SENTRON Switching and Protection Devices – Air Circuit Breakers

advertisement
© Siemens AG 2009
SENTRON Switching and
Protection Devices –
Air Circuit Breakers
15/2
15
Introduction
3WL Air Circuit Breakers
15/6
15/7
15/11
15/15
15/19
15/23
15/29
3WL Air Circuit Breakers/
Non-Automatic Air Circuit Breakers
up to 6300 A (AC)
General data
3-pole, fixed-mounted versions
3-pole, withdrawable versions
4-pole, fixed-mounted versions
4-pole, withdrawable versions
Options
Accessories and spare parts
15/50
15/51
15/52
15/53
3WL Non-Automatic Air Circuit Breakers
up to 4000 A (DC)
3- and 4-pole, fixed-mounted versions
3-pole, withdrawable versions
4-pole, withdrawable versions
Accessories and spare parts
Siemens LV 1 · 2009
© Siemens AG 2009
SENTRON Switching and Protection Devices — Air Circuit Breakers
Introduction
■ Overview
Size I
Size III
Size II
Air circuit breakers
3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC)
3WL non-automatic air circuit breakers up to 4000 A (DC)
Size
I, II, III
II
630, 800, 1000, 1250,
1600, 2000, 2500, 3200, 4000,
5000, 6300
1000, 2000, 4000
3-pole, 4-pole
3-pole, 4-pole
... 690/1000/1150
--
-... 1000
Rated current In
A
Number of poles
Rated operational
voltage Ue
V AC
V DC
Rated ultimate
short-circuit breaking capacity
at 500 V AC
kA
Endurance
Size I
Size II
Size III
55/66
66/80/100
100/150 (3-pole),
130 (4-pole)
30/25/20
(at 300/600/1000 V DC)
15000
10000
15000
Operating 20000
cycles
3 0 °
3 0 °
3 0 °
3 0 °
3 0 ° 3 0 °
3 0 °
IP55
IP41
3 0 °
N S E 0 _ 0 0 0 6 2 a
N S E 0 _ 0 0 0 6 1 a
N S E 0 _ 0 0 0 6 2 a
N S E 0 _ 0 0 0 6 1 a
Degree of protection
With cover
Without cover
(with door sealing frame)
IP55
IP41
460/590
704/914
460/590
434
291
434
291
434
291
434
291
Withdrawable
H mm
D mm
465.5
471
465.5
471
465.5
471
465.5
471
ETU25B
ETU27B
NSE0_01106a
NSS0_00535
ETU15B1)
Type
NSE0_01109a
320/410
H mm
D mm
NSE0_01108a
W mm
Fixed
mounting
D
NSE0_01107a
W
ETU45B
Rating Plug
NSE0_01111a
Dimensions 3-/4-pole
H
15
Mounting position
ETU76B
Electronic releases for SENTRON 3WL circuit breakers
Overload protection
✓
✓
✓
✓
✓
Short-time delayed
short-circuit protection
--
✓
✓
✓
✓
Instantaneous
short-circuit protection
✓
✓
✓
✓
✓
Neutral conductor protection
--
--
✓
✓
✓
Ground-fault protection
--
--
✓
❑
❑
Zone Selective Interlocking
--
--
--
❑
❑
LCD, 4-line
--
--
--
❑
--
LCD, graphic
--
--
--
--
✓
Communication through
PROFIBUS DP
--
--
--
❑
❑
Measurement function Plus
--
--
--
❑
❑
Selectable parameter sets
--
--
--
--
✓
Parameters freely programmable
--
--
--
--
✓
CubicleBUS
--
--
--
✓
✓
✓ Standard
-- Not available
❑ Optional
1)
ETU15B cannot be used with 3WL circuit breakers, size III.
15/2
Siemens LV 1 · 2009
3WL air circuit breakers/non-automatic air circuit breakers
according to UL 489 up to 5000 A, see Catalog LV 16.
© Siemens AG 2009
SENTRON Switching and Protection Devices — Air Circuit Breakers
Introduction
Switching capacity
Size
I
II
Type
3WL11
3WL12
Switching capacity class
N
N
S
S
III
N
3WL13
N
S
S
H
H
H
H
C
3-pole
C
C
4-pole
C
Short-circuit breaking capacity
Rated operational voltage Ue
up to 415 V AC
Icu
kA
55
66
66
80
100
100
150
130
Ics
kA
55
66
66
80
100
100
150
130
Icm
kA
121
145
145
176
220
220
330
286
Icu
kA
55
66
66
80
100
100
150
130
Ics
kA
55
66
66
80
100
100
150
130
Icm
kA
121
145
145
176
220
220
330
286
Icu
kA
42
50
50
75
85
85
150
130
Ics
kA
42
50
50
75
85
85
150
130
Icm
kA
88
105
105
165
187
187
330
286
--
--
--
50
50
704)
704)
Rated operational voltage Ue
up to 500 V AC
Rated operational voltage Ue
up to 690 V AC
Rated operational voltage Ue
up to 1000 V/1150 V AC
--
704)
Ics
kA
--
--
--
--
50
50
704)
Icm
kA
--
--
--
--
150
105
1544)
1544)
Rated short-time withstand current Icw
of the circuit breakers3)
0.5 s
kA
55
66
66
80
100
100
100
100
1s
kA
42
50
55
66
80
100
100
100
2s
kA
29.5
35
39
46
651)/702)
80
80
80
3s
kA
24
29
32
37
501)/652)
65
65
65
Short-circuit breaking capacity Icc
of the non-automatic air circuit breakers
Up to 500 V AC
kA
55
66
66
80
100
100
100
100
Up to 690 V AC
kA
42
50
50
75
85
85
100
100
N
Circuit breakers with ECO switching capacity N
(Icu = Ics up to 55 kA size I/up to 66 kA size II at 500 V)
S
Circuit breakers with standard switching capacity S
(Icu = Ics up to 66 kA size I/up to 80 kA size II at 500 V)
H
Circuit breakers with high switching capacity H
(Icu = Ics up to 100 kA at 500 V)
C
DC
1)
Size II with In max ≤ 2500 A.
2)
Size II with In max = 3200 A and In max = 4000 A.
3)
At a rated voltage of 690 V the Icw value of the circuit breaker cannot be
greater than the Icu or Ics value at 690 V.
4)
Rated operational voltage Ue = 1150 V.
Circuit breakers with very high switching capacity C
(Icu = Ics up to 150 kA (3-pole)/130 kA (4-pole)
at 500 V)
Non-automatic air circuit breakers with DC switching
capacity
These circuit breakers are indicated in the selection and
ordering data by orange backgrounds.
Siemens LV 1 · 2009
15/3
15
kA
Icu
© Siemens AG 2009
SENTRON Switching and Protection Devices — Air Circuit Breakers
Introduction
SENTRON 3WL:
Superior individual products integrated into uniform power
distribution systems - up to and including industry-specific
industrial and infrastructure solutions
6
7
2
3
8
5
4
9
1
15
25
21
10
19
22
11
23
12
24
18
13
14
20
16
15
$
%
Guide frame (pages 15/30 to 15/33)
&
(
)
*
+
,
.
/
0
1
2
3
Position indicator switch (pages 15/26 and 15/38)
Main circuit connection front, flange, horizontal, vertical
(pages 15/45 and 15/46)
Grounding contact, leading (page 15/42)
Shutter (page 15/41)
COM15 PROFIBUS module or COM16 MODBUS module (page 15/44)
External CubicleBUS module (page 15/43)
Closing solenoid, auxiliary release (page 15/40)
Auxiliary conductor plug-in system (page 15/39)
Auxiliary switch block (page 15/40)
Door sealing frame (page 15/41)
Interlocking set for base plate (page 15/36)
Transparent panel, function insert (page 15/35)
EMERGENCY-STOP pushbutton, key operated (page 15/38)
Motorized operating mechanism (page 15/40)
15/4
Siemens LV 1 · 2009
4
5
6
Operating cycles counter (page 15/38)
7
8
9
:
;
<
=
Remote reset solenoid (page 15/35)
Breaker Status Sensor (BSS) (page 15/44)
Protective device with device holder, electronic release (ETU)
(page 15/34)
Breaker Data Adapter (BDA) (page 15/43)
Four-line display (page 15/34)
Ground-fault protection module (page 15/34)
Rated current module (page 15/34)
Measuring function module (page 15/34)
Circuit breaker (pages 15/7 to 15/22)
NSE0_01887a
17
© Siemens AG 2009
SENTRON Switching and Protection Devices — Air Circuit Breakers
Introduction
Communication-capable circuit breakers (with ETU45B or ETU76B electronic release)
21
Ethernet
19
20
PROFIBUS
4
8
5
14
22
16
15
6
CubicleBUS
10
1
1
7
18
17
11
9
12
1
SENTRON 3VL
12 Electronic ETU release
2
Electronic LCD ETU release
13 Measurement function Plus
3
Electronic ETU release
14 ZSI module
4
COM10 PROFIBUS module complete with ZSI
15 Digital output module with relay contacts
5
COM20 PROFIBUS module2) complete with ZSI
16 Digital output module with relay contacts, configurable
6
Breaker Data Adapter (BDA)
17 Analog output module
7
BDA Plus with Ethernet interface
18 Digital input module
8
Browser-capable input and output device (e.g. notebook)
19 Switch ES Power on PC
9
SENTRON 3WL
20 PLC e.g. SIMATIC S7
10 COM15 PROFIBUS module1)
21 SIMATIC powercontrol
11 Breaker Status Sensor (BSS)
22 PAC
15
3
NSE0_01105h
2
13
1) For a MODBUS connection the COM16 module is required.
2) For a MODBUS connection the COM21 module is required.
Features
• Coordinated communication concept using the PROFIBUS DP
or MODBUS, ranging from 16 A to 6300 A with SENTRON 3VL
and SENTRON 3WL
• The high level of modularity of circuit breakers and accessories
allows easy retrofitting of all communication components
• Significant additional benefits for the switchboard due to the
possibility of linking up external input and output modules to
the circuit breaker-internal CubicleBUS of the SENTRON 3WL
Communication:
• For air circuit breakers with optional communication function
(ETU45B or ETU76B electronic release)
see pages 15/7 to 15/22.
• For accessories see pages 15/43 and 15/44.
• For more information see also the chapter "Power Management System" and "Software for Power Distribution".
• Innovative software products for parameterization, operation,
monitoring, and diagnostics of SENTRON circuit breakers,
both locally or via PROFIBUS DP, MODBUS or Ethernet/
Intranet/Internet
• Complete integration of the SENTRON circuit breakers into the
Totally Integrated Power and Totally Integrated Automation
solutions
Siemens LV 1 · 2009
15/5
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
• Fast and reliable parameterization
• Timely information and response can prevent plant
stoppages
• Effective diagnostics management
• Measured values are the basis for efficient load management,
for drawing up power demand profiles and for assigning energy to cost centers
• Preventive maintenance reduces the risk of expansive plant
down-times
■ Benefits
Low space requirements
The SENTRON 3WL devices require very little space. Size I devices (up to 1600 A) fit into a 400 mm wide switchgear panel.
Size III devices (up to 6300 A) are the smallest of their kind and
with their construction width of 704 mm fit into a 800 mm wide
switchgear panel.
Modular design
■ Application
Components like auxiliary releases, motorized operating
mechanisms, electronic releases, current sensors, auxiliary circuit signaling switches, automatic reset devices, interlocks and
engagement operating mechanisms can all be exchanged or
retrofitted at a later stage, thus allowing the circuit breaker to be
adapted to new, changing requirements.
• As incoming-feeder, distribution, tie, and outgoing-feeder circuit breakers in electrical installations
• For switching and protecting motors, capacitors, generators,
transformers, busbars and cables
The main contact elements can all be replaced in order to increase the endurance of the circuit breaker.
Due to the reinforced use of electronic I&C systems, the demands made on air circuit breakers in terms of operator control
and monitoring of network processes have increased.
Retrofittable modules for electronic releases
The extensive, coordinated SENTRON range of devices covers
all applications between 16 A and 6300 A with compact and air
circuit breakers.
15
Modularity is one of the main features of the new SENTRON 3WL
circuit breakers.
Special LCDs, ground-fault modules, rated current modules and
communication modules for the electronic releases are available
for fast and easy retrofitting and adaptation to changing
requirements.
The AC devices are available as circuit breakers and non-automatic air circuit breakers. DC devices are only available as nonautomatic air circuit breakers.
Standards
Communication
The use of modern communication-capable circuit breakers
opens up completely new possibilities in terms of start-up,
parameterization, diagnostics, maintenance and operation. This
allows many different ways of reducing costs and improving productivity in industrial plants, buildings and infrastructure projects
to be achieved.
SENTRON 3WL circuit breakers comply with:
• IEC 60947-1, EN 60947-1
• IEC 60947-2, EN 60947-2
• Climate-proof according to IEC 60068-2-30.
Versions with UL 489 also available, see Catalog LV 16.
For further standards, see Appendix.
Conductor cross-sections
Size
Type
Permissible load
At rear horizontal main
circuit connections
• Up to 55 °C (Cu bare)
• Up to 60 °C (Cu bare)1)
• Up to 70 °C (Cu black
painted)1)
Main conductor
minimum
cross-sections
• Copper bars,
bare
• Copper bars,
painted black
I
Up to
3WL11 10
A 1000
A 1000
A 1000
II
3WL11 12 3WL11 16 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20
1250
1250
1210
1600
1600
1490
800
800
800
1000
1000
1000
1250
1250
1250
1600
1600
1600
2000
2000
2000
Unit(s) 1 ×
mm2 60 × 10
2×
40 × 10
2×
50 × 10
1×
50 × 10
1×
60 × 10
2×
40 × 10
2×
50 × 10
3×
50 × 10
Unit(s) 1 ×
mm2 60 × 10
2×
40 × 10
2×
50 × 10
1×
50 × 10
1×
60 × 10
2×
40 × 10
2×
50 × 10
3×
50 × 10
Size
II
Type
3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
Permissible load
• Up to 55 °C (Cu bare)
• Up to 60 °C (Cu bare)1)
• Up to 70 °C (Cu black
painted)1)
Main conductor
minimum
cross-sections
• Copper bars,
bare
• Copper bars,
painted black
A 2500
A 2500
A 2280
3200
3020
2870
3950
3810
3600
4000
4000
4000
5000
5000
5000
5920
5810
5500
Unit(s) 2 ×
mm2 100 × 10
3×
100 × 10
4×
120 × 10
4x
100 x 10
6x
100 x 10
6x
120 x 10
Unit(s) 2 ×
mm2 100 × 10
3×
100 × 10
4×
4×
100 × 102) 100 × 10
6×
100 × 10
6×
120 × 10
1) ETU76B with graphics display can be used up to max. 55 °C.
2) Minimum main conductor cross-sections for 4-pole withdrawable circuit
breakers: 4 × 120 × 10 mm.
15/6
Siemens LV 1 · 2009
III
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
3-pole, fixed-mounted versions
■ Selection and ordering data
Size
Max. rated circuit breaker Rated current1)
In
current
In max.
Icu up to 55/66 kA at 500 V,
ECO switching capacity N
A
kA
DT
A
PU
PS*
(UNIT,
Basic price SET, M)
per PU
N
Order No.
For Order No. supplements,
see page 15/23
PG
Weight
per PU
approx.
kg
Horizontal main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@32-....
3WL11 08-2@@32-....
3WL11 10-2@@32-....
3WL11 12-2@@32-....
3WL11 16-2@@32-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
43.000
43.000
43.000
43.000
43.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@32-....
3WL12 10-2@@32-....
3WL12 12-2@@32-....
3WL12 16-2@@32-....
3WL12 20-2@@32-....
3WL12 25-2@@32-....
3WL12 32-2@@32-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@31-....
3WL11 08-2@@31-....
3WL11 10-2@@31-....
3WL11 12-2@@31-....
3WL11 16-2@@31-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
43.000
43.000
43.000
43.000
43.000
II
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
66
66
66
66
66
66
66
66
B
B
B
B
B
B
B
B
3WL12 08-2@@31-....
3WL12 10-2@@31-....
3WL12 12-2@@31-....
3WL12 16-2@@31-....
3WL12 20-2@@31-....
3WL12 25-2@@31-....
3WL12 32-2@@31-....
3WL12 40-2@@31-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
85.000
Front main circuit connection, single hole
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@33-....
3WL11 08-2@@33-....
3WL11 10-2@@33-....
3WL11 12-2@@33-....
3WL11 16-2@@33-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
43.000
43.000
43.000
43.000
43.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@33-....
3WL12 10-2@@33-....
3WL12 12-2@@33-....
3WL12 16-2@@33-....
3WL12 20-2@@33-....
3WL12 25-2@@33-....
3WL12 32-2@@33-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
Front main circuit connection, double hole
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@34-....
3WL11 08-2@@34-....
3WL11 10-2@@34-....
3WL11 12-2@@34-....
3WL11 16-2@@34-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
43.000
43.000
43.000
43.000
43.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@34-....
3WL12 10-2@@34-....
3WL12 12-2@@34-....
3WL12 16-2@@34-....
3WL12 20-2@@34-....
3WL12 25-2@@34-....
3WL12 32-2@@34-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
Non-automatic air circuit breakers2)
Without electronic release
Order No. supplements
Add. price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
BB
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/10.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/7
15
Vertical main circuit connection
I
I
I
I
I
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
3-pole, fixed-mounted versions
Size
Max. rated circuit breaker Rated current1)
In
current
In max.
Icu up to 66/80 kA at 500 V,
standard switching capacity S
A
kA
DT
A
PU
PS*
(UNIT,
Basic price SET, M)
per PU
S
Order No.
For Order No. supplements,
see page 15/23
PG
Weight
per PU
approx.
kg
Horizontal main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@32-....
3WL11 08-3@@32-....
3WL11 10-3@@32-....
3WL11 12-3@@32-....
3WL11 16-3@@32-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
43.000
43.000
43.000
43.000
43.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@32-....
3WL12 10-3@@32-....
3WL12 12-3@@32-....
3WL12 16-3@@32-....
3WL12 20-3@@32-....
3WL12 25-3@@32-....
3WL12 32-3@@32-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
15
Vertical main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@31-....
3WL11 08-3@@31-....
3WL11 10-3@@31-....
3WL11 12-3@@31-....
3WL11 16-3@@31-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
43.000
43.000
43.000
43.000
43.000
II
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
80
80
80
80
80
80
80
80
B
B
B
B
B
B
B
B
3WL12 08-3@@31-....
3WL12 10-3@@31-....
3WL12 12-3@@31-....
3WL12 16-3@@31-....
3WL12 20-3@@31-....
3WL12 25-3@@31-....
3WL12 32-3@@31-....
3WL12 40-3@@31-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
85.000
Front main circuit connection, single hole
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@33-....
3WL11 08-3@@33-....
3WL11 10-3@@33-....
3WL11 12-3@@33-....
3WL11 16-3@@33-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
43.000
43.000
43.000
43.000
43.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@33-....
3WL12 10-3@@33-....
3WL12 12-3@@33-....
3WL12 16-3@@33-....
3WL12 20-3@@33-....
3WL12 25-3@@33-....
3WL12 32-3@@33-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
Front main circuit connection, double hole
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@34-....
3WL11 08-3@@34-....
3WL11 10-3@@34-....
3WL11 12-3@@34-....
3WL11 16-3@@34-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
43.000
43.000
43.000
43.000
43.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@34-....
3WL12 10-3@@34-....
3WL12 12-3@@34-....
3WL12 16-3@@34-....
3WL12 20-3@@34-....
3WL12 25-3@@34-....
3WL12 32-3@@34-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
Non-automatic air circuit breakers2)
Without electronic release
Order No. supplements
Additional
price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
BB
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/10.
* You can order this quantity or a multiple thereof.
15/8
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
3-pole, fixed-mounted versions
Size
Max. rated circuit breaker Rated current1)
current
In
In max.
Icu up to 100 kA at 500 V,
high switching capacity H
A
kA
DT
A
PU
PS*
(UNIT,
Basic price SET, M)
per PU
H
Order No.
Order No. supplements,
see page 15/23
PG
Weight
per PU
approx.
kg
Horizontal main circuit connection
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@32-....
3WL12 10-4@@32-....
3WL12 12-4@@32-....
3WL12 16-4@@32-....
3WL12 20-4@@32-....
3WL12 25-4@@32-....
3WL12 32-4@@32-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
III
III
4000
5000
4000
5000
100 B
100 B
3WL13 40-4@@32-....
3WL13 50-4@@32-....
1
1
1 unit
1 unit
103
103
82.000
82.000
Vertical main circuit connection
II
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
100
100
100
100
100
100
100
100
B
B
B
B
B
B
B
B
3WL12 08-4@@31-....
3WL12 10-4@@31-....
3WL12 12-4@@31-....
3WL12 16-4@@31-....
3WL12 20-4@@31-....
3WL12 25-4@@31-....
3WL12 32-4@@31-....
3WL12 40-4@@31-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
85.000
III
III
III
4000
5000
6300
4000
5000
6300
100 B
100 B
100 B
3WL13 40-4@@31-....
3WL13 50-4@@31-....
3WL13 63-4@@31-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
82.000
82.000
90.000
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@33-....
3WL12 10-4@@33-....
3WL12 12-4@@33-....
3WL12 16-4@@33-....
3WL12 20-4@@33-....
3WL12 25-4@@33-....
3WL12 32-4@@33-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
III
4000
4000
100 B
3WL13 40-4@@33-....
1
1 unit
103
82.000
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
56.000
56.000
56.000
56.000
56.000
59.000
64.000
1
1 unit
103
82.000
Front main circuit connection, double hole
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@34-....
3WL12 10-4@@34-....
3WL12 12-4@@34-....
3WL12 16-4@@34-....
3WL12 20-4@@34-....
3WL12 25-4@@34-....
3WL12 32-4@@34-....
III
4000
4000
100 B
3WL13 40-4@@34-....
Non-automatic air circuit breakers2)
Without electronic release
Order No. supplements
Additional
price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI6)
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
BB
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/10.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/9
15
Front main circuit connection, single hole
II
II
II
II
II
II
II
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
3-pole, fixed-mounted versions
Size
Max. rated circuit breaker Rated current1)
current
In
In max.
Icu up to 150 kA at 500 V,
very high switching capacity C
A
kA
A
PU
PS*
(UNIT,
Basic price SET, M)
per PU
C
Order No.
Order No. supplements,
see page 15/23
PG
DT
Weight
per PU
approx.
kg
Horizontal main circuit connection
III
III
4000
5000
4000
5000
150 B
150 B
3WL13 40-5@@32-....
3WL13 50-5@@32-....
1
1
1 unit
1 unit
103
103
82.000
82.000
4000
5000
6300
150 B
150 B
150 B
3WL13 40-5@@31-....
3WL13 50-5@@31-....
3WL13 63-5@@31-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
82.000
82.000
90.000
Vertical main circuit connection
III
III
III
4000
5000
6300
Non-automatic air circuit breakers2)
Order No. supplements
Without electronic release
Additional
price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
15
Standard Order No. supplements (for further Order No. supplements, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
Footnotes for pages 15/7 to 15/10:
1)
2)
The rated current is determined by the rated current module. For the standard version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on
page 15/24.
For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see Technical Information LV 1T, "Technical specifications".
1AA2
Without
3)
Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 15/34.
4)
Current transformers for protection of the N conductor are to be ordered
separately, see page 15/34.
5)
ETU45B and ETU76B with ground-fault protection module GFM AT (alarm
and tripping), see page 15/34.
6)
ETU15B cannot be used with 3WL circuit breakers, size III.
* You can order this quantity or a multiple thereof.
15/10
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
3-pole, withdrawable versions
■ Selection and ordering data
Size
Max. rated circuit breaker Rated current1)
In
current
In max.
Icu up to 55/66 kA at 500 V,
ECO switching capacity N
A
kA
DT
A
PS*
PU
(UNIT,
Basic price SET, M)
per PU
N
Order No.
For Order No. supplements,
see page 15/23
PG
Weight
per PU
approx.
kg
Without guide frames
(for guide frames, see page 15/30 to 15/33)
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@35-....
3WL11 08-2@@35-....
3WL11 10-2@@35-....
3WL11 12-2@@35-....
3WL11 16-2@@35-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
45.000
45.000
45.000
45.000
45.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@35-....
3WL12 10-2@@35-....
3WL12 12-2@@35-....
3WL12 16-2@@35-....
3WL12 20-2@@35-....
3WL12 25-2@@35-....
3WL12 32-2@@35-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
60.000
60.000
60.000
60.000
60.000
63.000
68.000
70.000
70.000
70.000
70.000
70.000
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@36-....
3WL11 08-2@@36-....
3WL11 10-2@@36-....
3WL11 12-2@@36-....
3WL11 16-2@@36-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@36-....
3WL12 10-2@@36-....
3WL12 12-2@@36-....
3WL12 16-2@@36-....
3WL12 20-2@@36-....
3WL12 25-2@@36-....
3WL12 32-2@@36-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 91.000
103 91.000
103 91.000
103 91.000
103 91.000
103 102.000
103 113.000
With guide frames, vertical main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@37-....
3WL11 08-2@@37-....
3WL11 10-2@@37-....
3WL11 12-2@@37-....
3WL11 16-2@@37-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
70.000
70.000
70.000
70.000
70.000
II
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
66
66
66
66
66
66
66
66
B
B
B
B
B
B
B
B
3WL12 08-2@@37-....
3WL12 10-2@@37-....
3WL12 12-2@@37-....
3WL12 16-2@@37-....
3WL12 20-2@@37-....
3WL12 25-2@@37-....
3WL12 32-2@@37-....
3WL12 40-2@@37-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 91.000
103 91.000
103 91.000
103 91.000
103 91.000
103 102.000
103 113.000
103 121.000
With guide frames, connecting flanges
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@38-....
3WL11 08-2@@38-....
3WL11 10-2@@38-....
3WL11 12-2@@38-....
3WL11 16-2@@38-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@38-....
3WL12 10-2@@38-....
3WL12 12-2@@38-....
3WL12 16-2@@38-....
3WL12 20-2@@38-....
3WL12 25-2@@38-....
3WL12 32-2@@38-....
Order No. supplements
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 91.000
103 91.000
103 91.000
103 91.000
103 91.000
103 102.000
103 113.000
Non-automatic air circuit breakers2)
Without electronic release
AA
70.000
70.000
70.000
70.000
70.000
Additional
price
Without
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
BB
CB
EB
FB
NB
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/14.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/11
15
With guide frames, horizontal main circuit connection
I
I
I
I
I
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
3-pole, withdrawable versions
Size
Max. rated circuit breaker Rated current1)
In
current
In max.
Icu up to 66/80 kA at 500 V,
standard switching capacity S
A
kA
DT
A
PS*
PU
(UNIT,
Basic price SET, M)
per PU
S
Order No.
For Order No. supplements,
see page 15/23
PG
Weight
per PU
approx.
kg
Without guide frames
(for guide frames, see page 15/30 to 15/33)
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@35-....
3WL11 08-3@@35-....
3WL11 10-3@@35-....
3WL11 12-3@@35-....
3WL11 16-3@@35-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
45.000
45.000
45.000
45.000
45.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@35-....
3WL12 10-3@@35-....
3WL12 12-3@@35-....
3WL12 16-3@@35-....
3WL12 20-3@@35-....
3WL12 25-3@@35-....
3WL12 32-3@@35-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
60.000
60.000
60.000
60.000
60.000
63.000
68.000
70.000
70.000
70.000
70.000
70.000
15
With guide frames, horizontal main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@36-....
3WL11 08-3@@36-....
3WL11 10-3@@36-....
3WL11 12-3@@36-....
3WL11 16-3@@36-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@36-....
3WL12 10-3@@36-....
3WL12 12-3@@36-....
3WL12 16-3@@36-....
3WL12 20-3@@36-....
3WL12 25-3@@36-....
3WL12 32-3@@36-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 91.000
103 91.000
103 91.000
103 91.000
103 91.000
103 102.000
103 113.000
With guide frames, vertical main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@37-....
3WL11 08-3@@37-....
3WL11 10-3@@37-....
3WL11 12-3@@37-....
3WL11 16-3@@37-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
70.000
70.000
70.000
70.000
70.000
II
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
80
80
80
80
80
80
80
80
B
B
B
B
B
B
B
B
3WL12 08-3@@37-....
3WL12 10-3@@37-....
3WL12 12-3@@37-....
3WL12 16-3@@37-....
3WL12 20-3@@37-....
3WL12 25-3@@37-....
3WL12 32-3@@37-....
3WL12 40-3@@37-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 91.000
103 91.000
103 91.000
103 91.000
103 91.000
103 102.000
103 113.000
103 121.000
With guide frames, connecting flanges
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@38-....
3WL11 08-3@@38-....
3WL11 10-3@@38-....
3WL11 12-3@@38-....
3WL11 16-3@@38-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@38-....
3WL12 10-3@@38-....
3WL12 12-3@@38-....
3WL12 16-3@@38-....
3WL12 20-3@@38-....
3WL12 25-3@@38-....
3WL12 32-3@@38-....
Order No. supplements
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 91.000
103 91.000
103 91.000
103 91.000
103 91.000
103 102.000
103 113.000
Non-automatic air circuit breakers2)
Without electronic release
AA
70.000
70.000
70.000
70.000
70.000
Additional
price
Without
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
BB
CB
EB
FB
NB
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/14.
* You can order this quantity or a multiple thereof.
15/12
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
3-pole, withdrawable versions
Size
Max. rated circuit breaker Rated current1)
current
In
In max.
Icu up to 100 kA at 500 V,
high switching capacity H
A
kA
DT
A
PS*
PU
(UNIT,
Basic price SET, M)
per PU
H
Order No.
Order No. supplements,
see page 15/23
PG
Weight
per PU
approx.
kg
Without guide frames
(for guide frames, see page 15/30 to 15/33)
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@35-....
3WL12 10-4@@35-....
3WL12 12-4@@35-....
3WL12 16-4@@35-....
3WL12 20-4@@35-....
3WL12 25-4@@35-....
3WL12 32-4@@35-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
60.000
60.000
60.000
60.000
60.000
63.000
68.000
III
III
III
4000
5000
6300
4000
5000
6300
100 B
100 B
100 B
3WL13 40-4@@35-....
3WL13 50-4@@35-....
3WL13 63-4@@35-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
88.000
88.000
96.000
With guide frames, horizontal main circuit connection
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@36-....
3WL12 10-4@@36-....
3WL12 12-4@@36-....
3WL12 16-4@@36-....
3WL12 20-4@@36-....
3WL12 25-4@@36-....
3WL12 32-4@@36-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 91.000
103 91.000
103 91.000
103 91.000
103 91.000
103 102.000
103 113.000
III
III
4000
5000
4000
5000
100 B
100 B
3WL13 40-4@@36-....
3WL13 50-4@@36-....
1
1
1 unit
1 unit
103 148.000
103 148.000
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
100
100
100
100
100
100
100
100
B
B
B
B
B
B
B
B
3WL12 08-4@@37-....
3WL12 10-4@@37-....
3WL12 12-4@@37-....
3WL12 16-4@@37-....
3WL12 20-4@@37-....
3WL12 25-4@@37-....
3WL12 32-4@@37-....
3WL12 40-4@@37-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 91.000
103 91.000
103 91.000
103 91.000
103 91.000
103 102.000
103 113.000
103 121.000
III
III
III
4000
5000
6300
4000
5000
6300
100 B
100 B
100 B
3WL13 40-4@@37-....
3WL13 50-4@@37-....
3WL13 63-4@@37-....
1
1
1
1 unit
1 unit
1 unit
103 148.000
103 148.000
103 166.000
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 91.000
103 91.000
103 91.000
103 91.000
103 91.000
103 102.000
103 113.000
1
1 unit
103 148.000
With guide frames, connecting flanges
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@38-....
3WL12 10-4@@38-....
3WL12 12-4@@38-....
3WL12 16-4@@38-....
3WL12 20-4@@38-....
3WL12 25-4@@38-....
3WL12 32-4@@38-....
III
4000
4000
100 B
3WL13 40-4@@38-....
Non-automatic air circuit breakers 2)
Without electronic release
Order No. supplements
Additional
price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI6)
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
BB
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/14.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/13
15
With guide frames, vertical main circuit connection
II
II
II
II
II
II
II
II
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
3-pole, withdrawable versions
Size
Max. rated circuit breaker Rated current1)
current
In
In max.
Icu up to 150 kA at 500 V,
very high switching capacity C
A
kA
A
PU
PS*
(UNIT,
Basic price SET, M)
per PU
C
Order No.
Order No. supplements,
see page 15/23
PG
DT
Weight
per PU
approx.
kg
Without guide frames
(for guide frames, see page 15/30 to 15/33)
III
III
III
4000
5000
6300
4000
5000
6300
150 B
150 B
150 B
3WL13 40-5@@35-....
3WL13 50-5@@35-....
3WL13 63-5@@35-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
88.000
88.000
96.000
150 B
150 B
3WL13 40-5@@36-....
3WL13 50-5@@36-....
1
1
1 unit
1 unit
103 148.000
103 148.000
150 B
150 B
150 B
3WL13 40-5@@37-....
3WL13 50-5@@37-....
3WL13 63-5@@37-....
1
1
1
1 unit
1 unit
1 unit
103 148.000
103 148.000
103 166.000
With guide frames, horizontal main circuit connection
III
III
4000
5000
4000
5000
With guide frames, vertical main circuit connection
III
III
III
4000
5000
6300
4000
5000
6300
Non-automatic air circuit breakers2)
Order No. supplements
Without electronic release
Additional
price
Without
AA
15
Electronic releases
Versions without ground-fault protection
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
Footnotes for pages 15/11 to 15/14:
1)
2)
The rated current is determined by the rated current module. For the standard version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on
page 15/24.
For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see Technical Information LV 1T, "Technical specifications".
1AA2
Without
3)
Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 15/34.
4)
Current transformers for protection of the N conductor are to be ordered
separately, see page 15/34.
5)
ETU45B to ETU76B with ground-fault protection module GFM AT (alarm
and tripping), see page 15/34.
6)
ETU15B cannot be used with 3WL circuit breakers, size III.
* You can order this quantity or a multiple thereof.
15/14
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
4-pole, fixed-mounted versions
■ Selection and ordering data
Size
Max. rated circuit breaker Rated current1)
In
current
In max.
Icu up to 55/66 kA at 500 V,
ECO switching capacity N
A
kA
DT
A
PS*
PU
(UNIT,
Basic price SET, M)
per PU
N
Order No.
Order No. supplements,
see page 15/23
PG
Weight
per PU
approx.
kg
Horizontal main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@42-....
3WL11 08-2@@42-....
3WL11 10-2@@42-....
3WL11 12-2@@42-....
3WL11 16-2@@42-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
50.000
50.000
50.000
50.000
50.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@42-....
3WL12 10-2@@42-....
3WL12 12-2@@42-....
3WL12 16-2@@42-....
3WL12 20-2@@42-....
3WL12 25-2@@42-....
3WL12 32-2@@42-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
67.000
67.000
67.000
67.000
67.000
71.000
77.000
50.000
50.000
50.000
50.000
50.000
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@41-....
3WL11 08-2@@41-....
3WL11 10-2@@41-....
3WL11 12-2@@41-....
3WL11 16-2@@41-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
II
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
66
66
66
66
66
66
66
66
B
B
B
B
B
B
B
B
3WL12 08-2@@41-....
3WL12 10-2@@41-....
3WL12 12-2@@41-....
3WL12 16-2@@41-....
3WL12 20-2@@41-....
3WL12 25-2@@41-....
3WL12 32-2@@41-....
3WL12 40-2@@41-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 75.000
103 75.000
103 75.000
103 75.000
103 67.000
103 71.000
103 77.000
103 103.000
Front main circuit connection, single hole
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@43-....
3WL11 08-2@@43-....
3WL11 10-2@@43-....
3WL11 12-2@@43-....
3WL11 16-2@@43-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
50.000
50.000
50.000
50.000
50.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@43-....
3WL12 10-2@@43-....
3WL12 12-2@@43-....
3WL12 16-2@@43-....
3WL12 20-2@@43-....
3WL12 25-2@@43-....
3WL12 32-2@@43-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
67.000
67.000
67.000
67.000
67.000
71.000
77.000
Front main circuit connection, double hole
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@44-....
3WL11 08-2@@44-....
3WL11 10-2@@44-....
3WL11 12-2@@44-....
3WL11 16-2@@44-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
50.000
50.000
50.000
50.000
50.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@44-....
3WL12 10-2@@44-....
3WL12 12-2@@44-....
3WL12 16-2@@44-....
3WL12 20-2@@44-....
3WL12 25-2@@44-....
3WL12 32-2@@44-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
67.000
67.000
67.000
67.000
67.000
71.000
77.000
Non-automatic air circuit breakers2)
Without electronic release
Order No. supplements
Additional
price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
BB
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/18.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/15
15
Vertical main circuit connection
I
I
I
I
I
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
4-pole, fixed-mounted versions
Size
Max. rated circuit breaker Rated current1)
In
current
In max.
Icu up to 66/80 kA at 500 V,
standard switching capacity S
A
kA
DT
A
PU
PS*
(UNIT,
Basic price SET, M)
per PU
S
Order No.
Order No. supplements,
see page 15/23
PG
Weight
per PU
approx.
kg
Horizontal main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@42-....
3WL11 08-3@@42-....
3WL11 10-3@@42-....
3WL11 12-3@@42-....
3WL11 16-3@@42-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
50.000
50.000
50.000
50.000
50.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@42-....
3WL12 10-3@@42-....
3WL12 12-3@@42-....
3WL12 16-3@@42-....
3WL12 20-3@@42-....
3WL12 25-3@@42-....
3WL12 32-3@@42-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
67.000
67.000
67.000
67.000
67.000
71.000
77.000
50.000
50.000
50.000
50.000
50.000
15
Vertical main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@41-....
3WL11 08-3@@41-....
3WL11 10-3@@41-....
3WL11 12-3@@41-....
3WL11 16-3@@41-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
II
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
80
80
80
80
80
80
80
80
B
B
B
B
B
B
B
B
3WL12 08-3@@41-....
3WL12 10-3@@41-....
3WL12 12-3@@41-....
3WL12 16-3@@41-....
3WL12 20-3@@41-....
3WL12 25-3@@41-....
3WL12 32-3@@41-....
3WL12 40-3@@41-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 67.000
103 67.000
103 67.000
103 67.000
103 67.000
103 71.000
103 77.000
103 103.000
Front main circuit connection, single hole
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@43-....
3WL11 08-3@@43-....
3WL11 10-3@@43-....
3WL11 12-3@@43-....
3WL11 16-3@@43-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
50.000
50.000
50.000
50.000
50.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@43-....
3WL12 10-3@@43-....
3WL12 12-3@@43-....
3WL12 16-3@@43-....
3WL12 20-3@@43-....
3WL12 25-3@@43-....
3WL12 32-3@@43-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
67.000
67.000
67.000
67.000
67.000
71.000
77.000
Front main circuit connection, double hole
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@44-....
3WL11 08-3@@44-....
3WL11 10-3@@44-....
3WL11 12-3@@44-....
3WL11 16-3@@44-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
50.000
50.000
50.000
50.000
50.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@44-....
3WL12 10-3@@44-....
3WL12 12-3@@44-....
3WL12 16-3@@44-....
3WL12 20-3@@44-....
3WL12 25-3@@44-....
3WL12 32-3@@44-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
67.000
67.000
67.000
67.000
67.000
71.000
77.000
Non-automatic air circuit breakers2)
Without electronic release
Order No. supplements
Additional
price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
BB
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/18.
* You can order this quantity or a multiple thereof.
15/16
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
4-pole, fixed-mounted versions
Size
Max. rated circuit breaker Rated current1)
current
In
In max.
Icu up to 100 kA at 500 V,
high switching capacity H
A
kA
DT
A
PS*
PU
(UNIT,
Basic price SET, M)
per PU
H
Order No.
Order No. supplements,
see page 15/23
PG
Weight
per PU
approx.
kg
Horizontal main circuit connection
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@42-....
3WL12 10-4@@42-....
3WL12 12-4@@42-....
3WL12 16-4@@42-....
3WL12 20-4@@42-....
3WL12 25-4@@42-....
3WL12 32-4@@42-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
67.000
67.000
67.000
67.000
67.000
71.000
77.000
III
III
4000
5000
4000
5000
100 B
100 B
3WL13 40-4@@42-....
3WL13 50-4@@42-....
1
1
1 unit
1 unit
103
103
99.000
99.000
Vertical main circuit connection
II
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
100
100
100
100
100
100
100
100
B
B
B
B
B
B
B
B
3WL12 08-4@@41-....
3WL12 10-4@@41-....
3WL12 12-4@@41-....
3WL12 16-4@@41-....
3WL12 20-4@@41-....
3WL12 25-4@@41-....
3WL12 32-4@@41-....
3WL12 40-4@@41-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103 67.000
103 67.000
103 67.000
103 67.000
103 67.000
103 71.000
103 77.000
103 103.000
III
III
III
4000
5000
6300
4000
5000
6300
100 B
100 B
100 B
3WL13 40-4@@41-....
3WL13 50-4@@41-....
3WL13 63-4@@41-....
1
1
1
1 unit
1 unit
1 unit
103 99.000
103 99.000
103 108.000
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@43-....
3WL12 10-4@@43-....
3WL12 12-4@@43-....
3WL12 16-4@@43-....
3WL12 20-4@@43-....
3WL12 25-4@@43-....
3WL12 32-4@@43-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
67.000
67.000
67.000
67.000
67.000
71.000
77.000
III
4000
4000
100 B
3WL13 40-4@@43-....
1
1 unit
103
99.000
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
67.000
67.000
67.000
67.000
67.000
71.000
77.000
1
1 unit
103
99.000
Front main circuit connection, double hole
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@44-....
3WL12 10-4@@44-....
3WL12 12-4@@44-....
3WL12 16-4@@44-....
3WL12 20-4@@44-....
3WL12 25-4@@44-....
3WL12 32-4@@44-....
III
4000
4000
100 B
3WL13 40-4@@44-....
Non-automatic air circuit breakers2)
Without electronic release
Order No. supplements
Additional
price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI6)
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
BB
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/18.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/17
15
Front main circuit connection, single hole
II
II
II
II
II
II
II
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
4-pole, fixed-mounted versions
Size
Max. rated circuit breaker Rated current1)
current
In
In max.
Icu up to 130 kA at 500 V,
very high switching capacity C
A
kA
A
PU
PS*
(UNIT,
Basic price SET, M)
per PU
C
Order No.
Order No. supplements,
see page 15/23
PG
DT
Weight
per PU
approx.
kg
Horizontal main circuit connection
III
III
4000
5000
4000
5000
130 B
130 B
3WL13 40-5@@42-....
3WL13 50-5@@42-....
1
1
1 unit
1 unit
103
103
99.000
99.000
4000
5000
6300
130 B
130 B
130 B
3WL13 40-5@@41-....
3WL13 50-5@@41-....
3WL13 63-5@@41-....
1
1
1
1 unit
1 unit
1 unit
103 99.000
103 99.000
103 108.000
Vertical main circuit connection
III
III
III
4000
5000
6300
Non-automatic air circuit breakers2)
Order No. supplements
Without electronic release
Additional
price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
15
Standard Order No. supplements (for further Order No. supplements, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
Footnotes for pages 15/15 to 15/18:
1)
The rated current is determined by the rated current module. For the standard version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on
page 15/24.
2)
For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see Technical Information LV 1T, "Technical specifications".
1AA2
Without
3)
Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 15/34. The
internal current transformers for N conductors can be ordered by adding
the supplement "–Z" and the order code "F23", see page 15/26.
4)
Current transformers for protection of the N conductor are to be ordered
separately, see page 15/34.
5)
ETU45B to ETU76B with ground-fault protection module GFM AT (alarm
and tripping), see page 15/34.
6)
ETU15B cannot be used with 3WL circuit breakers, size III.
* You can order this quantity or a multiple thereof.
15/18
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
4-pole, withdrawable versions
■ Selection and ordering data
Size
Max. rated circuit breaker Rated current1)
In
current
In max.
A
A
Icu up to 55/66 kA at 500 V,
ECO switching capacity N
Order No.
Order No. supplements,
see page 15/23
kA DT
PS*
PU
(UNIT,
Basic price SET, M)
per PU
N
PG
Weight
per PU
approx.
kg
Without guide frames
(for guide frames, see page 15/30 to 15/33)
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@45-....
3WL11 08-2@@45-....
3WL11 10-2@@45-....
3WL11 12-2@@45-....
3WL11 16-2@@45-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
54.000
54.000
54.000
54.000
54.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@45-....
3WL12 10-2@@45-....
3WL12 12-2@@45-....
3WL12 16-2@@45-....
3WL12 20-2@@45-....
3WL12 25-2@@45-....
3WL12 32-2@@45-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
75.000
75.000
75.000
75.000
72.000
76.000
82.000
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@46-....
3WL11 08-2@@46-....
3WL11 10-2@@46-....
3WL11 12-2@@46-....
3WL11 16-2@@46-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
84.000
84.000
84.000
84.000
84.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@46-....
3WL12 10-2@@46-....
3WL12 12-2@@46-....
3WL12 16-2@@46-....
3WL12 20-2@@46-....
3WL12 25-2@@46-....
3WL12 32-2@@46-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
109.000
109.000
109.000
109.000
109.000
123.000
136.000
With guide frames, vertical main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@47-....
3WL11 08-2@@47-....
3WL11 10-2@@47-....
3WL11 12-2@@47-....
3WL11 16-2@@47-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
84.000
84.000
84.000
84.000
84.000
II
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
66
66
66
66
66
66
66
66
B
B
B
B
B
B
B
B
3WL12 08-2@@47-....
3WL12 10-2@@47-....
3WL12 12-2@@47-....
3WL12 16-2@@47-....
3WL12 20-2@@47-....
3WL12 25-2@@47-....
3WL12 32-2@@47-....
3WL12 40-2@@47-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
103
109.000
109.000
109.000
109.000
109.000
123.000
136.000
146.000
With guide frames, connecting flanges
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
55
55
55
55
55
B
B
B
B
B
3WL11 06-2@@48-....
3WL11 08-2@@48-....
3WL11 10-2@@48-....
3WL11 12-2@@48-....
3WL11 16-2@@48-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
84.000
84.000
84.000
84.000
84.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
66
66
66
66
66
66
66
B
B
B
B
B
B
B
3WL12 08-2@@48-....
3WL12 10-2@@48-....
3WL12 12-2@@48-....
3WL12 16-2@@48-....
3WL12 20-2@@48-....
3WL12 25-2@@48-....
3WL12 32-2@@48-....
Order No. supplements
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
109.000
109.000
109.000
109.000
109.000
123.000
136.000
Non-automatic air circuit breakers2)
Without electronic release
AA
Additional
price
Without
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
BB
CB
EB
FB
NB
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/22.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/19
15
With guide frames, horizontal main circuit connection
I
I
I
I
I
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
4-pole, withdrawable versions
Size
Max. rated circuit breaker Rated current1)
In
current
In max.
Icu up to 66/80 kA at 500 V,
standard switching capacity S
A
kA
DT
A
Order No.
Order No. supplements,
see page 15/23
PS*
PU
(UNIT,
Basic price SET, M)
per PU
S
PG
Weight
per PU
approx.
kg
Without guide frames
(for guide frames, see page 15/30 to 15/33)
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@45-....
3WL11 08-3@@45-....
3WL11 10-3@@45-....
3WL11 12-3@@45-....
3WL11 16-3@@45-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
54.000
54.000
54.000
54.000
54.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@45-....
3WL12 10-3@@45-....
3WL12 12-3@@45-....
3WL12 16-3@@45-....
3WL12 20-3@@45-....
3WL12 25-3@@45-....
3WL12 32-3@@45-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
72.000
72.000
72.000
72.000
72.000
76.000
82.000
15
With guide frames, horizontal main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@46-....
3WL11 08-3@@46-....
3WL11 10-3@@46-....
3WL11 12-3@@46-....
3WL11 16-3@@46-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
84.000
84.000
84.000
84.000
84.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@46-....
3WL12 10-3@@46-....
3WL12 12-3@@46-....
3WL12 16-3@@46-....
3WL12 20-3@@46-....
3WL12 25-3@@46-....
3WL12 32-3@@46-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
109.000
109.000
109.000
109.000
109.000
123.000
136.000
With guide frames, vertical main circuit connection
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@47-....
3WL11 08-3@@47-....
3WL11 10-3@@47-....
3WL11 12-3@@47-....
3WL11 16-3@@47-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
84.000
84.000
84.000
84.000
84.000
II
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
80
80
80
80
80
80
80
80
B
B
B
B
B
B
B
B
3WL12 08-3@@47-....
3WL12 10-3@@47-....
3WL12 12-3@@47-....
3WL12 16-3@@47-....
3WL12 20-3@@47-....
3WL12 25-3@@47-....
3WL12 32-3@@47-....
3WL12 40-3@@47-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
103
109.000
109.000
109.000
109.000
109.000
123.000
136.000
146.000
With guide frames, connecting flanges
I
I
I
I
I
630
800
1000
1250
1600
630
800
1000
1250
1600
66
66
66
66
66
B
B
B
B
B
3WL11 06-3@@48-....
3WL11 08-3@@48-....
3WL11 10-3@@48-....
3WL11 12-3@@48-....
3WL11 16-3@@48-....
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
84.000
84.000
84.000
84.000
84.000
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
80
80
80
80
80
80
80
B
B
B
B
B
B
B
3WL12 08-3@@48-....
3WL12 10-3@@48-....
3WL12 12-3@@48-....
3WL12 16-3@@48-....
3WL12 20-3@@48-....
3WL12 25-3@@48-....
3WL12 32-3@@48-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
109.000
109.000
109.000
109.000
109.000
123.000
136.000
Non-automatic air circuit breakers2)
Without electronic release
Order No. supplements
Additional
price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
BB
CB
EB
FB
NB
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/22.
* You can order this quantity or a multiple thereof.
15/20
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
4-pole, withdrawable versions
Size
Max. rated circuit breaker Rated current1)
current
In
In max.
Icu up to 100 kA at 500 V,
high switching capacity H
A
kA
DT
A
PS*
PU
(UNIT,
Basic price SET, M)
per PU
H
Order No.
Order No. supplements,
see page 15/23
PG
Weight
per PU
approx.
kg
Without guide frames
(for guide frames, see page 15/30 to 15/33)
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@45-....
3WL12 10-4@@45-....
3WL12 12-4@@45-....
3WL12 16-4@@45-....
3WL12 20-4@@45-....
3WL12 25-4@@45-....
3WL12 32-4@@45-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
72.000
72.000
72.000
72.000
72.000
76.000
82.000
III
III
III
4000
5000
6300
4000
5000
6300
100 B
100 B
100 B
3WL13 40-4@@45-....
3WL13 50-4@@45-....
3WL13 63-4@@45-....
1
1
1
1 unit
1 unit
1 unit
103 106.000
103 106.000
103 108.000
With guide frames, horizontal main circuit connection
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@46-....
3WL12 10-4@@46-....
3WL12 12-4@@46-....
3WL12 16-4@@46-....
3WL12 20-4@@46-....
3WL12 25-4@@46-....
3WL12 32-4@@46-....
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
109.000
109.000
109.000
109.000
109.000
123.000
136.000
III
III
4000
5000
4000
5000
100 B
100 B
3WL13 40-4@@46-....
3WL13 50-4@@46-....
1
1
1 unit
1 unit
103 190.000
103 190.000
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
2000
2500
3200
4000
100
100
100
100
100
100
100
100
B
B
B
B
B
B
B
B
3WL12 08-4@@47-....
3WL12 10-4@@47-....
3WL12 12-4@@47-....
3WL12 16-4@@47-....
3WL12 20-4@@47-....
3WL12 25-4@@47-....
3WL12 32-4@@47-....
3WL12 40-4@@47-....
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
103
109.000
109.000
109.000
109.000
109.000
123.000
136.000
146.000
III
III
III
4000
5000
6300
4000
5000
6300
100 B
100 B
100 B
3WL13 40-4@@47-....
3WL13 50-4@@47-....
3WL13 63-4@@47-....
1
1
1
1 unit
1 unit
1 unit
103 190.000
103 190.000
103 227.000
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
1
1 unit
103 190.000
With guide frames, connecting flanges
II
II
II
II
II
II
II
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
100
100
100
100
100
100
100
B
B
B
B
B
B
B
3WL12 08-4@@48-....
3WL12 10-4@@48-....
3WL12 12-4@@48-....
3WL12 16-4@@48-....
3WL12 20-4@@48-....
3WL12 25-4@@48-....
3WL12 32-4@@48-....
III
4000
4000
100 B
3WL13 40-4@@48-....
Non-automatic air circuit breakers2)
Without electronic release
Order No. supplements
109.000
109.000
109.000
109.000
109.000
123.000
136.000
Additional
price
Without
AA
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI6)
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
BB
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
1AA2
Without
For footnotes see page 15/22.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/21
15
With guide frames, vertical main circuit connection
II
II
II
II
II
II
II
II
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
4-pole, withdrawable versions
Size
Max. rated circuit breaker Rated current1)
current
In
In max.
Icu up to 130 kA at 500 V,
very high switching capacity C
A
kA
A
PU
PS*
(UNIT,
Basic price SET, M)
per PU
C
Order No.
Order No. supplements,
see page 15/23
PG
DT
Weight
per PU
approx.
kg
Without guide frames
(for guide frames, see page 15/30 to 15/33)
III
III
III
4000
5000
6300
4000
5000
6300
130 B
130 B
130 B
3WL13 40-5@@45-....
3WL13 50-5@@45-....
3WL13 63-5@@45-....
1
1
1
1 unit
1 unit
1 unit
103 115.000
103 106.000
103 108.000
130 B
130 B
3WL13 40-5@@46-....
3WL13 50-5@@46-....
1
1
1 unit
1 unit
103 190.000
103 190.000
130 B
130 B
130 B
3WL13 40-5@@47-....
3WL13 50-5@@47-....
3WL13 63-5@@47-....
1
1
1
1 unit
1 unit
1 unit
103 190.000
103 190.000
103 227.000
With guide frames, horizontal main circuit connection
III
III
4000
5000
4000
5000
With guide frames, vertical main circuit connection
III
III
III
4000
5000
6300
4000
5000
6300
Non-automatic air circuit breakers2)
Order No. supplements
Without electronic release
Additional
price
Without
AA
15
Electronic releases
Versions without ground-fault protection
ETU25B: Protection functions LSI
ETU45B: Protection functions LSIN3)
ETU45B: Protection functions LSIN3) with 4-line display
ETU76B: Protection functions LSIN3) with pixel graphics display
CB
EB
FB
NB
Versions with ground-fault protection
ETU27B: Protection functions LSING4)
ETU45B: Protection functions LSING3)5)
ETU45B: Protection functions LSING3)5) with 4-line display
ETU76B: Protection functions LSING3)5) with pixel graphics display
DG
EG
FG
NG
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 15/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO
Footnotes for pages 15/19 to 15/22:
1)
The rated current is determined by the rated current module. For the standard version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on
page 15/24.
2)
For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see Technical Information LV 1T, "Technical specifications".
1AA2
Without
3)
Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 15/34. The
internal current transformers for N conductors can be ordered by adding
the supplement "–Z" and the order code "F23", see page 15/26.
4)
Current transformers for protection of the N conductor are to be ordered
separately, see page 15/34.
5)
ETU45B to ETU76B with ground-fault protection module GFM AT (alarm
and tripping), see page 15/34.
6)
ETU15B cannot be used with 3WL circuit breakers, size III.
* You can order this quantity or a multiple thereof.
15/22
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Options
■ Selection and ordering data
Order No. supplement
Additional
price
3WL 1 . . . - . . . . . -7 7 7 7
Operating mechanisms
Manual operating mechanism with mechanical closing
Without
1
Manual operating mechanism with mechanical
and electrical closing, closing solenoid suitable
for uninterrupted duty, 100 % ON period
Closing solenoid
AC 50/60 Hz V
V DC
110
230
110 ... 125
220
2
3
Manual/motorized operating mechanism with mechanical
and electrical closing, closing solenoid suitable for
uninterrupted duty, 100 % ON period
Motor
Closing solenoid
AC 50/60 Hz V
V DC
AC 50/60 Hz V
V DC
208 ... 240
110 ... 127
--
220 ... 250
110 ... 125
24
230
110
--
220
110 ... 125
24
4
5
6
To order different voltages for
motorized operating mechanism and closing solenoid or
closing solenoid for synchronization purposes:
"1" at the 13th digit of the Order No. and order codes,
see page 15/25.
15
1st auxiliary release
Without 1st auxiliary release
Without
A
Shunt release suitable for uninterrupted duty, 100 % ON period
Operating range 0.85 ... 1.1 x Us
Us AC 50/60 Hz V Us V DC
----110
230
24
30
48
60
110 ... 125
220
B
C
D
E
F
G
2nd auxiliary release
Without 2nd auxiliary release
Without
A
Shunt release suitable for uninterrupted duty, 100 % ON period
Operating range 0.85 ... 1.1 x Us
Us AC 50/60 Hz V Us V DC
-24
-30
-48
-60
110
110 ... 125
230
220
B
C
D
E
F
G
Undervoltage release, instantaneous (≤ 80 ms),
short-delay (≤ 200 ms)
Operating range 0.85 ... 1.1 x Us
Us AC 50/60 Hz V Us V DC
-24
-30
-48
-60
110 ... 127
110 ... 125
208 ... 240
220 ... 250
380 ... 415
--
J
K
L
U
M
N
P
Undervoltage release, can be delayed between 0.2 s and 3.2 s
Operating range 0.85 ... 1.1 x Us
Us AC 50/60 Hz V Us V DC
-110 ... 127
208 ... 240
380 ... 415
48
110 ... 125
220 ... 250
--
Q
R
S
T
Auxiliary switches
1st auxiliary switch block
2 NO + 2 NC
2
1st + 2nd auxiliary switch block
4 NO + 4 NC
6 NO + 2 NC
5 NO + 3 NC
4
7
8
Without
Siemens LV 1 · 2009
15/23
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Options
Add "–Z" to the complete Order No. and
indicate the appropriate order code(s).
Order No. with "–Z"
1 2 3 4 5
6 7
Additional price
8 9 10 11 12
13 14 15 16
3WL . . . . - . . . . . - . . . . - Z
and additional order code(s)
@@@+ . . . + . . .
Code for
"Further versions"–Z
Operating manual
Printed version
In scope of supply of circuit breaker) French/Italian
A 1 1
In scope of supply of circuit breaker) Spanish/Portuguese
A 1 2
Rated voltage 1000 V AC/DC
Add.
price
3-pole
Only for circuit breakers with high switching capacity H
(8th digit of the Order No. is a "4")
Cannot be combined with "Rated voltage 1150 V AC order code "A15".
Size II1)
Up to 2000 A
2500 A
3200 A
A 0 5
A 0 5
A 0 5
Size III1)2)
4000 A
5000 A
6300 A
A 0 5
A 0 5
A 0 5
Add.
price
4-pole
Rated voltage 1150 V AC/DC
Only for circuit breakers with high switching capacity H
(8th digit of the Order No. is a "4")
Cannot be combined with "Rated voltage 1000 V AC order code "A05".
15
Size II
Up to 2000 A
2500 A
3200 A
4000 A
For size III select a circuit breaker with very high switching capacity C.
A
A
A
A
1
1
1
1
5
5
5
5
Tin-plated version of the customer's connections
on the guide frame3)4)
Only for circuit breakers in withdrawable version with horizontal connection or
flange connection. The normal delivery time increases to 15 work days.
Size I
Size II
Size III
A 0 8
A 0 8
A 0 8
Special packaging
Additional price
Special packaging for extended technical requirements
Cardboard packaging with wax coating (moisture protection),
internal bracing, tilt indicators
A 6 0
Rated current modules/rating plugs
Additional price
Rated current
In
A
Only one module is possible per For size I, II
circuit breaker (not in conjunction
with electronic release ETU15B).
As standard the overcurrent
releases are equipped with a
rated current module which is
equal to the maximum rated circuit breaker current (In max). The
rated current of the selected
rated current module must be
For size I, II, III
smaller than In max.
For size II, III
For size III
250
B 0 2
Without
315
B 0 3
Without
400
B 0 4
Without
500
B 0 5
Without
630
B 0 6
Without
800
B 0 8
Without
1000
B 1 0
Without
1250
B 1 2
Without
1600
B 1 6
Without
2000
B 2 0
Without
2500
B 2 5
Without
3200
B 3 2
Without
4000
B 4 0
Without
5000
B 5 0
Without
6300
B 6 3
Without
1)
If ordering withdrawable circuit breaker and guide frame separately,
specify order code "A05" for withdrawable circuit breaker and guide frame.
2)
Not necessary for circuit breakers with very high switching
capacity C as these circuit breakers can be used as standard up to
1150 V AC.
15/24
Siemens LV 1 · 2009
3)
Front connections are tinned as standard.
4)
The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Options
Add "–Z" to the complete Order No. and
indicate the appropriate order code(s).
Order No. with "–Z"
1 2 3 4 5
6 7
Additional price
8 9 10 11 12
13 14 15 16
3WL . . . . - . . . . . - . . . . - Z
and additional order code(s)
@@@+. . . + . . .
Code for
"Further versions"–Z
Indication/operator control elements, door sealing frames
5-digit mechanical operating cycles counter1)
C 0 1
Button with sealing cap
Electrical ON button
in the operator panel2)
Key operation with lock CES
Possible only for circuit breakers with
closing solenoid.
C 1 1
C 1 2
1 NO
C 2 0
Ready-to-close signal switch (S20) 1 NO
C 2 2
Signal switches2)
For the first auxiliary release (S22)
C 2 6
For the second auxiliary release (S23)
C 2 7
Storage status
signal switches 2) (S21)
Motor shutdown switch in the operator panel3)
EMERGENCY-STOP pushbuttons
Mushroom pushbutton instead of
the mechanical OFF pushbutton
Door sealing frames
S 2 5
S 2 4
T 4 0
Reclosing lockouts and remote resets
Automatic reset of the reclosing lockout
K 0 1
Tripped signal switch2)4)
K 0 7
1 CO
AC 50/60 Hz V
V DC
--120
208 ... 250
24
48
125
208 ... 250
K
K
K
K
1
1
1
1
0
1
2
3
M
M
M
M
0
0
0
0
1
3
5
6
15
Remote reset solenoid for displays and reset buttons
including automatic reset of the reclosing lockout
Motorized operating mechanisms and
closing/opening solenoids
Motorized operating mechanisms
Only possible if the 13th digit of the Order No. = "1"
Motor
AC 50/60 Hz V
V DC
--110 ... 127
208 ... 240
24 ... 30
48 ... 60
110 ... 125
220 ... 250
Closing solenoids suitable for uninterrupted duty, 100 % ON period
Only possible if the 13th digit of the Order No. = "1"
Activation solenoids
AC 50/60 Hz V
V DC
----110
230
24
30
48
M2 1
M2 2
M2 3
60
110
220
M2 4
M2 5
M2 6
Closing solenoids5) – unsuitable for uninterrupted duty, 5 % ON period
Only possible if the 13th digit of the Order No. = "1"
Activation solenoids
AC 50/60 Hz V
V DC
--110 ... 127
208 ... 240
24
48
110 ... 125
220 ... 250
M
M
M
M
3
3
3
3
1
3
5
6
M
M
M
M
4
4
4
4
1
3
5
6
1)
4)
2)
5)
Not available for non-automatic air circuit breakers.
Overexcited, i.e. opening time 50 ms (standard > 80 ms).
Only possible if the 14th position of the Order No. for the circuit breaker is
"A", i.e. "without 1st auxiliary release".
Opening solenoids (shunt releases)6) –
not suitable for uninterrupted duty, 5 % ON period
Activation solenoids
AC 50/60 Hz V
V DC
--110 ... 127
208 ... 240
24
48
110 ... 125
220 ... 250
Only possible with motorized operating mechanism.
Not possible with communications interface option, order code "F02" or
"F12".
3) Only for circuit breakers with motorized operating mechanism, not possible
with order codes "C11", "C12".
6)
Siemens LV 1 · 2009
15/25
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Options
Add "–Z" to the complete Order No. and
indicate the appropriate order code(s).
Order No. with "–Z"
1234 5 6 7
8 9 10 11 12
Additional price
13 14 15 16
3WL . . . . - . . . . . - . . . . -Z
and additional order code(s)
@@@ + . . . + . . .
Code for
"Further versions"
Interlocks, covers, position indicator switches
Mutual mechanical
interlockings
(interlocking module
with Bowden wire 2 m)
Arc chute covers
15
Not available for
- 1000 V version (order code "A05")
- DC version
- 4000 A size II
Shutters
2-part
lockable
with padlocks 1)
Position indicator switches
for guide frames
Fixed-mounted circuit breaker
-Z
Order
code for
fixedmounted
version
Order code
for withdrawable
version
@@@
@@@
S 5 5
-- -- --
For withdrawable circuit breakers
with guide frame
--
R 5 5
For guide frames
--
R 5 6
For withdrawable circuit breakers --
R 5 7
3-pole
Size I
Size II
Size III
----
R 1 0
R 1 0
R 1 0
4-pole
Size I
Size II
Size III
----
R 1 0
R 1 0
R 1 0
3-pole
Size I
Size II
Size III
----
R 2 1
R 2 1
R 2 1
4-pole
Size I
Size II
Size III
----
R 2 1
R 2 1
R 2 1
--
R 1 5
--
R 1 6
Connected Test
position
position
1 CO
1 CO
Disconnected
position
1 CO
3 CO
2 CO
1 CO
Add "–Z" to the complete Order No. and
indicate the appropriate order code(s).
Order No. with "–Z"
1 2 3 4 5
6 7
Additional price
8 9 10 11 12
13 14 15 16
3WL . . . . - . . . . . - . . . . - Z
and additional order code(s)
@@@
+. . . + . . .
Code for
"Further versions" -Z
Communication and measurement functions
Breaker status sensor (BSS)
F 0 1
PROFIBUS communications interface2) Including COM15 and breaker
status sensor (BSS)
F 0 2
MODBUS communications interface2)
F 1 2
Including COM16 and breaker
status sensor (BSS)
Measurement function Plus
(without PROFIBUS/MODBUS communications interface)3)
F 0 5
Overload and short-circuit protection for neutral conductors
Size I
Internal current transformers for
N conductors
Size II
Only possible with 4-pole circuit breakers
Size III
with ETU27B to ETU76B
F 2 3
F 2 3
F 2 3
EMC filters
Common-mode interference
F 3 1
suppressor filters (e.g. in IT networks, caused by frequency
converters)
Insertion loss (asymmetric) in
the range 40 kHz to 10 MHz
>40 dB.
EMC filters
1)
2)
Padlocks not included in scope of supply.
If ordering withdrawable circuit breaker and guide frame separately, specify order code "F02" or "F12" for withdrawable circuit breaker only.
15/26
Siemens LV 1 · 2009
3)
Additional voltage transformers are required for connection of the measurement function Plus, see page 15/43.
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Options
Add "–Z" to the complete Order No.
and indicate the appropriate order
code(s).
Order No. with "–Z"
1234 5 6 7
8 9 10 11 12
13 14 15 16
3WL . . . . - . . . . . - . . . . -Z
and additional order code(s)
@@@ + . . . + . . .
Code for
"Further versions"
Order code
for fixedmounted
version
Add. price
for fixedmounted version
-Z
Order code Add. price
for withfor withdrawdrawable
able version
version
@@@
@@@
S 0 1
S 0 1
S 0 3
S 0 3
S 0 5
S 0 5
Assembly kit for padlocks2)
S 0 7
S 0 7
Made by Ronis
S 0 8
S 0 8
Made by Profalux
S 0 9
S 0 9
EMERGENCY-STOP pushbuttons Mushroom pushbutton instead of
the mechanical OFF pushbutton
S 2 4
S 2 4
Locking devices against
Made by CES
unauthorized closing,
Made by Ronis
for withdrawable circuit breakers
Made by Profalux
The disconnector unit fulfills the
requirements for main circuit
breakers acc. to EN 60204-1,
consisting of a lock in the cabinet
door, active in the connected
position;
the function is retained when the circuit breaker is replaced
--
R 6 1
--
R 6 8
--
R 6 0
Locking devices
for operating mechanism handles
with padlock2)
S 3 3
S 3 3
Made by CES
--
S 7 1
Made by Profalux
--
S 7 5
Made by Ronis
--
S 7 6
--
R 8 1
--
R 8 5
--
R 8 6
Locking devices to prevent
movement of the withdrawable
circuit breakers
Safety lock for mounting on
the circuit breaker
15
Locking devices
Locking devices against
unauthorized closing,
in the operator panel
Made by CES
The disconnector unit fulfills the
requirements for main circuit break- Made by IKON
ers acc. to EN 60204-1
Assembly kit FORTRESS or Castell1)
Locking mechanisms
Locking mechanisms to prevent
Made by CES
movement of the withdrawable
Made by Profalux
circuit breaker in disconnected
Made by Ronis
positions,
consisting of Bowden wire and lock
in the cabinet door
Not possible in combination with
order code "R30" or "R50".
Locking mechanisms
Not possible in combination with
order code "R81", "R85" or "R86".
To prevent opening of the cabinet door in: S 3 0
ON position (fixed-mounted version)/
in connected position (withdrawable
version)
R 3 0
To prevent movement
with the cabinet door open
--
R 5 0
N 6 1
P 6 1
Connection methods for auxiliary conductors
Connections for screwless
terminals (tension spring)
1)
2)
Locks must be ordered from the manufacturer.
Padlock not included in the scope of supply.
Siemens LV 1 · 2009
15/27
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Options
Add "–Z" to the complete Order No. and
indicate the appropriate order code(s).
Order No. with "–Z"
1234 5 6 7
8 9 10 11 12
13 14 15 16
3WL . . . . - . . . . . - . . . . -Z
and additional order code(s)
@@@
+. . . + . . .
Code for
"Further versions"–Z
For withdrawable circuit breakers with guide frames
or for guide frames1)
Add. price
3-pole
Add. price
4-pole
Add. price
3-pole
Add. price
4-pole
To select this connection method,
the 12th digit of the Order No. for the
circuit breaker must be a "6"
15
Connection methods for main circuit connections
Top and bottom:
accessible from front,
single hole
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
Size III, up to 4000 A
P
P
P
P
P
0
0
0
0
0
0
0
0
0
0
Top and bottom:
accessible from front,
double hole
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
Size III, up to 4000 A
P
P
P
P
P
0
0
0
0
0
1
1
1
1
1
Top:
horizontal,
double hole
Bottom:
accessible from front,
single hole
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
Size III, up to 4000 A
P
P
P
P
P
0
0
0
0
0
7
7
7
7
7
Top:
vertical
Bottom:
horizontal
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
Size III, up to 4000 A
Size III, up to 5000 A
P
P
P
P
P
P
1
1
1
1
1
1
8
8
8
8
8
8
Top:
connecting flange
Bottom:
horizontal
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
Size III, up to 4000 A
P
P
P
P
P
1
1
1
1
1
9
9
9
9
9
Top:
horizontal
Bottom:
vertical
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
Size III, up to 4000 A
Size III, up to 5000 A
P
P
P
P
P
P
2
2
2
2
2
2
3
3
3
3
3
3
For fixed-mounted circuit breakers
To select this connection method,
the 12th digit of the Order No. for the
circuit breaker must be a "2"
Connection methods for main circuit connections
Top:
horizontal
Bottom:
accessible from front,
single hole
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
Size III, up to 4000 A
N
N
N
N
N
1
1
1
1
1
1
1
1
1
1
Top:
vertical
Bottom:
horizontal
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
Size III, up to 4000 A
Size III, up to 5000 A
N
N
N
N
N
N
2
2
2
2
2
2
0
0
0
0
0
0
Top:
horizontal
Bottom:
vertical
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
Size III, up to 4000 A
Size III, up to 5000 A
N
N
N
N
N
N
2
2
2
2
2
2
4
4
4
4
4
4
1)
Only horizontal connection and vertical connection are available for circuit
breakers with very high switching capacity C.
15/28
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
■ Overview
Determination of the number of auxiliary supply connectors required
X7
X6
X5
X8
The required number of auxiliary supply connectors
depends on:
• Operating mechanism type
• Electronic trip unit with/without current transformer
• Type and number of auxiliary releases
• Number of auxiliary switches
• COM15/COM16 communication interface
Number of auxiliary supply
connectors
Terminal
a
First auxiliary supply connector X6 always required.
1
X6
b
b1
b2
b3
Operating mechanisms
Manual operating mechanism with stored-energy feature with mechanical closing
Manual operating mechanism with stored-energy feature with mechanical and electrical closing
Manual/motorized operating mechanism with stored-energy feature with mechanical and electrical closing
0
0
+1
X6
X5
c
c1
c2
Electronic trip units
Electronic trip units ETU15B, ETU25B, ETU27B
Electronic trip units ETU45B, ETU76B (internal CubicleBUS)
0
+1
X8
c3
c4
Connections for external current transformers for overload protection in the N conductor and ground-fault protection
Current transformer installed in the N conductor (required with 3-pole circuit breakers if c2 is not selected)
Current transformer in the neutral point of the transformer (required if c2 or c3 is not selected)
+1
+1
X8
X8
d
d1
d2
Auxiliary releases
With/without 1st auxiliary release (shunt trip unit F1)
2nd auxiliary release (shunt trip unit F2, undervoltage trip unit F3, delayable undervoltage trip unit F4)
0
+1
X6
X5
e
e1
e2
Auxiliary switch blocks
1st auxiliary switch block 2 NO + 2 NC
1st and 2nd auxiliary switch block 4 NO + 4 NC or 6 NO + 2 NC or 5 NO + 3 NC (required if b3 or d2 is not selected)
0
+1
X6
X5
f
f1
f2
Communication modules
Without communication module COM15/COM16
With communication module COM15/COM16 –
occupies the entire terminal strip X7, making the following options no longer possible:
• Tripped signal switch S24
• Stored-energy status indication S21
• Electrical ON button S10
• Signaling switch on first and second auxiliary release S22 + S23
0
+1
X7
g
g1
g2
g3
g4
Optional signals/accessories
Tripped signal switch S24 (only possible if f2 is not selected)
Stored-energy status indication S21 (only possible if f2 is not selected, required if g1 is not selected)
Electrical ON button S10 (only possible if f2 is not selected, required if g1 or g2 is not selected)
Signal switch on first auxiliary release S22 (only possible if f2 is not selected,
required if g1, g2 or g3 is not selected)
Signal switch on second auxiliary release S23 (only possible if f2 is not selected,
required if g1, g2, g3 or g4 is not selected)
+1
+1
+1
+1
X7
X7
X7
X7
+1
X7
X6
X5
X8
g5
g6
g7
g8
Ready-to-close indicator switch S20
Motor shutdown switch S12 (only possible if motorized operating mechanism is selected)
Remote reset solenoid F7 (required if c2 is not selected)
0
0
+1
h
Total number of auxiliary supply connectors
(max. 4)
For ordering the auxiliary supply connectors see under
"Accessories and Spare Parts, Guide Frames for AC Circuit Breakers/Non-Automatic Air Circuit Breakers", pages 15/30 to 15/33
and under "Accessories and Spare Parts, Auxiliary Conductor Connections, Auxiliary Supply Connectors", page 15/39.
Siemens LV 1 · 2009
15/29
15
NSE0_01104
This selection is only required if the guide frame is ordered under a
separate Order No.
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
■ Selection and ordering data
Guide frames for AC circuit breakers/non-automatic air circuit breakers
Size
Max. rated circuit breaker
current
In max.
A
Switching DT
capacity
Icu
Guide frames for 3-pole circuit breakers/ PU
PS*
non-automatic air circuit breakers
(UNIT,
Order No.
Basic price SET, M)
kA
(Order No. supplements
required according to
table below)
PG
Weight
per PU
approx.
per PU
kg
Front main circuit connection, single hole
I
I
II
II
II
III
1000
1600
2000
2500
3200
4000
... 100
... 100
... 100
... 100
... 100
... 100
B
B
B
B
B
B
3WL9 211-1AA@@-@@A1
3WL9 211-2AA@@-@@A1
3WL9 212-3AA@@-@@A1
3WL9 212-4AA@@-@@A1
3WL9 212-5AA@@-@@A1
3WL9 213-6AA@@-@@A1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
25.000
25.000
31.000
39.000
45.000
60.000
... 100
... 100
... 100
... 100
... 100
... 100
B
B
B
B
B
B
3WL9 211-1AB@@-@@A1
3WL9 211-2AB@@-@@A1
3WL9 212-3AB@@-@@A1
3WL9 212-4AB@@-@@A1
3WL9 212-5AB@@-@@A1
3WL9 213-6AB@@-@@A1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
25.000
25.000
31.000
39.000
45.000
60.000
... 100
... 100
... 100
... 100
... 100
... 100
... 100
... 150
... 150
B
B
B
B
B
B
B
B
B
3WL9 211-1AC@@-@@A1
3WL9 211-2AC@@-@@A1
3WL9 212-3AC@@-@@A1
3WL9 212-4AC@@-@@A1
3WL9 212-5AC@@-@@A1
3WL9 213-6AC@@-@@A1
3WL9 213-7AC@@-@@A1
3WL9 213-6AC@@-@@C1
3WL9 213-7AC@@-@@C1
1
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
103
103
25.000
25.000
31.000
39.000
45.000
60.000
60.000
63.000
63.000
Front main circuit connection, double hole
I
I
II
II
II
III
1000
1600
2000
2500
3200
4000
15
Horizontal main circuit connection
I
I
II
II
II
III
III
III
III
1000
1600
2000
2500
3200
4000
5000
4000
5000
Number of auxiliary supply connectors
Order No. supplements
Without
1 connector
2 connectors
3 connectors
4 connectors
For required number of auxiliary supply connectors,
see table on page 15/29
Add. price
Without
0
1
2
3
4
Type of auxiliary circuit connections
Without
With screw connections (SIGUT)
With screwless connection method (tension spring)
Without
0
1
2
Position indicator switches
Without
Option 1
Option 2
Without
0
1
Connected position 1 CO contact,
test position 1 CO contact,
disconnected position 1 CO contact
Connected position 3 CO contacts,
test position 2 CO contacts,
disconnected position 1 CO contact
2
Shutters
Without
With shutter,
2-part,
lockable
A
B
Size I
Size II
Size III
Add "–Z" to the complete Order No.
and indicate the appropriate order code(s).
Order No. with "–Z"
and additional order code
Without
1234 5 6 7
8 9 10 11 12
13 14 15 16
Additional
3WL9 2 1 . – . . . . . – . . . . –Z price
@@@
Rated voltage 1000 V AC
Size II, except 4000 A (switching capacity H)
Size III, not necessary with with very high switching capacity
A05
A05
Size II, except 4000 A (switching capacity H)
A15
Rated voltage 1150 V AC
Tinned version of the customer's connections on the guide frame1)2)
Only for guide frames with horizontal connection or flange connection
Size I
Size II
Size III
A08
A08
A08
For main circuit connection vertical and main circuit connecting flange see the following page.
All other accessory parts must be ordered by specifying "–Z" and the corresponding order code, see pages 15/24 to 15/24.
1) Front connections are tinned as standard.
2) The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
15/30
Siemens LV 1 · 2009
* You can order this quantity or a multiple thereof.
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Size
Max. rated circuit breaker
current
In max.
A
Switching DT
capacity
Icu
Guide frames for 3-pole circuit breakers/ PU
PS*
non-automatic air circuit breakers
(UNIT,
Order No.
Basic price SET, M)
kA
(Order No. supplements
required according to
table below)
PG
Weight
per PU
approx.
per PU
kg
Vertical main circuit connection
I
I
II
II
II
II
III
III
III
III
III
III
1000
1600
2000
2500
3200
4000
4000
5000
6300
4000
5000
6300
... 100
... 100
... 100
... 100
... 100
... 100
... 100
... 100
... 100
... 150
... 150
... 150
B
B
B
B
B
B
B
B
B
B
B
B
3WL9 211-1AD@@-@@A1
3WL9 211-2AD@@-@@A1
3WL9 212-3AD@@-@@A1
3WL9 212-4AD@@-@@A1
3WL9 212-5AD@@-@@A1
3WL9 212-6AD@@-@@A1
3WL9 213-6AD@@-@@A1
3WL9 213-7AD@@-@@A1
3WL9 213-8AD@@-@@A1
3WL9 213-6AD@@-@@C1
3WL9 213-7AD@@-@@C1
3WL9 213-8AD@@-@@C1
1
1
1
1
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
103
103
103
103
103
25.000
25.000
31.000
39.000
45.000
52.000
60.000
60.000
70.000
63.000
63.000
74.000
... 100
... 100
... 100
... 100
... 100
... 100
B
B
B
B
B
B
3WL9 211-1AE@@-@@A1
3WL9 211-2AE@@-@@A1
3WL9 212-3AE@@-@@A1
3WL9 212-4AE@@-@@A1
3WL9 212-5AE@@-@@A1
3WL9 213-6AE@@-@@A1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
25.000
25.000
31.000
39.000
45.000
60.000
Main circuit connection connecting flanges
1000
1600
2000
2500
3200
4000
Number of auxiliary supply connectors
Order No. supplements
Without
1 connector
2 connectors
3 connectors
4 connectors
For required number of auxiliary supply connectors,
see table on page 15/29
Add. price
Without
0
1
2
3
4
15
I
I
II
II
II
III
Type of auxiliary circuit connections
Without
With screw connections (SIGUT)
With screwless connection method (tension spring)
Without
0
1
2
Position indicator switches
Without
Option 1
Option 2
Without
0
1
Connected position 1 CO contact,
test position 1 CO contact,
disconnected position 1 CO contact
Connected position 3 CO contacts,
test position 2 CO contacts,
disconnected position 1 CO contact
2
Shutters
Without
With shutter,
2-part,
lockable
A
B
Size I
Size II
Size III
Add "–Z" to the complete Order No.
and indicate the appropriate order code(s).
Order No. with "–Z"
and additional order code
Without
1234 5 6 7
8 9 10 11 12
13 14 15 16
Additional
3WL9 2 1 . – . . . . . – . . . . –Z price
@@@
Rated voltage 1000 V AC
Size II, except 4000 A (switching capacity H)
A05
Size III, not necessary with circuit breakers with very high switching capacity A 0 5
Rated voltage 1150 V AC
Size II, except 4000 A (switching capacity H)
Tinned version of the customer's connections on the guide frame1)2)
Only for guide frames with horizontal connection or flange connection
Size I
Size II
Size III
A15
A08
A08
A08
For main circuit connection front, single hole, main circuit connection front, double hole, and main circuit connection horizontal see
the previous page.
All other accessory parts must be ordered by specifying "–Z" and the corresponding order code, see pages 15/24 to 15/28.
1) Front connections are tinned as standard.
2) The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/31
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Size
Max. rated circuit breaker
current
In max.
Switching DT
capacity
Icu
A
kA
Guide frames for 4-pole circuit breakers/ PU
PS*
non-automatic air circuit breakers
(UNIT,
Order No.
Basic price SET, M)
(Order No. supplements
required according to
table below)
PG
Weight
per PU
approx.
per PU
kg
Front main circuit connection, single hole
I
I
II
II
II
III
1000
1600
2000
2500
3200
4000
... 100
... 100
... 100
... 100
... 100
... 100
B
B
B
B
B
B
3WL9 211-1BA@@-@@A1
3WL9 211-2BA@@-@@A1
3WL9 212-3BA@@-@@A1
3WL9 212-4BA@@-@@A1
3WL9 212-5BA@@-@@A1
3WL9 213-6BA@@-@@A1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
30.000
30.000
37.000
47.000
54.000
84.000
... 100
... 100
... 100
... 100
... 100
... 100
B
B
B
B
B
B
3WL9 211-1BB@@-@@A1
3WL9 211-2BB@@-@@A1
3WL9 212-3BB@@-@@A1
3WL9 212-4BB@@-@@A1
3WL9 212-5BB@@-@@A1
3WL9 213-6BB@@-@@A1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
30.000
30.000
37.000
47.000
54.000
84.000
... 100
... 100
... 100
... 100
... 100
... 100
... 100
... 130
... 130
B
B
B
B
B
B
B
B
B
3WL9 211-1BC@@-@@A1
3WL9 211-2BC@@-@@A1
3WL9 212-3BC@@-@@A1
3WL9 212-4BC@@-@@A1
3WL9 212-5BC@@-@@A1
3WL9 213-6BC@@-@@A1
3WL9 213-7BC@@-@@A1
3WL9 213-6BC@@-@@C1
3WL9 213-7BC@@-@@C1
1
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
103
103
30.000
30.000
37.000
47.000
54.000
84.000
84.000
87.000
87.000
Front main circuit connection, double hole
I
I
II
II
II
III
1000
1600
2000
2500
3200
4000
Horizontal main circuit connection
15
I
I
II
II
II
III
III
III
III
1000
1600
2000
2500
3200
4000
5000
4000
5000
Number of auxiliary supply connectors
Order No. supplements
Without
1 connector
2 connectors
3 connectors
4 connectors
For required number of auxiliary supply connectors,
see table on page 15/29
Add. price
Without
0
1
2
3
4
Type of auxiliary circuit connections
Without
With screw connections (SIGUT)
With screwless connection method (tension spring)
Without
0
1
2
Position indicator switches
Without
Option 1
Option 2
Without
0
1
Connected position 1 CO contact,
test position 1 CO contact,
disconnected position 1 CO contact
Connected position 3 CO contacts,
test position 2 CO contacts,
disconnected position 1 CO contact
2
Shutters
Without
With shutter,
2-part,
lockable
A
B
Size I
Size II
Size III
Add "–Z" to the complete Order No.
and indicate the appropriate order code(s).
Order No. with "–Z"
and additional order code
Without
1234 5 6 7
8 9 10 11 12
13 14 15 16
Additional
3WL9 2 1 . – . . . . . – . . . . –Z price
@@@
Rated voltage 1000 V AC
Size II, except 4000 A (switching capacity H)
A05
Size III, not necessary with circuit breakers with very high switching capacity A 0 5
Rated voltage 1150 V AC
Size II, except 4000 A (switching capacity H)
Tinned version of the customer's connections on the guide frame1)2)
Only for guide frames with horizontal connection or flange connection
Size I
Size II
Size III
A15
A08
A08
A08
For main circuit connection vertical and main circuit connecting flange see the following page.
All other accessory parts must be ordered by specifying "–Z" and the corresponding order code, see pages 15/24 to 15/28.
1) Front connections are tinned as standard.
2) The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
15/32
Siemens LV 1 · 2009
* You can order this quantity or a multiple thereof.
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Size
Max. rated circuit breaker
current
In max.
Switching DT
capacity
Icu
A
kA
Guide frames for 4-pole circuit breakers/ PU
PS*
non-automatic air circuit breakers
(UNIT,
Order No.
Basic price SET, M)
(Order No. supplements
required according to
table below)
PG
Weight
per PU
approx.
per PU
kg
Vertical main circuit connection
I
I
II
II
II
II
III
III
III
III
III
III
1000
1600
2000
2500
3200
4000
4000
5000
6300
4000
5000
6300
... 100
... 100
... 100
... 100
... 100
... 100
... 100
... 100
... 100
... 130
... 130
... 130
B
B
B
B
B
B
B
B
B
B
B
B
3WL9 211-1BD@@-@@A1
3WL9 211-2BD@@-@@A1
3WL9 212-3BD@@-@@A1
3WL9 212-4BD@@-@@A1
3WL9 212-5BD@@-@@A1
3WL9 212-6BD@@-@@A1
3WL9 213-6BD@@-@@A1
3WL9 213-7BD@@-@@A1
3WL9 213-8BD@@-@@A1
3WL9 213-6BD@@-@@C1
3WL9 213-7BD@@-@@C1
3WL9 213-8BD@@-@@C1
1
1
1
1
1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
103
103
103
103
103
30.000
30.000
37.000
47.000
54.000
62.000
84.000
84.000
119.000
88.000
88.000
124.000
... 100
... 100
... 100
... 100
... 100
... 100
B
B
B
B
B
B
3WL9 211-1BE@@-@@A1
3WL9 211-2BE@@-@@A1
3WL9 212-3BE@@-@@A1
3WL9 212-4BE@@-@@A1
3WL9 212-5BE@@-@@A1
3WL9 213-6BE@@-@@A1
Order No. supplements
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
30.000
30.000
37.000
47.000
54.000
84.000
Main circuit connection connecting flanges
1000
1600
2000
2500
3200
4000
Number of auxiliary supply connectors
Without
1 connector
2 connectors
3 connectors
4 connectors
For required number of auxiliary supply connectors,
see table on page 15/29
Add. price
Without
0
1
2
3
4
15
I
I
II
II
II
III
Type of auxiliary circuit connections
Without
With screw connections (SIGUT)
With screwless connection method (tension spring)
Without
0
1
2
Position indicator switches
Without
Option 1
Option 2
Without
0
1
Connected position 1 CO contact,
test position 1 CO contact,
disconnected position 1 CO contact
Connected position 3 CO contacts,
test position 2 CO contacts,
disconnected position 1 CO contact
2
Shutters
Without
With shutter,
2-part,
lockable
A
B
Size I
Size II
Size III
Add "–Z" to the complete Order No.
and indicate the appropriate order code(s).
Order No. with "–Z"
and additional order code
Without
1234 5 6 7
8 9 10 11 12
13 14 15 16
Additional
3WL9 2 1 . – . . . . . – . . . . –Z price
@@@
Rated voltage 1000 V AC
Size II, except 4000 A (switching capacity H)
A05
Size III, not necessary with circuit breakers with very high switching capacity A 0 5
Rated voltage 1150 V AC
Size II, except 4000 A (switching capacity H)
Tinned version of the customer's connections on the guide frame1)2)
Only for guide frames with horizontal connection or flange connection
Size I
Size II
Size III
A15
A08
A08
A08
For main circuit connection front, single hole, main circuit connection front, double hole, and main circuit connection horizontal see
the previous page.
All other accessory parts must be ordered by specifying "–Z" and the corresponding order code, see pages 15/24 to 15/28.
1) Front connections are tinned as standard.
2) The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/33
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Protective devices with device holder and optional measurement
function1)
With protection
function
Measurement function
ETU15B
LI
Without
C
3WL9 311-5AA00-0AA2
1 1 unit
103
0.720
ETU25B
LSI
Without
C
3WL9 312-5AA00-0AA2
1 1 unit
103
0.720
ETU27B
LSING
Without
C
3WL9 312-7AA00-0AA2
1 1 unit
103
0.720
ETU45B
(without
display)
LSIN(G)
Without
With measurement
function Plus
C
B
3WL9 314-5AA00-0AA2
3WL9 314-5AA20-0AA2
1 1 unit
1 1 unit
103
103
0.720
0.720
ETU76B
LSIN(G)
Without
With measurement
function Plus
C
B
3WL9 317-6AA00-0AA2
3WL9 317-6AA20-0AA2
1 1 unit
1 1 unit
103
103
0.720
0.720
250
315
400
500
B
B
B
B
3WL9 111-0AA51-0AA0
3WL9 111-0AA52-0AA0
3WL9 111-0AA53-0AA0
3WL9 111-0AA54-0AA0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
103
103
103
103
0.010
0.010
0.010
0.010
630
800
1000
B
B
B
3WL9 111-0AA55-0AA0
3WL9 111-0AA56-0AA0
3WL9 111-0AA57-0AA0
1 1 unit
1 1 unit
1 1 unit
103
103
103
0.010
0.010
0.010
I, II, III
1250
1600
B
B
3WL9 111-0AA58-0AA0
3WL9 111-0AA61-0AA0
1 1 unit
1 1 unit
103
103
0.010
0.010
II, III
2000
2500
3200
4000
B
B
B
B
3WL9 111-0AA62-0AA0
3WL9 111-0AA63-0AA0
3WL9 111-0AA64-0AA0
3WL9 111-0AA65-0AA0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
103
103
103
103
0.010
0.010
0.010
0.010
III
5000
6300
B
B
3WL9 111-0AA66-0AA0
3WL9 111-0AA67-0AA0
1 1 unit
1 1 unit
103
103
0.010
0.010
GFM AT 45B (only for ETU45B) alarm and tripping
B
3WL9 111-0AT53-0AA0
1 1 unit
103
0.030
GFM AT 55B–76B (only for ETU76B) alarm and tripping
B
3WL9 111-0AT56-0AA0
1 1 unit
103
0.030
4-line displays for ETU45B
B
3WL9 111-0AT81-0AA0
1 1 unit
103
0.060
Internal transf. for N conductors Size I
(not for ETU release 2)
Size II
Including wiring kit
Size III
B
B
B
3WL9 111-0AA11-0AA0
3WL9 111-0AA12-0AA0
3WL9 111-0AA13-0AA0
1 1 unit
1 1 unit
1 1 unit
103
103
103
0.200
0.280
0.500
Internal transf. for N conductors Size I
Only for ETU release 2
Size II
Including wiring kit
Size III
B
B
B
3WL9 111-0AA14-0AA0
3WL9 111-0AA15-0AA0
3WL9 111-0AA16-0AA0
1 1 unit
1 1 unit
1 1 unit
103
103
103
0.200
0.280
0.500
3WL9 111-0AA2.-0AA0 External transf. for N conductors Size I
(T5, see Technical Information
Size II
LV 1 T, "Functions", "Measurement Size III
Method")
B
B
B
3WL9 111-0AA21-0AA0
3WL9 111-0AA22-0AA0
3WL9 111-0AA23-0AA0
1 1 unit
1 1 unit
1 1 unit
103
103
103
0.300
0.380
0.680
External transf. for N conductors Size I
With copper connection pieces
Size II
(T5, see Technical Information
Size III
N S E 0 _ 0 0 9 9 1 a
LV 1 T, "Functions", "Measurement
3WL9 111-0AA3.-0AA0 Method")
B
B
B
3WL9 111-0AA31-0AA0
3WL9 111-0AA32-0AA0
3WL9 111-0AA33-0AA0
1 1 unit
1 1 unit
1 1 unit
103
103
103
1.600
4.260
8.500
Not for ETU release 2
X
3WL9 111-0AK32-0AA0
1 1 unit
103
0.280
Only for ETU release 2
X
3WL9 111-0AK34-0AA0
1 1 unit
103
0.280
NSE0_01610b
Type
3WL9 31.-.AA.0-0AA1
Rated current modules/Rating plugs2)
For size
n
I, II
= 3 2 0 0 A
N S E 0 _ 0 0 9 9 2 b
15
3WL9 111-0AA64-0AA0
Rated current In (A)
Ground-fault modules3)
G F M
S I
g T R IP
A L A R M
G
B
T R IP
C
O F F
A L A R M
A
D
A T 4 5 B
t g (s )
.1
.3
.3
.1
.5
.4
.2
E
I 2 tg
.5
.2
.4
N S E 0 _ 0 1 0 2 7 a
3WL9 111-0AT53-0AA0
Displays
N S E 0 _ 0 1 6 0 9
3WL9 111-0AT81-0AA0
Current transformers for N conductor protection
N S E 0 _ 0 0 9 9 0 a
EMC filters
EMC filters
Common-mode interference suppressor filters (e.g. in IT networks,
caused by frequency converters)
Insertion loss (asymmetric) in the
range 40 kHz to 10 MHz >40 dB
1)
For replacement in existing circuit breakers please specify the circuit
breaker ID No. when ordering.
2)
With the rated current module selected, the maximum rated current In max of
the circuit breaker must not be exceeded. The following applies In ≤ In max.
3)
For direct measurement of the ground-fault current, e.g. in the neutral point
of the transformer, a 1200 A/1 A current transformer, class 1, is required.
The internal load of the SENTRON 3WL is 0.11 m. If the ground-fault current is to be determined using the vectorial sum of the phases, a current
transformer must be installed in the neutral conductor.
* You can order this quantity or a multiple thereof.
15/34
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNI
T,
SET,
M)
PG
Weight
per PU
approx.
kg
More accessories for electronic releases
NSE0_00983b
Sealable covers
ETU25B
N S E 0 _ 0 0 9 9 9 a
3WL9 111-0AT45-0AA0
1 1 unit
For ETU76
103
0.050
B
3WL9 111-0AT46-0AA0
1 1 unit
103
0.050
3WL9 111-0AK21-0AA0
1 1 unit
103
0.050
Remote reset solenoids1)
For mechanical tripped indicator
24 V DC
B
3WL9 111-0AK03-0AA0
1 1 unit
103
0.200
48 V DC
B
3WL9 111-0AK04-0AA0
1 1 unit
103
0.200
Spare part for option K10 to K13, see
"-Z" + order code, page 15/25.
120 V AC/
125 V DC
B
3WL9 111-0AK05-0AA0
1 1 unit
103
0.200
208-250 V AC/
208-250 V DC
B
3WL9 111-0AK06-0AA0
1 1 unit
103
0.200
For ETU45B and
ETU76B
B
3WL9 111-0AK30-0AA0
1 1 unit
103
0.150
Retrofittable internal wiring for connection of the
external N- and G-transformers to terminal X8
(without male connector, not for ETU release 2)
D
3WL9 111-0AK31-0AA0
1 1 unit
103
0.020
Retrofittable internal wiring for connection of the
external N- and G-transformers to terminal X8
for ETU release 2 (without male connector)
D
3WL9 111-0AK33-0AA0
1 1 unit
103
0.020
Protective covers for
Without safety lock B
mechanical ON/OFF
Made by CES
Consisting of 2 transparent covers each Made by IKON
B
4)
for sealing or for attaching padlocks ,
B
cover with 6.35 mm hole (for tool actuation), lock mount for safety lock for key
operation
3WL9 111-0BA21-0AA0
1
1 unit
103
0.100
3WL9 111-0BA22-0AA0
3WL9 111-0BA24-0AA0
1
1
1 unit
1 unit
103
103
0.300
0.300
Assembly kit
FORTRESS or
CASTELL3)
Made by Ronis
Made by KIRKKey
Made by Profalux
B
3WL9 111-0BA31-0AA0
1
1 unit
103
0.200
B
B
3WL9 111-0BA33-0AA0
3WL9 111-0BA34-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
0.400
0.270
0.250
B
3WL9 111-0BA35-0AA0
Made by CES
Made by IKON
Assembly kit for
padlocks4)
B
B
3WL9 111-0BA36-0AA0
3WL9 111-0BA38-0AA0
1
1
1 unit
1 unit
103
103
0.200
0.200
1
1 unit
103
0.360
B
3WL9 111-0BA41-0AA0
Made by CES
Made by IKON
Made by KIRKKey
Made by Ronis
Made by Profalux
B
B
B
3WL9 111-0BA51-0AA0
3WL9 111-0BA53-0AA0
3WL9 111-0BA57-0AA0
B
B
3WL9 111-0BA58-0AA0
3WL9 111-0BA50-0AA0
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
0.300
0.300
0.300
0.300
0.227
B
3WL9 111-0BA71-0AA0
1
1 unit
103
0.080
Made by CES
Made by IKON
Made by Profalux
Made by Ronis
B
B
B
B
3WL9 111-0BA73-0AA0
3WL9 111-0BA75-0AA0
3WL9 111-0BA76-0AA0
3WL9 111-0BA77-0AA0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
103
103
103
103
0.300
0.200
0.300
0.300
Made by KIRKKey
B
3WL9 111-0BA80-0AA0
1
1 unit
103
0.400
B
3WL9 111-0BA43-0AA0
1
1 unit
103
0.360
Retrofittable internal CubicleBUS
wiring for connection to terminal X8
(without male connector2))
3WL9 111-0AK0.-0AA0
B
B
Automatic reset of the reclosing lockout
Spare part for option K01, see "-Z" + order code, page 15/25.
3WL9 111-0AT45-0AA0
F 7
For ETU15B to
ETU45B
NSE00980
Locking devices against
unauthorized closing,
in the operator panel
3WL9 111-0BA22-0AA0 The disconnector unit fulfills the
■
requirements for main circuit breakers
according to EN 60204-1
Spare part for option S01 to S09, see
"-Z" + order code, page 15/27.
NSE00981
Locking devices against
unauthorized closing,
for withdrawable circuit breakers ■
3WL9 111-0BA31-0AA0 The disconnector unit fulfills the requirements for main circuit breakers according to EN 60204-1, consisting of lock in
the cabinet door, active in connected
position; function is retained when circuit
breaker is replaced
Spare part for option R60, R61, R68, see
NSE00982
3WL9 111-0BA53-0AA0 "-Z" + order code, page 15/27.
Locking devices for operating mechanism handle with padlock4)
Spare part for option S33, see
"-Z" + order code, page 15/27.
Locking devices against movement of
the withdrawable circuit breakers
Safety lock for mounting on the circuit
breaker.
Spare part for opt. S71, S75, S76,
see "-Z" + order code, page 15/27.
■
NSE00984
Interlocking systems
Made by CES
3WL9 111-0BA71-0AA0 2 of the same keys for 3 switches,
Locking device OFF position,
Key-operated switch on operator panel.
A maximum of 2 switches can be
switched on.
NSE00986
3WL9 111-0BA76-0AA0
1)
Can only be used in conjunction with "automatic reset of reclosing lockout",
e.g. "–Z" + "K01", 3WL9 111-0AK21-0AA0.
2)
Required if communication is retrofitted.
3)
4)
Locks must be ordered from the manufacturer.
Padlock not included in the scope of supply.
■ Start of delivery on request.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/35
15
Locking devices
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Locking mechanisms
To prevent movement of the
withdrawable circuit breakers
in disconnected position,
consisting of Bowden wire and
lock in the cabinet door
NSE00987
Made by CES
Made by IKON
Made by Profalux
Made by Ronis
B
B
B
B
3WL9 111-0BA81-0AA0
3WL9 111-0BA83-0AA0
3WL9 111-0BA85-0AA0
3WL9 111-0BA86-0AA0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
103
103
103
103
0.800
0.800
0.800
0.800
Fixed mounting
B
3WL9 111-0BB12-0AA0
1
1 unit
103
0.600
Guide frames
B
3WL9 111-0BB13-0AA0
1
1 unit
103
0.150
Guide frames
B
3WL9 111-0BB15-0AA0
1
1 unit
103
0.150
Fixed-mounted circuit
breaker
B
3WL9 111-0BB21-0AA0
1
1 unit
103
2.700
Module for withdrawable B
circuit breaker with frame
3WL9 111-0BB24-0AA0
1
1 unit
103
1.130
B
3WL9 111-0BB22-0AA0
1
1 unit
103
1.100
Module for withdrawable B
circuit breaker
3WL9 111-0BB23-0AA0
1
1 unit
103
0.150
B
3WL9 111-0BB30-0AA0
1
1 unit
103
0.100
B
3WL9 112-8AH47-0AA0
1
1 unit
103
0.160
B
B
B
3WL9 111-0BB45-0AA0
3WL9 111-0BB46-0AA0
3WL9 111-0BB47-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
0.150
0.220
0.360
3WL9 111-0BA83-0AA0 Spare part for option R81, R85,
R86, see "-Z" + order code,
page 15/27.
Not possible in combination with
"Locking mechanism to prevent
opening of the cabinet door"
(order code "R30") or "Locking
mechanism to prevent move3WL9 111-0BB12-0AA0 ment with the cabinet door open"
(order code "R50").
Interlocking
To prevent opening of the
cabinet door in ON position
(can be defeated)
Spare part for option S30, see
"-Z" + order code, page 15/27.
To prevent opening of the
cabinet door
(can be defeated)
Spare part for option R30, see
"-Z" + order code, page 15/27.
15
Not possible in combination with
"Locking mechanism to prevent
movement of the withdrawable
circuit breakers in disconnected
position" (order codes "R81",
"R85" or "R86").
To prevent movement with the
cabinet door open
Spare part for option R50, see
"-Z" + order code, page 15/27.
Not possible in combination with
"Locking mechanism to prevent
movement of the withdrawable
circuit breakers in disconnected
position" (order codes "R81",
"R85" or "R86").
Interlocks
Mutual mechanical
interlocking,
with 2000 mm Bowden wire
(one required for each circuit
breaker)
NSE00989
3WL9 111-0BB21-0AA0
Spare part for option
S55, see "-Z" + order
code, page 15/26.
Spare part for option
R55, see "-Z" + order
code, page 15/26.
When ordered separately
Module for guide frame
Spare part for option
R56, see "-Z" + order
code, page 15/26.
Spare part for option
R57, see "-Z" + order
code, page 15/26.
Adapter for size III
Withdrawable circuit
breaker
Couplings on the circuit
breaker (with ring) for
mutual interlocking
Can be used in all circuit
breakers
NSE0_01886
Bowden wires
3WL9 112-8HA47-0AA0
2000 mm
3000 mm
4500 mm
* You can order this quantity or a multiple thereof.
15/36
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Test devices
3WL9 111-0AT32-0AA0
1
1 unit
103
1.100
C
3WL9 111-0AT44-0AA0
1
1 unit
103
8.210
B
3WL9 111-0BA14-0AA0
1
1 unit
103
0.520
Manual testers release 2 for electronic releases ETU15B B
to ETU76B
For testing the electronic release functions
Function testers
For testing the tripping characteristics for
electronic release ETU15B
to ETU76B
Capacitor storage devices
Capacitor storage devices
For shunt release
Storage time 5 min
Rated control supply voltage
must match the rated control
supply voltage of the shunt
release
Rated control supply
voltage/rated operational voltage
AC 50/60 Hz V V DC
220 ... 240
220 ...
250
15
Suitable also for
3VL and 3WN circuit breakers
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/37
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Indicators, control elements
B
3WL9 111-0AH01-0AA0
1
1 unit
103
0.020
B
3WL9 111-0AH02-0AA0
1
1 unit
103
0.020
B
3WL9 111-0AH14-0AA0
1
1 unit
103
0.080
B
3WL9 111-0AH07-0AA0
1
1 unit
103
0.100
B
3WL9 111-0AH08-0AA0
1
1 unit
103
0.030
1st block (3 CO
contacts)
B
3WL9 111-0AH11-0AA0
1
1 unit
103
0.200
2nd block (6 CO
contacts)
B
3WL9 111-0AH12-0AA0
1
1 unit
103
0.400
Ready-to-close signaling switches
1 NO contact
Spare part for option C22,
see "-Z" + order code,
page 15/25.
Signaling switches1)2)
Spare part for option C26
and C27, see "-Z" + order
code, page 15/25.
N S E 0 _ 0 0 9 9 3 a
1st or 2nd auxiliary
releases
3WL9 111-0AH01-0AA0 Tripped signaling
switches1)2)
1 CO
N S E 0 _ 0 0 9 9 4 b
Spare part for option K07,
see "-Z" + order code,
page 15/25.
Operating cycles
counters, mechanical3)
Spare part for option C01,
see "-Z" + order code,
page
15/25.
3WL9 111-0AH02-0AA0
Stored energy status
signaling switches1)2)
1 NO contact
15
Spare part for option C20,
see "-Z" + order code,
page 15/25.
Position signaling
switches for guide
3WL9 111-0AH07-0AA0 frames
Spare part for option R15
and R16, see "-Z" + order
code, page 15/26.
N S E 0 _ 0 0 9 9 5 a
Electrical ON buttons1)4)
(button+wiring)2),
3WL9 111-0AH12-0AA0 for operator panel.
Possible only for circuit
breakers with closing
solenoid.
N S E 0 _ 0 0 9 9 6 a
With sealing cap
B
3WL9 111-0AJ02-0AA0
1
1 unit
103
0.150
With CES assembly kit
B
3WL9 111-0AJ03-0AA0
1
1 unit
103
0.140
With BKS assembly kit
B
3WL9 111-0AJ04-0AA0
1
1 unit
103
0.140
With IKON assembly kit
B
3WL9 111-0AJ05-0AA0
1
1 unit
103
0.140
B
3WL9 111-0AJ06-0AA0
1
1 unit
103
0.100
B
3WL9 111-0BA72-0AA0
1
1 unit
103
0.080
Spare part for option C11
and C12, see "-Z" + order
code, page 15/25.
N S E 0
0 0 9 9 7 a
3WL9 111-0AJ0.-0AA0
Motor shutdown
switches 5) (mounting on
operator panel)
Spare part for option S25,
see "-Z" + order code,
page 15/25.
NSE00985
EMERGENCY-STOP
3WL9 111-0BA72-0AA0 pushbuttons
Mushroom pushbutton
instead of the mechanical
OFF pushbutton
Spare part for option S24,
see "-Z" + order code,
page 15/25.
1)
2)
Not possible with communications interface option, order code "F02" or
"F12".
3)
Only in conjunction with motorized operating mechanism.
4)
Not possible with motor shutdown switch.
X7 manual connector required for circuit breakers or guide frames.
If this is not already available, please order additionally
(see pages 15/29 and 15/39).
5)
Not possible with electrical ON button.
* You can order this quantity or a multiple thereof.
15/38
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Auxiliary conductor connections
B
3WL9 111-0AB01-0AA0
1
1 unit
103
0.100
Extension for the 1000 V
male connector versions
(male connector must be ordered separately)
B
3WL9 111-0AB02-0AA0
1
1 unit
103
0.150
Male connectors and extension for 1000 V
B
3WL9 111-0AB10-0AA0
1
1 unit
103
1.000
Auxiliary supply connec- Screw connection
B
tors for circuit breakers or (SIGUT)
guide frames%
Screwless connection B
3WL9 111-0AB03-0AA0
method (tension
spring)
3WL9 111-0AB03-0AA0
1
1 unit
103
0.070
3WL9 111-0AB04-0AA0
1
1 unit
103
0.070
NSE00978
Male connectors for circuit breakers $
N S E 0 _ 0 1 2 6 9
N S E 0 _ 0 1 2 6 8
3WL9 111-0AB01-0AA0
B
3WL9 111-0AB07-0AA0
1
1 unit
103
0.020
Sliding contact modules for guide frames (
B
3WL9 111-0AB08-0AA0
1
1 unit
103
0.100
One-part sliding contact modules for guide
frames
Screw connection (SIGUT))
B
3WL9 111-0AB18-0AA0
1
1 unit
103
0.120
Blanking blocks for circuit breakers
B
3WL9 111-0AB12-0AA0
1
1 unit
103
0.030
NSE00974
Coding kits for fixed-mounted version
(X5 to X8) &
3WL9 111-0AB07-0AA0
7 a
9 7
0 0
0 _
E
N S
NSE0_01586
3WL9 111-0AB08-0AA0
3WL9 111-0AB18-0AA0
For a complete auxiliary current connection you must order:
Fixed-mounted version:
Withdrawable version:
$+%+&
$+(+%
or
$+)
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/39
15
3WL9 111-0AB04-0AA0
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Auxiliary releases
Closing solenoids/shunt releases
24 V DC
3WL9 111-0AD06-0AA0
B
3WL9 111-0AD01-0AA0
1
1 unit
103
0.700
30 V DC
B
3WL9 111-0AD02-0AA0
1
1 unit
103
0.700
48 V DC
B
3WL9 111-0AD03-0AA0
1
1 unit
103
0.700
60 V DC
B
3WL9 111-0AD04-0AA0
1
1 unit
103
0.700
110 ... 125 V DC/110 V AC
B
3WL9 111-0AD05-0AA0
1
1 unit
103
0.700
220 V DC/230 V AC
B
3WL9 111-0AD06-0AA0
1
1 unit
103
0.700
B
3WL9 111-0AD11-0AA0
1
1 unit
103
0.700
B
3WL9 111-0AD12-0AA0
1
1 unit
103
0.700
110 ... 125 V DC/110 ... 127 V AC
B
3WL9 111-0AD13-0AA0
1
1 unit
103
0.700
220 ... 250 V DC/208 ... 240 V AC
B
3WL9 111-0AD14-0AA0
1
1 unit
103
1.800
24 V DC
100 % ON period
5 % ON period
48 V DC
NSE01001
Undervoltage releases
3WL9 111-0AE0.-0AA0
15
NSE01002
Instantaneous
24 V DC
B
3WL9 111-0AE01-0AA0
1
1 unit
103
0.730
30 V DC
B
3WL9 111-0AE02-0AA0
1
1 unit
103
0.730
48 V DC
B
3WL9 111-0AE03-0AA0
1
1 unit
103
0.730
60 V DC
B
3WL9 111-0AE07-0AA0
1
1 unit
103
0.730
110 ... 125 V DC/110 ... 127 V AC
B
3WL9 111-0AE04-0AA0
1
1 unit
103
0.730
220 ... 250 V DC/208 ... 240 V AC
B
3WL9 111-0AE05-0AA0
1
1 unit
103
0.730
380 ... 415 V AC
B
3WL9 111-0AE06-0AA0
1
1 unit
103
0.730
3WL9 111-0AE1.-0AA0
Delayed
B
3WL9 111-0AE11-0AA0
1
1 unit
103
0.740
110 ... 125 V DC/110 ... 127 V AC
48 V DC
B
3WL9 111-0AE12-0AA0
1
1 unit
103
0.740
220 ... 250 V DC/208 ... 240 V AC
B
3WL9 111-0AE13-0AA0
1
1 unit
103
0.740
380 ... 415 V AC
B
3WL9 111-0AE14-0AA0
1
1 unit
103
0.740
Operating mechanisms
Motorized operating
mechanisms1)
I
24 ... 30 V DC
B
3WL9 111-0AF01-0AA0
1
1 unit
103
1.510
48 ... 60 V DC
B
3WL9 111-0AF02-0AA0
1
1 unit
103
1.510
110 ... 125 V DC/110 ... 127 V AC
B
3WL9 111-0AF03-0AA0
1
1 unit
103
1.510
220 ... 250 V DC/208 ... 240 V AC
B
3WL9 111-0AF04-0AA0
1
1 unit
103
1.510
N S E 0 _ 0 1 0 0 3 a
3WL9 111-0AF0.-0AA0
Auxiliary contacts
Auxiliary switch blocks
2 NO + 2 NC
B
3WL9 111-0AG01-0AA0
1
1 unit
103
0.180
2 NO
B
3WL9 111-0AG02-0AA0
1
1 unit
103
0.080
1 NO + 1 NC
B
3WL9 111-0AG03-0AA0
1
1 unit
103
0.070
3WL9 111-0AG03-0AA0
1)
X7 manual connector required for circuit breakers or guide frames.
If this is not already available, please order additionally
(see pages 15/29 and 15/39).
* You can order this quantity or a multiple thereof.
15/40
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Door sealing frames, covers, shutters
B
3WL9 111-0AP01-0AA0
1
1 unit
103
0.360
B
3WL9 111-0AP02-0AA0
1
1 unit
103
1.600
Size I
B
3WL9 111-0AP04-0AA0
1
1 unit
103
0.500
Size II
B
3WL9 111-0AP06-0AA0
1
1 unit
103
0.630
Size III
B
3WL9 111-0AP07-0AA0
1
1 unit
103
0.860
Size I
B
3WL9 111-0AP08-0AA0
1
1 unit
103
0.600
Size II
B
3WL9 111-0AP11-0AA0
1
1 unit
103
0.770
Size III
B
3WL9 111-0AP12-0AA0
1
1 unit
103
1.070
Size I
B
3WL9 111-0AS01-0AA0
1
1 unit
103
1.110
Size II
B
3WL9 111-0AS02-0AA0
1
1 unit
103
1.680
Size III
B
3WL9 111-0AS03-0AA0
1
1 unit
103
2.980
Size II
B
3WL9 111-0AS05-0AA0
1
1 unit
103
3.140
Size III
B
3WL9 111-0AS06-0AA0
1
1 unit
103
5.620
Size I
B
3WL9 111-0AS32-0AA0
1
1 unit
103
1.850
Size II
B
3WL9 111-0AS36-0AA0
1
1 unit
103
2.600
Size III
B
3WL9 111-0AS38-0AA0
1
1 unit
103
4.050
Size I
B
3WL9 111-0AS42-0AA0
1
1 unit
103
2.340
Size II
B
3WL9 111-0AS44-0AA0
1
1 unit
103
3.300
Size III
B
3WL9 111-0AS46-0AA0
1
1 unit
103
5.210
B
3WL9 111-0AR12-0AA0
1
1 unit
103
0.400
Door sealing frames
Spare part for option T40, see
"-Z" + order code, page 15/25.
Protective covers, IP55
cannot be used in conjunction with
door sealing frames, cover removable and can be opened on both
sides
NSE0_01028a
Shutters
3WL9 111-0AP02-0AA0
Spare part for option R21, see
"-Z" + order code, page 15/26.
3-pole
4-pole
3WL9 111-0AP0.-0AA0
Arc chutes
NSE01007
690 V
3WL9 111-0AS0.-0AA0
1000 V/1150 V
Arc chute covers1)
Assembly kit for guide frame
Spare part for option R10, see
"-Z" + order code, page 15/26.
3-pole
NSE01008
3WL9 111-0AS3.-0AA0
4-pole
Withdrawable part coding
Withdrawable part coding
By customer, for 36 coding variants
NSE01009
3WL9 111-0AR12-0AA0
1)
Not available for 1000 V version, 1150 V version, DC version and size II
with rated circuit breaker current of 4000 A.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/41
15
Arc chutes
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Ground-fault protection
NSE0 01018a
3WL9 111-0BA02-0AA0
Ground-fault protection between
the guide frame and the
withdrawable circuit breakers
For 30 kA ground short-circuit
current1)
Contacting module for guide frame
Size I, II
B
3WL9 111-0BA01-0AA0
1 1 unit
103
0.330
Size III
B
3WL9 111-0BA02-0AA0
1 1 unit
103
0.350
Contacting modules for
withdrawable circuit breakers
Size I
B
3WL9 111-0BA05-0AA0
1 1 unit
103
1.250
NSE01019
3-pole
Size II
B
3WL9 111-0BA06-0AA0
1 1 unit
103
1.530
3WL9 111-0BA07-0AA0
Size III
B
3WL9 111-0BA07-0AA0
1 1 unit
103
2.270
Size I
B
3WL9 111-0BA08-0AA0
1 1 unit
103
1.500
Size II
B
3WL9 111-0BA04-0AA0
1 1 unit
103
1.850
Size III
B
3WL9 111-0BA10-0AA0
1 1 unit
103
2.950
Support brackets
For mounting fixed-mounted circuit breakers
on vertical plane, only for sizes I and II
(1 set = 2 units)
B
3WL9 111-0BB50-0AA0
1 1 unit
103
7.000
4-pole
NSE-01022
15
Support brackets
3WL9 111-0BB50-0AA0
1)
For 60 kA ground short-circuit current, order 2.
* You can order this quantity or a multiple thereof.
15/42
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
CubicleBUS modules1)
Digital output modules with rotary coding switch,
relay outputs
B
3WL9 111-0AT26-0AA0
1 1 unit 103
0.240
Digital output modules, configurable, relay outputs
B
3WL9 111-0AT20-0AA0
1 1 unit 103
0.310
Digital input modules
B
3WL9 111-0AT27-0AA0
1 1 unit 103
0.240
Analog output modules
B
3WL9 111-0AT23-0AA0
1 1 unit 103
0.240
Zone Selective Interlocking modules
B
3WL9 111-0AT21-0AA0
1 1 unit 103
0.240
Breaker Data
Adapters
(BDA)3)
Parameterization, operation, monitoring and B
diagnostics of SENTRON circuit breakers
using the local interface; Breaker Data
Adapter, connection cable to the SENTRON
3WL circuit breaker and to the programming
device (e.g. notebook); can be run with
Internet Explorer with JAVA2 VM 1.4.0-01 and
higher
3WL9 111-0AT28-0AA0
1 1 unit 103
0.900
BDA Plus3)
Same as BDA, but with additional Ethernet
interface for connection to Ethernet/Intranet/Internet
B
3WL9 111-0AT33-0AA0
1 1 unit 103
1.200
Connection
Connection cable for connection of BDA Plus B
cables for BDA to terminal X8 of the SENTRON 3WL circuit
Plus
breaker. Required if neither COM15 nor
3WL9 111-0AT28-0AA0
COM16 nor other external
CubicleBUS modules are available,
length 2 m.
3WL9 111-0BC21-0AA0
1 1 unit 103
0.350
Calibration, operation, monitoring, and diag- A
nostics of SENTRON circuit breakers via
PROFIBUS DP; runs under Windows 95,
Windows 98, Windows NT, Windows 2000 and
Windows XP Professional, requires additional
PROFIBUS card e.g. CP5613
3ZS2 311-0CC10-0YA0
1 1 unit 133
0.200
0.2 m long, for connection to SENTRON 3WL B
with COM15/COM16
3WL9 111-0BC04-0AA0
1 1 unit 103
0.020
1 m long, for connection to SENTRON 3WL
with COM15/COM16
B
3WL9 111-0BC02-0AA0
1 1 unit 103
0.050
2 m long, for connection to SENTRON 3WL
with COM15/COM16
B
3WL9 111-0BC03-0AA0
1 1 unit 103
0.060
2 m long, for connection to SENTRON 3WL
without COM15/COM16
B
3WL9 111-0BC05-0AA0
1 1 unit 103
0.070
N S E 0 _ 0 1 0 2 3 a
3WL9 111-0AT23-0AA0
Parameterization systems
Switch ES
Power
parameterization
software
15
N S E 0 _ 0 1 0 2 4 a
Accessories for communications
Preassembled
cables for
CubicleBUS
modules
SENTRON
manuals for
communication
solutions2)
Detailed description of the communication
functions for SENTRON circuit breakers incl.
installation, connection, commissioning, data
transmission to PLC as well as description of
Switch ES Power and BDA.
English
Token fee on request
A5E0151353-01
German
Token fee on request
A5E0151347-01
To be ordered from:
http://www.click4business-supplies.de
Free download from:
http://www.siemens.com/lowvoltage/manuals
Voltage
380 ... 690 V/100 V, class 0.5
transformers,
3-pole, for
SENTRON 3WL
with measurement function
Plus
B
1 1 unit 103 2.600
3WL9 111-0BB68-0AA0
All communication components, CubicleBUS modules and measurement functions are available for the ETU45B and ETU76B releases.
1)
Each CubicleBUS module is supplied with a 0,2 m factory-fitted cable to
connect the modules with each other. A longer factory-fitted cable is
required for connection to the circuit breaker.
2)
Manual for MODBUS communication solution available on request.
3)
A 24 V DC power supply unit is required.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/43
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Retrofitting and spare parts for communication
1
2
3
4
5
6
7
8
9
B
3WL9 111-0AT12-0AA0
1 1 unit 103 0.260
B
3WL9 111-0AT15-0AA0
1 1 unit 103 0.140
B
3WL9 111-0AT14-0AA0
1 1 unit 103 0.260
COM16
MODBUS
modules
B
3WL9 111-0AT17-0AA0
1 1 unit 103 0.140
Breaker
status sensor
(BSS)
B
3WL9 111-0AT16-0AA0
1 1 unit 103 0.120
Measurement For all ETUs except ETU release 2
function Plus1) (voltage transformer required)
B
3WL9 111-0AT03-0AA0
1 1 unit 103 0.250
B
3WL9 111-0AT04-0AA0
1 1 unit 103 0.250
PROFIBUS
retrofit kits
Device
CubicleBus
PROFIBUS DP
Retrofit kit for PROFIBUS communications
including COM15, BSS and set of cables for
all SENTRON 3WL circuit breakers with
ETU45B and ETU76B releases
COM15
PROFIBUS
modules
NSE-01025
MODBUS
3WL9 111-0AT15-0AA0 retrofit kits
S45
S43
S42
S40
S44
S41
NSE01026
Retrofit kit for MODBUS communications
including COM16, BSS and set of cables for
all SENTRON 3WL circuit breakers with
ETU45B and ETU76B releases
Measurement For ETU release 2
1)
3WL9 111-0AT16-0AA0 function Plus (voltage transformer required)
All communication components, CubicleBUS modules and measurement functions are available for the ETU45B and ETU76B releases.
If retrofitted, a measuring accuracy of 3 % is achieved.
15
1)
* You can order this quantity or a multiple thereof.
15/44
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Main conductor connections,
fixed mounting (essential accessory)
Specified for each connection
Front-accessible
main circuit
connections,
single hole at top
Size I, up to 1000 A
Size I, 1250 to 1600 A
B
B
3WL9 111-0AL01-0AA0
3WL9 111-0AL02-0AA0
1
1
1 unit
1 unit
103
103
1.100
1.600
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
B
B
B
3WL9 111-0AL03-0AA0
3WL9 111-0AL04-0AA0
3WL9 111-0AL05-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
2.000
3.600
3.500
NSE-01010
Size III, up to 4000 A
B
3WL9 111-0AL06-0AA0
1
1 unit
103
6.100
3WL9 111-0AL56-0AA0 Front-accessible
Size I, up to 1000 A
Size I, 1250 to 1600 A
B
B
3WL9 111-0AL51-0AA0
3WL9 111-0AL52-0AA0
1
1
1 unit
1 unit
103
103
1.000
1.300
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
B
B
3WL9 111-0AL53-0AA0
3WL9 111-0AL54-0AA0
3WL9 111-0AL55-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
1.800
3.100
3.000
main circuit
connections,
single hole at
bottom
3WL9 111-0AL14-0AA0
NSE-01011
3WL9 111-0AL64-0AA0
Front-accessible
main circuit
connections,
acc. to DIN 43673,
double hole at top
Front-accessible
main circuit
connections,
acc. to DIN43673,
double hole at
bottom
Rear vertical
main circuit
connections
Size III, up to 4000 A
B
B
3WL9 111-0AL56-0AA0
1
1 unit
103
5.200
Size I, up to 1000 A
Size I, 1250 to 1600 A
B
B
3WL9 111-0AL07-0AA0
3WL9 111-0AL08-0AA0
1
1
1 unit
1 unit
103
103
1.400
2.000
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
B
B
B
3WL9 111-0AL11-0AA0
3WL9 111-0AL12-0AA0
3WL9 111-0AL13-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
2.400
4.500
4.400
Size III, up to 4000 A
B
3WL9 111-0AL14-0AA0
1
1 unit
103
7.800
Size I, up to 1000 A
Size I, 1250 to 1600 A
B
B
3WL9 111-0AL57-0AA0
3WL9 111-0AL58-0AA0
1
1
1 unit
1 unit
103
103
1.300
1.700
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
B
B
B
3WL9 111-0AL61-0AA0
3WL9 111-0AL62-0AA0
3WL9 111-0AL63-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
2.000
3.700
3.600
Size III, up to 4000 A
B
3WL9 111-0AL64-0AA0
1
1 unit
103
6.400
Size I1), up to 1600 A
B
3WL9 111-0AM01-0AA0
1
1 unit
103
0.500
Size II2), up to 3200 A
B
3WL9 111-0AM02-0AA0
1
1 unit
103
2.200
Size III, up to 6300 A
B
3WL9 111-0AM03-0AA0
1
1 unit
103
5.000
NSE-01012
3WL9 111-0AM03-0AA0
1)
In the case of vertical connection size I, up to 1000 A
one 3WL9 111–0AM01-0AA0 vertical connection is required,
up to 1600 A two 3WL9 111-0AM01-0AA0 vertical connections
are required.
2)
In the case of vertical connection size II, up to 2500 A
one 3WL9 111–0AM02-0AA0 vertical connection is required,
up to 3200 A two 3WL9 111-0AM02-0AA0 vertical connections
are required.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/45
15
3WL9 111-0AL06-0AA0
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Main conductor connections,
withdrawable versions (essential accessory)
Specified for each connection
Front-accessible
main circuit
connections,
single hole at top
or at bottom1)
NSE-01013
3WL9 111-0AN06-0AA0
Front-accessible
main circuit
connections,
acc. to DIN 43673,
double hole at top
or at bottom1)
NSE-01014
Size I, up to 1000 A
Size I, 1250 to 1600 A
B
B
3WL9 111-0AN01-0AA0
3WL9 111-0AN02-0AA0
1
1
1 unit
1 unit
103
103
1.000
1.300
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
B
B
B
3WL9 111-0AN03-0AA0
3WL9 111-0AN04-0AA0
3WL9 111-0AN05-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
1.800
3.100
3.000
Size III, up to 4000 A
B
3WL9 111-0AN06-0AA0
1
1 unit
103
5.200
Size I, up to 1000 A
Size I, 1250 to 1600 A
B
B
3WL9 111-0AN07-0AA0
3WL9 111-0AN08-0AA0
1
1
1 unit
1 unit
103
103
1.300
1.700
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
B
B
B
3WL9 111-0AN11-0AA0
3WL9 111-0AN12-0AA0
3WL9 111-0AN13-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
2.000
3.700
3.600
Size III, up to 4000 A
B
3WL9 111-0AN14-0AA0
1
1 unit
103
6.400
3WL9 111-0AN14-0AA0
Supports
for front and DIN
connecting bars
15
3-pole for 3 bars
4-pole for 4 bars
Rear vertical
main circuit
connections
NSE-01017
3WL9 111-0AN41-0AA0
NSE-01015
3WL9 111-0AN23-0AA0
Rear
horizontal
circuit connections
NSE-01016
Connecting flanges
Size I
B
3WL9 111-0AN41-0AA0
1
1 unit
103
0.700
Size II
B
3WL9 111-0AN42-0AA0
1
1 unit
103
1.350
Size III
B
3WL9 111-0AN43-0AA0
1
1 unit
103
2.420
Size I
B
3WL9 111-0AN44-0AA0
1
1 unit
103
1.200
Size II
B
3WL9 111-0AN45-0AA0
1
1 unit
103
2.200
Size III
B
3WL9 111-0AN46-0AA0
1
1 unit
103
3.200
Size I, up to 1000 A
Size I, 1250 to 1600 A
B
B
3WL9 111-0AN15-0AA0
3WL9 111-0AN16-0AA0
1
1
1 unit
1 unit
103
103
0.660
0.870
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
B
B
B
3WL9 111-0AN17-0AA0
3WL9 111-0AN18-0AA0
3WL9 111-0AN21-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
1.150
1.490
2.580
Size III, up to 5000 A
B
3WL9 111-0AN22-0AA0
1
1 unit
103
6.380
Size III, up to 6300 A
(3 busbar connection
pieces for 3-pole circuit
breakers)
B
3WL9 111-0AN23-0AA0
1
1 unit
103
19.170
Size III, up to 6300 A
(4 busbar connection
pieces for 4-pole circuit
breakers)
B
3WL9 111-0AN20-0AA0
1
1 unit
103
18.410
Size III, up to 6300 A
(4 busbar connection
pieces for 4-pole circuit
breakers)
B
3WL9 111-0AN10-0AA0
1
1 unit
103
18.300
Size I, up to 1000 A
Size I, 1250 to 1600 A
B
B
3WL9 111-0AN32-0AA0
3WL9 111-0AN33-0AA0
1
1
1 unit
1 unit
103
103
0.770
Size II, up to 2000 A
Size II, up to 2500 A
B
B
3WL9 111-0AN34-0AA0
3WL9 111-0AN35-0AA0
1
1
1 unit
1 unit
103
103
0.630
1.020
Size II, up to 3200 A
B
3WL9 111-0AN36-0AA0
1
1 unit
103
1.240
2.170
Size III, up to 5000 A
B
3WL9 111-0AN37-0AA0
1
1 unit
103
3.860
Size I, up to 1000 A
Size I, 1250 to 1600 A
B
B
3WL9 111-0AN24-0AA0
3WL9 111-0AN25-0AA0
1
1
1 unit
1 unit
103
103
0.610
0.640
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3200 A
B
B
B
3WL9 111-0AN26-0AA0
3WL9 111-0AN27-0AA0
3WL9 111-0AN28-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
0.980
1.020
1.310
Size III, up to 4000 A
B
3WL9 111-0AN31-0AA0
1
1 unit
103
2.370
3WL9 111-0AN24-0AA0
1)
When using front-accessible main circuit connections
(withdrawable circuit breakers) supports are required.
* You can order this quantity or a multiple thereof.
15/46
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Conversion sets
For converting fixed-mounted circuit breakers into withdrawable circuit breakers
Guide frames and sliding contact modules must be ordered separately.
Number of poles
Size
3-pole
I
B
3WL9 111-0BC11-0AA0
1
1 unit
103
5.100
II
B
3WL9 111-0BC12-0AA0
1
1 unit
103
5.900
III
B
3WL9 111-0BC13-0AA0
1
1 unit
103
8.100
I
B
3WL9 111-0BC14-0AA0
1
1 unit
103
6.400
II
B
3WL9 111-0BC15-0AA0
1
1 unit
103
6.450
III
B
3WL9 111-0BC16-0AA0
1
1 unit
103
10.700
4-pole
Main contact elements
You must specify the circuit breaker ID No. when ordering!
Specified for each connection (depending on the number of poles on the circuit breaker,
order 3 or 4 units)
In max
I
Up to 1600 A
B
3WL9 111-0AM90
L1Y1)
1
1 unit
103 On req.
II
Up to 2500 A
B
3WL9 111-0AM91
L1Y1)
1
1 unit
103 On req.
II
Up to 4000 A
B
3WL9 111-0AM92
L1Y1)
1
1 unit
103 On req.
III
Up to 6300 A
B
3WL9 111-0AM93
L1Y1)
1
1 unit
103 On req.
NSE-01021
1)
Order No. is automatically adapted
to the circuit breaker ID number
Please specify the circuit breaker ID No. in plain text when ordering.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/47
15
Sizes
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
Schematics in as-supplied state
Version
Size
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
L1 L2 L3
NSE0_01118
Withdrawable short-circuits, grounding and bridging units
NSE0_01119
NSE0_01113
(as-supplied state)
N
Top and
bottom
parts of
system
are
shortcircuited
and
grounded
3-pole
Up to
1600 A
I
C
3WL9 111-0BD01-0AA0
1
1 unit
103
30.000
Up to
3200 A
II
C
3WL9 111-0BD03-0AA0
1
1 unit
103
40.500
Up to
6300 A
III
C
3WL9 111-0BD05-0AA0
1
1 unit
103
65.000
Up to
1600 A
I
C
3WL9 111-0BD02-0AA0
1
1 unit
103
35.000
Up to
3200 A
II
C
3WL9 111-0BD04-0AA0
1
1 unit
103
46.000
Up to
6300 A
III
C
3WL9 111-0BD06-0AA0
1
1 unit
103
70.000
4-pole
L1 L2 L3
NSE0_01112
NSE0_01119
NSE0_01113
N
L1 L2 L3
Top part of system is short-circuited and grounded,
infeed from bottom
N S E 0 _ 0 1 1 2 2 a
Top and bottom parts of system are short-circuited and grounded
(as-supplied state)
L1 L2 L3
L1 L2 L3
NSE0_01114
N S E 0 _ 0 1 1 2 3 a
NSE0_01115
Withdrawable bridging unit, infeed and outgoing terminals are permanently
connected to each other
N
L1 L2 L3
NSE0_01121
N
NSE0_01116
L1 L2 L3
NSE0_01120
15
L1 L2 L3
NSE0_01117
NSE0_01118
Conversion for the following applications is possible
Bottom part of system is short-circuited and grounded,
infeed from top
* You can order this quantity or a multiple thereof.
15/48
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Accessories and spare parts
■ Options
Structure of the Order No.
3WL1 Ô Ô Ò – Ö é â Õ Ó – Ó á Ü Ô
Example
Ô
5th position:
Size
Size II
6th and 7th
positions:
Max. rated
circuit breaker
current In max
In max = 2000 A
8th position:
Switching capacity
class
High breaking capacity
"H": 100 kA
9th position:
Electronic releases
ETU76B with pixel graphics
display
10th position:
Electronic release
supplement
... with ground-fault protection
11th position:
Number of poles
3-pole
12th position:
Installation type
Fixed mounting, main circuit
connections on rear, vertical
They are used as an unambiguous
means of communication for various
purposes:
ÔÒ
• Offer processing
Selection and configuration
• Order processing
Ordering
Order confirmation
Handling warehouse products
Order processing at the
supply bases
Delivery and shipment
• Reporting and
planning
• Service and warranty
Ö
é
â
Õ
13th position:
Operating
mechanisms
14th position:
1st auxiliary release Shunt release
AC 50/60 Hz 110 V
15th position:
2nd auxiliary release Without 2nd auxiliary release
16th position:
Auxiliary switch
An important prerequisite for computerbased order processing is that order
numbers must be structured according
to standardized criteria.
The standardized structure ensures that
only one Order No. has to be administered for one device.
Ó
This saves time and effort during
planning, configuring, ordering
and stock keeping, and consequently
above all it saves costs.
Ó
Manual operating mechanism
with mechanical closing
The example opposite explains the
various positions within an
Order No.
15
á
Ü
Ô
2 NO + 2 NC
Accessories: with first order (components are already mounted)
Example
3WL1 Ô Ó Ø – Ö å â Õ Ó – Ó á Ü Õ – õ
áÒÔ
"–Z" with order code
Communications interface
"Standard" + Breaker Status Sensor (BSS)
+ communication module COM15 for
connection to PROFIBUS DP
õ
áÒÔ
Additional accessory components can
be ordered ready-mounted.
These supplements are identified
by "-Z".
Even with additional components,
one Order No. is sufficient.
Accessories: for retrofitting (components for subsequent fitting)
Example
3WL9 Ó Ó Ó – Ò Á Ü Ô Ó – Ò Ü Ü Ò
Additional accessories which are not
intended to be ready-mounted in the
factory, such as spare parts for storage,
can also be ordered separately from
the circuit breaker.
Protective cover for mechanical ON/OFF
without lock
Accessories for retrofitting are identified
by the Order No. stem 3WL9.
Documentation
Operating manual
Complete set
German/English
French/Italian
Spanish/Portuguese
Order No.
Order No.
Order No.
3ZX18 12-0WL00-0AN1
3ZX18 12-0WL00-0AJ1
3ZX18 12-0WL00-0AL1
Manual
Communication
German
English
Order No.
Order No.
A5E0151347-01
A5E0151353-01
Delivery time class C
On request
On request
Free download of documentation from
http://www.siemens.com/lowvoltage/manuals
■ More information
Up-to-date information on the Internet at:
http://www.siemens.com/sentron
Siemens LV 1 · 2009
15/49
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
3- and 4-pole, fixed-mounted versions
■ Selection and ordering data
For general data see page 15/6.
Size
Max. rated circuit breaker DT
current
In max.
A
3-pole non-automatic
air circuit breakers
Order No.
For Order No. supplements,
see page 15/23
DC
Price
per PU
PS*
PU
(UNIT,
SET, M)
Weight
per PU
approx.
PG
kg
Horizontal main circuit connection
II
II
II
1000
2000
40001)
B
B
B
3WL12 10-8@@32-....
3WL12 20-8@@32-....
3WL12 40-8@@32-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
56,000
56,000
64,000
B
B
B
3WL12 10-8@@31-....
3WL12 20-8@@31-....
3WL12 40-8@@31-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
56,000
56,000
85,000
B
B
3WL12 10-8@@33-....
3WL12 20-8@@33-....
1
1
1 unit
1 unit
103
103
56,000
56,000
B
B
3WL12 10-8@@34-....
3WL12 20-8@@34-....
1
1
1 unit
1 unit
103
103
56,000
56,000
Vertical main circuit connection
II
II
II
1000
2000
40001)
Front main circuit connection, single hole
II
II
1000
2000
Front main circuit connection, double hole
II
II
1000
2000
Non-automatic air circuit breakers2)
Order No. supplements
Without electronic release
AA
Add. price
Without
Standard Order No. supplements (for further Order No. supplements, see page 15/23)
15
Manual operating mechanism with mechanical closing
Size
Max. rated circuit breaker DT
current
In max.
A
1AA2
Without
4-pole non-automatic
air circuit breakers
DC
Order No.
For Order No. supplements,
see page 15/23
Price
per PU
PS*
PU
(UNIT,
SET, M)
Weight
per PU
approx.
PG
kg
Horizontal main circuit connection
II
II
II
1000
2000
40001)
B
B
B
3WL12 10-8@@42-....
3WL12 20-8@@42-....
3WL12 40-8@@42-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
67,000
67,000
77,000
B
B
B
3WL12 10-8@@41-....
3WL12 20-8@@41-....
3WL12 40-8@@41-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
75,000
75,000
103,000
B
B
3WL12 10-8@@43-....
3WL12 20-8@@43-....
1
1
1 unit
1 unit
103
103
67,000
67,000
B
B
3WL12 10-8@@44-....
3WL12 20-8@@44-....
1
1
1 unit
1 unit
103
103
67,000
67,000
Vertical main circuit connection
II
II
II
1000
2000
40001)
Front main circuit connection, single hole
II
II
1000
2000
Front main circuit connection, double hole
II
II
1000
2000
2)
Non-automatic air circuit breakers
Without electronic release
Order No. supplements
AA
Add. price
Without
Standard Order No. supplements (for further Order No. supplements, see page 15/23)
Manual operating mechanism with mechanical closing
Add "–Z" to the complete Order No.
and indicate the appropriate order code(s).
1AA2
Order No. with "–Z"
and additional order code
Without
1234 5 6 7
8 9 10 11 12
13 14 15 16
Additional
3WL1 2 . 0 – 8 . . . . – . . . . –Z price
@@@
3-pole
4-pole
Rated voltage 1000 V DC
Size II
Up to 2000 A
Size II
Up to 4000 A
Note:
For voltages over 600 V use the version for 1000 V DC rated voltage: Order with "-Z" and order code "A05".
All other accessory parts must be ordered by specifying "–Z"
and the corresponding order code, see "3WL Air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC)", "
Options", page 15/24 onwards.
1)
Provisions to dissipate heat must be made on the line side.
2)
For permissible rated short-time current Icw and rated short-circuit switching capacity Icc for non-automatic air circuit breakers, see Technical
Information LV 1T, "General Data", "Technical specifications".
A05
A05
An external overload and short-circuit protection device is available from the company "mat" for the SENTRON 3WL non-automatic air circuit breakers.
Available only directly from the company "mat" – Maschinen- und
Anlagentechnik (for address see "Appendix, External Partners").
* You can order this quantity or a multiple thereof.
15/50
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
3-pole, withdrawable versions
Size
Max. rated circuit breaker DT
current
In max.
A
3-pole non-automatic
air circuit breakers
Order No.
For Order No. supplements,
see page 15/23
DC
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Without guide frames
(for guide frames, see page 15/53)
II
II
II
1000
2000
40001)
B
B
B
3WL12 10-8@@35-....
3WL12 20-8@@35-....
3WL12 40-8@@35-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
60.000
60.000
68.000
B
B
B
3WL12 10-8@@36-....
3WL12 20-8@@36-....
3WL12 40-8@@36-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
91.000
91.000
113.000
B
B
B
3WL12 10-8@@37-....
3WL12 20-8@@37-....
3WL12 40-8@@37-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
91.000
91.000
121.000
B
B
B
3WL12 10-8@@38-....
3WL12 20-8@@38-....
3WL12 40-8@@38-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
91.000
91.000
113.000
With guide frames,
horizontal main circuit connection
II
II
II
1000
2000
40001)
With guide frames,
vertical main circuit connection
II
II
II
1000
2000
40001)
With guide frames, connecting flanges
II
II
II
1000
2000
40001)
Non-automatic air circuit breakers2)
Without electronic release
Order No. supplements
AA
Add. price
Without
Manual operating mechanism with mechanical closing
Add "–Z" to the complete Order No.
and indicate the appropriate order code(s).
1AA2
Order No. with "–Z"
and additional order code
15
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 15/23)
Without
1234 5 6 7
8 9 10 11 12
13 14 15 16
Additional
3WL1 2 . 0 – 8 . . 3 . – . . . . –Z price
@@@
3-pole
Rated voltage 1000 V DC
Size II4)
Up to 2000 A
A05
Size II4)
Up to 4000 A
A05
Tinned version of the customer's connections on the guide frame3)
Only for circuit breakers in withdrawable version with horizontal connection or flange connection.
The normal delivery time increases to 15 work days.
Size II
Note:
For voltages over 600 V use the version for 1000 V DC rated voltage; order with "-Z" and order code A05.
All other accessory parts must be ordered by specifying "–Z"
and the corresponding order code, see "3WL Air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC)", "Options", page 15/24 onwards.
1)
Provisions to dissipate heat must be made on the line side.
2)
For permissible rated short-time current Icw and rated short-circuit switching capacity Icc for non-automatic air circuit breakers, see Technical Information LV 1T, "General Data", "Technical specifications".
3)
The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
4)
If ordering withdrawable circuit breaker and guide frame separately,
specify order code "A05" for withdrawable circuit breaker and guide frame.
A08
An external overload and short-circuit protection device is available from the company "mat" for the SENTRON 3WL non-automatic air circuit breakers.
Available only directly from the company "mat" – Maschinen- und
Anlagentechnik (for address see "Appendix, External
Partners").
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/51
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
4-pole, withdrawable versions
Size
Max. rated circuit breaker DT
current
In max.
A
4-pole non-automatic
air circuit breakers
Order No.
For Order No. supplements,
see page 15/23
DC
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Without guide frames
(for guide frames, see page 15/53)
II
II
II
1000
2000
40001)
B
B
B
3WL12 10-8@@45-....
3WL12 20-8@@45-....
3WL12 40-8@@45-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
75.000
75.000
82.000
B
B
B
3WL12 10-8@@46-....
3WL12 20-8@@46-....
3WL12 40-8@@46-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
109.000
109.000
136.000
B
B
B
3WL12 10-8@@47-....
3WL12 20-8@@47-....
3WL12 40-8@@47-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
109.000
109.000
146.000
B
B
B
3WL12 10-8@@48-....
3WL12 20-8@@48-....
3WL12 40-8@@48-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
109.000
109.000
136.000
With guide frames,
horizontal main circuit connection
II
II
II
1000
2000
40001)
With guide frames,
vertical main circuit connection
II
II
II
1000
2000
40001)
With guide frames, connecting flanges
II
II
II
1000
2000
40001)
Non-automatic air circuit breakers2)
Without electronic release
Order No. supplements
AA
Add. price
Without
15
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 15/23)
Manual operating mechanism with mechanical closing
Add "–Z" to the complete Order No.
and indicate the appropriate order code(s).
1AA2
Order No. with "–Z"
and additional order code
Without
1234 5 6 7
8 9 10 11 12
13 14 15 16
Additional
3WL1 2 . 0 – 8 . . 4 . – . . . . –Z price
@@@
4-pole
Rated voltage 1000 V DC
Size II4)
Up to 2000 A
A05
Size II4)
Up to 4000 A
A05
Tinned version of the customer's connections on the guide frame3)
Only for circuit breakers in withdrawable version with horizontal connection or flange connection.
The normal delivery time increases to 15 work days.
Size II
A08
Note:
For voltages over 600 V use the version for 1000 V DC rated voltage; order with "-Z" and order code A05.
All other accessory parts must be ordered by specifying "–Z"
and the corresponding order code, see "3WL Air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC)", "Options", page 15/24 onwards.
1)
Provisions to dissipate heat must be made on the line side.
2)
For permissible rated short-time current Icw and rated short-circuit switching capacity Icc for non-automatic air circuit breakers, see Technical Information LV 1T, "General Data", "Technical specifications".
3)
The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
4)
If ordering withdrawable circuit breaker and guide frame separately, specify order code "A05" for withdrawable circuit breaker and guide frame.
An external overload and short-circuit protection device is available from the company "mat" for the SENTRON 3WL non-automatic air circuit breakers.
Available only directly from the company "mat" – Maschinen- und
Anlagentechnik (for address see "Appendix, External
Partners").
* You can order this quantity or a multiple thereof.
15/52
Siemens LV 1 · 2009
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Accessories and spare parts
■ Selection and ordering data
Guide frames for DC non-automatic air circuit breakers
Size
Max. rated circuit breaker current
In max
DT
For 3-pole non-automatic
air circuit breakers
Order No.
(Order No. supplements
required according to
table below)
A
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Front main circuit connection, single hole
II
2000
B
3WL9 212-3DA@@-@@A1
1
1 unit
103
31,000
B
3WL9 212-3DB@@-@@A1
1
1 unit
103
31,000
B
B
3WL9 212-3DC@@-@@A1
3WL9 212-6DC@@-@@A1
1
1
1 unit
1 unit
103
103
31,000
60,000
B
B
3WL9 212-3DD@@-@@A1
3WL9 212-6DD@@-@@A1
1
1
1 unit
1 unit
103
103
31,000
60,000
B
B
3WL9 212-3DE@@-@@A1
3WL9 212-6DE@@-@@A1
1
1
1 unit
1 unit
103
103
31,000
60,000
Front main circuit connection, double hole
II
2000
Horizontal main circuit connection
II
II
2000
4000
Vertical main circuit connection
II
II
2000
4000
Main circuit connection connecting flanges
II
II
2000
4000
Order No. supplements
Number of auxiliary supply connectors
Add. price
3-pole
Without
1 connector
2 connectors
3 connectors
4 connectors
For required number of auxiliary supply connectors,
see table on page 15/29
Without
15
0
1
2
3
4
Type of auxiliary circuit connections
Without
With screw connections (SIGUT)
With screwless connection method (tension spring)
Without
0
1
2
Position indicator switches
Without
Option 1
Option 2
Without
0
1
Connected 1 CO contact,
test 1 CO contact,
disconnected 1 CO contact
Connected 3 CO contacts,
test 2 CO contacts,
disconnected 1 CO contact
2
Shutters
Without
With shutter, 2 parts, lockable
Add "–Z" to the complete Order No.
and indicate the appropriate order code(s).
A
B
Order No. with "–Z"
and additional order code
Without
1234 5 6 7
8 9 10 11 12
13 14 15 16
Add.
3WL9 2 1 2 – . . . . . – . . A1 –Z price
@@@
Rated voltage 1000 V DC
Size II
A05
Tinned version of the customer's connections on the guide
frame1)
Only for guide frames with horizontal connection or
flange connection
Size II
A08
Guide frames for 4-pole DC non-automatic air circuit breakers
All other accessory parts must be ordered by specifying "–Z" and the corresponding order code, see "3WL Air circuit breakers/NonAutomatic Air circuit breakers up to 6300 A (AC)", "Options", page 15/24 onwards.
1) The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
15/53
© Siemens AG 2009
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Accessories and Spare Parts
Size
Max. rated circuit breaker current
In max
DT
For 4-pole non-automatic
air circuit breakers
Order No.
(Order No. supplements
required according to
table below)
A
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Front main circuit connection, single hole
II
2000
B
3WL9 212-3EA@@-@@A1
1
1 unit
103
37,000
B
3WL9 212-3EB@@-@@A1
1
1 unit
103
37,000
B
B
3WL9 212-3EC@@-@@A1
3WL9 212-6EC@@-@@A1
1
1
1 unit
1 unit
103
103
37,000
84,000
B
B
3WL9 212-3ED@@-@@A1
3WL9 212-6ED@@-@@A1
1
1
1 unit
1 unit
103
103
37,000
84,000
B
B
3WL9 212-3EE@@-@@A1
3WL9 212-6EE@@-@@A1
1
1
1 unit
1 unit
103
103
37,000
84,000
Front main circuit connection, double hole
II
2000
Horizontal main circuit connection
II
II
2000
4000
Vertical main circuit connection
II
II
2000
4000
Main circuit connection connecting flanges
II
II
2000
4000
Add. price
Order No. supplements
Number of auxiliary supply connectors
4-pole
15
Without
1 connector
2 connectors
3 connectors
4 connectors
For required number of auxiliary supply connectors,
see table on page 15/29
Without
0
1
2
3
4
Type of auxiliary circuit connections
Without
With screw connections (SIGUT)
With screwless connection method (tension spring)
Without
0
1
2
Position indicator switches
Without
Option 1
Option 2
Without
0
1
Connected 1 CO contact,
test 1 CO contact,
disconnected 1 CO contact
Connected 3 CO contacts,
test 2 CO contacts,
disconnected 1 CO contact
2
Shutters
Without
With shutter, 2 parts, lockable
Add "–Z" to the complete Order No.
and indicate the appropriate order code(s).
Without
A
B
1234 5 6 7
8 9 10 11 12
13 14 15 16
Add.
3WL9 2 1 2 – . . . . . – . . A1 –Z price
@@@
Order No. with "–Z"
and additional order code
Rated voltage 1000 V DC
Size II
A05
Tinned version of the customer's connections on the guide
frame1)
Only for guide frames with horizontal connection or
flange connection
Size II
A08
For guide frames for 3-pole DC non-automatic air circuit breakers see previous page
All other accessory parts must be ordered by specifying "–Z" and the corresponding order code, see "3WL Air circuit breakers/NonAutomatic Air circuit breakers up to 6300 A (AC)", "Options", page 15/24 onwards.
1) The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
* You can order this quantity or a multiple thereof.
15/54
Siemens LV 1 · 2009
Download