs: ±2 kV line-to-line (DM) ±4 kV line-to-ground (CM) Three-phase power inputs: ±2 kV line-to-line (DM) ±4 kV line-to-ground (CM) Three-phase power inputs: ±2 kV line-to-line (DM) ±4 kV line-to-ground (CM) Three-phase power inputs: ±2 kV line-to-line (DM) ±4 kV line-to-ground (CM) IEC 61000-4-5 Class 3 User IO and communication lines: ±1 kV line-to-line (DM) ±2 kV line-to-ground (CM) IEC 61000-4-5 Class 3 User IO and communication lines: ±1 kV line-to-line (DM) ±2 kV line-to-ground (CM) IEC 61000-4-5 Class 3 User IO and communication lines: ±1 kV line-to-line (DM) ±2 kV line-to-ground (CM) IEC 61000-4-5 Class 3 User IO and communication lines: ±1 kV line-to-line (DM) ±2 kV line-to-ground (CM) IEC 61000-4-5 Class 3 User IO and communication lines: ±1 kV line-to-line (DM) ±2 kV line-to-ground (CM) Voltage variations immunity IEC 60947-4-1 30% dip, at 100 ms 60% dip at 10 ms >95% interrupt at 5 ms 30% dip, at 100 ms 60% dip at 10 ms >95% interrupt at 5 ms 30% dip, at 100 ms 60% dip at 10 ms >95% interrupt at 5 ms 30% dip, at 100 ms 60% dip at 10 ms >95% interrupt at 5 ms 30% dip, at 100 ms 60% dip at 10 ms >95% interrupt at 5 ms Electromagnetic field IEC 60947-4-1 (Table 13) IEC 61000-4-3 10 V/m 10 V/m 10 V/m 10 V/m 10 V/m Ground fault UL 508, UL 1053 Sections 21 and 27 UL 508, UL 1053 Sections 21 and 27 UL 508, UL 1053 Sections 21 and 27 UL 508, UL 1053 Sections 21 and 27 UL 508, UL 1053 Sections 21 and 27 Electrical/EMC AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 56 1.2 1 C441 Overload and monitoring relay Technical data and specifications Motor Insight, continued Specification C441B_ Description C441C_ C441D_ C441_ _ _ _NOUI Environmental Ratings Feature Range Ambient temperature (operating) –4° to 122°F (–20° to 50°C) –4° to 122°F (–20° to 50°C) –4° to 122°F (–20° to 50°C) –4° to 122°F (–20° to 50°C) Ambient temperature (storage) –40° to 85°C –40° to 85°C –40° to 85°C –40° to 85°C Operating humidity 5% to 95% noncondensing 5% to 95% noncondensing 5% to 95% noncondensing 5% to 95% noncondensing Altitude (no derating) 2000m 2000m 2000m 2000m Shock (IEC 60068-2-27) 15G any direction 15G any direction 15G any direction 15G any direction Vibration (IEC 60068-2-6) 3G any direction 3G any direction 3G any direction 3G any direction Pollution degree per IEC 60947-1 3 3 3 3 Ingress protection IP20 IP20 IP20 IP20 Capacity Input, auxiliary contact and external reset terminals Terminal capacity 18–12 AWG 18–12 AWG 18–12 AWG 18–12 AWG Tightening torque 5.3 lb-in (0.6 Nm) 5.3 lb-in (0.6 Nm) 5.3 lb-in (0.6 Nm) 5.3 lb-in (0.6 Nm) Voltages Monitoring voltage 170–264 Vac 50/60Hz 323–528 Vac 50/60Hz 489–660 Vac 60Hz 0–660 Vac 50/60Hz Insulation voltage Ui (three-phase voltage) 600 Vac 600 Vac 600 Vac 600 Vac Insulation voltage Ui (control) 240 Vac 240 Vac 240 Vac 240 Vac Impulse withstand Uimp (main/control) 6 kV 6 kV 6 kV 6 kV 10 years 10 years 10 years 10 years B300 pilot duty 5A thermal continuous current 30A make 3.00A break at 120 Vac and 15A make 1.50A break at 240 Vac B300 pilot duty 5A thermal continuous current 30A make 3.00A break at 120 Vac and 15A make 1.50A break at 240 Vac B300 pilot duty 5A thermal continuous current 30A make 3.00A break at 120 Vac and 15A make 1.50A break at 240 Vac B300 pilot duty 5A thermal continuous current 30A make 3.00A break at 120 Vac and 30A make 1.50A break at 240 Vac ① Isolated 120 Vac digital input IEC 61131-2 Section 5 Type 1 Isolated 120 Vac digital input IEC 61131-2 Section 5 Type 1 Isolated 120 Vac digital input IEC 61131-2 Section 5 Type 1 Isolated 120 Vac digital input IEC 61131-2 Section 5 Type 1 Trip Fault Fault Fault Fault Reset Ready Ready Ready Ready Autoreset Trip faulted/Ready flashing Trip faulted/Ready flashing Trip faulted/Ready flashing Trip faulted/Ready flashing 5W 5W 5W 5W Expected Life Mechanical/electrical Output Contact Ratings Two output relays One Form C SPDT (fault relay) One Form A SPST (ground fault relay) C441_ _ _ _NOUI models: One Form A SPST One Form B SPST External remote reset terminal Indications Power Consumption Maximum Options Remote display Type 1, 12 and Type 3R kit Type 1, 12 and Type 3R kit Type 1, 12 and Type 3R kit Type 1, 12 and Type 3R kit Communications modules Modbus, DeviceNet and PROFIBUS with I/O Modbus, DeviceNet and PROFIBUS with I/O Modbus, DeviceNet and PROFIBUS with I/O Modbus, DeviceNet and PROFIBUS with I/O Note ① In this model, there are two isolated relays: one Form A and one Form B SPST. One is the fault relay, and one is a programmable auxiliary relay. 57 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 1.2 C441 Overload and monitoring relay Technical data and specifications Motor Insight Short Circuit Ratings (North America CSA and UL) 1 Standard-Fault Short Circuit Data Overload FLA Range Maximum Operating Voltage Withstand Rating Maximum Fuse (RK5) Maximum Thermal-Magnetic Circuit Breaker 1–9A 264 Vac 5000A at 240 Vac 35A 35A 1–9A 1–9A 528 Vac 660 Vac 5000A at 480 Vac 5000A at 600 Vac 35A 35A 35A 35A 1–9A 660 Vac 5000A at 600 Vac 35A 35A 5–90A 264 Vac 10,000A at 240 Vac 350A 350A 5–90A 5–90A 5–90A 528 Vac 660 Vac 660 Vac 10,000A at 480 Vac 10,000A at 600 Vac 10,000A at 600 Vac 350A 350A 350A 350A 350A 350A Maximum Withstand Rating Maximum Fuse (RK5) Eaton Thermal-Magnetic Circuit Breaker Catalog Number C441BA 100 kA at 240 Vac 35A — 100 kA at 240 Vac — FDC3035L 100 kA at 480 Vac 35A — 100 kA at 480 Vac — FDC3035L C441CA 100 kA at 600 Vac 35A — 35 kA at 600 Vac — FDC3035L 100 kA at 240 Vac 100 kA at 240 Vac 100 kA at 480 Vac 100 kA at 480 Vac 100 kA at 600 Vac 35 kA at 600 Vac 35A — 35A — 35A — — FDC3035L — FDC3035L — FDC3035L C4410109NOUI C441BB 100 kA at 240 Vac 350A — 100 kA at 240 Vac — KDC3350 100 kA at 480 Vac 350A — 100 kA at 480 Vac — KDC3350 100 kA at 600 Vac 350A — 65 kA at 600 Vac — KDC3350 100 kA at 240 Vac 100 kA at 240 Vac 100 kA at 480 Vac 100 kA at 480 Vac 100 kA at 600 Vac 35 kA at 600 Vac 350A — 350A — 350A — — KDC3350 — KDC3350 — KDC3350 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical C441DA C441CB C441DB C4410590NOUI 58 1.2 1 C441 Overload and monitoring relay Technical data and specifications Line Powered Models Terminal Connection Diagram 18–12 AWG; Torque 5.3 lb-in/0.6 Nm B300 Pilot Duty Only Use 75C CU wire only 120 Vac NC L1 ① L2 ① L3 ① 95 NO 96 97 GF Shunt 98 15 16 Reset R1 R2 For C441BA, BB, CA, CB, DA and DB Terminal Connection Specifications Name Designation Input Description Line voltage L1, L2, L3 Line voltage Three-phase line voltage input L1, L2, L3 connections must correspond to the respective CT1, CT2, CT3 current leads Fault relay 95/96 96/97 (common) 97/98 B300 UL 508 Form C contact: 95/96 Contact opens when the unit is faulted or unpowered 97/98 Contact closes when the unit is faulted or unpowered GF shunt 15 16 B300 UL 508 Form A contact: Contact closes when a ground fault is active Reset input R1, R2 120 Vac Fault reset input IEC 61131-2 Type 1 Control Powered Models Terminal Connection Diagram 120 Vac NC L1 L2 L3 95 NO 96 97 Cntrl. Pwr. 98 X1 X2 120 Vac Reset R1 R2 For C4410109NOUI and C441059NOUI Terminal Connection Specifications N a me Designation Input Description Line voltage L1, L2, L3 Line voltage Three-phase line voltage input L1, L2, L3 connections must correspond to the respective CT1, CT2, CT3 current leads Terminal provided for wiring control power transformer (9A maximum capacity) Control power X1, X2 Control power option for C441_ _ _ _NOUI 110–120 Vac 50–60Hz (+10/–15%) Fault relay 95/96 For C441_ _ _ _NOUI, the fault relay and auxiliary relay are 96/97 (isolated) isolated and do not share a common. By default they will 97/98 behave like a Form C, but they can be programmed to act independently from one another. B300 UL 508 Form C contact: 95/96 Contact opens when the unit is faulted or unpowered 97/98 Contact closes when the unit is faulted or unpowered Can be programmed to act independently of the 95/96 only in the C441_ _ _ _NOUI models GF shunt This relay does not exist on the C441_ _ _ _NOUI models. Instead, this functionality is available in the fully programmable 97/98 auxiliary relay. 97/98 B300 UL 508 Form A contact: Contact closes when a ground fault is active Separate GF control can still be achieved by programming auxiliary relay 97/98 to act independently of the 95/96 relay Reset input R1, R2 120 Vac Fault reset input IEC 61131-2 Type 1 Note ① No motor loads, 9A maximum. 59 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical C441 Overload and monitoring relay Technical data and specifications 1.2 Modbus Communication Modules Description 1 Specification Electrical/EMC Radiated emissions IEC 60947-4-1—Table 15, EN 55011 (CISPIR 11) Group 1, Class A 30–1000 mHz Conducted emissions IEC 60947-4-1—Table 14, EN 55011 (CISPIR 11) Group 1, Class A 0.15–30 mHz ESD immunity IEC 60947-4-1 (Table 13) IEC 61000-4-2 ±8 kV air, ±4 kV contact Radiated immunity IEC 60947-4-1 10 V/m 80–1000 mHz 80% amplitude modulated 1 kHz sine wave Conducted immunity IEC 60947-4-1 140 dBuV (10V rms) 150 kHz–80 mHz Fast transient immunity IEC 60947-4-1 (Table 13) IEC 61000-4-4 ±2 kV using direct method Surge immunity IEC 60947-4-1 (Table 13) IEC 61000-4-5 Class 3 User IO and communication lines ① : ±1 kV line-to-line (DM) ±2 kV line-to-ground (CM) Electromagnetic field 1 IEC 60947-4-1 (Table 13) IEC 61000-4-3 10 V/m Environmental Ratings Ambient temperature (operating) –20° to 50°C Ambient temperature (storage) –40° to 85°C Operating humidity 5 to 95% noncondensing Altitude (no derating) 2000m Shock (IEC 60068-2-27) 15G any direction Vibration (IEC 60068-2-6) 3G any direction Pollution degree per IEC 60947-1 3 Degree of protection IP20 Over voltage category per UL 508 III C441P 24 Vdc Input Nominal input voltage 24 Vdc Operating voltage 18–30 Vdc Number of inputs 4 Signal delay 5 ms (programmable to 65 sec) OFF-state voltage <6 Vdc ON-state voltage >18 Vdc Nominal input current 5 mA Isolation 1500V Terminal screw torque 7–9 in-lb 24 Vdc source current 50 mA Operating Voltage Range—DC Input Modules OFF State Transition Region ON State 0–6 Vdc 6–18 Vdc 18–30 Vdc C441N 120 Vac Input Nominal input voltage 120 Vac Operating voltage 80–140 Vac Number of inputs 4 OFF-state voltage <30 Vac ON-state voltage >80 Vac Nominal input current 1 5 mA Signal delay 1/2 cycle Isolation 1500V Terminal screw torque 7–9 in-lb Note ① Relates to C441M only. AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 60 1.2 1 C441 Overload and monitoring relay Technical data and specifications Modbus Communication Modules, continued Description Specification Operating Voltage Range—AC Input Modules OFF State Transition Region ON State 0–30 Vac 30–80 Vac 80–140 Vac Output Modules Nominal voltage 120 Vac 24 Vdc Number of outputs (2) 1NO Form A 1NO/NC Form C Relay OFF time 3 ms Relay ON time 7 ms Max. current per point ① 5A (B300 rated) Electrical life 100,000 cycles Mechanical life 1,000,000 cycles DeviceNet Communication Modules Description Specification Electrical/EMC Radiated emissions IEC 60947-4-1—Table 15, EN 55011 (CISPIR 11) Group 1, Class A 30–1000 mHz Conducted emissions IEC 60947-4-1—Table 14, EN 55011 (CISPIR 11) Group 1, Class A 0.15–30 mHz ESD immunity IEC 60947-4-1 (Table 13) IEC 61000-4-2 ±8 kV air, ±4 kV contact Radiated immunity IEC 60947-4-1 10 V/m 80–1000 mHz 80% amplitude modulated 1 kHz sine wave Conducted immunity IEC 60947-4-1 140 dBuV (10V rms) 150 kHz–80 mHz Fast transient immunity IEC 60947-4-1 (Table 13) IEC 61000-4-4 ±2 kV using direct method Surge immunity IEC 60947-4-1 (Table 13) IEC 61000-4-5 Class 2 User IO and communication lines: ±1 kV line-to-line (DM) ±2 kV line-to-ground (CM) Electromagnetic field IEC 60947-4-1 Table 13, IEC 61000-4-3 10 V/m Environmental Ratings Ambient temperature (operating) –20° to 50°C Ambient temperature (storage) –40° to 85°C Operating humidity 5–95% noncondensing Altitude (no derating) 2000m Shock (IEC 60068-2-27) 15G any direction Vibration (IEC 60068-2-6) 3G any direction Pollution degree per IEC 60947-1 3 Degree of protection IP20 DeviceNet DeviceNet connections Group 2, polling, bit strobe, explicit, no UCMM DeviceNet baud rate 125K, 250K, 500K Note ① Resistive current at 55°C ambient. 61 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical C441 Overload and monitoring relay Technical data and specifications 1.2 DeviceNet Communication Modules, continued Description 1 Specification C441L 24 Vdc Input Nominal input voltage 24 Vdc Operating voltage 18–30 Vdc Number of inputs 4 Signal delay 5 ms (programmable to 65 sec) OFF-state voltage <6 Vdc ON-state voltage >18 Vdc Nominal input current 5 mA Isolation 250V Terminal screw torque 7–9 in-lb 24V source current 5 0 mA Operating Voltage Range—DC Input Modules OFF State Transition Region ON State 0–6 Vdc 6–18 Vdc 18–30 Vdc C441K 120 Vac Input Nominal input voltage 120 Vac Operating voltage 80–140 Vac Number of inputs 4 OFF-state voltage <30 Vac ON-state voltage >80 Vac Nominal input current 1 5 mA Signal delay 1/2 cycle Isolation 250V Terminal screw torque 7–9 in-lb Operating Voltage Range—AC Input Modules OFF State Transition Region ON State 0–30 Vac 30–80 Vac 80–140 Vac Output Modules Nominal voltage 120 Vac 24 Vdc Number of outputs (2) 1NO Form A 1NO/NC Form C Relay OFF time 3 ms Relay ON time 7 ms Max. current per point ① 5A (B300 rated) Electrical life 100,000 cycles Mechanical life 1,000,000 cycles Note ① Resistive current at 55°C ambient. AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 62 1.2 1 C441 Overload and monitoring relay Technical data and specifications PROFIBUS Communication Modules Description Specification Electrical/EMC Radiated emissions IEC 60947-4-1—Table 15, EN 55011 (CISPIR 11) Group 1, Class A 30–1000 mHz Conducted emissions IEC 60947-4-1—Table 14, EN 55011 (CISPIR 11) Group 1, Class A 0.15–30 mHz ESD immunity IEC 60947-4-1 (Table 13) IEC 61000-4-2 ±8 kV air, ±4 kV contact Radiated immunity IEC 60947-4-1 Table 13, IEC 61000-4-3 10 V/m 80–1000 mHz 80% amplitude modulated 1 kHz sine wave Conducted immunity IEC 60947-4-1 140 dBuV (10V rms) 150 kHz–80 mHz Fast transient immunity IEC 60947-4-1 (Table 13) IEC 61000-4-4 ±2 kV using direct method Surge immunity IEC 60947-4-1 (Table 13) IEC 61000-4-5 Class 2 User IO and communication lines: ±1 kV line-to-line (DM) ±2 kV line-to-ground (CM) Environmental Ratings Ambient temperature (operating) –20° to 50°C Ambient temperature (storage) –40° to 85°C Operating humidity 5–95% noncondensing Altitude (no derating) 2000m Shock (IEC 60068-2-27) 15G any direction Vibration (IEC 60068-2-6) 3G any direction Pollution degree per IEC 60947-1 3 Degree of protection IP20 PROFIBUS PROFIBUS connections Group 2, polling, bit strobe, explicit, no UCMM PROFIBUS baud rate 9.6K, 19.2K, 45.45K, 93.75K, 187.5K, 500K, 1.5M, 3M, 6M, 12M C441Q 24 Vdc Input Nominal input voltage 24 Vdc Operating voltage 18–30 Vdc Number of inputs 4 Signal delay 5 ms (programmable to 65 sec) OFF-state voltage <6 Vdc ON-state voltage >10 Vdc Nominal input current 5 mA Isolation 1500V Terminal screw torque 7–9 in-lb 24V source current 50 mA 63 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical C441 Overload and monitoring relay Technical data and specifications 1.2 1 PROFIBUS Communication Modules, continued Description Specification Operating Voltage Range—DC Input Modules OFF State Transition Region ON State 0–6 Vdc 6–18 Vdc 18–30 Vdc C441S 120 Vac Input Nominal input voltage 120 Vac Operating voltage 80–140 Vac Number of inputs 4 OFF-state voltage <20 Vac ON-state voltage >70 Vac Nominal input current 1 5 mA Signal delay 1/2 cycle Isolation 1500V Terminal screw torque 7–9 in-lb Operating Voltage Range—AC Input Modules OFF State Transition Region ON State 0–30 Vac 30–80 Vac 80–140 Vac Output Modules Nominal voltage 120 Vac 24 Vdc Number of outputs (2) 1NO Form A 1NO/NC Form C Relay OFF time 3 ms Relay ON time 7 ms Max. current per point ① 5A (B300 rated) Electrical life 100,000 cycles Mechanical life 1,000,000 cycles Note ① Resistive current at 55°C ambient. AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 64 1.2 1 C441 Overload and monitoring relay Technical data and specifications Ethernet (Modbus TCP / EtherNet/IP) Communication Modules Description Specification Electrical/EMC Radiated emissions IEC 60947-4-1, Table 15, EN 55011 (CISPIR 11) Group 1, Class A 30–1000 mHz Conducted emissions IEC 60947-4-1, Table 15, EN 55011 (CISPIR 11) Group 1, Class A 0.15–30 mHz ESD immunity IEC 60947-4-1 (Table 13) IEC 61000-4-2 ±8 kV air, ±4 kV contact Radiated immunity IEC 60947-4-1 (Table 13) IEC 61000-4-3 10 V/m 80–1000 mHz 80% amplitude modulated 1 kHz sine wave Conducted immunity IEC 60947-4-1 140 dBuV (10V rms) 150 kHz to 80 mHz Fast transient immunity IEC 60947-4-1 (Table 13) IEC 61000-4-4 ±2 kV using direct method Surge immunity IEC 60947-4-1 (Table 13) IEC 61000-4-5 Class 2 User IO and communication lines: ±1 kV line-to-line (DM) ±2 kV line-to-ground (CM) Environmental Ratings Ambient temperature (operating) –20° to 50°C Ambient temperature (storage) –40° to 85°C Operating humidity 5–95% noncondensing Altitude (no derating) 2000m Shock (IEC 60068-2-27) 15G any direction Vibration (IEC 60068-2-6) 3G any direction Pollution degree per IEC 60947-1 3 Degree of protection IP20 Ethernet Ethernet connections Integrated two-port switch with dual RJ45 Ethernet connections Ethernet type Ethernet 10/100 Mbs, AutoMDX, Auto Negotiation C441T 24 Vdc Input Nominal input voltage 24 Vdc Operating voltage 18–30 Vdc Number of inputs 4 Signal delay 5 ms (programmable to 65 sec) OFF-state voltage <6 Vdc ON-state voltage >18 Vdc Nominal input current 5 mA Isolation 1500V Terminal screw torque 7–9 in-lb 24V source current 50 mA 65 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical C441 Overload and monitoring relay Technical data and specifications 1.2 Ethernet (Modbus TCP / EtherNet/IP) Communication Modules, continued Description 1 Specification Operating Voltage Range—DC Input Modules OFF State Transition Region ON State 0–6 Vdc 6–18 Vdc 18–30 Vdc C441R 120 Vac Input Nominal input voltage 120 Vac Operating voltage 80–140 Vac Number of inputs 4 OFF-state voltage <30 Vac ON-state voltage >80 Vac Nominal input current 1 5 mA Signal delay 1/2 cycle Isolation 1500V Terminal screw torque 7–9 in-lb Operating Voltage Range—AC Input Modules OFF State Transition Region ON State 0–30 Vac 30–80 Vac 80–140 Vac Nominal voltage 120 Vac 24 Vdc Number of outputs (2) 1NO Form A 1NO/NC Form C Relay OFF time 3 ms Relay ON time 7 ms Maximum current per point ① 5A (B300 rated) Electrical life 100,000 cycles Mechanical life 1,000,000 cycles Note ① Resistive current at 55°C ambient. AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 66 1.2 1 C441 Overload and monitoring relay Dimensions Dimensions Approximate Dimensions in mm Motor Insight Overload Relay Terminal Ref. 97.0 84.1 5.1 4 Places 100.1 100.1 88.9 100.1 Mounting Dimension (4) 10-32 Dia. 17.5 3 Places 101.1 125.0 Motor Insight with Mounted DeviceNet, PROFIBUS or Modbus with I/O Communication Module 5.1 Terminal Ref. 97.0 84.1 100.1 88.9 100.1 100.1 83.1 Mounting Dimensions (4) 10-32 122.9 125.0 Dia. 17.5 3 Places 101.1 16.0 67 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical C441 Overload and monitoring relay Dimensions 1.2 1 Approximate Dimensions in mm Motor Insight with Mounted Modbus Communication Module 5.1 4 Places Terminal Ref. 97.0 84.1 48.0 88.9 100.1 100.1 100.1 Mounting Dimensions (4) 10-32 125.0 115.1 125.0 15.0 Dia. 101.1 17.5 3 Places Motor Insight Remote Display 2X ø 31.0 Hole in Panel 68.6 30.5 27.9 44.5 12 GA Max. Panel Thickness 116.8 99.1 25.4 15.2 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical 68 1.2 1 C441 Overload and monitoring relay Dimensions Approximate Dimensions in mm Motor Insight Cover Assembly 44.5 33.0 111.8 35.6 Motor Insight 50.8 106.7 109.2 25.4 35.6 Motor Insight Conversion Plate 7.6 99.1 5.1 10.2 5.1 101.6 91.4 68.6 58.4 78.7 5.1 83.8 69 AUTOMATION AND CONTROL www.eaton.com/seasia-electrical