Air Circuit Breakers

advertisement
www.lsis.com
Super Solution
Air Circuit Breakers
Codes and Standards
UA Series are manufactured and tested in accordance
with the following standards Low-Voltage Power
Circuit Breaker
�ANSI C37.13
�ANSI C37.16
�ANSI C37.17
�ANSI C37.50
�UL 1066 (cULus Listed)
�CSA C22.2 No.31-10
Note) Throughout this document, the phrase “ANSI Certified” means the product meets the
requirements of UL 1066 and ANSI C37
UL File Numbers:
Susol UA Series , 1600AF
Susol UA Series , 3200AF
Susol UA Series ,5000AF
E326950 Vol.1 Sec.1
E326951 Vol.1 Sec.2
E326952 Vol.1 Sec.3
Contents
●
Overview
4
●
External configuration
14
●
Internal configuration
16
●
Ordering
18
●
Ratings
22
●
Trip relays
24
●
Accessories
50
●
Electrical diagram
76
●
Dimensions
78
Premium Susol ACB meets your demands for high breaking capacity, fully line-up, and
optimized panel size.
Various accessories and connection methods realize user-friendly handling.
Susol ACB provides you with total solutions with an advanced trip relay for
measurement, diagnosis, analysis, and communication as well as protective functions for
absolute protective coordination and electric power monitoring system.
Super Solution
UL Listed/ANSI Certified
Low-Voltage Power Circuit Breaker UA series
LSIS Super Solution series
Modular design
� High (130kA) Breaking Capacity Full Line-up to 5000A
� Satisfy the needs for a compact sized panels
� N-Phase conducting capacity 100%
� Interchangeable Trip unit and Rating plug
�
Safety
Monitor temperatures for safety (Optional)
�Careful selection of materials
�Arc space is zero
�Perform discriminations between upstream and
downstream levels
User convenience
various connection type for main circuit terminals
�Easy installation of accessories
�Interchangeable Trip unit and Rating plug
Intelligent Trip relay
Various and advanced functions
protection, measurement, diagnosis, analysis, communication
Susol Manual
Motor Starters
Susol Air Circuit Breakers
Susol Molded Circuit Breakers
Susol Magnetic Contactors &
Overload Relays
Full line-up & Compact
Up to 5000A, Susol ACB provides fully lined-up 3 frame.
For each frame, there is just one size, which is smaller and more compact.
H = 430mm
It makes it possible for you to design the optimized volume panel.
W = 334mm
85kA
UAS-08/16D
08
16
800AF
1600AF
85kA at 508Vac
W=334(3p), 419(4p)mm
W = 412mm
100kA
UAH-08~32E
08
16
20
25
32
800AF
1600AF
2000AF
2500AF
3200AF
100kA at 508Vac
W=412(3p), 527(4p)mm
m
5m
37
=
D
W = 785mm
130kA
�The high breaking capacity:
85/100/130kA (at 508Vac)
�3 ampere frame sizes:
1600/3200/5000AF
�N phase current conducting capacity: 100%
UAH- 32~50G
32
40
50
3200AF
4000AF
5000AF
130kA at 508Vac
W=785(3p), 1015(4p)mm
Trip Relay
(OCR)
Trip relays are classified according to function.
Trip relays are classified according to their usages and functions to maximize
customers’ satisfaction. Classified trip relays and easy installation.
�Protection: overload, short current, ground fault, earth leakage, under voltage, over voltage,
under frequency, over frequency, reverse power, unbalance, etc
�Measurement: voltage, ampere, power, energy, frequency, power factor, harmonics, etc.
�Event & fault recording: Max. 256 events & faults
�Communication: Modbus/RS-485, Profibus-DP
Susol ACB Trip Relay functioning world-best protection can be interlocked with mechanism.
It makes the breaking capacity of ACB improved and ACB’s life enhanced, and provides
advanced functions - measurement, diagnosis, analysis, and communication.
Susol ACB Trip relay
N type
�L/S/I/G/Thermal
�Self Power
�RTC Timer mounted
�Fault information (LED)
A type
P/S type
�L/S/I/G/Thermal
�ZSI
�Remote Reset
�Modbus/RS-485
�Profibus-DP
�Self Power
�AC/DC 100~250V
�DC 24~60V
�RTC Timer mounted
�Fault Recording (10EA)
�L/S/ I/G/Thermal(Continuous)
�UV/OV/OF/UF/rP/Vun/Iun
�Measurement: V/A/W/Wh/F/PF
�Harmonics (63th), Waveform (S Type)
�ZSI
�Remote Reset
�Modbus/RS-485
�Profibus-DP
�AC/DC 100~250V
�DC 24~60V
�RTC Timer mounted
�Event Recording (256EA)
�Fault Recording (256EA)
�Fault Wave (S Type)
Trip relays series
N
type
N Type (Normal)
�Self-power + Current protection
P
type
P Type (Power Meter)
�A type + Power Meter +
Voltage / Frequency / Unbalance protection
A
type
A Type (Ammeter)
�Current Meter + Current protection +
DO control + Communication
S
type
S Type (Supreme)
�P type + Harmonics analysis (63 th) +
Fault wave recording
Accessories
�
�
�
�
�
�
�
�
�
�
�
�
�
�
ACB
� Trip Relay (OCR)
� Auxiliary Switch (AX)
� Motor (M)
� Key Lock (K1),
� Closing Coil (CC)
Double Key Lock (K3)
� Shunt Coil (SHT)
� Counter (C)
� Under Voltage Trip Device (UVT)
� On/Off Button Lock (B)
� Door Interlock (DI)
� Miss Insertion Preventing Device (MIP)
� MOC (Mechanically
� Manual Reset Button (MRB)
Operated Cell Switch)
� Mechanical Interlock (MI)
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
Cradle
Other
� Safety Shutter (ST)
� Mechanical Interlock (MI)
� Door Frame (DF)
� Zero Arc Space (ZAS)
� Miss Insertion Prevent Device (MIP)
� Dust Cover (DC)
� Cell Switch (CEL)
� Safety Control Cover (SC)
� Lifting Hook (LH)
� Door Interlock (DI)
� Racking Interlock (RI)
� UVT Time Delay Controller (UDC)
� MOC (Mechanical
Operated Cell switch)
� Profibus-DP Communication module
� Remote I/O
� Temperature Alarm
Connection
and Installation
Diversified terminal connection methods of the ACB main circuit for users.
Multiple connections
Various installation methods
Standard connection
Horizontal type
Vertical type
Front type
Mixed connection
Horizontal / Vertical type
Vertical / Horizontal type
Horizontal / Front type
Vertical / Front type
Front / Horizontal type
Front / Vertical type
�Front connection type is available to be connected regardless of the depth of main circuit terminal, and it is
suited for the panel required for limited installation space.
�The vertical and horizontal type terminal are module types which can easily compose the vertical and
。
horizontal terminals by rotating 90。
�Please refer to the rating lists (Page 22~25) because the installation method is various according to the rated current.
External configuration
Fixed type ACB
Terms
�
� Trip relay
� Counter
�
�
� OFF button
�
� ON button
�
� Series name
�
� Charge handle
�
� Rated name plate
�
�
�
� Charge/Discharge indicator
� Closed/Open indicator
� Corporation logo
�
� Arc cover (Zero Arc Space)
�
� Safety control cover
� Cradle
� Draw-out handle
�
� Position indicator
� Handle inserting hole
�
� Pad lock button
� Arc chute
� Control cover
� Fixed type bracket
� Rating plug
Draw-out ACB (Cradle)
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
14
�
�
�
Cradle (Internal)
Cradle (Rear)
�
�
�
�
�
�
�
�
�
Terms
� Safety control cover
� Pad lock button
� Draw-out handle
� Connecting conductor (Line side)
� Position indicator
� Connecting conductor (Load side)
� Handle inserting hole
Main nameplate
[Acronym explanation]
[Secondary nameplate]
Explanation of terminologies
� Motor charge
Control power and
� Closing coil
terminal No.
� Shunt tripping coil
� Auxiliary switches: Contact specification
and terminal No.
�Under voltage trip: UVT terminal No.
� OCR control source: Trip relay control power
� Alarm switch: Alarm and terminal No.
� Digital trip relay: Switching diagram
� Z.S.I: Input/Output terminal No.
� Reset: LED/LCD reset
� Communication: Communication and
terminal No.
� Voltage module: Phase voltage and symbol
� Earth/Leakage: Ground fault / Earth
leakage input terminal No.
15
Internal configuration
Terms
�
� Arc chute
� Aux. switch control terminal
� Control power supply terminal
�
�
� Trip relay control terminal
�
� Carrying grip
�
� Shunt coil or UVT coil
�
�
�
�
�
� Mechanism
� Main body
� Counter
� Shunt coil
�
� Closing coil
� Motor Ass’y
�
�
� Aux. switch
�
� Closed button
�
� Open button
� MTD base
�
� Trip relay
� Front cover
�
�
16
�
�
Terms
�
�
�
�
�
�
�
� Control circuit terminal block
� Control terminal
� Auxiliary switches
�
� Closing, Shunt, UVT coil
�
� Trip relay
�
� Front cover
� Mechanism
�
� Charge handle
� Trip spring
� Closing spring
�
� Draw-in/out device
�
�
�
� Arc extinguishing part
� Moving contact
� Fixed contact
� Conductor on line side
�
� Cradle finger
� Cradle
� Connecting conductor
�
� CT (Current transformer)
� Conductor on load side
�
17
Ordering
Breaker and Accessories
10
UAS
Frame Type
D
3
Frame Size
Phasing
08
800AF
3/4P Standard
3
3P
04~08 400A~800A
16
1600AF
RST(N)
4
4P
08~16 800A~1600A
D
W
Poles
10
Sensor Rating
A
Mounting and Terminal
Mounting
A
Drawout
H
Horizontal terminals
V
Vertical terminals
4P Reversed NRST
Fixed
M
N
E
32
UAH
Frame Size
Phasing
800AF
3/4P Standard
3
3P
04~08 400A~800A
16
1600AF
RST(N)
4
4P
08~16 800A~1600A
20
2000AF
25
2500AF
12~25 1200A~2500A
32
3200AF
16~32 1600A~3200A
32
3200AF
40
4000AF
50
5000AF
E
X
G
Z
4P Reversed NRST
10~20 1000A~2000A
3
3P
16~32 1600A~3200A
RST(N)
4
4P
20~40 2000A~4000A
4P Reversed NRST
25~50 2500A~5000A
D
3
Frame Size
Phasing
08
800AF
3/4P Standard
3
3P
16
1600AF
RST(N)
4
4P
20
2000AF
25
2500AF
32
3200AF
40
4000AF
50
5000AF
Frame Type
D
W
E
X
G
Z
Sensor Rating
3/4P Standard
16
UAA
Poles
10
32
08
Frame Type
18
3
4P Reversed NRST
3/4P Standard
RST(N)
4P Reversed NRST
3/4P Standard
RST(N)
4P Reversed NRST
Poles
10
00
Sensor Rating
Not applied
Horizontal for line
Vertical for load
Vertical for line
Horizontal for load
P
Front terminal
G
Horizontal-con type
W
Vertical-con type
* Terminals for P type must be
ordered separately
* G and W types can be applicable
to UAS-08D, UAS-16D only
* Front terminal is only available for
800~2000A
M1
D1
D1
Motor Operator
AX
Shunt Trip
Trip relay
None (Manual operated)
D0
None
M1
AC/DC 100V~125V
D1
AC/DC 100V~125V
M2
AC/DC 200V~250V
D2
AC/DC 200V~250V
M3
DC 125V
D3
DC 125V
M4
DC 24V~30V
D4
DC 24V~30V
M5
DC 48V~60V
D5
DC 48V~60V
M8
AC 48V
D7
AC 48V
Closing Coil
N01
N02
N03
N04
N05
N06
U1
AL
C
Option
Refer to 21page
MA
Code
AL
A1
A2
A3
A4
A5
A6
A7
A8
A9
C
S
B
NG0
Charging/Auxiliary Switch
UVT
D0
None
AX
Standard OFF charge/3a3b
U0
None
D1
AC/DC 100V~125V
AC
Standard ON charge/3a3b
U1
AC/DC 100V~125V
D2
AC/DC 200V~250V
BX
Standard OFF charge/5a5b
U2
AC/DC 200V~250V
D3
DC 125V
BC
Standard ON charge/5a5b
U3
DC 125V
D4
DC 24V~30V
HX
High capacity OFF charge/5a5b
U4
DC 24V~30V
D5
DC 48V~60V
HC
High capacity ON charge/5a5b
U5
DC 48V~60V
D7
AC 48V
CC
Standard ON charge/6a6b
U6
AC 380V~480V
JC
High capacity ON charge/6a6b
U7
AC 48V
Description
Code
M MI
AL1+MRB
D
DI or MOC
AL1+MRB +RES(AC110~130V) *AC only
K
K1
AL1+AL2 +MRB
K2 K2
AL1+MRB +RES(DC110~125V) *DC only
K3 K3
AL1+MRB +RES(AC200~250V) *AC only
R
RCS
AL1+MRB +Auto Reset
T
TM
AL1+AL2 +MRB +Auto Reset
AL1+MRB +RES(DC110~125V) +Auto Reset *DC only H1
AL1+MRB +RES(AC200~250V) +Auto Reset *AC only H2
AL1+MRB +RES(AC110~130V) +Auto Reset *AC only H3 SHT2 Note 2)
C
COUNTER
H4
CS2
Charge switch communication
H5
B
On/Off Button lock
H7
Description
Mechanical interlock
Door Interlock or MOC(Mechanism operated cell switch)
Key Lock
Key Interlock Set
Key Interlock Double
Ready to Close switch
Temperature Monitoring
AC/DC 100V ~125V, Double Shunt coil
AC/DC 200V ~250V, Double Shunt coil
DC 125V, Double Shunt coil
DC 24V ~30V, Double Shunt coil
DC 48V ~60V, Double Shunt coil
AC 48V, Double Shunt coil
A4 (AL1+MRB +RES(AC200~250V))+C(Counter)+B(ON/OFF Button Lock)+K(Key Lock)+R(Ready to Close switch)+M(Mechanic
Interlock)+E(Spring Auto Release)
AL (AL1+MRB)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+D(Door Interlock or MOC)+H1(AC/DC 100V ~ 130V, Double Shunt
coil)+E(Spring Auto Release)
C(Counter)+B(ON/OFF Button Lock)+K2(Key Interlock Set)+R(Ready to Close switch)+T(Temperature Monitoring)
A4(AL1+MRB+RES(AC200~250V))+B(ON/OFF Button Lock)+K(Key Lock(OFF Lock))+M(Mechanical Interlock)+T(Temperature Monitoring)
A1(AL1+MRB+RES110~130V)+B(ON/OFF Button Lock)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+M(Mechanical
Interlock)+T(Temperature Monitoring)
A2(AL1+AL2+MRB)+C(Counter)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+T(Temperature Monitoring)
Note) * Codes for over 5 optional accessories are composed separately
**UVT and SHT2 can not be selected together. Select one of two.
19
Ordering
Product number structure
UAL
For UL ACB
Cradle type
N16D
Frame Size
S16D
1600AF
S20E
2000AF
S25E
2500AF
S32E
3200AF
S40E
S50G
20
4000AF
5000AF
3
A
H
Number of poles
Terminal configuration
3
3P
H
Horizontal type
4
4P
V
Vertical type
M
Secondary
Connector type
N
Line: Horizontal
Load: Vertical
E
N
Shutter
E
F
Without safety
shutter
With safety
shutter
Line: Vertical
Load: Horizontal
P
Front type
A
Connector type
G
Horizontal-con type
B
Screw joint type
W
Vertical-con type
C
Spring tension type
* Terminals for P type must be ordered separately
* G and W types can be applicable to S16D (1600AF) only.
Other options
S
Arc cover
Trip relay
N
G
0
OCR(Trip Unit) type
Communication & Ground fault protection
Control voltage & frequency
G
0
0
No OCR
N
N
Normal
G
Ground fault, No Communication
A
A
Ammeter
Power meter
Supreme meter
60Hz
Self-power
50Hz
0
G
Ground fault, No Communication
0
No Control voltage
C
Ground fault and Communication
1
AC/DC 110V~250V 60Hz
E
Ground fault(with external CT), No Communication
2
DC 24V~60V
60Hz
X
Ground fault(with external CT) and Communication
5
No Control voltage
50Hz
6
AC/DC 110V~250V 50Hz
7
DC 24V~60V
C
60Hz
50Hz
1
C
Ground fault and Communication
1
AC/DC 110V~250V 60Hz
X
Ground fault(with external CT) and Communication
2
DC 24V~60V
6
AC/DC 110V~250V 50Hz
7
DC 24V~60V
S
S
Self-power
5
G
P
P
0
C
60Hz
50Hz
1
C
Communication
1
AC/DC 110V~250V 60Hz
X
Ground fault and Communication
2
DC 24V~60V
6
AC/DC 110V~250V 50Hz
7
DC 24V~60V
60Hz
50Hz
* Ground fault detection by current vector sum of 4 phase (R,S,T,N)
* Communication and output contacts for L,S,I,G do not work except OCR LED without control power supply.
* P and S types require Voltage Module to be ordered separately.
* LCD in trip unit can be display more than 10% of rated current.
* Currnet measuring value display more than 15% of rated current.
21
Ratings for UL Listed/ANSI Certified Susol UA Circuit Breakers
TYPE
AF
Rated current (In max)
Rated current
UAS-��D
(A)
(A)
at 40°C
at 40°C
08
800
16
1600
800
1000
1200
1250
1600
400
600
630
800
Rated Maximum Voltage (V)
Frequency
(Hz)
Number of poles
(P)
Type of Trip relay (Electronic trip device)
Rated short circuit current (kA)
(Sym.)
UL 1066
ANSI C37.13
Rated short Time current (kA)
Operating time
(t)
(ms)
Life cycle
ACB
(time)
Weight
lb (kg)
External
dimension
Draw-out type
With
instantaneous
AC
Without
instantaneous
AC
635V
508V
254V
635V
508V
254V
Maximum total breaking time
Maximum closing time
Mechanical
Without maintenance
With maintenance
Electrical
Without maintenance
With maintenance
Drawout type
Main Body
3P
with Cradle
4P
Only Cradle
3P
4P
Fixed type
Motor charging
3P
type
4P
in (mm)
H×W×D
3P
4P
H
Fixed type
in (mm)
H×W×D
3P
D
W
4P
Enclosure dimension
in (mm)
H×W×D
3P
4P
22
254V / 508V / 635V
50/60
3P / 4P
N, A, P, S (4 type)
65
85
85
65
65
65
65
50ms
80ms
12,500
2,800
154 (70)
187 (85)
71 (32)
84 (38)
77 (35)
99 (45)
16.93×13.15×16.02
(430×334×407)
16.93×16.5×16.02
(430×419×407)
11.81×11.81×11.61
(300×300×295)
11.81×15.16×11.61
(300×385×295)
19.69×15.75×13.39
(500×400×340)
19.69×19.69×13.39
(500×500×340)
08
800
400
600
630
800
UAH-��E
20
2000
1000
1200
1250
1600
2000
254V / 508V / 635V
50/60
3P / 4P
N, A, P, S (4 type)
85
100
100
85
85
85
85
50ms
80ms
12,500
5,000
UAH-��G
40
4000
2000
2500
3000
3200
3600
4000
254V / 508V / 635V
50/60
3P / 4P
N, A, P, S (4 type)
100
130
130
100
100
100
100
50ms
90ms
5,000
2,800
1,000
1,000
326 (148)
414 (188)
205 (93)
256 (116)
196 (89)
249 (113)
489 (222)
626 (284)
276 (125)
355 (161)
227 (103)
287 (130)
18.11×30.91×16.02
(460×785×407)
18.11×39.96×16.02
(460×1015×407)
11.81×29.57×11.61
(300×751×295)
11.81×38.62×11.61
(300×981×295)
31.5×32.48×13.39
(800×825×340)
31.5×41.54×13.39
(800×1055×340)
16
1600
800
1000
1200
1250
1600
214 (97)
269 (122)
99 (45)
121 (55)
101 (46)
126 (57)
25
2500
1200
1250
1600
2000
2500
245 (111)
309 (140)
123 (56)
152 (69)
110 (50)
137 (62)
16.93×16.22×16.02
(430×412×407)
16.93×20.75×16.02
(430×527×407)
11.81×14.88×11.61
(300×378×295)
11.81×19.41×11.61
(300×493×295)
19.69×19.69×13.39
(500×500×340)
19.69×24.21×13.39
(500×615×340)
32
3200
1600
2000
2500
3000
3200
32
3200
1600
2000
2500
3000
3200
50
5000
2500
3000
3200
3600
4000
5000
23
Trip relay(OCR)
The trip relay of Susol ACB provides the additional protection functions for
voltage, frequency, unbalance, and others in addition to main protection
functions for over current, short-circuit, ground fault. It supports the
advanced measurement functions for voltage, current, power, electric energy,
harmonics, communication function, and others.
Analog trip function interlocked with mechanism enhanced a durability of
devices as well as the breaking capacity of ACB.
Zone selective interlocking function makes the protective coordination more
simple and thermal memory can be applied to various loads.
Contents
Trip relay types
25
�type
N type:�Normal�
26
�type
A type:�Ammeter�
28
�type
P type:�Power meter�
30
�type
S type:�Supreme meter�
32
Operation characteristic
34
Measurement function
36
Man machine interface
37
Protection element setting
38
Measurement element display
39
Characteristic curves
40
ZSI - Zone Selective Interlocking
45
Remote reset and digital I/O
46
Communication
47
Event & fault recording
48
System information
48
System block diagram
49
Trip relays
Trip relay types
Classification
N type
A type
P type
S type
Externals
Current
protection
Other
protection
�L / S / I / G
�L / S / I / G / Thermal
�ZSI(Protective coordination)
� Earth leakage (Option)
-
�Current (R / S / T / N)
Measurement
function
-
Fine adjustment
-
Pre Trip Alarm
-
Digital Output
-
�3DO (Fixed)
�L, S/I, G Alarm
IDMTL setting
-
-
Communication
Power supply
RTC timer
LED for
trip info.
Fault recording
Event recording
Operating
button
-
�Modbus/RS-485
�Profibus-DP
�Self Power
�Self Power
- Power shource
- Power shource works
works over 20% of
over 20% of load current.
load current.
- External power source are
required for comm.
�AC/DC 100~250V
�DC 24~60V
�Available
�Long time delay
�Long time delay
�Short time delay/Instantaneous �Short time delay/Instantaneous
�Ground fault
�Ground fault
�10 records
(Fault/Current/Date and Time)
�Reset button
�Reset, Menu
Up/Down, Left/Right, Enter
-
�L / S / I / G / Thermal(Continuous) �L / S / I / G / Thermal(Continuous)
�ZSI(Protective coordination)
�ZSI(Protective coordination)
�Earth leakage(Option)
�Earth leakage(Option)
�Over/Under current
�Over/Under current
�Over/Under frequency
�Over/Under frequency
�Unbalance(Voltage/Current)
�Unbalance(Voltage/Current)
�Reverse power
�Reverse power
�3 Phase Voltage/Current RMS/Vector �3 Phase Voltage/Current RMS/Vector
�Power(P, Q, S), PF(3-Phase) �Power(P, Q, S), PF(3-Phase)
�Energy(Positive/Negative)
�Energy(Positive/Negative)
�Frequency, Demand
�Frequency, Demand
�Voltage/Current harmonics (1st~63th)
�3 Phase Waveforms
�THD, TDD, K-Factor
�Fine adjustment for long/short �Fine adjustment for long/short
time delay/instantaneous/ ground
time delay/instantaneous/ ground
�Overload protection relays
�Overload protection relays
: DO (Alarm) (Ground fault is not
: DO (Alarm) (Ground fault is not
available when using Pre trip alarm)
available when using Pre trip alarm)
�3DO (Programmable)
�3DO (Programmable)
�Trip, Alarm, General
�Trip, Alarm, General
�Compliance with IEC60255-3 �Compliance with IEC60255-3
SIT, VIT, EIT, DT
SIT, VIT, EIT, DT
�Modbus / RS-485
�Modbus / RS-485
�Profibus-DP
�Profibus-DP
�AC/DC 100~250V
�AC/DC 100~250V
�DC 24~60V
�DC 24~60V
Basic protection function(L / S / I / G)
is still under normal operation
without control power.
�Available
�Long time delay
�Short time delay/Instantaneous
�Ground fault
�256 records
(Fault/Current/Date and Time)
�256 records(Content, Status, Date)
�Reset, Menu
Up/Down, Left/Right, Enter
�Available
�Long time delay
�Short time delay/Instantaneous
�Ground fault
�256 records
�Last fault wave recording (3 Phase)
�256 records(Content, Status, Date)
�Reset, Menu
Up/Down, Left/Right, Enter
25
Trip relays
�type
N type:�Normal�
■ Optimized protection function
■ OCR, OCGR function according IEC60947-2
■ Overload protection
- Long-time delay
- Thermal
■ Short-circuit protection
- Short-time delay / Instantaneous
- I2t On/Off optional (for short-time delay)
■ Ground fault protection
- I2t On/Off optional
■ Self-Power
① LED: Indication of trip info. and overload state
Alarm SP
Ir
Isd
Ii
Ig
Ig: LED indicating ground-fault
Isd/Ii: LED indicating short-time or instantaneous tripping
Ir: LED indicating long-time delay
SP: Self-protection and battery test LED
Alarm: LED indicating an overload
(Turn on above 90%, Blink above 105%)
①
②
② Reset Key: Fault reset or battery check
③ Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting
④ Isd: Short-time current setting, tsd: Short-time tripping delay setting
⑤ Ii: Instantaneous current setting
③
⑥ Ig: Ground fault current setting, tg: Ground fault tripping delay setting
⑦ Test terminal: OCR test terminal (Connected with OCR tester)
④
⑥
⑤
⑦
⑧
26
⑧ Rating plug
- Rated current setting (45~100% of the AF)
- Frequency selectable(60Hz/50Hz)
Trip relays
Protection
Long time
t
Current setting (A)
Iu = In×...
0.5
0.6
Ir = Iu×...
0.8
0.83 0.85 0.88 0.9
Time delay (s)
tr@(1.5×lr)
12.5 25
50
100
Accuracy: ±15% or below
tr@(6.0×lr)
0.5
2
4
100ms
tr@(7.2×lr)
0.34 0.69 1.38 2.7
Isd = Ir×...
1.5
1
0.7
0.8
0.9
1.0
Ir
0.93 0.95 0.98
1.0
200
300
400
500
Off
8
12
16
20
Off
5.5
8.3
11
13.8
Off
6
8
10
Off
10
12
15
Off
tr
lsd
tsd
Ii
Short time
I
Current setting (A)
Accuracy: ±10%
Time delay (s)
@ 10×Ir
tsd
(I t Off)
3
4
5
I2t Off
0.05 0.1
0.2
0.3
0.4
I t On
0.1
0.2
0.3
0.4
20
80
160
260
360
80
140
240
340
440
2
3
4
6
8
2
Min. Trip
2
2
Time(ms)
Max. Trip
Time(ms)
Instantaneous
Current setting (A)
Ii = In×...
Tripping time
below 50ms
Ground fault
t
Pick-up (A)
Accuracy: ±10%(Ig�0.4In)
Ig = In×...
0.2
0.3
0.4
0.5
0.6
±20%(Ig≤0.4In)
0.7
0.8
1.0
Off
Ig
I t Off
0.05 0.1
0.2
0.3
0.4
I2t On
0.1
0.2
0.3
0.4
20
80
160
260
360
80
140
240
340
440
2
tg
Time delay (s)
Min. Trip
@ 1×In
Time(ms)
(I t Off)
2
Max. Trip
Time(ms)
tg
I
27
Trip relays
�type
A type:�Ammeter�
■ Measurement and Display Function
- High detailed measurement for current
- character LCD type
■ Fault recording
- Records Max. up to 10 fault information about fault type,
fault phase, fault data, occurrence time of fault
■ SBO (Select Before Operation)
- High reliability for control and setting change method
■ 3 DO(Digital Output)
- Fixed
■ Communication
- Modbus/RS485
- Profibus-DP
■ Overload protection
- Long-time delay
- Thermal
■ Short-circuit protection
- Short-time delay / Instantaneous
- I2t On/Off optional (for short-time delay)
■ Ground fault protection
- I2t On/Off optional
- Trip/Alarm selectable (need external power)
- Blocking Time (0~60s)
Do not ground fault detect during Blocking time
■ Realization of protective coordination by ZSI
(Zone Selective Interlocking)
- Disable/Enable Selectable
■ High-performance and high-speed MCU built-in
- Accurate measurement with tolerance of 1.0%
① LCD: Indication of measurement and information
② LED: Indication of trip info. and overload state
Alarm SP
Ir
Isd
Ii
Ig
Comm
①
Ig: LED indicating ground-fault
Isd/Ii: LED indicating short-time or instantaneous tripping
Ir: LED indicating long-time delay
SP: Self-protection and battery test LED
Alarm: LED indicating an overload
(Turn on above 90%, Blink above 105%)
③ Key: Move to menu or reset
②
Reset
Esc
③
Reset/ESC: Fault reset or ESC from menu
Enter: Enter into secondary menu or setting input
Up/Down: Move the cursor up/down on screen or
increase/decrease a setting value
Right/Left: Move the cursor or setting right/left on screen
(Rotation)
Menu: Menu display ↔ Measurement display
④
⑤
⑥
⑦
⑧
④ Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting
⑤ Isd: Short-time current setting, tsd: Short-time tripping delay setting
⑥ Ii: Instantaneous current setting
⑦ Ig: Ground fault current setting, tg: Ground fault tripping delay setting
⑨
⑧ Test terminal: OCR test terminal (Connected with OCR tester)
⑨ Rating plug
- Rated current setting (45~100% of the AF)
- Frequency selectable(60Hz/50Hz)
28
Trip relays
Protection
Long time
t
Current setting (A)
Iu = In×...
0.5
0.6
Ir = Iu×...
0.8
0.83 0.85 0.88 0.9
Time delay (s)
tr@(1.5×lr)
12.5 25
50
100
Accuracy: ±15% or below
tr@(6.0×lr)
0.5
2
4
100ms
tr@(7.2×lr)
0.34 0.69 1.38 2.7
Isd = Ir×...
1.5
1
0.7
0.8
0.9
1.0
Ir
0.93 0.95 0.98
1.0
200
300
400
500
Off
8
12
16
20
Off
5.5
8.3
11
13.8
Off
6
8
10
Off
10
12
15
Off
tr
lsd
tsd
Ii
Short time
I
Current setting (A)
Accuracy: ±10%
Time delay (s)
@ 10×Ir
tsd
(I t Off)
3
4
5
I2t Off
0.05 0.1
0.2
0.3
0.4
I t On
0.1
0.2
0.3
0.4
20
80
160
260
360
80
140
240
340
440
2
3
4
6
8
2
Min. Trip
2
2
Time(ms)
Max. Trip
Time(ms)
Instantaneous
Current setting (A)
Ii = In×...
Tripping time
below 50ms
Ground fault
t
Pick-up (A)
Accuracy: ±10%(Ig�0.4In)
Ig = In×...
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1.0
Off
Ig
±20%(Ig≤0.4In)
I t Off
0.05 0.1
0.2
0.3
0.4
I2t On
0.1
0.2
0.3
0.4
20
80
160
260
360
80
140
240
340
440
0.5
1
2
3
5
140
230
350
800
950
140
230
350
800
2
tg
Time delay (s)
Min. Trip
@ 1×In
Time(ms)
(I t Off)
2
Max. Trip
Time(ms)
tg
I
Earth leakage (Option)
Current setting (A)
t
I△n
Time delay (ms)
Accuracy: ±15%
Alarm
△t
Time(ms)
Trip
Time(ms)
Note) Current setting values are secondary current of the external CT.
Recommend : not to use current setting values more than 5A.
10
20
30
Off
I n
t
I
29
Trip relays
�type
P type:�Power meter�
■ Overload protection
- Long-time delay
- Thermal
■ Short-circuit protection
- Short-time delay / Instantaneous
- I2t On/Off optional (for short-time delay)
■ Ground fault protection
- I2t On/Off optional
- Trip/Alarm selectable (need external power)
- Blocking Time (0~60s)
Do not ground fault detect during Blocking time
■ Protection for Over voltage/Under voltage/Over
frequency/Under frequency/Unbalance/Reverse power
■ Realization of protective coordination by ZSI
(Zone Selective Interlocking)
- Disable/Enable Selectable
■ The fine-adjustable setting by knob and Key
■ IDMTL setting (SIT, VIT, EIT, DT curve)
- Basic setting : “None”. Thermal curve.
■ Measurement and Display Function
- High detailed measurement for 3 phase
current/Voltage/Power/Energy/Phase
angle/Frequency/PF/Demand
- 128 x 128 Graphic LCD
- Indicates current/voltage Vector Diagram and Waveform
■ Fault recording
- Records Max. up to 256 fault information about fault
type, fault phase, fault value, occurrence time of fault
■ Event recording
- Records events of device related to setting change,
operation and state change. (Max. up to 256)
■ SBO (Select Before Operation)
- High reliability for control and setting change method
■ 3 DO(Digital output)
- Programmable for alarm, trip and general DO
■ Communication
- Modbus/RS485
- Profibus-DP
① Graphic LCD: Indication of measurement and information
② LED: Indication of trip info. and overload state
Alarm SP
Ir
Isd
Ii
Ig
Comm
①
Comm: LED indicating comm. state (Blink when running)
Ig: LED indicating ground-fault
Isd/Ii: LED indicating short-time or instantaneous tripping
Ir: LED indicating long-time delay
SP: Self-protection and battery test LED
Alarm: LED indicating an overload
(Turn on above 90%, Blink above 105%)
③ Key: Move to menu or reset
②
Reset
Esc
③
Reset/ESC: Fault reset or ESC from menu
Enter: Enter into secondary menu or setting input
Up/Down: Move the cursor up/down on screen or
increase/decrease a setting value
Right/Left: Move the cursor or setting right/left on screen
(Rotation)
Menu: Menu display ↔ Measurement display
④
⑤
⑥
⑦
⑧
④ Ir: Long-time current setting, tr: Long-time tripping delay setting
⑤ Isd: Short-time current setting, tsd: Short-time tripping delay setting
⑥ Ii: Instantaneous current setting
⑦ Ig: Ground fault current setting, tg: Ground fault tripping delay setting
⑨
⑧ Test terminal: OCR test terminal (Connected with OCR tester)
⑨ Rating plug
- Rated current setting (45~100% of the AF)
- Frequency selectable(60Hz/50Hz)
30
Trip relays
Protection
Long time
Current setting (A)
Time delay (s)
Accuracy: ±15% or below
100ms
Short time
Current setting (A)
Accuracy: ±10%
Time delay (s)
@ 10×Ir
Ir = In×...
tr@(1.5×lr)
tr@(6.0×lr)
tr@(7.2×lr)
Isd = Ir×...
tsd
Earth leakage (Option)
Current setting (A)
Time delay (ms)
Accuracy: ±15%
1.5
I2t Off
0.6
50
2
1.38
0.7
100
4
2.7
0.8
200
8
5.5
3
4
5
0.05 0.1
0.1
0.2
0.2
0.3
0.3
0.4
0.4
80
160
260
360
140
240
340
440
6
8
I2t On
Min. Trip
20
Time(ms)
Max. Trip
80
Time(ms)
Ii = In×...
0.9
300
12
8.3
1.0
400
16
11
t
Ir
500
20
13.8
Off
Off
Off
2
2
3
4
below 50ms
6
8
10
Off
10
12
15
Off
Ig = In×...
0.2
0.3
0.4
0.5
0.6
0.05 0.1
I2t Off
I2t On
0.1
Min. Trip
20
80
Time(ms)
Max. Trip
80
140
Time(ms)
0.2
0.2
0.3
0.3
0.4
0.4
160
260
360
240
340
440
1
2
3
5
230
350
800
950
0.7
0.8
1.0
Other protection
Under voltage
Over voltage
Voltage unbalance
Reverse power
Over power
Current unbalance
Over
60Hz
frequency
50Hz
Under
60Hz
frequency
50Hz
lsd
Ii
I
Off
Ig
(I2t Off)
tg
I
t
I△n
△t
0.5
Alarm
140
Time(ms)
Trip
140
Time(ms)
10
20
30
Off
I n
230
350
800
t
Note) Current setting values are secondary current of the external CT.
Recommend : not to use current setting values more than 5A.
PTA(Pre Trip Alarm)
Current setting (A)
Time delay (s)
Accuracy: ±15%
tr
t
tg
Time delay (s)
@ 1×In
0.5
25
1
0.69
tsd
(I2t Off)
Instantaneous
Current setting (A)
Tripping time
Ground fault
Pick-up (A)
Accuracy: ±10%(Ig�0.4In)
±20%(Ig≤0.4In)
0.4
12.5
0.5
0.34
I
Ip = Ir x …
0.6
0.65 0.7
0.75 0.8
0.85 0.9
0.95
1
tp@(1.2×Ip)
1
5
15
25
35
Off
Setting range
80V ~ 0V_Pick-up
UV_Pick-up ~ 980V
6% ~ 99%
10~500 kW
500~5000 kW
6% ~ 99%
UF_Pick-up ~ 65
UF_Pick-up ~ 55
55Hz ~ OF_Pick-up
45Hz ~ OF_Pick-up
Pick-up
Step
1V
1V
1%
1kW
1kW
1%
1Hz
1Hz
1Hz
1Hz
10
Accuracy
±5%
±5%
±2.5% or (*±10%)
±10%
±10%
±2.5% or (*±10%)
±0.1Hz
±0.1Hz
±0.1Hz
±0.1Hz
20
30
Time delay(s)
Setting range Step Accuracy
1.2~40sec
0.2~40sec
0.1sec
±0.1sec
1.2~40sec
31
Trip relays
�type
S type:�Supreme meter�
- 128 x 128 Graphic LCD
- Indicates current/voltage Vector Diagram and Waveform
■ Fault recording
- Records Max. up to 256 fault information about fault
type, fault phase, fault value, occurrence time of fault
- Fault wave recording: records the latest fault wave
■ Event recording
- Records events of device related to setting change,
operation and state change. (Max. up to 256)
■ SBO (Select Before Operation)
- High reliability for control and setting change method
■ Power quality analysis
- Measurement for 1st~63th harmonics
- THD, TDD, k-Factor
- Voltage/current waveform capture
■ 3 DO(Digital output)
- Programmable for alarm, trip and general DO
■ Communication
- Modbus/RS485
- Profibus-DP
■ Overload protection
- Long-time delay
- Thermal
■ Short-circuit protection
- Short-time delay / Instantaneous
- I2t On/Off optional (for short-time delay)
■ Ground fault protection
- I2t On/Off optional
- Trip/Alarm selectable (need external power)
- Blocking Time (0~60s)
Do not ground fault detect during Blocking time
■ Protection for Over voltage/Under voltage/Over
frequency/Under frequency/Unbalance/Reverse power
■ Realization of protective coordination by ZSI
(Zone Selective Interlocking)
- Disable/Enable
■ The fine-adjustable setting by knob and Key
■ IDMTL setting (SIT, VIT, EIT, DT curve)
- Basic setting : “None”. Thermal curve.
■ Measurement and Display Function
- High detailed measurement for 3 phase current/Voltage/
Power/Energy/Phase angle/Frequency/PF/Demand
① Graphic LCD: Indication of measurement and information
② LED: Indication of trip info. and overload state
Alarm SP
Ir
Isd
Ii
Ig
Comm
①
Comm: LED indicating comm. state (Blink when running)
Ig: LED indicating ground-fault
Isd/Ii: LED indicating short-time or instantaneous tripping
Ir: LED indicating long-time delay
SP: Self-protection LED and battery test LED
Alarm: LED indicating an overload
(Turn on above 90%, Blink above 105%)
③ Key: Move to menu or reset
②
Reset
Esc
③
Reset/ESC: Fault reset or ESC from menu
Enter: Enter into secondary menu or setting input
Up/Down: Move the cursor up/down on screen or
increase/decrease a setting value
Right/Left: Move the cursor or setting right/left on screen
(Rotation)
Menu: Menu display ↔ Measurement display
④
⑤
⑥
④ Ir: Long-time current setting, tr: Long-time tripping delay setting
⑦
⑧
⑤ Isd: Short-time current setting, tsd: Short-time tripping delay setting
⑥ Ii: Instantaneous current setting
⑦ Ig: Ground fault current setting, tg: Ground fault tripping delay setting
⑧ Test terminal: OCR test terminal (Connected with OCR tester)
⑨
32
⑨ Rating plug
- Rated current setting (45~100% of the AF)
- Frequency selectable(60Hz/50Hz)
Trip relays
Protection
Long time
Current setting (A)
Time delay (s)
Accuracy: ±15% or below
100ms
Short time
Current setting (A)
Accuracy: ±10%
Time delay (s)
@ 10×Ir
Iu = In×...
tr@(1.5×lr)
tr@(6.0×lr)
tr@(7.2×lr)
Isd = Ir×...
tsd
Earth leakage (Option)
Current setting (A)
Time delay (ms)
Accuracy: ±15%
1.5
I2t Off
0.6
50
2
1.38
0.7
100
4
2.7
0.8
200
6
5.5
3
4
5
0.05 0.1
0.1
0.2
0.2
0.3
0.3
0.4
0.4
80
160
260
360
140
240
340
440
6
8
I2t On
Min. Trip
20
Time(ms)
Max. Trip
80
Time(ms)
Ii = In×...
0.9
300
12
8.3
1.0
400
16
11
t
Ir
500
20
13.8
Off
Off
Off
2
2
3
4
below 50ms
6
8
10
Off
10
12
15
Off
Ig = In×...
0.2
0.3
0.4
0.5
0.6
I2t Off
0.05 0.1
I2t On
0.1
Min. Trip
20
80
Time(ms)
Max. Trip
80
140
Time(ms)
0.2
0.2
0.3
0.3
0.4
0.4
160
260
360
240
340
440
1
2
3
5
230
350
800
950
0.7
0.8
1.0
Other protection
Under voltage
Over voltage
Voltage unbalance
Reverse power
Over power
Current unbalance
Over
60Hz
frequency
50Hz
Under
60Hz
frequency
50Hz
lsd
Ii
I
Off
Ig
(I2t Off)
tg
I
t
I△n
△t
0.5
Alarm
140
Time(ms)
Trip
140
Time(ms)
10
20
30
Off
I n
230
350
800
t
Note) Current setting values are secondary current of the external CT.
Recommend : not to use current setting values more than 5A.
PTA(Pre Trip Alarm)
Current setting (A)
Time delay (s)
Accuracy: ±15%
tr
t
tg
Time delay (s)
@ 1×In
0.5
25
1
0.69
tsd
(I2t Off)
Instantaneous
Current setting (A)
Tripping time
Ground fault
Pick-up (A)
Accuracy: ±10%(Ig�0.4In)
±20%(Ig≤0.4In)
0.4
12.5
0.5
0.34
I
Ip = Ir x …
0.6
0.65 0.7
0.75 0.8
0.85 0.9
0.95
1
tp@(1.2×Ip)
1
5
15
25
35
Off
Setting range
80V ~ 0V_Pick-up
UV_Pick-up ~ 980V
6% ~ 99%
10~500 kW
500~5000 kW
6% ~ 99%
UF_Pick-up ~ 65
UF_Pick-up ~ 55
55Hz ~ OF_Pick-up
45Hz ~ OF_Pick-up
Pick-up
Step
1V
1V
1%
1kW
1kW
1%
1Hz
1Hz
1Hz
1Hz
10
Accuracy
±5%
±5%
±2.5% or (*±10%)
±10%
±10%
±2.5% or (*±10%)
±0.1Hz
±0.1Hz
±0.1Hz
±0.1Hz
20
30
Time delay(s)
Setting range Step Accuracy
1.2~40sec
0.2~40sec
0.1sec
±0.1sec
1.2~40sec
33
Trip relays
Operation characteristics
Long-time delay (L)
The function for overload protection which has time delayed
Iu
N, A type
characteristic in inverse ratio to fault current.
.8
Ir
.9
1
.9
tr
4
.93
.85
.95
2
.6
.83
.98
1
.5
1. Standard current setting knob: Ir
1) Setting range in P type and S type: (0.4-0.5-0.6-0.7-0.8-0.9-1.0)×In
2) Setting range in N type and A type: (0.4 ~1.0)×In
- Iu: (0.5-0.6-0.7-0.8-0.9-1.0)×In
- Ir: (0.8-0.83-0.85-0.88-0.9-0.93-0.95-0.98-1.0)×Iu
2. Time delay setting knob: tr
- Standard operating time is based on the time of 6×Ir
- Setting range: 0.5-1-2-4-8-12-16-20-Off sec (9 modes)
3. Relay pick-up current
- When current over (1.15)×Ir flows in, relay is picked up.
4. Relay operates basing on the largest load current among R/S/T/N phase.
.88
.7
Iong time
.8
×In
1
P, S type
.7
.8
.9
(S)
.5
Iong time
×In
I
Short-time delay (S)
The function for fault current (over current) protection which has definite
1. Standard current setting knob: Isd
- Setting range: (1.5-2-3-4-5-6-8-10-Off)×Ir
2. Time delay setting knob: tsd
- Standard operating time is based on the time of 10×Ir.
- Inverse time (I2t On ): 0.1-0.2-0.3-0.4 sec
- Definite time (I2t Off): 0.05-0.1-0.2-0.3-0.4 sec
3. Relay operates basing on the largest load current among R/S/T/N phase.
4. When ZSI function was set, the protection operation will take place instantaneously with input absence
by downstream devices. It is advised to disable its ZSI function on the last downstream device.
4
5
tsd
6
(S)
8
.3
2
10
.2
1.5
.4
.4
.3
.2
.1
off
.1
short time
.05
on 2 off
×Ir
I t
t
Isd
tsd
I
Instantaneous (I)
The function for breaking fault current above the setting value within
the shortest time to protect the circuit from short-circuit.
1. Standard current setting knob: Ii
- Setting range: (2-3-4-6-8-10-12-15-Off)×In
2. Relay operates basing on the largest load current among R/S/T/N phase.
3. Total breaking time is below 50ms.
Ii
6
8
10
4
12
3
15
2
off
instantaneous
×In
t
Ii
I
34
12
16
20
.5
off
@6 Ir
tr
3
8
1
.4
Isd
4
2
1
Ir
time characteristic and time delayed in inverse ratio to fault current.
16
off
@6 Ir
tr
.6
t
12
20
.5
×Iu
Ir
8
Trip relays
Ground Fault (G)
The function for breaking ground fault current above setting value
after time-delay to protect the circuit from ground fault.
1. Standard setting current knob: Ig
- Setting range: (0.2-0.3-0.4-0.5-0.6-0.7-0.8-1.0-Off)×In
2. Time delay setting knob: tg
- Inverse time (I2t On): 0.1-0.2-0.3-0.4 sec
- Definite time (I2t Off): 0.05-0.1-0.2-0.3-0.4 sec
3. Ground fault current is vector sum of each phase current. Therefore, 3Pole products may operate
under its phase-unbalance including ground fault situations.(R+S+T+(N) Phase)
4. When ZSI function was set, the protection operation will take place instantaneously with input absence
by downstream devices. It is advised to disable its ZSI function on the last downstream device.
5. Ground-fault functions are basically provided with products equipped with a trip relay through its
internal CT that is embedded in each phase.(But, it can’t be used with earth-leakage protection
function at the same time)
Ig
.5
.6
tg
.7
.4
(S)
.4
.8
.3
.3
1
.2
.2
.4
.3
.2
.1
off
.1
ground fault
.05
on 2 off
×In
I t
t
Ig
tg
I
Earth Leakage (G) - Option
The function for breaking earth leakage current above setting value after
time delay to protect the circuit from earth leakage. (A, P, S type)
1. Standard setting current knob: I△n
- Setting range: 0.5-1-2-3-5-10-20-30-Off (A)
2. Time delay setting knob: △t
- Trip time: 140-230-350-800 ms
- Alarm time: 140-230-350-800-950 ms
3. Settings within its alarm range will prevent its breaker from tripping but activating its alarm.
4. This function is enabled and can be used only with private external CT(secondary output 5A)
selected by customers.
5. When ZSI function was set, the protection operation will take place instantaneously with input
absence by downstream devices. It is advised to disable its ZSI function on the last downstream
device.
※Use cautions with earth-leakage current settings
I n
3
t
(ms)
10
800
950
800
20
350
350
1
30
230
230
0.5
140
off
140
earth leakage trip alarm
t
I n
t
I
R S T N
- When using other CT selected by customers, the setting range is from 0.5 to 5A based on its
secondary current.(Secondary output rating : 5A)
Hence, under 100:5A CT, if trip relay is set to 0.5A, earth-leakage exceeding 10A will activate its
operation (0.5A×20 = 10A)
ZCT or External
CT
※Guideline for the external CT usage
- Earth-leakage protection characteristics using the standard CT which is installed inside of ACB can
protect currents from 20 to 100% range on its rated current.
- As rated currents on ACB increases, current that is covered by its standard CT increase as well.
This can not protect against small leakage currents.
ex) 400A ACB Min. Earth-leakage current 400A×20% =80A
4000A ACB Min. Earth-leakage current 4000A×20% =800A
- Therefore, customers are advised to install an external CT in accordance with its rated currents
within its systems. And choose trip relay(E, X type) which is required with external CT usage in
order to provide earth-leakage functions.
5
2
A
ZCT or External
CT
B
35
Trip relays
Measurement function
Measurement
element
Class.
Current
Voltage
Angle
Power
Line current
Ia,Ib,Ic
Normal current
I1
Reverse current
I2
Vab,Vbc,Vca
Va,Vb,Vc
Unbalance
V1
Reverse voltage
V2
Line-to-line
∠VabIa, ∠VabIb, ∠VabIc,
Line-to-current
∠VabVbc, ∠VabVca
V
60~690V
°
0~360°
±1°
∠VaVb,∠VaVc
∠VaIa, ∠VbIb, ∠VcIc
Active power
Pa(ab), Pb(bc), Pc(ca), P
kW
1kW~99,999kW
±3%
Reactive power
Qa(ab), Qb(bc), Qc(ca), Q
kVar
1kVar~99,999kVar
±3%
1kVA~99,999kVA
±3%
1kWh~9999.99MWh
±3%
1kVarh~9999.99MVarh
±3%
1kWh ~9999.99MWh
±3%
Sa(ab), Sb(bc), Sc(ca), S
kVA
WHa(ab), WHb(bc),
kWh
WHc(ca), WH
MWh
VARHa(ab), VARHb(bc),
kVarh
VARHc(ca), VARH
Mvarh
Reverse active
rWHa(ab), rWHb(bc),
kWh
energy
rWHc(ca), rWH
MWh
Frequency
F
Hz
45~65Hz
Power factor(PF)
PFa(ab), PFb(bc), PFc(ca), PF
Unbalance rate
Iunalance, Vunbalance
%
0.0~100.0
Peak demand
kW
1kW~99999kW
Current demand
Peak demand
A
80A~65,535A
Voltage
1st~63th harmonics of
harmonics
Va(ab),Vb(bc),Vc(ca)
V
60~690V
Current harmonics
1st~63th harmonics of Ia,Ib,Ic
A
80A~65,535A
THD, TDD
%
0.0~100.0
K-Factor
-
0.0~100.0
+: Lead, -: Lag
For P and S type Trip relay, separate voltage module is necessary
to measure other element besides current (Seperate purchase is needed)
- Voltage input range: AC 60~690V
Vr Vs Vt Vn
Vr Vs Vt
Voltage
module
3P4W wiring
36
13
14
15
16
17
18
19
20
V1
V2
V3
Vn
1
2
3
4
5
6
7
8
9
10
11
12
±1°
±1°
Voltage module
1
2
3
4
5
6
7
8
9
10
11
12
±1%
Phase-to-phase
demand
Harmonics
80A~65,535A
Phase-to-current
Active power
Demand
Accuracy
±1%
Normal voltage
Reactive energy
Power factor
Display range
A
Line voltage
Active energy
Freq.
Unit
±3%
Phase voltage
Apparent power
Energy
Detailed element
Voltage
module
3P3W wiring
13
14
15
16
17
18
19
20
V1
V2
V3
Vn
Trip relays
Man machine interface
Measurement display
Initial display
1000 A
M
R
S
T
N
Setting display
100%
1. H/W set
2. Relay set
3. Events
1. Wiring
1. OCR
1. Event
2. Comm
2. OCGR
2. Clear All
3. Password
3. OVR/UVR
3. Fault
4. Time-RTC
4. Unbal
4. Clear All
5. PT Ratio
5. rP/OPR
6. Demand
6. OFR/UFR
5. L/R (L)
4. Sys info
50%
Initial display
7. Data Rst
Max Power
Demand
Energy
CB Count
Run Time
8. DO Setup
9. Language
10. Option
An example of graphic LCD display
1000 A
1000 A
R
S
T
R
N
S
T
N
Ir
.7
.8
Ir =
.9
.6
1
100%
50%
.5
100%
.4
1000 A
×In
50%
Ir adjustment
knob
Displayed screen when changing
Ir value into 1.0
(After 3 sec, return to initial display)
Initial display
tg
(S)
.4
.4
Tg =
.3
.3
.2
.1
.2
.1
.05
on 2 off
I t
200 ms
[I2t](Off)
tg adjustment
knob
Displayed screen when changing
tg value into 0.2
(After 3sec, return to initial display)
37
Trip relays
Protection element setting
Initial display
1000 A
R
S
T
Setting display
M
N
100%
50%
PASSWORD
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
XXXX
1.OCR
2.OCGR
3.OVR/UVR
4.Unbal
5.rP/OPR
Password input
Relay setting display
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
Find adjustment of protection setting current
Find adjustment of long-time delay
OCR-L, S, I
I2T
[Off]
800 A
EIT
6400 A
Find adjustment of short-time delay
Find adjustment of Instantaneous
15000 A
OCR-L, S, I
I2T
[Off]
OCR-L, S, I
800 A
EIT
6400 A
I2T
[Off]
800 A
EIT
6400 A
15000 A
1.OCR
2.OCGR
3.OVR/UVR
4.Unbal
5.rP/OPR
15000 A
�
Relay setting
display
38
OVR/UVR Set
Pick Up
Delay
Action
Pick Up
Delay
Action
Protection setting
display
1.OCR
2.OCGR
3.OVR/UVR
4.Unbal
5.rP/OPR
�OCR and OCGR's current
setting is basically controlled by
knob's setting values.
�The fine current that cannot
be controlled by knob is
adjustable by using , key.
�Fine adjustment is only
adjustable in the present knob
and next knob's setting range,
when moving knob, the
adjusted data becomes reset
state.
Select one IDTM characteristic
curve among DT, SIT, VIT and EIT
: 724 V
: 1.2 s
: None
: 150 V
: 1.2 s
: D01
OVR/UVR setting
�
rPower
Pick Up
Delay
Action
Pick Up
Delay
Action
OCR-L, S, I
I2T
[Off]
800 A
EIT
6401 A
15000 A
1.OCR
2.OCGR
3.OVR/UVR
4.Unbal
5.rP/OPR
�
6.OFR/UFR
Relay setting display
Unbal V/I
Pick Up
Delay
Action
Pick Up
Delay
Action
Relay setting display
:100 kW
: 10.0 s
: D02
: 2400 kW
: 0.2 s
: TRIP
Reverse power setting
�The setting method of OCGR
is same with OCR's, fine
adjustment is available.
: 6%
: 10.0 s
: D02
: 12 %
: 10.0 s
: D03
Unbalance setting
�
OFR/UFR Set
Pick Up
Delay
Action
Pick Up
Delay
Action
: 65 Hz
: 10.0 s
: D01
: 55 Hz
: 10.0 s
: None
Frequency setting
Trip relays
Measurement element display
Load current
1000 A
R
S
N
T
100%
50%
��
Measurement
overview
Metering Overview
Demand Current [A]
Max Power [kW]
VR 220
V∠0.0
R :
1000
987
IR
1000
A∠330.0
S :
1000
2007/05/14
P
986
kW
T :
1000
10:00:00
Q
589
kVar
PF 0.866 F 60.0
Max Demand [kW]
986
EP 56
kWh
2007/05/14
EQ 32
kVarh
11:15:00
��
Voltage/Current
vector diagram
Vector Diagram
Vt
It
Vr
Is
Ir
Vs
VOLTGAE [V]
VR :
220∠ 0.0
VS :
220∠240.0
VT :
220∠120.0
V unbal 3Phase
Vpos : 220 V
CURRENT [A]
IR :
1000∠330.0
IS :
1000∠210.0
IT :
1000∠ 90.0
IN :
0
I unbal 3Phase
Active Power [kW]
Apparent [kVA]
R :
328
Total
R :
379
Total
S :
328
986
S :
379
1139
T :
379
Vneg :
0
V
Unbal :
0.0
%
Ipos : 1000
A
Ineg :
0
A
Unbal :
0.0
%
��
Power and
power factor
Power Diagram
P=986
Q=589
T :
328
Reactive [kVar]
kW
1000
kVar 2000
Power Factor
R :
189
Total
R :
0.87
Total
S :
189
589
S :
0.87
0.866
T :
189
T :
0.87
��
Energy
Forward Energy
Forward P [kWh]
Reverse P [kWh]
P+
R :
360
Total
R :
0
Total
S :
360
1080
S :
0
0
Q+
1051 kWh
607 kVarh
T :
Reverse Energy
360
Forward Q [kVarh]
T :
0
Reverse Q [kVarh]
P-
0 kWh
R :
210
Total
R :
0
Total
Q-
S :
210
630
S :
0
0
0 kVarh
T :
210
T :
0
��
Voltage/Current
harmonics
(S type)
Volt Wave & FFT [%]
THD[S] : 25.0
I
R
S
S Volt Harmonics [V]
S Volt Harmonics [V]
S Volt Harmonics [V]
H1
220 H8
0
H15
0 H22
0
H57
0
H2
0 H9
0
H16
0 H23
0
H58
0
H3
55 H10
0
H17
55 H24
0
H59
0
H4
0 H11
0
H18
0 H25
0
H60
0
H5
0 H12
0
H19
0 H26
0
H61
0
H6
0 H13
0
H20
0 H27
0
H62
0
H7
0 H14
0
H21
0 H28
0
H63
0
��
Curr Wave & FFT [%]
THD[R] : 3.0
T
R Curr Harmonics [A]
R Curr Harmonics [A]
TDD 3Phase
H1 1000 H8
0
H15
1 H22
0
H57
0
R :
0.1 %
H2
0 H9
3
H16
0 H23
1
H58
0
S :
0.1 %
H3
15 H10
0
H17
1 H24
0
H59
0
T :
0.1 %
H4
0 H11
1
H18
0 H25
1
H60
0
Current K - Factor
R Curr Harmonics [A]
H5
20 H12
0
H19
1 H26
0
H61
0
R :
1.2
R
H6
0 H13
1
H20
0 H27
1
H62
0
S :
1.2
S
H7
0 H14
0
H21
1 H28
0
H63
0
T :
1.3
39
Trip relays
Characteristics curves
Long-time delay (L)
5000
2000
Ir = 0.4...1 In
1000
500
200
100
50
40
30
tr = 0.5...20s
20
20
12
10
t(s)
8
5
4
3
4
2
2
1
1
0.5
0.4
0.3
0.2
0.1
0.05
× Ir
40
20
10
7
5
4
3
2
1
0.7
0.01
0.5
0.02
Trip relays
5000
2000
1000
500
Isd = 1.5...10 Ir
200
100
50
40
30
20
10
t(s)
5
4
3
2
1
0.4
0.3
0.4
0.2
0.2
I2t ON
0.4
0.3
0.3
0.2
I2t OFF
0.1
0.1
0.1
0.05
0.05
20
10
7
5
4
3
2
1
0.01
0.7
0.02
0.5
Short-time delay (S)
× Ir
41
Trip relays
Characteristics curves
Instantaneous (I)
Ground fault (G)
100
50
40
30
20
Ig = 0.2...1 In
10
5
4
3
2
t(s)
1
I2t ON
0.4
0.4
0.3
0.3
0.2
0.2
0.2
0.1
I2t OFF
0.1
0.1
0.4
0.3
0.05
0.05
Ii = 2...15 In
42
× In
3
2
10
7
4
5
3
2
1
0.7
0.4
0.5
0.3
0.2
0.1
0.07
0.01
0.05
0.02
Trip relays
10000
5000
2000
EIT
1000
500
VIT
200
100
SIT
t(s)
50
20
DT
10
5
2
20
10
7
5
4
3
2
1
0.05
0.7
1
0.5
IDMTL
× Ir
43
Trip relays
Characteristics curves
Pre Trip Alarm
500
200
100
50
40
35
30
20
15
10
5
5
4
3
t(s)
2
1
1
0.4
0.3
0.2
0.1
0.05
× Ip
44
30
20
10
7
5
4
3
2
1
0.7
0.01
0.5
0.02
Trip relays
ZSI - Zone Selective Interlocking (A, P, S type)
Zone-selective interlocking drops delay time that eliminates faults for breakers.
It minimizes the shock that all kinds of electric machineries get under
fault conditions.
1. In case of that short time-delay or ground fault accident occurs at ZSI built in system,
the breaker at accident site sends ZSI signal to halt upstream breaker’s operation.
2. To eliminate a breakdown, trip relay of ACB at accident site activates trip operation
without time delay.
3. The upstream breaker that received ZSI signal adhere to pre-set short time-delay or
ground fault time-delay for protective coordination in the system.
However upstream breaker that did not receive its signal will trip instantaneously.
4. For ordinary ZSI operation, it should arrange operation time accordingly so that downstream
circuit breakers will react before upstream ones under overcurrent/short time delay/
ground fault situations.
5. ZSI connecting line needs to be Max. 3m.
①
Z4
Z3
Z2
Z1
ZSI input
Fault A
②
Z4
Z3
Z2
Z1
ZSI output
ZSI input
Fault B
Z4
Z4
Z4
Z3
Z3
Z3
Z2
Z2
Z2
Z1
Z1
Z1
1) Occurrence of fault A
- Only breaker ① performs instantaneous trip operation.
2) Occurrence of fault B
- Breaker ② performs instantaneous trip operation,
breaker ① performs trip operation after prearranged delay time
- But if breaker ② did not break the fault normally,
breaker ① performs instantaneous trip operation to protect system.
45
Trip relays
Remote reset and digital I/O (A, P, S type)
In case of that ACB operates due to accidents or over current,
Trip relay indicates the information of the accident through the LED and LCD.
Trip relay A, P and S type is possible to perform the remote reset by digital input,
and have 3 DO(Digital output).
1. Methods to reset Trip relay is to push the Reset button on the frontal side and to
use the remote reset.
2. Digital input
- [R11-R22] input: Remote reset
- [Z1-Z2] Input: ZSI input
- [E1-E2] Input: ZCT for earth leakage detection or external CT input
※All DI are dry contact that has 3.3V of recognition voltage. When inputting close by
SSR(Solid State Relay) or open-collector, connect collector(Drain) to R11.
V1
V2
V3
Vn
E1
Z3
Z1
Common
Reset
ZCT
ZSI input
Voltage module
ZSI output
3. Digital output 3a(524, 534, 544-513)
- Fault output: Long/Short time delay, Instantaneous, Ground fault, UVR, OVR, UFR,
OFR, rPower, Vunbal, Iunbal
(Maintains state as Latch form until user pushes reset.)
- General DO: when setting L/R as remote, it is available to control close/open
remotely by using communication.
485+
R11
R22
513
544
534
524
Power supply
R2
R1
485-
Trip
Relay
Digital
Output
LTD
Z2
GTD
Z4
S/I
Trip relay
Long Short Instantaneous Ground Overload OVR UVR rPower Vunbal Iunbal OFR UFR OPR
Alarm
time time
DO1(524)
P, S DO2(534)
type
DO3(544)
●
○
○
○
○
○
○
○
○
○
○
○
○
○
●
●
○
○
○
○
○
○
○
○
○
○
○
○
○
●
○
○
○
○
○
○
○
○
○
DO1(524)
●
×
×
×
A type DO2(534)
×
●
●
×
DO3(544)
×
×
×
●
46
Not available
Note
Programmable
Fixed
Trip relays
Communication
Modbus/RS-485
�Operation mode: Differential
�Distance: Max. 1.2km
�Cable :
General RS-485 shielded twist
2-pair cable
�Baud rate :
9600bps, 19200bps, 38400bps
�Transmission method: Half-Duplex
�Termination: 100Ω
SCADA system
Modbus/RS-485
Profibus-DP
�Profibus-DP module is installed
separately (Option)
�Operation mode: Differential
�Distance: Max. 1.2km
�Cable :
Profibus-DP shielded twist 2-pair cable
�Baud rate: 9600bps~12Mbps
�Transmission method: Half-Duplex
�Termination resistor: 100Ω
�Standard: EN 50170 / DIN 19245
Ethernet/TCP/IP
Area
controller
TCP/IP/Ethernet
TCP/IP
CNC
Profibus-FMS
PC
DCS
PLC
Profibus-DP
Profibus-DP
communication module
(Option)
Profibus-DP
communication
module (Option)
PLC
Modbus/RS-485
47
Trip relays
Event & fault recording (P, S type)
When there are events such as setting change, Info. change, error of self-diagnose,
state change, P and S type record Max. up to 256 information of the events in accordance with
time(ms). In addition, they can record Max. up to 256(up to 10 for A type) information of the faults
such as fault cause, fault phase, fault value and so on in accordance with time(ms).
Event information display
Initial display
Setting display
1000 A
R
S
T
M
N
100%
50%
Password
input
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
1.Event
2.Clear All
3.Fault
4.Clear All
1. Event-L
2007/05/15
20:29:41
Sta Change
10. Event-L
2007/04/15
10:11:24
Cfg Change
Power On
Comm Set up
Fault information display
Initial display
Setting display
1000 A
R
S
T
M
N
100%
50%
Password
input
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
1.Event
2.Clear All
3.Fault
4.Clear All
1. Trip
2007/04/26
08:35:52
OCR-Short
9. Trip
2007/04/11
09:11:32
UVR
Phase T
Phase R
930A
System information
P and S type can indicate information as followings with the information of the ACB.
- Present time: year/month/date/hour/minute/ms
- ACB current ratings
- N-phase current ratings: 100%
- Frequency information: 60Hz / 50Hz
- Closing numbers of breaker: CB ON numbers
- Trip relay operating time: OCR ON time
- ON time of breaker: CB ON time
- F/W ver. information
System information display
Initial display
Setting display
1000 A
R
100%
50%
48
S
T
N
M
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
Password
input
System Info
Date Time
2007/05/15 21:23:30
Rating
1000 A
Ex-Func 4POCGR
Freq
60 Hz
CB ON# 23
Ver-Arm 1.5
System Info
Date Time
2007/05/15 21:23:30
Rating
1000 A
Ex-Func 4POCGR
T-OPER 220 h
T-CB ON 180 h
Ver-Msp 4.01A
OV
Trip relays
System block diagram
R
S
T
N
ACB Trip
ACB
Vcc/+9V/-9V
CN2-1
CN2-11
Filter
Amp.
CN2-3
CN2-13
Signal CT
CN2-5
CN2-15
Vcc
CPU
Output
Power PCB
Ass’y
+5V
+24V
Display
(LED, LCD)
Main PCB
Ass’y
MTD
CN2-6
Output
CN2-8
Main PCB
Ass’y
CN2-7
CN2-16
CN2-14
Setting
part
GND 24
CN2-4
Vcc
Self
power
RY0 (K1)
CN4-2
GTD contact
+24V
GND+24V
Power CT
Main PCB
Ass’y
RY1 (K2)
CN4-4
STD/INST contact
+5V
RY2 (K3)
-5V
CN4-6
LTD contact
CN2-2
CN4-9
SMPS
CN4-10
Power PCB
Ass’y
Trip relay
Additional source
AC/DC 100~250V
DC 24~60V
CN4-8
Common contact
CN1-1
ZSI output+ terminal
CN1-2
ZSI output- terminal
CN1-3
ZSI input+ terminal
CN1-4
ZSI input- terminal
CN1-9
CN1-10
VDM
CN1-11
CN1-12
CN1-5
Remote reset+ terminal
CN1-6
Remote reset- terminal
CN1-7
Earth
CN1-8
CN1-7
Earth leakage+ terminal
Input signal(R phase) CN3-2
Input signal(S phase) CN3-4
CN1-8
Earth leakage- terminal
Input signal(T phase) CN3-6
Input signal(N phase) CN3-8
DC 24V
CN3-5
UTXO
CN3-1
URXO
CN3-3
GND 24V
CN3-7/9
AD GND
CN3-10
Test
Main PCB
Ass’y
Comm.
Power PCB
Ass’y
CN4-1
485+ terminal
CN4-3
485- terminal
49
Accessories
Mounting
Accessories
AH
Standard
●
SHT1 Shunt Coil
M
CS1
Internal
●
54
Motor
●
55
Charge Switch
●
55
CS2
Charge Switch Communication **
○
55
UVT
Under Voltage Trip Device
○
56
Trip Alarm Contact **
○
57
MRB Manual Reset Button **
○
57
RES
○
58
○
58
AL
C
Remote Reset Switch
●
Counter
65
AX
Auxiliary Switch
○
59
TM
Temperature Alarm **
○
74
K1
Key Lock
○
60
K2
Key Interlock Set
○
60
K3
Double Key Lock
○
61
B
On/Off Button lock
○
61
Lifting Hook
○
62
CTD
Condenser Trip Device *
○
62
ATS
Automatic Transfer Switch Controller *
○
63
DC
Dust Cover
○
65
DF
Door Frame
○
68
OT
OCR Tester
○
64
LH
*
* Non UL Listed.
** Separate purchasing is not allowed. Each item should be purchased with the main body.
50
53
Closing Coil
RCS Ready to Close Switch
External
Page
52
○
SHT2 Double Shunt Coil
CC
Option
Accessories
Mounting
Accessories
Page
26
A
A type
○
28
P
P type
○
30
32
S type
○
VM
Voltage Module
○
SBC
Shorting "b" Contact *
○
MI
Mechanical Interlock **
○
67
ST
Safety Shutter
○
68
MIP
Miss Insertion Prevent Device
○
72
MOC Mechanical Operated Cell Switch
○
66
CEL
Cell Switch
○
69
Door Interlock
○
67
Body Supporter
○
70
○
70
DI
BSP
Other
Option
○
S
Cradle
Standard
N type
N
Trip relay
AH
RI
Racking Interlock
PL
Pad Lock/ Position Lock
●
71
UDC UVT Time Delay Controller
○
73
RCO Remote I/O
○
75
PC
Profibus-DP comm. module
○
* Non UL Listed.
** Separate purchasing is not allowed. Each item should be purchased with the main body.
*** Voltage module should be purchased with P/S type trip relay.
**** It is available only when the control block is in the mode of auto-connection.
***** Trip unit P type & S type are under development, coming soon.
51
Accessories
Shunt Coil [SHT1]
�SHT1 is a control device which trips a
circuit breaker from remote place, when
applying voltage continuously or
instantaneously over 200ms to coil
terminals(C1, C2).
Shunt coil 1
�When UVT coil is installed, its location
is changed.
1. Rated voltage and characteristics of Trip coil
Rated voltage [Vn]
DC [V]
AC [V]
Power consumption (VA or W)
Operating voltage range [V]
24~30
-
14 ~ 33
48~60
48
28 ~ 66
100~125
100~125
70 ~ 140
200~250
200~250
140 ~ 280
-
380~480 *
266 ~ 528
Inrush
Steady-state
200
5
Trip time [ms]
Opening
order
Less
40ms
2. Specification of the wire
�Refer to the below table regarding the length and specification of wire when using trip coil with
DC 24~30[V] or DC/AC 48~60[V] of rated voltage.
The maximum wire length
Rated voltage [Vn]
Wire type
Operating
voltage
52
SHT1
C2
Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).
* Non UL Listed.
DC 24~30 [V]
C1
than
DC/AC 48 [V]
#14 AWG
#16 AWG
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
95.7m
61m
457.8m
287.7m
85%
62.5m
38.4m
291.7m
183.2m
* 점선은
The dotted
to
Userline
배선임
be made by the
Wiring Diagram
customer
Wiring Diagram
Accessories
Double Shunt Coil [SHT2]
�SHT2 is a control device which trips a
circuit breaker doubly from the outside.
When SHT1 doesn’t operate normally, it
can trip a circuit breaker safely.
Shunt coil 1
Shunt coil 2
�Shunt coil 1: Install it at existing
location.
�Shunt coil 2: Install it on the right side of
the Shunt coil 1
�It is not available with UVT coil when
installing double shunt coil.
1. Rated voltage and characteristics of Trip coil
Rated voltage [Vn]
DC [V]
AC [V]
Power consumption (VA or W)
Operating voltage range [V]
24~30
-
14 ~ 33
48~60
48
28 ~ 66
100~125
100~125
70 ~ 140
200~250
200~250
140 ~ 280
-
380~480 *
266 ~ 528
Inrush
Steady-state
200
5
Trip time [ms]
Less
Opening
order
C11
than
40ms
SHT2
C12
Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).
* Non UL Listed.
2. Specification of the wire
�Refer to the below table regarding the length and specification of wire when using trip coil with
DC 24~30[V] or DC/AC 48~60[V] of rated voltage.
* The dotted line to
be made by the
customer
Wiring Diagram
The maximum wire length
Rated voltage [Vn]
DC 24~30 [V]
Wire type
Operating
voltage
DC/AC 48 [V]
#14 AWG
#16 AWG
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
95.7m
61m
457.8m
287.7m
85%
62.5m
38.4m
291.7m
183.2m
53
Accessories
Closing Coil [CC]
�It is a control device which closes a
circuit breaker, when the voltage is
applied continuously or instantaneously
over 200ms to the coil terminals
(A1, A2).
Closing coil
1. Rated voltage and characteristics of Closing coil
Rated voltage [Vn]
DC [V]
AC [V]
Power consumption (VA or W)
Operating voltage range [V]
24~30
-
14 ~ 33
48~60
48
28 ~ 66
100~125
100~125
70 ~ 140
200~250
200~250
140 ~ 280
-
380~480 *
266 ~ 528
Inrush
Steady-state
200
5
Close time
[ms]
Less
2. Specification of the wire
�Refer to the below table regarding the length and specification of wire when using trip coil with
DC 24~30[V] or DC/AC 48~60[V] of rated voltage.
The maximum wire length
Rated voltage [Vn]
Operating
voltage
54
CC
A2
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
* Non UL Listed.
** Close time of G frame (3200~5000A) is less than 95ms.
Wire type
A1
than
80ms **
DC 24~30 [V]
Closing
order
DC/AC 48 [V]
#14 AWG
#16 AWG
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
95.7m
61m
457.8m
287.7m
85%
62.5m
38.4m
291.7m
183.2m
* The dotted line to
be made by the
customer
Wiring Diagram
Accessories
Motor [M]
�Charge the closing spring of a
circuit breaker by the external power
source. Without the external power
source, charge manually.
Motor
�Operating voltage range 85%~110%Vn
Gear
Main
axis
Input voltage(V)
Load current(max.)
DC 24~30V AC/DC 48~60V AC/DC 100~130V AC/DC 200~250V
5A
3A
1A
0.5A
Starting current(Max.)
5 times of load current
Load rpm(Motor)
15000 ~ 19000 rpm
Charge time
AC 380V * AC 440~480V *
0.3A
0.3A
Less than 5sec.
Dielectric strength
2kV/min
Using temperature range
-20。
~ 60。
Using humidity range
Max. RH 80% (No dew condensation)
Endurance
15,000 cycle (Load connection, 2 times/min)
Charge switch
10A at 250VAC
* Non UL Listed.
Charge Switch [CS1]
Charge Switch Communication [CS2]
�It is a built-in contact which sends the signal to the outside, when motor charging is
completed. (2a)
�It has a “1a” contact for communication and the other “1a” contact for complete charging.
�When using an extra communication module (Remote I/O), the state of contacts
can be displayed through the network.
Classification
Contactor
Capacity
Standard
Remark
250/125 Vac
10 A
250 Vdc
0.3 A
125 Vdc
0.6 A
48 Vdc
3A
24 Vdc
5A
55
Accessories
Under Voltage Trip device [UVT]
�If the voltage of the main or the control
power is under voltage, UVT which is
installed inside of the breaker breaks
the circuit automatically.
Please connect with UVT time-delay
device in order to present the timedelay function because UVT is
technically instantaneous type.
UVT coil
Shunt coil
�The closing of a circuit breaker is
impossible mechanically or electrically if
control power not supplied to UVT.
To close the circuit breaker, 65~85% of
rated voltage should be applied to both
terminals of UVT coil (D1, D2).
Closing
coil
�When using UVT coil, the double trip
coil can not be used, and the location of
trip coil is changed.
1. Rated voltage and characteristics of UVT coil
Rated voltage [Vn]
DC [V]
AC [V]
24~30
-
48~60
48
100~130
100~130
200~250
200~250
-
380~480
Operating voltage range [V]
Power consumption (VA or W)
Pick up
Drop out
Inrush
Steady-state
0.65~0.85 Vn
0.3~0.6 Vn
200
5
Trip time [ms]
Less
than
50ms
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
2. Specification of the wire
�Refer to the below table regarding the length and specification of wire when using trip coil with
DC 24~30[V] or DC/AC 48~60[V] of rated voltage.
The maximum wire length
Rated voltage [Vn]
DC 24~30 [V]
#16 AWG
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
48.5m
30.5m
233.2m
143.9m
85%
13.4m
8.8m
62.5m
39.3m
Wire type
Operating
voltage
Note) In case of using UVT coil, the location of Shunt coil is changed.
56
DC/AC 48 [V]
#14 AWG
Accessories
Trip Alarm Contact [AL]
�When a circuit breaker is tripped by OCR which operates against the fault current
(Over Current Relay), Trip Alarm switch provides the information regarding the trip of circuit
breaker by sending the electrical signal from the mechanical indicator on front cover of main
circuit breaker or internal auxiliary switch. (Installed at the inside of circuit breaker)
AL1, 1a
AL2, 1a
�When a circuit breaker tripped by fault current, a mechanical trip indicator
(MRB, Manual Reset Button) pops out from the front cover and the switch (AL) which sends
control signal electrically is conducted to output the information occurred from fault circuit
breaker.
�MRB and AL can be operated only when tripping by OCR,
but doesn’t be operated by Off button and OFF operation of trip coil.
�To re-close a circuit breaker after a trip, press MRB to reset it for closing.
�2pcs of electrical trip switch (AL1, AL2, 1a) are provided (Option)
�Trip alarm contact and MRB(Manual reset bottom) need to be purchased together.
1. Electrical characteristics of trip alarm contact
Classification
Contactor
Capacity
Standard
Remark
250/125 Vac
10 A
250 Vdc
0.3 A
125 Vdc
0.6 A
48 Vdc
3A
24 Vdc
5A
Manual Reset Button [MRB]
�It is a function which resets a circuit
breaker manually when a circuit breaker is tripped by OCR.
�When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset
Button) pops out from the front cover and the switch(AL) which sends control signal electrically is
conducted to output the information occurred from fault circuit breaker.
�MRB can be operated only by OCR but not by OFF operation of circuit breaker. To re-close a
circuit breaker after a trip, press MRB to reset it for closing.
Manual
reset button
MRB reset lever
Manual reset button
Note) The manual reset button is protruded in the event of trip.
57
Accessories
Remote Reset Switch [RES]
�Following tripping, this function resets the "fault trip" alarm contacts(AL) and the mechanical
indicator(MRB) and enables circuit breaker closing.
Push button switch : AC 125V 10A, AC 250V 6A, DC 110V 2.2A, DC 220V 1.1A Resistive load
�In case of auto reset type circuit breaker
Following tripping, a reset of Manual Reset Button(MRB) or Remote Reset Switch(RES) is
no longer required to enable circuit breaker closing.
The mechanical indicator(MRB) and electrical indicator(AL) remain in fault position until the reset
button is pressed.
�AL2 and RES are alternative.
1. Rated voltage and rated current of RES
Rated voltage
Operating current(Max.)
AC/DC 100~130V
AC/DC 200~250V
AC
6A
DC
5A
AC
3A
DC
2.5A
Operating time
Wire spec.
#14 AWG (2.08 mm2)
Less 40ms
#16 AWG (1.31 mm )
2
Reset
order
183
Connect to inner
micro switch
RES
184
Connect to
AL2 / RES
* The dotted line to
be made by the
customer
Wiring Diagram
Ready to Close Switch [RCS]
�It interlocks with mechanism of circuit
breaker.
�It indicates the status that the circuit
breaker is ready to do closing operation.
�When mechanism is in OFF position or
in Charge, contact is output with “ON”
and it indicates that mechanism can be
closed.
Classification
Standard
Ready to
close switch
Remark
250/125 Vac 10 A
Contactor
Capacity
58
250 Vdc
0.3 A
125 Vdc
0.6 A
48 Vdc
3A
24 Vdc
5A
“A” contact
Contact part
Accessories
Auxiliary switch [AX]
�It is a contact used to monitor
ON/OFF position of ACB from
remote place.
AUX. contact & charging types
AX
Standard OFF charge 3a3b
AC
Standard ON charge 3a3b
BX
Standard OFF charge 5a5b
BC
Standard ON charge 5a5b
HX
High capacity OFF charge 5a5b
HC
High capacity ON charge 5a5b
Standard
CC
Standard ON charge 6a6b
JC
High capacity ON Charge 6a6b
High capacity
Standard classification
Standard
2000, 5000AF
High capacity
4000, 6300AF
Classification
Standard
Contactor Capacity
No. of Contact
that can be used
2000, 5000AF
4000, 6300AF
High capacity
250/125 Vac
10 A
250/125 Vac
10 A
250 Vdc
0.3 A
250 Vdc
3A
125 Vdc
0.6 A
125 Vdc
5A
48 Vdc
3A
48 Vdc
10 A
24 Vdc
5A
24 Vdc
10 A
AX
3a3b
-
BX
5a5b
-
HX
-
5a5b
AC
3a3b
-
BC
5a5b
-
CC
6a6b
-
HC
-
5a5b
JC
-
6a6b
Remark
Standard
charging
type
Rapid autoreclosing
charging type
59
Accessories
Key Lock [K1]
�It is a device for locking which
prevents a certain circuit breaker from
being operated by user‘s discretion
when two or more circuit breakers are
used at the same time.
�K1: Preventing mechanical closing
K1
Key Interlock Set [K2]
�3 circuit breakers can be arranged for the continuous
power supply to the load side and be interlocked
mutually by using Key Lock embedded in each circuit
breaker.
ACB-1
ACB-2
ACB-3
●
●
●
Wiring
Status
LOAD1
LOAD2
●
OFF
OFF
○
○
ON
ON
○
●
○
ON
ON
○
○
●
ON
ON
●
●
○
OFF
OFF
●
○
●
OFF
ON
○
●
●
ON
OFF
ACB1
ACB2
○: Release ●: Lock
ACB3
Load 1
60
Load 2
Accessories
Double Key Lock [K3]
�When only two keys are released at the
same time, circuit breakers operate.
Handling method is same as K1.
Key interlock double
ON/OFF Button Lock [B]
�It is to prevent manual operation of
ACB’s closing/tripping button due to
user’s wrong handling.
�It is not possible to handle ON/OFF
operation under the
“Button lock” status.
Note) Padlocks(∅5 ~ ∅6) are not supplied.
ON/OFF button lock
61
Accessories
Lifting Hook [LH]
�It is a device to
make an ACB easy to shift.
�Please hang it to both handles
of the arc cover.
Condenser Trip Device [CTD]
Ratings
�It gets a circuit breaker tripped
electrically within regular time when
control power supply is broken down and
is used with Shunt coil, SHT. In case
there is no DC power, It can be used as
the rectifier which supplies DC power to
a circuit breaker by rectifying AC power.
External dimension
131
118
Ratings
Specification
Model
CTD-100
Rated input voltage (V)
AC 100/110
CTD-200
AC 200/220
㎐)
Frequency (㎐
50/60
50/60
Rated charge voltage (V)
140/155
280/310
Charging time
Within 5S
Within 5S
Trip possible time
Over 3 min.
Over 2 min.
Range of Input voltage (%)
85~110
85~111
Condenser capacity
㎌
400㎌
㎌
160㎌
Circuit diagram
7.5
15
AC input
108
75
75
Side view
* Non UL Listed.
Rear view
62
Front view
DC output
Accessories
Automatic Transfer Switch Controller [ATS]
Ratings
Model type
ATSC-110
ATSC-220
Rated voltage
AC 110V
AC 220V
Voltage range
AC 93.5(±5%) ~126.5V(±5%)
AC 187(±5%) ~ 253V(±5%)
Frequency
50Hz/60Hz
Power consumption (apparent power)
15.4W
4-location switch (stop, N, R, Auto)
�
�
Test function
�
�
Generator control function
�
�
N power source setting (phase-to-phase/ 3phases)
�
�
Time setting (T1~T6)
�
�
Fault function (OCR/Circuit breaker trouble)
�
�
Output contact (Auto, Load burden)
�
�
-
-
Communication function (RS-485)
�T1: The delayed time from when UN (power supply of electric company) is tripped to when
generator start-up signal contact is closed. (t1: 0.2, 0.5, 1, 2, 4, 8, 15, 30, 40, 50secs)
�T2: The delayed time from when UN is closed to when ACB2 is tripped.
(t2: 0.2, 1, 2, 4, 8, 15, 30, 60, 120, 240secs)
�T3: The delayed time from when ACB1 is tripped to when ACB2 is closed.
(t3: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs)
�T4: The delayed time from when ACB2 is tripped to when ACB1 is closed.
(t4: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs)
�T5: The delayed time when ACB1 is closed to when generator start-up signal contact is
opened. (t5: 60, 120, 180, 240, 300, 360, 420, 480, 540, 600secs)
�Stop-mode: This mode is for compulsory trip of ACB1(electric power company) or
ACB2 (power station) when UN (power supply of electric power company) or UR (power supply
of power station) is available
*UN or UR should be kept in ON position
�N-mode: This mode is for compulsory closing of ACB1 when UN is available.
* it does not matter to be ON or OFF position of UR and if converting to N-mode while using UR,
generator start-up signal contact is opened.
�R-mode: This mode is for compulsory closing of ACB2 during the use of UR regardless of that
UN is available or not.
�Auto-mode: This mode is for transferring a circuit breaker automatically to available power
supply of UN or UR. In short, it trips the circuit breaker where power supply is not available and it
close the circuit breaker where power supply is available.
* Non UL Listed.
63
Accessories
OCR Tester [OT]
�It is a device which can test for the
operation of Trip Relay under no power
condition.
1. Maximum 17 times rated current
can be inputted.
2. It is possible to enter the current value
and phase on each of R/S/T/N
3. Frequency is adjustable.
4. It is available to test for long time
delay/short time delay/instantaneous
/ground fault.
OCR tester
Configuration
R
S
T
N
R, S, T, N phase signal input
Increase/Decrease signal input
ENT.
ESC
START
STOP
Signal setting/Delete
Waveform generation/Stop
50Hz 60Hz
Hz
* Non UL Listed.
64
Select frequency
Accessories
Dust Cover [DC]
�Attach it to the door frame.
�It protects the product against the dust
(IP5X) which may cause fault operation
and enhances the sealing degree by
being mounted to protrude type of
panel.
�It is transparent so that the front side of
ACB is visible and the Cover can be
opened/closed even if ACB is drawn out
to until TEST position.
Panel
door
Dust cover
Door frame
Counter [C]
�It displays the total number of ON/OFF
operation of ACB.
Counter
65
Accessories
Mechanical Operated Cell Switch [MOC]
a1 a2
a3
a4 a5
b1 b2
b3 b4
b5
a1 a2
a3
a4 a5
b1 b2
b3 b4
b5
13 23
33
43 53
11 21
31 41 51
13 23
33
43 53
11 21
31 41 51
14 24
34
44 54
12 22
32 42 52
14 24
34
44 54
12 22
32 42 52
AUX S/W
AUX S/W
�It is the contact (10a10b) which displays the ON/OFF condition of ACB.
It mechanically operates only when the breaker is “CONNECTED” position.
A standard type and a high capacity type is available.
�The contact capacity is as same as the ratings of aux. contacts.
�When MOC link is installed to cradle, MOC can be equipped with the inside of panel.
66
Accessories
Mechanical Interlock [MI]
�It is used to interlock closing and trip between two or three breakers mechanically
so as to prevent unintended operation at the same time.
�Wire type interlock can be applied upto 3 breakers
Door Interlock [DI]
�It is a safety device which
does not allow the panel
door to open when a
circuit breaker is in the
“ON” position.
Install on the door of panel
Install on the side plate of
ACB cradle
67
Accessories
Safety Shutter [ST]
�It is the automatic safety device to
protect the connectors of main circuit by
cutting off dangerous contact from
outside while the breaker is drawn out.
When the ACB is drawn in, the shutter is
automatically opened.
�There are 4 types of Safety Shutter and
they are divided as shown in figure below.
The types of safety shutter plate
1600AF, 3P
1600AF, 4P
3200AF, 3P
3200AF, 4P
Safety shutter
5000AF, 4P
5000AF, 4P
Door Frame [DF]
�When structuring the embedded type of
ACB panel, it protects the protrude front
of ACB and the cutting side of
panel door by attaching it to the panel
door.
Fixed type
Door frame
Panel door
Draw-out type
68
Accessories
Cell Switch [CEL]
�It is a contact which indicates the
present position of ACB.(CONNECTED,
TEST, DISCONNECTED)
Cell switch
<Contact configuration>
4C: 1Disconnected +1Test +2Connected
※ Contact configuration can be changeable if necessary.
ACB position
Draw-in and draw-out position
DISCONNECTED
DISCONNECTED
CONNECTED
TEST
CONNECTED
ON
CL-C
(Connected)
Contact
OFF
CL-T
operation
(Test)
ON
OFF
ON
CL-D
OFF
(Disconnected)
Classification
Standard
250/125 Vac
10 A
Contact
250 Vdc
0.3 A
capacity
125 Vdc
0.6 A
48 Vdc
3A
24 Vdc
Contact number
5A
4C
69
Accessories
Body Supporter [BSP]
�It interlocks the main body of circuit
breaker and cradle mechanically to fix
the former in connected position.
Therefore, all draw-in/outs are not
available.
Body supporter
* Non UL Listed.
Racking Interlock [RI]
Door plate
Handle inserting hole
Racking interlock
�When panel door is opened, Draw in/out handle doesn’t be inserted.
Thus, panel handle can be inserted only when panel door is closed.
70
Accessories
Pad Lock / Position Lock [PL]
Draw-in button
Pad lock
ACB is subject to restriction regarding moving in connected, test, disconnected when drawing in or
out. If main body of ACB is placed in 3 positions, it is locked and stopped when drawing in or out.
�As shown in the figure, if draw-in/out button pops out, it means locking is operating.
�To continue Draw-in/out operation, release lock by pushing Draw-in/out button
�In case it is locked as shown in the figure above, main body of ACB can not be drawn in or
out into the cradle.
�For the lock device, user has to purchase it. (∅5 ~ ∅6)
71
Accessories
Miss Insertion Prevent Device [MIP]
C
E
G
1
2
A
B
3
4
D
5
6
F
7
Cradle
ACB body
�When the main body of ACB is inserted to the cradle, if the ratings of ACB does not match with
cradle, it mechanically prevents ACB from being inserted into cradle of ACB.
�The installation method is variable according to ratings.
72
Cradle
ACB
ABCD
567
ABCE
467
ABCF
457
ABCG
Cradle
ACB
Cradle
ACB
Cradle
ACB
ADEF
237
ABEG
346
BCEG
146
ADEG
236
ABFG
345
BDEF
137
ADFG
235
ACDE
267
BDEG
136
456
AEFG
234
ACDF
257
BDFG
135
ABDE
367
BCDE
167
ACDG
256
CDEF
127
ABDF
357
BCDF
157
ACEF
247
CDEG
126
ABDG
356
BCDG
156
ACEG
246
CEFG
124
ABEF
347
BCEF
147
ACFG
245
DEFG
123
Accessories
UVT Time Delay Controller [UDC]
�UVT is a device which makes ACB
tripped automatically to prevent the
accident on load side due to under
voltage or power breakdown.
There are two types, Instantaneous
type and time delay type.
�It can be installed on the rail or to the
cradle.
�Instantaneous type: only available with
UVT coil.
�Time delay type: available by
connecting UVT coil and UVT time
delay controller.
�Common use for the all types.
UVT time delay controller
1. The rated voltage and characteristic of UVT time delay controller
Rated voltage [Vn]
DC [V]
Operating voltage range [V]
AC [V]
48~60
48
100~130
100~130
200~250
200~250
-
380~480
Power consumption (VA or W)
Pick up
Drop out
Inrush
Steady-state
0.65~0.85 Vn
0.4~0.6 5Vn
200
5
Trip time[s]
0.5, 1,
1.5, 3
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
2. Wiring
1. Wiring for general type
2. Wiring for special type
Rated
voltage
(Vn)
Rated
voltage
(Vn)
Delay trip
function
5
7
5
7
14
16
14
16
D2
Instantaneous
trip
function
D1
D2
D1
ACB
ACB
Rated
voltage
(Vn)
Rated
voltage
(Vn)
* The wiring presented with red color should be set by uesers.
73
Accessories
Temperature Alarm [TM]
�Temperature Alarm Unit is a device to
show the temperature through a
sensor inside of ACB.
Temperature
alarm
�The temperature sensor can be
installed up to 2 and the output is
connected to control terminal blocks.
�It displays the maximum temperature
of them and transmits through a
network.
�If the temperature is higher than a
standard, an alarm can occur.
�Temperature alarm unit
communicates with Modbus /
RS-485 basically, Profibus-DP need
to be purchased separately.
�Temperature alarm unit is installed
on the cradle or the inside of panel.
Control power
AC/DC 110/220V
1
2
Power
24V
24V GND
5V
5V GND
13
14
15
3
16
4
5
Relay 3
DO control
17
18
6
Temperature alarm
Temperature Alarm(+)
Temperature Alarm(-)
7
Temp. Sensor input 1
8
9
RS-485(-)
19
10
RS-485(+)
20
Temp. Sensor input 2
Temp. Sensor input 3
Temp. Sensor input 4
Temp_COM
11
12
Temperature LED(℃): 10 ~150℃,
Warning
(Indicates the maximum value)
74
*
RS-485
MODBUS
Profibus-DP
*In case of using
Profibus-DP communication,
it needs to communicate with
ACB trip relay.
Accessories
Remote I/O Unit [RCO]
Control Power
AC/DC 110/220V
1
Power
2
CB ON
3
CB OFF
4
General DI 1
24V
24V GND
5V
5V GND
Relay 0
CB close
13
14
CB ON(+)
CB ON(-)
15
Relay 1
CB open
CB OFF(+)
16
CB OFF(-)
Remote I/O Unit
5
General DI 2
6
DI_COM
7
8
RS-485(-)
19
RS-485(+)
20
9
10
11
RS-485
12
Alarm
MODBUS
Profibus-DP
*In case of using
Profibus-DP communication,
it needs to communicate with
ACB trip relay.
Classification
CB control
*
Applied range
Contact switching capacity
Remarks
AC230V 16A / DC30V 16A
Max. switching capacity
3680VA, 480W
Contact switching capacity
AC230V 6A / DC25V 6A
Max. switching capacity
1880VA, 150W
Induction load
(cos∅=0.4, L/R=7ms)
�Remote I/O unit has the I/O contact which can
trip or close the ACB from the remote site by
communication.
�For the General DO, the output of DI1 or DI2 is
selectable.
�Remote I/O Unit communicates with Modbus /
RS-485 communication basically, Profibus-DP
need to be purchased separately.
�It supports SBO (Select Before Operation)
function and guarantees the control reliability.
�Remote I/O Unit can be installed on the cradle
of ACB or the inside of panel.
- Baud rate setting
- Comm. address setting
- Temperature setting
LED
1
Status
DI1
Indicates digital Input #1condition
2
DI2
Indicates digital Input #2condition
3
DO ON
Indicates temperature alarm output is ON
4
DO OFF
Indicates temperature alarm output is OFF
5
CB ON
Indicates circuit break close condition
6
CB OFF
Indicates circuit break open condition
7
RUN LED
8
CB ERROR
Indicates unit run condition
Indicates circuit break terminal
Disconnection / control Err condition
75
Electrical diagram
V2
V3
VN
E1
Z3
Z1
485+
R11
R22
513
R2
R1
251
83
183
/RES(+)
Trip relay
D1
C11
ON
OFF
Power supply
OFF
Common
Reset
ZCT
V1
ZSI Input
Voltage module
ZSI Output
This diagram is based on “CONNECTED” position of a circuit breaker and Opening, Motor charging, Releasing of locking plate
should be normal condition.
C1
UVT SHT2 SHT1
A1
CC
485-
544
534
524
LTD
Z2
252
Digital trip relay
84
184
/RES(-)
D2
C12
Ready to close
Secondary
trip coil
Terminal code description
13
14 ~ 63
64
Auxiliary switch “a”
D1
D2
Voltage input terminal of UVT
11
12 ~ 61
62
84
Alarm1 “a”
Auxiliary switch “b”
83
413 414
Charged signal
183 184
Alarm2 “a”
423 424
Charged signal communication
251 252
Ready to close switch
U1
U2
Motor charging
R1
Control power
A1
A2
Closing coil
513 ~ 544
Alarm contact
C1
C2
Shunt trip
R11 R22
Alarm reset (Trip cause LED, Alarm contact)
2nd shunt trip
485+ 485-
RS-485 communication
C11 C12
R2
Note) 1. The diagram is shown with circuits de-energized, all devices open, connected and charged and relays in normal position
2. Relay is normal condition and charging type is "ON-Charging"
3. The standard of auxiliary contact is 3a3b. The auxiliary switch in above diagram is composed of 5a5b. See 48 page for more detail on auxiliary switches.
4. Option
- Ready to close contact, Trip alarm contact, UVT coil, Fully charged contact, secondary trip coil
- Cell switch, Temperature module, Voltage module, Remote close-open module, ZCT, ZSI
5. Please consult us for the use of ZSI (Zone selective Interlocking).
6. Refer to the page 33 for the connection of Trip relay and the page 43 for UVT.
7. For connecting RS-485 verify if the polarity is correct
76
C2
A2
Electric operatio
circuit
Fault trip
UVT
Main circuit
Z4
STD/Inst
E2
GTD
or
n
Temperature
Module
41
31
21
11
53
43
33
23
13
T1
TC1
TC2
341
331
321
311
Temperature
Sensor-2
CL
Axa
Axa
Axa
Axa
Axa
Axb
Axb
Axb
Axb
Axb
Temperature
Sensor-1
T2
CL
51
CL
423
CL
413
Axb
U1
52
42
32
22
12
54
44
34
24
Charge
completion
contact
14
342
344
332
334
322
324
312
314
ON
424
OFF
414
Charged
U2
Charged
M
Thermal,
communication
remote control module
Auxiliary switch
Cell switch
Accessory code description
ZSI input
Z1
Z2
Z3
Z4
ZSI output
E1
E2
ZCT
VN ~ V3
TC1 , TC2 ~ T1
311 ~ 344
Voltage module
,
T2
Temperature module
Position switch
Ax
LTD
STD/Inst
GTD
CL
M
Auxiliary switch
Internal wiring
Long time delay trip indicator
External wiring
(by customer)
Short time delay/instantaneous
Ground fault trip indicator
Cell switch
Motor
CC
Closing coil
SHT1
Shunt tripping device 1
SHT2
Shunt tripping device 2
UVT
UVT coil
Connector of the control
circuit terminal of
drawout type
77
Dimensions
Fixed type 800~1600A
(UAS-08/16D)
Side view
15.16
(385)
11.81
(300)
11.02
(280)
11.02
(280)
5.51
(140)
5.51
(140)
Operating panel center
10.63
(270)
12.6
(320)
2.56
(65)
0.47
(12)
9.84
(250)
6.50
(165)
17.28
(439)
13.94
(354)
3P
1.46
(37)
4P
Vertical-con
Vertical
Operating panel center
Operating panel center
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Earthing Hole)
Ø0.55(Ø14)
(Earthing Hole)
3.15
(80)
3.35
(85)
3.15
(80)
6.50
(165)
3.35
(85)
6.50
(165)
Back view
6.50
(165)
Side view
0.49
(12.5)
1.97
(50)
0.98
(25)
5.24
(133)
3.62
(92)
78
0.79
(20)
12.99
(330)
1.65
(42)
11.81
(300)
Ø0.55
(Ø14)
13.94
(353.6)
0.59
(15)
3.35
(85)
1.91
(48.5)
13.52
(343.5)
4.88
(124)
0.98
(25)
0.59
(15)
3.35
(85)
6.50
(165)
3.19
(81)
0.98
(25)
6.99
(177.5)
6.99
(177.5)
2.34
(59.5)
2.34
(59.5)
Vertical
type_3P
0.79
(20)
0.79
(20)
6.50
(165)
6.50
(165)
0.47
(12)
1.38
(35)
2.64
(67)
10.63
(270)
10.63
(270)
11.81
(300)
12.60
(320)
Operating panel center
5.24
(133)
Front view
11.81
(300)
12.60
(320)
Front view
6.5
(165)
13.52
(343.5)
2.83
(72)
3.35
(85)
Dimensions
Vertical-con
Vertical
Operating panel center
Operating panel center
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Earthing Hole)
Ø0.55(Ø14)
(Earthing Hole)
2.34
(59.5)
Ø0.55(Ø14)
(Mounting Hole)
3.15
(80)
3.35
(85)
3.35
(85)
3.35
(85)
6.50
(165)
4.88
(124)
0.98
(25)
3.91
(81)
0.98
(25)
6.99
(177.5)
6.99
(177.5)
2.34
(59.5)
Vertical
type_4P
0.59
(15)
3.15
(80)
9.84
(250)
3.35
(85)
3.35
(85)
6.50
(165)
Back view
3.35
(85)
0.59
(15)
9.84
(250)
Side view
0.49
(12.5)
1.97
(50)
0.98
(25)
5.24
(133)
3.62
(92)
1.91
(48.5)
0.79
(20)
16.34
(415)
3.62
(42)
11.83
(300)
Ø0.55
(Ø14)
13.52
(343.5)
17.28
(438.6)
Horizontal-con
Horizontal
Operating panel center
Operating panel center
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Earthing Hole)
Ø0.55(Ø14)
(Earthing Hole)
3.35
(85)
2.66
(67.5)
6.50
(165)
1.77
(45)
Ø0.55(Ø14)
3.15
(80)
6.50
(165)
3.35
(85)
6.99
(177.5)
3.35
(85)
6.50
(165)
6.50
(165)
Side view
5.24
(133)
2.64
(67)
11.81
(300)
0.59
(15)
Back view
4.88
(124)
0.98
(25)
1.75
(44.5)
Ø0.55
(Ø14)
0.49
(12.5)
0.98
(25)
3.35
(85)
0.75
(19)
3.19
(81)
6.99
(177.5)
59.5
(2.34)
2.34
(59.5)
0.98
(25)
1.97
(50)
12.99
(330)
13.94
(353.6)
0.79
(20)
Horizontal
type_3P
1.91
(48.5)
13.52
(343.5)
79
Dimensions
Fixed type 800~1600A
(UAS-08/16D)
Operating panel center
Ø0.55(Ø14)
(Mounting Hole)
Horizontal-con
Operating panel center
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Earthing Hole)
Ø0.55(Ø14)
(Earthing Hole)
6.99
(177.5)
2.34
(59.5)
0.98
(25)
6.99
(177.5)
3.19
(81)
0.98
(25)
2.66
(67.5)
3.35
(85)
3.35
(85)
3.35
(85)
6.50
(165)
1.75
(44.5)
Ø0.55
(Ø14)
Ø0.55
(Ø14)
1.77
(45)
3.15
(80)
9.84
(250)
3.35
(85)
3.35
(85)
6.50
(165)
3.35
(85)
9.84
(250)
Side view
5.24
(133)
2.64
(67)
11.81
(300)
0.59
(15)
Back view
0.75
(19)
0.98
(25)
0.49
(12.5)
1.97
(50)
4.88
(124)
Horizontal
2.34
(59.5)
Horizontal
type_4P
0.79
(20)
16.34
(415)
1.91
(48.5)
13.52
(343.5)
17.28
(438.6)
Top view
Operating panel center
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Earthing Hole)
Ø0.55(Ø14)
(Earthing Hole)
2.34
(59.5)
0.98
(25)
6.99
(177.5)
6.50
(165)
6.50
(165)
3P
6.50
(165)
9.84
(250)
4P
7.97
(202.5)
19.90
(505.5)
9.21
(234)
Side view
0.98
(25)
80
1.50
(38)
1.50
(38)
0.98
(25)
3.15
(80)
3.15
(80)
11.83
(300.5)
6.99
(177.5)
Operating panel center
2.34
(59.5)
Front
connection
type
Dimensions
Draw-out type 800~1600A
(UAS-08/16D)
Front view
Operating panel center
Operating panel center
5.51 (140)
5.51 (140)
2.56
(65)
2.56
(65)
10.63 (270)
16.93 (430)
8.46(215)
10.63 (270)
5.51 (140)
10.24(260)
3.35(85)
10.24(260)
13.15(334)
16.50(419)
3P
4P
Vertical-con
Bottom view
1.77
(45)
3.35
(85)
1.77
(45)
3.35
(85)
3.35
(85)
3.35
(85)
0.59
(15)
3.94
(100)
3.94
(100)
3.94
(100)
7.76
(197.3)
9.45
(240.3)
0.59
(15)
3.94
(100)
10.24
(260)
10.24
(260)
Ø0.51(Ø13)
(Mounting Hole)
Back view
Ø0.51(Ø13)
(Mounting Hole)
Side view
0.49
(12.5)
13.14
(334)
16.93
(430)
0.99
(25)
2.83
(72)
5.23
(133)
1.97
(50)
Ø0.55(Ø14)
4.80
(122)
Vertical
type_3P
16.93 (430)
Front view
23.82
(60.5)
18.39
(467.3)
81
Dimensions
Draw-out type 800~1600A
(UAS-08/16D)
Bottom view
Vertical-con
3.35
(85)
3.35
(85)
3.35
(85)
0.59
(15)
1.77
(45)
3.35
(85)
3.35
(85)
3.35
(85)
0.59
(15)
9.45
(240.3)
1.77
(45)
3.93
(100)
3.94
(100)
3.93
(100)
3.94
(100)
7.76
(197.3)
Vertical
type_4P
13.59
(345)
13.58
(345)
Ø0.51(Ø13)
(Mounting Hole)
Back view
Ø0.51(Ø13)
(Mounting Hole)
Side view
0.49
(12.5)
16.92
(430)
2.83
(72)
4.80
(122)
5.23
(133)
1.97
(50)
0.98
(25)
Ø0.55(Ø14)
23.82
(60.5)
16.50
(419)
Horizontal
type_3P
Bottom view
1.28
(32.5)
18.39
(467.3)
Vertical-con
3.35
(85)
1.97
(50)
3.35
(85)
1.77
(45)
0.98
(25)
3.35
(85)
3.35
(85)
1.77
(45)
Ø0.55(Ø14)
9.45
(240.3)
0.75
(19)
3.94
(100)
0.49
(12.5)
7.76
(197.3)
3.94
(100)
3.94
(100)
3.94
(100)
10.24
(260)
1.77
(44.5)
Ø0.55(Ø14)
10.24
(260)
Ø0.51(Ø13)
(Mounting Hole)
Side view
3.82
(97)
5.24
(133)
16.93
(430)
0.59
(15)
Back view
Ø0.51(Ø13)
(Mounting Hole)
13.15
(334)
82
23.82
(60.5)
18.39
(467.3)
Dimensions
Vertical-con
3.35
(85)
3.35
(85)
3.35
(85)
1.28
(32.5)
3.35
(85)
1.77
(45)
1.97
(50)
0.98
(25)
3.35
(85)
1.77
(45)
Ø0.55(Ø14)
Ø0.55(Ø14)
3.35
(85)
0.75
(19)
Botttom view
9.45
(240.3)
3.94
(100)
7.76
(197.3)
3.94
(100)
3.94
(100)
3.94
(100)
0.49
(12.5)
1.75
(44.5)
Horizontal
type_4P
13.58
(345)
13.58
(345)
Ø0.51(Ø13)
(Mounting Hole)
Side view
3.81
(97)
5.23
(133)
16.93
(430)
0.60
(15)
Back view
Ø0.51(Ø13)
(Mounting Hole)
16.50
(419)
18.39
(467.3)
Bottom view
1.77(45)
3.94
(100)
3.94
(100)
3.94
(100)
3.94
(100)
6.38
(162)
6.38
(162.3)
1.77(45)
10.24(260)
13.58(345)
Ø0.51(Ø13)
(Mounting Hole)
3P
4P
Ø0.51(Ø13)
(Mounting Hole)
Side view
0.98
(25)
1.77
(45)
3.35
(85)
2.89
(73.5)
1.63
(41.5)
Ø0.55(Ø14)
7.97
(202.5)
19.90
(505.5)
16.93
(430)
9.21
(234)
1.26
(32)
Back view
1.26
(32)
Front
connection
type
23.82
(60.5)
0.98
(25)
2.26
(57.5)
17.00
(432.3)
3.35
(85)
13.15(334)
83
Dimensions
Fixed type 800~2000A
(UAH-08~20E)
19.41
(493)
11.97
(304)
0.47
(12)
17.01
(432)
0.47
(12)
3P
8.03
(204)
21.54
(547)
10.63
(270)
1.38
(35)
12.56
(319)
0.47
(12)
1.91
(56.5)
4P
2.83
(72)
13.52
(343.5)
Side view
Top view
Operating panel center
Operating panel center
Ø0.55 (Ø14)
6.99
(177.5)
0.98
(25)
6.99
(177.5)
3.19
(81)
0.98
(25)
2.34
(59.5)
2.34
(59.5)
Ø0.55 (Ø14)
3.50
(89)
0.79
(20)
4.53
(115)
4.53
(115)
8.03
(204)
8.03
(204)
3P
0.75
(19)
1.16
(29.5)
4.11
(104.5)
2.95
(75)
1.75
(44.5)
Ø0.55 (Ø14)
5.24
(133)
4.53
(115)
4.53
(115)
8.03
(204)
1.91
(48.5)
13.52
(343.5)
4.53
(115)
12.56
(319)
4P
Side view
84
3.50
(89)
0.75
(20)
3.19
(81)
Vertical
type
10.63
(270)
11.81
(300)
0.79
(20)
8.03
(204)
10.63
(270)
12.60
(320)
8.03
(204)
0.47
(12)
1.38
(35)
0.79
(20)
11.81
(300)
Operating panel center
0.59
(15)
7.44
(189)
11.02
(280)
Operating panel center
11.02
(280)
0.79
(20)
7.44
(189)
12.60
(320)
14.88
(378)
7.44
(189)
1.38
(35)
Front view
Dimensions
Top view
Operating panel center
Operating panel center
Ø0.55 (Ø14)
2.64
(67)
1.75
(44.5)
2.95
(75)
4.53
(115)
4.53
(115)
8.03
(204)
1.75
(44.5)
2.95
(75)
Ø0.55 (Ø14)
2.64
(67)
8.03
(204)
4.53
(115)
4.53
(115)
4.53
(115)
8.03
(204)
3P
6.99
(177.5)
2.34
(59.5)
0.75
(19)
0.98
(25)
6.99
(177.5)
0.75
(19)
3.19
(81)
0.98
(25)
2.34
(59.5)
Ø0.55 (Ø14)
3.19
(81)
Horizontal
type
Ø0.55 (Ø14)
12.56
(319)
4P
2.64
(67)
5.26
(133.5)
0.79
(20)
Side view
1.91
(48.5)
Top view
Operating panel center
Operating panel center
Ø0.55(Ø14)
3.50
(89)
4.53
(115)
8.03
(204)
6.99
(177.5)
0.98
(25)
1.50
(38)
0.98
(25)
1.50
(38)
6.99
(177.5)
2.34
(59.5)
2.34
(59.5)
Ø0.55(Ø14)
3.50
(89)
8.03
(204)
3P
12.56
(319)
8.03
(204)
4P
19.92
(506)
9.21
(234)
Side view
7.97
(202.5)
Front
connection
type
13.19
(343.5)
0.98
(25)
11.83
(300.5)
85
Dimensions
Fixed type 2500A
(UAH-25E)
Vertical
type
Top view
Operating panel center
Operating panel center
Ø0.55(Ø14)
3.50
(89)
0.79
(20)
4.53
(115)
4.53
(115)
4.53
(115)
3.50
(89)
8.03
(204)
8.03
(204)
5.08
(129)
5.08
(129)
0.98
(25)
0.98
(25)
6.99
(177.5)
6.99
(177.5)
2.34
(59.5)
2.34
(59.5)
Ø0.55(Ø14)
4.53
(115)
4.53
(115)
0.79
(20)
12.56
(319)
8.03
(204)
4P
3P
Side view
17.01
(432)
21.54
(547)
3P
4P
1.75
(44.5)
1.26
(32)
1.75
(44.5)
2.95
(75)
1.16
(29.5)
4.11
(104.5)
5.26
(133.5)
Ø0.55(Ø14)
3.80
(96.5)
15.41
(391.5)
86
20.59
(523)
0.79
(20)
0.79
(20)
16.06
(408)
11.81
(300)
11.81
(300)
Back view
Dimensions
Operating panel center
Operating panel center
Ø0.55 (Ø14)
2.64
(67)
0.98
(25)
6.99
(177.5)
6.99
(177.5)
1.75
(44.5)
4.53
(115)
8.03
(204)
8.03
(204)
8.03
(204)
2.95
(75)
4.53
(115)
2.64
(67)
4.53
(115)
4.53
(115)
Ø0.55 (Ø14)
Ø0.55 (Ø14)
3P
1.75
(44.5)
1.26
(32)
1.75
(44.5)
2.95
(75)
5.08
(129)
1.26 1.75
(32) (44.5)
0.98
(25)
2.34
(59.5)
2.34
(59.5)
Ø0.55 (Ø14)
5.08
(129)
Top view
4.53
(115)
12.56
(319)
4P
20.59
(523)
17.01
(432)
21.54
(547)
3P
4P
0.79
(20)
0.79
(20)
16.06
(408)
11.81
(300)
11.81
(300)
Back view
5.26
(133.5)
0.79
(20)
Side view
2.64
(67)
Horizontal
type
3.80
(96.5)
15.41
(391.5)
87
Dimensions
Fixed type 3200A
(UAH-32E)
Vertical
type
Top view
Operating panel center
Operating panel center
Ø0.55 (Ø14)
8.88
(225.5)
8.88
(225.5)
0.98
(25)
0.98
(25)
6.99
(177.5)
6.99
(177.5)
2.34
(59.5)
2.34
(59.5)
Ø0.55 (Ø14)
0.20
(5)
4.53
(115)
4.53
(115)
8.03
(204)
0.79
(20)
4.53
(115)
4.53
(115)
0.20
(5)
8.03
(204)
8.03
(204)
12.56
(319)
20.98
(533)
3P
4P
16.46
(418)
20.98
(533)
3P
4P
Back view
Side view
1.75
(44.5)
0.44
(11.2)
15.14
(384.5)
3.07
(78)
7.76
(197)
1.75
(44.5)
0.62
(15.7)
Ø0.55 (Ø14)
1.76
(44.8)
0.62
(15.7)
1.75
(44.5)
5.12
(130)
Ø0.95(Ø19)
1.75
(44.5)
7.60
(193)
19.21
(488)
88
0.79
(20)
Dimensions
Draw-out type 800~2000A
(UAH-08~20E)
Front view
Operating panel center
5.51
(140)
12.57
(319.3)
Operating panel center
5.51
(140)
5.51
(140)
5.51
(140)
2.95
(75)
2.36
(60)
Disconnected
Disconnected & Test
3P
10.63
(270)
1.85
(47)
7.87
(200)
13.38
(339.8)
5.12
(130)
14.76
(375)
20.75
(527)
17.65
(448.3)
4P
Side view
2.56
(65)
14.23
(361.5)
5.24
(133)
3.82
(97)
2.56
(65)
9.65
(245)
10.24
(260)
16.22
(412)
2.36
(60)
Bottom view
4.53
(115)
4.53
(115)
0.59
(15)
0.79
(20)
4.53
(115)
4.53
(115)
0.79
(20)
3.94
(100)
3.94
(100)
3.94
(100)
3.94
(100)
10.24
(260)
4.53
(115)
8.15
(207)
8.15
(207)
0.59
(15)
14.76
(375)
Ø0.51 (Ø13)
3P
Ø0.51 (Ø13)
4P
Back view
16.22
(412)
20.75
(527)
3P
4P
Side view
0.75
(19)
16.93
(430)
2.95
(75)
1.75
(44.5)
3.00
(75)
5.30
(134.5)
5.24
(133)
Ø0.55 (Ø14)
2.34
(59.5)
Vertical
type
16.93
(430)
10.63
(270)
16.93
(430)
2.56
(65)
10.63
(270)
1.97
(50)
2.78
(70.5)
18.78
(477)
89
Dimensions
Draw-out type 800~2000A
(UAH-08~20E)
Bottom view
4.53
(115)
2.95
(75)
1.75
(44.5)
2.83
(7.2)
Ø0.55 (Ø14)
4.53
(115)
4.53
(115)
2.95
(75)
Ø0.55 (Ø14)
8.15
(207)
3.94
(100)
14.76
(375)
Ø0.51 (Ø13)
3P
4P
16.22
(412)
20.75
(527)
3P
4P
Back view
3.82
(97)
5.24
(133)
16.93
(430)
0.79
(20)
Side view
2.78
(70.5)
18.78
(477)
90
1.75
(44.5)
3.94
(100)
8.15
(207)
3.94
(100)
3.94
(100)
10.24
(260)
4.53
(115)
0.75
(19)
4.53
(115)
0.29
(7.3)
0.75
(19)
Horizontal
type
Ø0.51 (Ø13)
Dimensions
Bottom view
0.59
(15)
3.94
(100)
3.94
(100)
3.94
(100)
3.94
(100)
6.46
(164)
6.46
(164)
0.59
(15)
10.24
(260)
14.76
(375)
Ø13(0.51)
(Mounting Hole)
3P
Ø0.51(Ø13)
4P
Ø0.55 (Ø14)
Ø0.55 (Ø14)
4.53
(115)
20.75
(527)
4.53
(115)
4.53
(115)
4.53
(115)
1.26
(32)
4.53
(115)
1.26
(32)
17.6
(44.5)
2.95
(75)
1.63
(41.5)
1.63
(41.5)
19.90
(505.5)
1.26
(32)
1.26
(32)
Back view
16.22
(412)
3P
4P
19.90
(505.5)
16.93
(430)
9.21
(234)
Side view
2.89
(73.5)
7.97
(202.5)
Front
connection
type
0.98
(25)
17.09
(434)
91
Dimensions
Draw-out type 2500A
(UAH-25E)
Bottom view
4.53
(115)
0.59
(15)
4.53
(115)
4.53
(115)
0.79
(20)
4.53
(115)
0.59(15)
3.94
(100)
14.76
(375)
Ø0.51 (Ø13)
3P
4P
16.22
(412)
20.75
(527)
3P
4P
Back view
Side view
1.75
(44.5)
Ø0.55 (Ø14)
16.93
(430)
2.95
(75)
2.34
(59.5)
5.30
(134.5)
5.24
(133)
1.75
(44.5)
1.26
(32)
4.67
(118.5)
20.67
(525)
92
0.79
(20)
3.94
(100)
3.94
(100)
3.94
(100)
10.24
(260)
4.53
(115)
10.04
(255)
10.04
(255)
Vertical
type
Ø0.51 (Ø13)
Dimensions
Bottom view
3.94
(100)
3.94
(100)
3.94
(100)
3.94
(100)
10.24
(260)
1.75
(44.5)
10.04
(255)
Ø0.55(Ø14)
1.26
(32)
2.95
(75)
0.29
(7.3)
Ø0.55(Ø14)
4.53
(115)
1.75
(44.5)
1.75
(44.5)
4.53
(115)
10.04
(255)
2.95
(75)
4.53
(115)
1.75
(44.5)
0.29
(7.3)
4.53
(115)
1.26
(32)
4.53
(115)
14.76
(375)
Ø0.51 (Ø13)
3P
4P
16.22
(412)
20.75
(527)
3P
4P
Ø0.51 (Ø13)
Back view
16.93
(430)
0.79
(20)
5.24
(133)
Side view
3.82
(97)
Horizontal
type
4.67
(118.5)
20.67
(525)
93
Dimensions
Draw-out type 3200A
(UAH-32E)
Bottom view
16.46
(418)
9.06
(230)
0.79
(20)
3.11
(79.2)
3.94
(100)
3.94
(100)
3.94
(100)
Ø0.51(Ø13)
(Mounting Hole)
10.24
(260)
14.76
(375)
3P
4P
16.22
(412 )
20.75
(527)
3P
4P
Back view
Side view
2.11
(53.5)
0.44
(11.2)
15.31
(389)
16.93
(430)
3.07 1.75
(78) (44.5)
7.76
(197)
0.62
(15.7)
Ø0.55(Ø14)
0.20
(5)
0.62
(15.7)
1.75
(44.5)
5.31
(135)
1.75
(44.8)
Ø0.75(Ø19)
1.49
(38)
23.50
(597)
94
0.79
(20)
3.94
(100)
12.87
(327)
3.13
(79.2)
20.98
(533)
13.58
(345)
4.53
(115)
12.87
(327)
Vertical
type
Ø0.51(Ø13)
(Mounting Hole)
Dimensions
Fixed type 3200~5200A
(UAH-32~50G)
Front view
29.57(751)
22.13(562)
38.62(981)
7.44(189)
31.18(792)
7.44(189)
11.02(280)
11.02(280)
8.03(204)
22.72(577)
0.47(12)
0.47(12)
31.69(805)
1.38
(35)
10.63 (270)
12.60 (320)
11.81(300)
0.79
(20)
0.79
(20)
1.38
(35)
12.60 (320)
Operating panel center
10.63 (270)
11.81(300)
Operating panel center
31.77(807)
0.47(12)
8.03(204)
3P
4P
Top view
Operating panel center
Operating panel center
Ø0.55 (Ø14)
2.99
(76)
9.61
(244)
0.79
(20)
0.79
(20)
2.99
(76)
9.61
(244)
9.61
(244)
3P
6.99
(177.5)
6.65
(169)
0.98
(25)
6.99
(177.5)
6.65
(169)
0.98
(25)
2.34
(59.5)
2.34
(59.5)
Ø0.55 (Ø14)
9.61
(244)
9.61
(244)
4P
0.79
(20)
30.75
(781)
31.69
(805)
3P
Side view
1.26
(32)
11.81
(300)
39.80
(1011)
40.75
(1035)
0.79
(20)
11.81
(300)
Back view
4P
0.55
(44.5)
1.75
(44.5)
2.95
(75)
5.24
(133)
Ø0.55 (Ø14)
1.16
(29.5)
4.11
(104.5)
Vertical
type
0.47(12)
40.75(1035)
5.37
(136.5)
16.99
(431.5)
95
Dimensions
Fixed type 3200~5200A
(UAH-32~50G)
Operating panel center
Operating panel center
Ø0.55 (Ø14)
2.34
0.98
(59.5)
(25)
6.99
(177.5)
Ø0.55 (Ø14)
9.61
(244)
9.61
(244)
1.75
(44.5)
Ø0.55 (Ø14)
Ø0.55 (Ø14)
3P
1.75
(44.5)
9.61
(244)
5.94
(151)
9.61
(244)
1.25
(31.7)
1.26
(32)
1.25
(31.7)
6.65
(169)
1.75
(44.5)
5.95
(151.2)
1.26
(32)
1.75
(44.5)
6.65
(169)
Top view
2.34
0.98
(59.5)
(25)
6.99
(177.5)
Horizontal
type
9.61
(244)
4P
3P
2.64
(67)
5.24
(133)
0.79
(20)
Side view
5.37
(136.5)
16.99
(431.5)
96
11.81
(300)
39.80
(1011)
40.75
(1035)
4P
0.79
(20)
30.75
(781)
31.77
(805)
0.79
(20)
11.81
(300)
Back view
Dimensions
Draw-out type 3200~5200A
(UAH-32~50G)
Front view
Operating panel center
Operating panel center
5.51
(140)
5.51
(140)
10.24
(260)
4.45
(113)
18.11
(460)
10.24
(733)
18.11
(460)
19.8
(503)
10.24
(260)
10.24
(260)
13.5
(343)
39.96
(1015)
30.91
(785)
4P
3P
Bottom view
9.61(244)
9.61(244)
9.61(244)
3
(76.2)
9.61(244)
9.61(244)
2.99
(76.2)
0.79
(20)
1.36
(34.6)
10.24
(260)
5.24
(113)
10.24
(260)
3P
7.87
(200)
7.87
(200)
10.83
(275.3)
10.83
(275.3)
0.79
(20)
1.09
(27.6)
Ø0.51(Ø13)
(Mounting Hole)
10.24
(260)
13.5
(343)
4P
10.24
(260)
Ø0.51(Ø13)
(Mounting Hole)
0.59
(15)
28.11
(714)
39.96
(1015)
30.91
(785)
Ø0.31(Ø8)
(Earthing Hole)
3P
Side view
Ø0.31(Ø8)
(Earthing Hole)
2.95
(75)
1.75
(44.5)
1.75
(44.5)
3.52
(89.5)
5.24
(133)
4P
Ø0.55 (Ø14)
1.26
(32)
6.48
(164.5)
37.01
(940)
0.59
(15)
18.11
(460)
18.11
(460)
Back view
17.05
(433)
Vertical
type
10.24
(260)
5.45(138.5)
21.47
(545.3)
97
Dimensions
Draw-out type 3200~5200A
(UAH-32~50G)
9.61
(244)
Ø0.55(Ø14)
3
(76.2)
1.75
(44.5)
3
(76.2)
9.61
(244)
1.75
(44.5)
1.25
(31.7)
1.36
(34.6)
10.24
(260)
5.24
(113)
10.24
(260)
Ø0.51(Ø13)
(Mounting Hole)
3P
7.87
(200)
7.87
(200)
10.83
(275.3)
1.25
(31.7)
9.61
(244)
5.94(151.2)
1.26
(32)
9.61
(244)
5.94(151.2)
1.75
(44.5)
9.61
(244)
10.83
(275.3)
Bottom view
1.26
(32)
Horizontal
type
1.09
(27.6)
10.24
(260)
13.50
(343)
10.24
(260)
Ø0.51(Ø13)
(Mounting Hole)
4P
0.59
(15)
28.11
(714)
30.91
(785)
Ø0.31(Ø8)
(Earthing Hole)
3P
4.61
(117)
17.05
(433)
5.24
(133)
0.79
(20)
Side view
5.45
(138.5)
21.56
(545.3)
98
37.01
(940)
39.96
(1015)
4P
0.59
(15)
18.11
(460)
18.11
(460)
Back view
Ø0.31(Ø8)
(Earthing Hole)
� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions
� Any maintenance and inspection shall be performed by the personnel having expertise concerned.
ⓒ 2011.9 LSIS Co.,Ltd. All rights reserved.
� HEAD OFFICE
LS-ro 127 (Hogye-dong) dongan-gu Anyang-si
Gyeonggi-do Korea
Tel. (82-2)2034-4887, 4873, 4918, 4148
Fax. (82-2)2034-4648
www.lsis.com
� Global Network
�LSIS (Middle East) FZE �
�Dubai, U.A.E.
Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates
Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: dhleef@lsis.biz
�Dalian LSIS Co., Ltd. �
�Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: tangyh@lsis.com.cn
�LSIS (Wuxi) Co., Ltd. �
�Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: luw@lsis.com.cn
� CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,
Cheong Ju, 361-720, Korea
�LSIS-VINA Co., Ltd. �
�Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: sjbaik@lsis.biz
�LSIS-VINA Co., Ltd. �
�Hochiminh , Vietnam
Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam
Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: hjchoid@lsis.biz
�LSIS Shanghai Office �
�Shanghai, China
Address: Room 32 floors of the Great Wall Building, No. 3000 North Zhongshan Road, Putuo District, Shanghai, China
Tel: 86-21-5237-9977 Fax: 89-21-5237-7189 e-mail: baijh@lsis.com.cn
�LSIS Beijing Office �
�Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: sunmj@lsis.com.cn
�LSIS Guangzhou Office �
�Guangzhou, China
Address: Room 1403, 14/F, New Poly Tower, No.2 Zhongshan Liu Road, Guangzhou 510180, P.R. China
Tel: 020-8326-6754 Fax: 020-8326-6287 e-mail: chenxs@lsis.com.cn
�LSIS Chengdu Office �
�Chengdu, China
Address: Room 1701 17Floor, huamin hanjun internationnal Building, No1 Fuxing Road Chengdu, 610016, P.R. China
Tel: 86-28-8670-3201 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn
�LSIS Qingdao Office �
�Qingdao, China
Address: Room 2001,20/F,7B40, Galaxy Building, No.29 Shandong Road, Shinan District, Qingdao 266071, P.R. China
Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 e-mail: wangzy@lsis.com.cn
�LSIS NETHERLANDS Co.Ltd �
�Schiphol-Rijk, Netherlands
Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands
Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: junshickp@lsis.biz
Specifications in this catalog are subject to change without notice due to
continuous product development and improvement.
2013. 11
�LSIS Gurgaon Office �