EE 369 Per Unit Calculations

advertisement
4/6/2016
EE 369
POWER SYSTEM ANALYSIS
Lecture 8
Per Unit
Tom Overbye and Ross Baldick
1
Per Unit Calculations
 A key problem in analyzing power systems is
the large number of transformers.
– It would be very difficult to continually have to refer
impedances to the different sides of the
transformers
 This problem is avoided by a normalization of
all variables.
 This normalization is known as per unit analysis.
quantity in per unit 
actual quantity
base value of quantity
2
1
4/6/2016
Per Unit Conversion Procedure, 1f
1. Pick a 1f VA base for the entire system, SB
2. Pick a voltage base for each different voltage
level, VB. Voltage bases are related by
transformer turns ratios. Voltages are line to
neutral.
3. Calculate the impedance base, ZB= (VB)2/SB
4. Calculate the current base, IB = VB/ZB
5. Convert actual values to per unit
Note, per unit conversion affects magnitudes, not
the angles. Also, per unit quantities no longer have
units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts)
3
Per Unit Solution Procedure
1. Convert to per unit (p.u.) (many problems
are already in per unit)
2. Solve
3. Convert back to actual as necessary
4
2
4/6/2016
Per Unit Example
Solve for the current, load voltage and load power
in the circuit shown below using per unit analysis
with an SB of 100 MVA, and voltage bases of
8 kV, 80 kV and 16 kV, respectively.
Original Circuit
5
Per Unit Example, cont’d
Z BLeft 
82 (kV) 2
 0.64
100MVA
Z BMiddle 
Z BRight 
802 (kV) 2
 64
100MVA
162 (kV) 2
 2.56
100MVA
Same circuit, with
values expressed
in per unit.
6
3
4/6/2016
Per Unit Example, cont’d
1.00
 0.22  30.8 p.u. (not amps)
3.91  j 2.327
VL  1.00  0.22  30.8 
I 
    p.u.
2
V
SL 
 L  0.189 p.u.
Z
SG  1.00 0.2230.8  30.8 p.u.
VL I L*
7
Per Unit Example, cont’d
To convert back to actual values just multiply the
per unit values by their per unit base
V LActual  0.859  30.8 16 kV  13.7  30.8 kV
S LActual  0.1890 100 MVA  18.90 MVA
SGActual  0.2230.8 100 MVA  22.030.8 MVA
100 MVA
 1250 Amps
80 kV
I BMiddle

Actual
I Middle
 0.22  30.8  275  30.8 
8
4
4/6/2016
Three Phase Per Unit
Procedure is very similar to 1f except we use a 3f
VA base, and use line to line voltage bases
1. Pick a 3f VA base for the entire system, S B3f
2. Pick a voltage base for each different
voltage level, VB,LL. Voltages are line to line.
3. Calculate the impedance base
ZB 
VB2, LL
S B3f

( 3 VB , LN )2
3S 1Bf

VB2, LN
S 1Bf
Exactly the same impedance bases as with single phase using
the corresponding single phase VA base and voltage base!9
Three Phase Per Unit, cont'd
4. Calculate the current base, IB
I B3f 
S B3f
3 S 1Bf
S 1Bf


 I B1f
3 VB, LL
3 3 VB, LN VB , LN
Exactly the same current bases as with single phase!
5. Convert actual values to per unit
10
5
4/6/2016
Three Phase Per Unit Example
•Solve for the current, load voltage and load
power in the previous circuit, assuming:
–a 3f power base of 300 MVA,
–and line to line voltage bases of 13.8 kV, 138 kV
and 27.6 kV (square root of 3 larger than the 1f
example voltages)
–the generator is Y-connected so its line to line
voltage is 13.8 kV.
Convert to per unit
as before.
Note the system is
exactly the same!
11
3f Per Unit Example, cont'd
1.00
 0.22  30.8 p.u. (not amps)
3.91  j 2.327
VL  1.00  0.22  30.8 
I 
    p.u.
2
V
SL 
 L  0.189 p.u.
Z
SG  1.00 0.2230.8  30.8 p.u.
VL I L*
Again, analysis is exactly the same!
12
6
4/6/2016
3f Per Unit Example, cont'd
Differences appear when we convert back to actual values
VLActual  0.859  30.8 27.6 kV  23.8  30.8 kV
SLActual  0.1890 300 MVA  56.70 MVA
SGActual  0.2230.8 300 MVA  66.030.8 MVA
300 MVA
 1250 Amps
3 138 kV
I BMiddle

Actual
I Middle
 0.22  30.8  Amps  275  30.8 
(same current!)
13
7
Download