www.lsis.com Super Solution Air Circuit Breakers Codes and Standards UA Series are manufactured and tested in accordance with the following standards Low-Voltage Power Circuit Breaker �ANSI C37.13 �ANSI C37.16 �ANSI C37.17 �ANSI C37.50 �UL 1066 (cULus Listed) �CSA C22.2 No.31-10 Note) Throughout this document, the phrase “ANSI Certified” means the product meets the requirements of UL 1066 and ANSI C37 UL File Numbers: Susol UA Series , 1600AF Susol UA Series , 3200AF Susol UA Series ,5000AF E326950 Vol.1 Sec.1 E326951 Vol.1 Sec.2 E326952 Vol.1 Sec.3 Contents ● Overview 4 ● External configuration 14 ● Internal configuration 16 ● Ordering 18 ● Ratings 22 ● Trip relays 24 ● Accessories 50 ● Electrical diagram 76 ● Dimensions 78 Premium Susol ACB meets your demands for high breaking capacity, fully line-up, and optimized panel size. Various accessories and connection methods realize user-friendly handling. Susol ACB provides you with total solutions with an advanced trip relay for measurement, diagnosis, analysis, and communication as well as protective functions for absolute protective coordination and electric power monitoring system. Super Solution UL Listed/ANSI Certified Low-Voltage Power Circuit Breaker UA series LSIS Super Solution series Modular design � High (130kA) Breaking Capacity Full Line-up to 5000A � Satisfy the needs for a compact sized panels � N-Phase conducting capacity 100% � Interchangeable Trip unit and Rating plug � Safety Monitor temperatures for safety (Optional) �Careful selection of materials �Arc space is zero �Perform discriminations between upstream and downstream levels User convenience various connection type for main circuit terminals �Easy installation of accessories �Interchangeable Trip unit and Rating plug Intelligent Trip relay Various and advanced functions protection, measurement, diagnosis, analysis, communication Susol Manual Motor Starters Susol Air Circuit Breakers Susol Molded Circuit Breakers Susol Magnetic Contactors & Overload Relays Full line-up & Compact Up to 5000A, Susol ACB provides fully lined-up 3 frame. For each frame, there is just one size, which is smaller and more compact. H = 430mm It makes it possible for you to design the optimized volume panel. W = 334mm 85kA UAS-08/16D 08 16 800AF 1600AF 85kA at 508Vac W=334(3p), 419(4p)mm W = 412mm 100kA UAH-08~32E 08 16 20 25 32 800AF 1600AF 2000AF 2500AF 3200AF 100kA at 508Vac W=412(3p), 527(4p)mm m 5m 37 = D W = 785mm 130kA �The high breaking capacity: 85/100/130kA (at 508Vac) �3 ampere frame sizes: 1600/3200/5000AF �N phase current conducting capacity: 100% UAH- 32~50G 32 40 50 3200AF 4000AF 5000AF 130kA at 508Vac W=785(3p), 1015(4p)mm Trip Relay (OCR) Trip relays are classified according to function. Trip relays are classified according to their usages and functions to maximize customers’ satisfaction. Classified trip relays and easy installation. �Protection: overload, short current, ground fault, earth leakage, under voltage, over voltage, under frequency, over frequency, reverse power, unbalance, etc �Measurement: voltage, ampere, power, energy, frequency, power factor, harmonics, etc. �Event & fault recording: Max. 256 events & faults �Communication: Modbus/RS-485, Profibus-DP Susol ACB Trip Relay functioning world-best protection can be interlocked with mechanism. It makes the breaking capacity of ACB improved and ACB’s life enhanced, and provides advanced functions - measurement, diagnosis, analysis, and communication. Susol ACB Trip relay N type �L/S/I/G/Thermal �Self Power �RTC Timer mounted �Fault information (LED) A type P/S type �L/S/I/G/Thermal �ZSI �Remote Reset �Modbus/RS-485 �Profibus-DP �Self Power �AC/DC 100~250V �DC 24~60V �RTC Timer mounted �Fault Recording (10EA) �L/S/ I/G/Thermal(Continuous) �UV/OV/OF/UF/rP/Vun/Iun �Measurement: V/A/W/Wh/F/PF �Harmonics (63th), Waveform (S Type) �ZSI �Remote Reset �Modbus/RS-485 �Profibus-DP �AC/DC 100~250V �DC 24~60V �RTC Timer mounted �Event Recording (256EA) �Fault Recording (256EA) �Fault Wave (S Type) Trip relays series N type N Type (Normal) �Self-power + Current protection P type P Type (Power Meter) �A type + Power Meter + Voltage / Frequency / Unbalance protection A type A Type (Ammeter) �Current Meter + Current protection + DO control + Communication S type S Type (Supreme) �P type + Harmonics analysis (63 th) + Fault wave recording Accessories � � � � � � � � � � � � � � ACB � Trip Relay (OCR) � Auxiliary Switch (AX) � Motor (M) � Key Lock (K1), � Closing Coil (CC) Double Key Lock (K3) � Shunt Coil (SHT) � Counter (C) � Under Voltage Trip Device (UVT) � On/Off Button Lock (B) � Door Interlock (DI) � Miss Insertion Preventing Device (MIP) � MOC (Mechanically � Manual Reset Button (MRB) Operated Cell Switch) � Mechanical Interlock (MI) � � � � � � � � � � � � � � � � Cradle Other � Safety Shutter (ST) � Mechanical Interlock (MI) � Door Frame (DF) � Zero Arc Space (ZAS) � Miss Insertion Prevent Device (MIP) � Dust Cover (DC) � Cell Switch (CEL) � Safety Control Cover (SC) � Lifting Hook (LH) � Door Interlock (DI) � Racking Interlock (RI) � UVT Time Delay Controller (UDC) � MOC (Mechanical Operated Cell switch) � Profibus-DP Communication module � Remote I/O � Temperature Alarm Connection and Installation Diversified terminal connection methods of the ACB main circuit for users. Multiple connections Various installation methods Standard connection Horizontal type Vertical type Front type Mixed connection Horizontal / Vertical type Vertical / Horizontal type Horizontal / Front type Vertical / Front type Front / Horizontal type Front / Vertical type �Front connection type is available to be connected regardless of the depth of main circuit terminal, and it is suited for the panel required for limited installation space. �The vertical and horizontal type terminal are module types which can easily compose the vertical and 。 horizontal terminals by rotating 90。 �Please refer to the rating lists (Page 22~25) because the installation method is various according to the rated current. External configuration Fixed type ACB Terms � � Trip relay � Counter � � � OFF button � � ON button � � Series name � � Charge handle � � Rated name plate � � � � Charge/Discharge indicator � Closed/Open indicator � Corporation logo � � Arc cover (Zero Arc Space) � � Safety control cover � Cradle � Draw-out handle � � Position indicator � Handle inserting hole � � Pad lock button � Arc chute � Control cover � Fixed type bracket � Rating plug Draw-out ACB (Cradle) � � � � � � � � � � � � � � � 14 � � � Cradle (Internal) Cradle (Rear) � � � � � � � � � Terms � Safety control cover � Pad lock button � Draw-out handle � Connecting conductor (Line side) � Position indicator � Connecting conductor (Load side) � Handle inserting hole Main nameplate [Acronym explanation] [Secondary nameplate] Explanation of terminologies � Motor charge Control power and � Closing coil terminal No. � Shunt tripping coil � Auxiliary switches: Contact specification and terminal No. �Under voltage trip: UVT terminal No. � OCR control source: Trip relay control power � Alarm switch: Alarm and terminal No. � Digital trip relay: Switching diagram � Z.S.I: Input/Output terminal No. � Reset: LED/LCD reset � Communication: Communication and terminal No. � Voltage module: Phase voltage and symbol � Earth/Leakage: Ground fault / Earth leakage input terminal No. 15 Internal configuration Terms � � Arc chute � Aux. switch control terminal � Control power supply terminal � � � Trip relay control terminal � � Carrying grip � � Shunt coil or UVT coil � � � � � � Mechanism � Main body � Counter � Shunt coil � � Closing coil � Motor Ass’y � � � Aux. switch � � Closed button � � Open button � MTD base � � Trip relay � Front cover � � 16 � � Terms � � � � � � � � Control circuit terminal block � Control terminal � Auxiliary switches � � Closing, Shunt, UVT coil � � Trip relay � � Front cover � Mechanism � � Charge handle � Trip spring � Closing spring � � Draw-in/out device � � � � Arc extinguishing part � Moving contact � Fixed contact � Conductor on line side � � Cradle finger � Cradle � Connecting conductor � � CT (Current transformer) � Conductor on load side � 17 Ordering Breaker and Accessories 10 UAS Frame Type D 3 Frame Size Phasing 08 800AF 3/4P Standard 3 3P 04~08 400A~800A 16 1600AF RST(N) 4 4P 08~16 800A~1600A D W Poles 10 Sensor Rating A Mounting and Terminal Mounting A Drawout H Horizontal terminals V Vertical terminals 4P Reversed NRST Fixed M N E 32 UAH Frame Size Phasing 800AF 3/4P Standard 3 3P 04~08 400A~800A 16 1600AF RST(N) 4 4P 08~16 800A~1600A 20 2000AF 25 2500AF 12~25 1200A~2500A 32 3200AF 16~32 1600A~3200A 32 3200AF 40 4000AF 50 5000AF E X G Z 4P Reversed NRST 10~20 1000A~2000A 3 3P 16~32 1600A~3200A RST(N) 4 4P 20~40 2000A~4000A 4P Reversed NRST 25~50 2500A~5000A D 3 Frame Size Phasing 08 800AF 3/4P Standard 3 3P 16 1600AF RST(N) 4 4P 20 2000AF 25 2500AF 32 3200AF 40 4000AF 50 5000AF Frame Type D W E X G Z Sensor Rating 3/4P Standard 16 UAA Poles 10 32 08 Frame Type 18 3 4P Reversed NRST 3/4P Standard RST(N) 4P Reversed NRST 3/4P Standard RST(N) 4P Reversed NRST Poles 10 00 Sensor Rating Not applied Horizontal for line Vertical for load Vertical for line Horizontal for load P Front terminal G Horizontal-con type W Vertical-con type * Terminals for P type must be ordered separately * G and W types can be applicable to UAS-08D, UAS-16D only * Front terminal is only available for 800~2000A M1 D1 D1 Motor Operator AX Shunt Trip Trip relay None (Manual operated) D0 None M1 AC/DC 100V~125V D1 AC/DC 100V~125V M2 AC/DC 200V~250V D2 AC/DC 200V~250V M3 DC 125V D3 DC 125V M4 DC 24V~30V D4 DC 24V~30V M5 DC 48V~60V D5 DC 48V~60V M8 AC 48V D7 AC 48V Closing Coil N01 N02 N03 N04 N05 N06 U1 AL C Option Refer to 21page MA Code AL A1 A2 A3 A4 A5 A6 A7 A8 A9 C S B NG0 Charging/Auxiliary Switch UVT D0 None AX Standard OFF charge/3a3b U0 None D1 AC/DC 100V~125V AC Standard ON charge/3a3b U1 AC/DC 100V~125V D2 AC/DC 200V~250V BX Standard OFF charge/5a5b U2 AC/DC 200V~250V D3 DC 125V BC Standard ON charge/5a5b U3 DC 125V D4 DC 24V~30V HX High capacity OFF charge/5a5b U4 DC 24V~30V D5 DC 48V~60V HC High capacity ON charge/5a5b U5 DC 48V~60V D7 AC 48V CC Standard ON charge/6a6b U6 AC 380V~480V JC High capacity ON charge/6a6b U7 AC 48V Description Code M MI AL1+MRB D DI or MOC AL1+MRB +RES(AC110~130V) *AC only K K1 AL1+AL2 +MRB K2 K2 AL1+MRB +RES(DC110~125V) *DC only K3 K3 AL1+MRB +RES(AC200~250V) *AC only R RCS AL1+MRB +Auto Reset T TM AL1+AL2 +MRB +Auto Reset AL1+MRB +RES(DC110~125V) +Auto Reset *DC only H1 AL1+MRB +RES(AC200~250V) +Auto Reset *AC only H2 AL1+MRB +RES(AC110~130V) +Auto Reset *AC only H3 SHT2 Note 2) C COUNTER H4 CS2 Charge switch communication H5 B On/Off Button lock H7 Description Mechanical interlock Door Interlock or MOC(Mechanism operated cell switch) Key Lock Key Interlock Set Key Interlock Double Ready to Close switch Temperature Monitoring AC/DC 100V ~125V, Double Shunt coil AC/DC 200V ~250V, Double Shunt coil DC 125V, Double Shunt coil DC 24V ~30V, Double Shunt coil DC 48V ~60V, Double Shunt coil AC 48V, Double Shunt coil A4 (AL1+MRB +RES(AC200~250V))+C(Counter)+B(ON/OFF Button Lock)+K(Key Lock)+R(Ready to Close switch)+M(Mechanic Interlock)+E(Spring Auto Release) AL (AL1+MRB)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+D(Door Interlock or MOC)+H1(AC/DC 100V ~ 130V, Double Shunt coil)+E(Spring Auto Release) C(Counter)+B(ON/OFF Button Lock)+K2(Key Interlock Set)+R(Ready to Close switch)+T(Temperature Monitoring) A4(AL1+MRB+RES(AC200~250V))+B(ON/OFF Button Lock)+K(Key Lock(OFF Lock))+M(Mechanical Interlock)+T(Temperature Monitoring) A1(AL1+MRB+RES110~130V)+B(ON/OFF Button Lock)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+M(Mechanical Interlock)+T(Temperature Monitoring) A2(AL1+AL2+MRB)+C(Counter)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+T(Temperature Monitoring) Note) * Codes for over 5 optional accessories are composed separately **UVT and SHT2 can not be selected together. Select one of two. 19 Ordering Product number structure UAL For UL ACB Cradle type N16D Frame Size S16D 1600AF S20E 2000AF S25E 2500AF S32E 3200AF S40E S50G 20 4000AF 5000AF 3 A H Number of poles Terminal configuration 3 3P H Horizontal type 4 4P V Vertical type M Secondary Connector type N Line: Horizontal Load: Vertical E N Shutter E F Without safety shutter With safety shutter Line: Vertical Load: Horizontal P Front type A Connector type G Horizontal-con type B Screw joint type W Vertical-con type C Spring tension type * Terminals for P type must be ordered separately * G and W types can be applicable to S16D (1600AF) only. Other options S Arc cover Trip relay N G 0 OCR(Trip Unit) type Communication & Ground fault protection Control voltage & frequency G 0 0 No OCR N N Normal G Ground fault, No Communication A A Ammeter Power meter Supreme meter 60Hz Self-power 50Hz 0 G Ground fault, No Communication 0 No Control voltage C Ground fault and Communication 1 AC/DC 110V~250V 60Hz E Ground fault(with external CT), No Communication 2 DC 24V~60V 60Hz X Ground fault(with external CT) and Communication 5 No Control voltage 50Hz 6 AC/DC 110V~250V 50Hz 7 DC 24V~60V C 60Hz 50Hz 1 C Ground fault and Communication 1 AC/DC 110V~250V 60Hz X Ground fault(with external CT) and Communication 2 DC 24V~60V 6 AC/DC 110V~250V 50Hz 7 DC 24V~60V S S Self-power 5 G P P 0 C 60Hz 50Hz 1 C Communication 1 AC/DC 110V~250V 60Hz X Ground fault and Communication 2 DC 24V~60V 6 AC/DC 110V~250V 50Hz 7 DC 24V~60V 60Hz 50Hz * Ground fault detection by current vector sum of 4 phase (R,S,T,N) * Communication and output contacts for L,S,I,G do not work except OCR LED without control power supply. * P and S types require Voltage Module to be ordered separately. * LCD in trip unit can be display more than 10% of rated current. * Currnet measuring value display more than 15% of rated current. 21 Ratings for UL Listed/ANSI Certified Susol UA Circuit Breakers TYPE AF Rated current (In max) Rated current UAS-��D (A) (A) at 40°C at 40°C 08 800 16 1600 800 1000 1200 1250 1600 400 600 630 800 Rated Maximum Voltage (V) Frequency (Hz) Number of poles (P) Type of Trip relay (Electronic trip device) Rated short circuit current (kA) (Sym.) UL 1066 ANSI C37.13 Rated short Time current (kA) Operating time (t) (ms) Life cycle ACB (time) Weight lb (kg) External dimension Draw-out type With instantaneous AC Without instantaneous AC 635V 508V 254V 635V 508V 254V Maximum total breaking time Maximum closing time Mechanical Without maintenance With maintenance Electrical Without maintenance With maintenance Drawout type Main Body 3P with Cradle 4P Only Cradle 3P 4P Fixed type Motor charging 3P type 4P in (mm) H×W×D 3P 4P H Fixed type in (mm) H×W×D 3P D W 4P Enclosure dimension in (mm) H×W×D 3P 4P 22 254V / 508V / 635V 50/60 3P / 4P N, A, P, S (4 type) 65 85 85 65 65 65 65 50ms 80ms 12,500 2,800 154 (70) 187 (85) 71 (32) 84 (38) 77 (35) 99 (45) 16.93×13.15×16.02 (430×334×407) 16.93×16.5×16.02 (430×419×407) 11.81×11.81×11.61 (300×300×295) 11.81×15.16×11.61 (300×385×295) 19.69×15.75×13.39 (500×400×340) 19.69×19.69×13.39 (500×500×340) 08 800 400 600 630 800 UAH-��E 20 2000 1000 1200 1250 1600 2000 254V / 508V / 635V 50/60 3P / 4P N, A, P, S (4 type) 85 100 100 85 85 85 85 50ms 80ms 12,500 5,000 UAH-��G 40 4000 2000 2500 3000 3200 3600 4000 254V / 508V / 635V 50/60 3P / 4P N, A, P, S (4 type) 100 130 130 100 100 100 100 50ms 90ms 5,000 2,800 1,000 1,000 326 (148) 414 (188) 205 (93) 256 (116) 196 (89) 249 (113) 489 (222) 626 (284) 276 (125) 355 (161) 227 (103) 287 (130) 18.11×30.91×16.02 (460×785×407) 18.11×39.96×16.02 (460×1015×407) 11.81×29.57×11.61 (300×751×295) 11.81×38.62×11.61 (300×981×295) 31.5×32.48×13.39 (800×825×340) 31.5×41.54×13.39 (800×1055×340) 16 1600 800 1000 1200 1250 1600 214 (97) 269 (122) 99 (45) 121 (55) 101 (46) 126 (57) 25 2500 1200 1250 1600 2000 2500 245 (111) 309 (140) 123 (56) 152 (69) 110 (50) 137 (62) 16.93×16.22×16.02 (430×412×407) 16.93×20.75×16.02 (430×527×407) 11.81×14.88×11.61 (300×378×295) 11.81×19.41×11.61 (300×493×295) 19.69×19.69×13.39 (500×500×340) 19.69×24.21×13.39 (500×615×340) 32 3200 1600 2000 2500 3000 3200 32 3200 1600 2000 2500 3000 3200 50 5000 2500 3000 3200 3600 4000 5000 23 Trip relay(OCR) The trip relay of Susol ACB provides the additional protection functions for voltage, frequency, unbalance, and others in addition to main protection functions for over current, short-circuit, ground fault. It supports the advanced measurement functions for voltage, current, power, electric energy, harmonics, communication function, and others. Analog trip function interlocked with mechanism enhanced a durability of devices as well as the breaking capacity of ACB. Zone selective interlocking function makes the protective coordination more simple and thermal memory can be applied to various loads. Contents Trip relay types 25 �type N type:�Normal� 26 �type A type:�Ammeter� 28 �type P type:�Power meter� 30 �type S type:�Supreme meter� 32 Operation characteristic 34 Measurement function 36 Man machine interface 37 Protection element setting 38 Measurement element display 39 Characteristic curves 40 ZSI - Zone Selective Interlocking 45 Remote reset and digital I/O 46 Communication 47 Event & fault recording 48 System information 48 System block diagram 49 Trip relays Trip relay types Classification N type A type P type S type Externals Current protection Other protection �L / S / I / G �L / S / I / G / Thermal �ZSI(Protective coordination) � Earth leakage (Option) - �Current (R / S / T / N) Measurement function - Fine adjustment - Pre Trip Alarm - Digital Output - �3DO (Fixed) �L, S/I, G Alarm IDMTL setting - - Communication Power supply RTC timer LED for trip info. Fault recording Event recording Operating button - �Modbus/RS-485 �Profibus-DP �Self Power �Self Power - Power shource - Power shource works works over 20% of over 20% of load current. load current. - External power source are required for comm. �AC/DC 100~250V �DC 24~60V �Available �Long time delay �Long time delay �Short time delay/Instantaneous �Short time delay/Instantaneous �Ground fault �Ground fault �10 records (Fault/Current/Date and Time) �Reset button �Reset, Menu Up/Down, Left/Right, Enter - �L / S / I / G / Thermal(Continuous) �L / S / I / G / Thermal(Continuous) �ZSI(Protective coordination) �ZSI(Protective coordination) �Earth leakage(Option) �Earth leakage(Option) �Over/Under current �Over/Under current �Over/Under frequency �Over/Under frequency �Unbalance(Voltage/Current) �Unbalance(Voltage/Current) �Reverse power �Reverse power �3 Phase Voltage/Current RMS/Vector �3 Phase Voltage/Current RMS/Vector �Power(P, Q, S), PF(3-Phase) �Power(P, Q, S), PF(3-Phase) �Energy(Positive/Negative) �Energy(Positive/Negative) �Frequency, Demand �Frequency, Demand �Voltage/Current harmonics (1st~63th) �3 Phase Waveforms �THD, TDD, K-Factor �Fine adjustment for long/short �Fine adjustment for long/short time delay/instantaneous/ ground time delay/instantaneous/ ground �Overload protection relays �Overload protection relays : DO (Alarm) (Ground fault is not : DO (Alarm) (Ground fault is not available when using Pre trip alarm) available when using Pre trip alarm) �3DO (Programmable) �3DO (Programmable) �Trip, Alarm, General �Trip, Alarm, General �Compliance with IEC60255-3 �Compliance with IEC60255-3 SIT, VIT, EIT, DT SIT, VIT, EIT, DT �Modbus / RS-485 �Modbus / RS-485 �Profibus-DP �Profibus-DP �AC/DC 100~250V �AC/DC 100~250V �DC 24~60V �DC 24~60V Basic protection function(L / S / I / G) is still under normal operation without control power. �Available �Long time delay �Short time delay/Instantaneous �Ground fault �256 records (Fault/Current/Date and Time) �256 records(Content, Status, Date) �Reset, Menu Up/Down, Left/Right, Enter �Available �Long time delay �Short time delay/Instantaneous �Ground fault �256 records �Last fault wave recording (3 Phase) �256 records(Content, Status, Date) �Reset, Menu Up/Down, Left/Right, Enter 25 Trip relays �type N type:�Normal� ■ Optimized protection function ■ OCR, OCGR function according IEC60947-2 ■ Overload protection - Long-time delay - Thermal ■ Short-circuit protection - Short-time delay / Instantaneous - I2t On/Off optional (for short-time delay) ■ Ground fault protection - I2t On/Off optional ■ Self-Power ① LED: Indication of trip info. and overload state Alarm SP Ir Isd Ii Ig Ig: LED indicating ground-fault Isd/Ii: LED indicating short-time or instantaneous tripping Ir: LED indicating long-time delay SP: Self-protection and battery test LED Alarm: LED indicating an overload (Turn on above 90%, Blink above 105%) ① ② ② Reset Key: Fault reset or battery check ③ Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting ④ Isd: Short-time current setting, tsd: Short-time tripping delay setting ⑤ Ii: Instantaneous current setting ③ ⑥ Ig: Ground fault current setting, tg: Ground fault tripping delay setting ⑦ Test terminal: OCR test terminal (Connected with OCR tester) ④ ⑥ ⑤ ⑦ ⑧ 26 ⑧ Rating plug - Rated current setting (45~100% of the AF) - Frequency selectable(60Hz/50Hz) Trip relays Protection Long time t Current setting (A) Iu = In×... 0.5 0.6 Ir = Iu×... 0.8 0.83 0.85 0.88 0.9 Time delay (s) tr@(1.5×lr) 12.5 25 50 100 Accuracy: ±15% or below tr@(6.0×lr) 0.5 2 4 100ms tr@(7.2×lr) 0.34 0.69 1.38 2.7 Isd = Ir×... 1.5 1 0.7 0.8 0.9 1.0 Ir 0.93 0.95 0.98 1.0 200 300 400 500 Off 8 12 16 20 Off 5.5 8.3 11 13.8 Off 6 8 10 Off 10 12 15 Off tr lsd tsd Ii Short time I Current setting (A) Accuracy: ±10% Time delay (s) @ 10×Ir tsd (I t Off) 3 4 5 I2t Off 0.05 0.1 0.2 0.3 0.4 I t On 0.1 0.2 0.3 0.4 20 80 160 260 360 80 140 240 340 440 2 3 4 6 8 2 Min. Trip 2 2 Time(ms) Max. Trip Time(ms) Instantaneous Current setting (A) Ii = In×... Tripping time below 50ms Ground fault t Pick-up (A) Accuracy: ±10%(Ig�0.4In) Ig = In×... 0.2 0.3 0.4 0.5 0.6 ±20%(Ig≤0.4In) 0.7 0.8 1.0 Off Ig I t Off 0.05 0.1 0.2 0.3 0.4 I2t On 0.1 0.2 0.3 0.4 20 80 160 260 360 80 140 240 340 440 2 tg Time delay (s) Min. Trip @ 1×In Time(ms) (I t Off) 2 Max. Trip Time(ms) tg I 27 Trip relays �type A type:�Ammeter� ■ Measurement and Display Function - High detailed measurement for current - character LCD type ■ Fault recording - Records Max. up to 10 fault information about fault type, fault phase, fault data, occurrence time of fault ■ SBO (Select Before Operation) - High reliability for control and setting change method ■ 3 DO(Digital Output) - Fixed ■ Communication - Modbus/RS485 - Profibus-DP ■ Overload protection - Long-time delay - Thermal ■ Short-circuit protection - Short-time delay / Instantaneous - I2t On/Off optional (for short-time delay) ■ Ground fault protection - I2t On/Off optional - Trip/Alarm selectable (need external power) - Blocking Time (0~60s) Do not ground fault detect during Blocking time ■ Realization of protective coordination by ZSI (Zone Selective Interlocking) - Disable/Enable Selectable ■ High-performance and high-speed MCU built-in - Accurate measurement with tolerance of 1.0% ① LCD: Indication of measurement and information ② LED: Indication of trip info. and overload state Alarm SP Ir Isd Ii Ig Comm ① Ig: LED indicating ground-fault Isd/Ii: LED indicating short-time or instantaneous tripping Ir: LED indicating long-time delay SP: Self-protection and battery test LED Alarm: LED indicating an overload (Turn on above 90%, Blink above 105%) ③ Key: Move to menu or reset ② Reset Esc ③ Reset/ESC: Fault reset or ESC from menu Enter: Enter into secondary menu or setting input Up/Down: Move the cursor up/down on screen or increase/decrease a setting value Right/Left: Move the cursor or setting right/left on screen (Rotation) Menu: Menu display ↔ Measurement display ④ ⑤ ⑥ ⑦ ⑧ ④ Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting ⑤ Isd: Short-time current setting, tsd: Short-time tripping delay setting ⑥ Ii: Instantaneous current setting ⑦ Ig: Ground fault current setting, tg: Ground fault tripping delay setting ⑨ ⑧ Test terminal: OCR test terminal (Connected with OCR tester) ⑨ Rating plug - Rated current setting (45~100% of the AF) - Frequency selectable(60Hz/50Hz) 28 Trip relays Protection Long time t Current setting (A) Iu = In×... 0.5 0.6 Ir = Iu×... 0.8 0.83 0.85 0.88 0.9 Time delay (s) tr@(1.5×lr) 12.5 25 50 100 Accuracy: ±15% or below tr@(6.0×lr) 0.5 2 4 100ms tr@(7.2×lr) 0.34 0.69 1.38 2.7 Isd = Ir×... 1.5 1 0.7 0.8 0.9 1.0 Ir 0.93 0.95 0.98 1.0 200 300 400 500 Off 8 12 16 20 Off 5.5 8.3 11 13.8 Off 6 8 10 Off 10 12 15 Off tr lsd tsd Ii Short time I Current setting (A) Accuracy: ±10% Time delay (s) @ 10×Ir tsd (I t Off) 3 4 5 I2t Off 0.05 0.1 0.2 0.3 0.4 I t On 0.1 0.2 0.3 0.4 20 80 160 260 360 80 140 240 340 440 2 3 4 6 8 2 Min. Trip 2 2 Time(ms) Max. Trip Time(ms) Instantaneous Current setting (A) Ii = In×... Tripping time below 50ms Ground fault t Pick-up (A) Accuracy: ±10%(Ig�0.4In) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 Off Ig ±20%(Ig≤0.4In) I t Off 0.05 0.1 0.2 0.3 0.4 I2t On 0.1 0.2 0.3 0.4 20 80 160 260 360 80 140 240 340 440 0.5 1 2 3 5 140 230 350 800 950 140 230 350 800 2 tg Time delay (s) Min. Trip @ 1×In Time(ms) (I t Off) 2 Max. Trip Time(ms) tg I Earth leakage (Option) Current setting (A) t I△n Time delay (ms) Accuracy: ±15% Alarm △t Time(ms) Trip Time(ms) Note) Current setting values are secondary current of the external CT. Recommend : not to use current setting values more than 5A. 10 20 30 Off I n t I 29 Trip relays �type P type:�Power meter� ■ Overload protection - Long-time delay - Thermal ■ Short-circuit protection - Short-time delay / Instantaneous - I2t On/Off optional (for short-time delay) ■ Ground fault protection - I2t On/Off optional - Trip/Alarm selectable (need external power) - Blocking Time (0~60s) Do not ground fault detect during Blocking time ■ Protection for Over voltage/Under voltage/Over frequency/Under frequency/Unbalance/Reverse power ■ Realization of protective coordination by ZSI (Zone Selective Interlocking) - Disable/Enable Selectable ■ The fine-adjustable setting by knob and Key ■ IDMTL setting (SIT, VIT, EIT, DT curve) - Basic setting : “None”. Thermal curve. ■ Measurement and Display Function - High detailed measurement for 3 phase current/Voltage/Power/Energy/Phase angle/Frequency/PF/Demand - 128 x 128 Graphic LCD - Indicates current/voltage Vector Diagram and Waveform ■ Fault recording - Records Max. up to 256 fault information about fault type, fault phase, fault value, occurrence time of fault ■ Event recording - Records events of device related to setting change, operation and state change. (Max. up to 256) ■ SBO (Select Before Operation) - High reliability for control and setting change method ■ 3 DO(Digital output) - Programmable for alarm, trip and general DO ■ Communication - Modbus/RS485 - Profibus-DP ① Graphic LCD: Indication of measurement and information ② LED: Indication of trip info. and overload state Alarm SP Ir Isd Ii Ig Comm ① Comm: LED indicating comm. state (Blink when running) Ig: LED indicating ground-fault Isd/Ii: LED indicating short-time or instantaneous tripping Ir: LED indicating long-time delay SP: Self-protection and battery test LED Alarm: LED indicating an overload (Turn on above 90%, Blink above 105%) ③ Key: Move to menu or reset ② Reset Esc ③ Reset/ESC: Fault reset or ESC from menu Enter: Enter into secondary menu or setting input Up/Down: Move the cursor up/down on screen or increase/decrease a setting value Right/Left: Move the cursor or setting right/left on screen (Rotation) Menu: Menu display ↔ Measurement display ④ ⑤ ⑥ ⑦ ⑧ ④ Ir: Long-time current setting, tr: Long-time tripping delay setting ⑤ Isd: Short-time current setting, tsd: Short-time tripping delay setting ⑥ Ii: Instantaneous current setting ⑦ Ig: Ground fault current setting, tg: Ground fault tripping delay setting ⑨ ⑧ Test terminal: OCR test terminal (Connected with OCR tester) ⑨ Rating plug - Rated current setting (45~100% of the AF) - Frequency selectable(60Hz/50Hz) 30 Trip relays Protection Long time Current setting (A) Time delay (s) Accuracy: ±15% or below 100ms Short time Current setting (A) Accuracy: ±10% Time delay (s) @ 10×Ir Ir = In×... tr@(1.5×lr) tr@(6.0×lr) tr@(7.2×lr) Isd = Ir×... tsd Earth leakage (Option) Current setting (A) Time delay (ms) Accuracy: ±15% 1.5 I2t Off 0.6 50 2 1.38 0.7 100 4 2.7 0.8 200 8 5.5 3 4 5 0.05 0.1 0.1 0.2 0.2 0.3 0.3 0.4 0.4 80 160 260 360 140 240 340 440 6 8 I2t On Min. Trip 20 Time(ms) Max. Trip 80 Time(ms) Ii = In×... 0.9 300 12 8.3 1.0 400 16 11 t Ir 500 20 13.8 Off Off Off 2 2 3 4 below 50ms 6 8 10 Off 10 12 15 Off Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.05 0.1 I2t Off I2t On 0.1 Min. Trip 20 80 Time(ms) Max. Trip 80 140 Time(ms) 0.2 0.2 0.3 0.3 0.4 0.4 160 260 360 240 340 440 1 2 3 5 230 350 800 950 0.7 0.8 1.0 Other protection Under voltage Over voltage Voltage unbalance Reverse power Over power Current unbalance Over 60Hz frequency 50Hz Under 60Hz frequency 50Hz lsd Ii I Off Ig (I2t Off) tg I t I△n △t 0.5 Alarm 140 Time(ms) Trip 140 Time(ms) 10 20 30 Off I n 230 350 800 t Note) Current setting values are secondary current of the external CT. Recommend : not to use current setting values more than 5A. PTA(Pre Trip Alarm) Current setting (A) Time delay (s) Accuracy: ±15% tr t tg Time delay (s) @ 1×In 0.5 25 1 0.69 tsd (I2t Off) Instantaneous Current setting (A) Tripping time Ground fault Pick-up (A) Accuracy: ±10%(Ig�0.4In) ±20%(Ig≤0.4In) 0.4 12.5 0.5 0.34 I Ip = Ir x … 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 tp@(1.2×Ip) 1 5 15 25 35 Off Setting range 80V ~ 0V_Pick-up UV_Pick-up ~ 980V 6% ~ 99% 10~500 kW 500~5000 kW 6% ~ 99% UF_Pick-up ~ 65 UF_Pick-up ~ 55 55Hz ~ OF_Pick-up 45Hz ~ OF_Pick-up Pick-up Step 1V 1V 1% 1kW 1kW 1% 1Hz 1Hz 1Hz 1Hz 10 Accuracy ±5% ±5% ±2.5% or (*±10%) ±10% ±10% ±2.5% or (*±10%) ±0.1Hz ±0.1Hz ±0.1Hz ±0.1Hz 20 30 Time delay(s) Setting range Step Accuracy 1.2~40sec 0.2~40sec 0.1sec ±0.1sec 1.2~40sec 31 Trip relays �type S type:�Supreme meter� - 128 x 128 Graphic LCD - Indicates current/voltage Vector Diagram and Waveform ■ Fault recording - Records Max. up to 256 fault information about fault type, fault phase, fault value, occurrence time of fault - Fault wave recording: records the latest fault wave ■ Event recording - Records events of device related to setting change, operation and state change. (Max. up to 256) ■ SBO (Select Before Operation) - High reliability for control and setting change method ■ Power quality analysis - Measurement for 1st~63th harmonics - THD, TDD, k-Factor - Voltage/current waveform capture ■ 3 DO(Digital output) - Programmable for alarm, trip and general DO ■ Communication - Modbus/RS485 - Profibus-DP ■ Overload protection - Long-time delay - Thermal ■ Short-circuit protection - Short-time delay / Instantaneous - I2t On/Off optional (for short-time delay) ■ Ground fault protection - I2t On/Off optional - Trip/Alarm selectable (need external power) - Blocking Time (0~60s) Do not ground fault detect during Blocking time ■ Protection for Over voltage/Under voltage/Over frequency/Under frequency/Unbalance/Reverse power ■ Realization of protective coordination by ZSI (Zone Selective Interlocking) - Disable/Enable ■ The fine-adjustable setting by knob and Key ■ IDMTL setting (SIT, VIT, EIT, DT curve) - Basic setting : “None”. Thermal curve. ■ Measurement and Display Function - High detailed measurement for 3 phase current/Voltage/ Power/Energy/Phase angle/Frequency/PF/Demand ① Graphic LCD: Indication of measurement and information ② LED: Indication of trip info. and overload state Alarm SP Ir Isd Ii Ig Comm ① Comm: LED indicating comm. state (Blink when running) Ig: LED indicating ground-fault Isd/Ii: LED indicating short-time or instantaneous tripping Ir: LED indicating long-time delay SP: Self-protection LED and battery test LED Alarm: LED indicating an overload (Turn on above 90%, Blink above 105%) ③ Key: Move to menu or reset ② Reset Esc ③ Reset/ESC: Fault reset or ESC from menu Enter: Enter into secondary menu or setting input Up/Down: Move the cursor up/down on screen or increase/decrease a setting value Right/Left: Move the cursor or setting right/left on screen (Rotation) Menu: Menu display ↔ Measurement display ④ ⑤ ⑥ ④ Ir: Long-time current setting, tr: Long-time tripping delay setting ⑦ ⑧ ⑤ Isd: Short-time current setting, tsd: Short-time tripping delay setting ⑥ Ii: Instantaneous current setting ⑦ Ig: Ground fault current setting, tg: Ground fault tripping delay setting ⑧ Test terminal: OCR test terminal (Connected with OCR tester) ⑨ 32 ⑨ Rating plug - Rated current setting (45~100% of the AF) - Frequency selectable(60Hz/50Hz) Trip relays Protection Long time Current setting (A) Time delay (s) Accuracy: ±15% or below 100ms Short time Current setting (A) Accuracy: ±10% Time delay (s) @ 10×Ir Iu = In×... tr@(1.5×lr) tr@(6.0×lr) tr@(7.2×lr) Isd = Ir×... tsd Earth leakage (Option) Current setting (A) Time delay (ms) Accuracy: ±15% 1.5 I2t Off 0.6 50 2 1.38 0.7 100 4 2.7 0.8 200 6 5.5 3 4 5 0.05 0.1 0.1 0.2 0.2 0.3 0.3 0.4 0.4 80 160 260 360 140 240 340 440 6 8 I2t On Min. Trip 20 Time(ms) Max. Trip 80 Time(ms) Ii = In×... 0.9 300 12 8.3 1.0 400 16 11 t Ir 500 20 13.8 Off Off Off 2 2 3 4 below 50ms 6 8 10 Off 10 12 15 Off Ig = In×... 0.2 0.3 0.4 0.5 0.6 I2t Off 0.05 0.1 I2t On 0.1 Min. Trip 20 80 Time(ms) Max. Trip 80 140 Time(ms) 0.2 0.2 0.3 0.3 0.4 0.4 160 260 360 240 340 440 1 2 3 5 230 350 800 950 0.7 0.8 1.0 Other protection Under voltage Over voltage Voltage unbalance Reverse power Over power Current unbalance Over 60Hz frequency 50Hz Under 60Hz frequency 50Hz lsd Ii I Off Ig (I2t Off) tg I t I△n △t 0.5 Alarm 140 Time(ms) Trip 140 Time(ms) 10 20 30 Off I n 230 350 800 t Note) Current setting values are secondary current of the external CT. Recommend : not to use current setting values more than 5A. PTA(Pre Trip Alarm) Current setting (A) Time delay (s) Accuracy: ±15% tr t tg Time delay (s) @ 1×In 0.5 25 1 0.69 tsd (I2t Off) Instantaneous Current setting (A) Tripping time Ground fault Pick-up (A) Accuracy: ±10%(Ig�0.4In) ±20%(Ig≤0.4In) 0.4 12.5 0.5 0.34 I Ip = Ir x … 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 tp@(1.2×Ip) 1 5 15 25 35 Off Setting range 80V ~ 0V_Pick-up UV_Pick-up ~ 980V 6% ~ 99% 10~500 kW 500~5000 kW 6% ~ 99% UF_Pick-up ~ 65 UF_Pick-up ~ 55 55Hz ~ OF_Pick-up 45Hz ~ OF_Pick-up Pick-up Step 1V 1V 1% 1kW 1kW 1% 1Hz 1Hz 1Hz 1Hz 10 Accuracy ±5% ±5% ±2.5% or (*±10%) ±10% ±10% ±2.5% or (*±10%) ±0.1Hz ±0.1Hz ±0.1Hz ±0.1Hz 20 30 Time delay(s) Setting range Step Accuracy 1.2~40sec 0.2~40sec 0.1sec ±0.1sec 1.2~40sec 33 Trip relays Operation characteristics Long-time delay (L) The function for overload protection which has time delayed Iu N, A type characteristic in inverse ratio to fault current. .8 Ir .9 1 .9 tr 4 .93 .85 .95 2 .6 .83 .98 1 .5 1. Standard current setting knob: Ir 1) Setting range in P type and S type: (0.4-0.5-0.6-0.7-0.8-0.9-1.0)×In 2) Setting range in N type and A type: (0.4 ~1.0)×In - Iu: (0.5-0.6-0.7-0.8-0.9-1.0)×In - Ir: (0.8-0.83-0.85-0.88-0.9-0.93-0.95-0.98-1.0)×Iu 2. Time delay setting knob: tr - Standard operating time is based on the time of 6×Ir - Setting range: 0.5-1-2-4-8-12-16-20-Off sec (9 modes) 3. Relay pick-up current - When current over (1.15)×Ir flows in, relay is picked up. 4. Relay operates basing on the largest load current among R/S/T/N phase. .88 .7 Iong time .8 ×In 1 P, S type .7 .8 .9 (S) .5 Iong time ×In I Short-time delay (S) The function for fault current (over current) protection which has definite 1. Standard current setting knob: Isd - Setting range: (1.5-2-3-4-5-6-8-10-Off)×Ir 2. Time delay setting knob: tsd - Standard operating time is based on the time of 10×Ir. - Inverse time (I2t On ): 0.1-0.2-0.3-0.4 sec - Definite time (I2t Off): 0.05-0.1-0.2-0.3-0.4 sec 3. Relay operates basing on the largest load current among R/S/T/N phase. 4. When ZSI function was set, the protection operation will take place instantaneously with input absence by downstream devices. It is advised to disable its ZSI function on the last downstream device. 4 5 tsd 6 (S) 8 .3 2 10 .2 1.5 .4 .4 .3 .2 .1 off .1 short time .05 on 2 off ×Ir I t t Isd tsd I Instantaneous (I) The function for breaking fault current above the setting value within the shortest time to protect the circuit from short-circuit. 1. Standard current setting knob: Ii - Setting range: (2-3-4-6-8-10-12-15-Off)×In 2. Relay operates basing on the largest load current among R/S/T/N phase. 3. Total breaking time is below 50ms. Ii 6 8 10 4 12 3 15 2 off instantaneous ×In t Ii I 34 12 16 20 .5 off @6 Ir tr 3 8 1 .4 Isd 4 2 1 Ir time characteristic and time delayed in inverse ratio to fault current. 16 off @6 Ir tr .6 t 12 20 .5 ×Iu Ir 8 Trip relays Ground Fault (G) The function for breaking ground fault current above setting value after time-delay to protect the circuit from ground fault. 1. Standard setting current knob: Ig - Setting range: (0.2-0.3-0.4-0.5-0.6-0.7-0.8-1.0-Off)×In 2. Time delay setting knob: tg - Inverse time (I2t On): 0.1-0.2-0.3-0.4 sec - Definite time (I2t Off): 0.05-0.1-0.2-0.3-0.4 sec 3. Ground fault current is vector sum of each phase current. Therefore, 3Pole products may operate under its phase-unbalance including ground fault situations.(R+S+T+(N) Phase) 4. When ZSI function was set, the protection operation will take place instantaneously with input absence by downstream devices. It is advised to disable its ZSI function on the last downstream device. 5. Ground-fault functions are basically provided with products equipped with a trip relay through its internal CT that is embedded in each phase.(But, it can’t be used with earth-leakage protection function at the same time) Ig .5 .6 tg .7 .4 (S) .4 .8 .3 .3 1 .2 .2 .4 .3 .2 .1 off .1 ground fault .05 on 2 off ×In I t t Ig tg I Earth Leakage (G) - Option The function for breaking earth leakage current above setting value after time delay to protect the circuit from earth leakage. (A, P, S type) 1. Standard setting current knob: I△n - Setting range: 0.5-1-2-3-5-10-20-30-Off (A) 2. Time delay setting knob: △t - Trip time: 140-230-350-800 ms - Alarm time: 140-230-350-800-950 ms 3. Settings within its alarm range will prevent its breaker from tripping but activating its alarm. 4. This function is enabled and can be used only with private external CT(secondary output 5A) selected by customers. 5. When ZSI function was set, the protection operation will take place instantaneously with input absence by downstream devices. It is advised to disable its ZSI function on the last downstream device. ※Use cautions with earth-leakage current settings I n 3 t (ms) 10 800 950 800 20 350 350 1 30 230 230 0.5 140 off 140 earth leakage trip alarm t I n t I R S T N - When using other CT selected by customers, the setting range is from 0.5 to 5A based on its secondary current.(Secondary output rating : 5A) Hence, under 100:5A CT, if trip relay is set to 0.5A, earth-leakage exceeding 10A will activate its operation (0.5A×20 = 10A) ZCT or External CT ※Guideline for the external CT usage - Earth-leakage protection characteristics using the standard CT which is installed inside of ACB can protect currents from 20 to 100% range on its rated current. - As rated currents on ACB increases, current that is covered by its standard CT increase as well. This can not protect against small leakage currents. ex) 400A ACB Min. Earth-leakage current 400A×20% =80A 4000A ACB Min. Earth-leakage current 4000A×20% =800A - Therefore, customers are advised to install an external CT in accordance with its rated currents within its systems. And choose trip relay(E, X type) which is required with external CT usage in order to provide earth-leakage functions. 5 2 A ZCT or External CT B 35 Trip relays Measurement function Measurement element Class. Current Voltage Angle Power Line current Ia,Ib,Ic Normal current I1 Reverse current I2 Vab,Vbc,Vca Va,Vb,Vc Unbalance V1 Reverse voltage V2 Line-to-line ∠VabIa, ∠VabIb, ∠VabIc, Line-to-current ∠VabVbc, ∠VabVca V 60~690V ° 0~360° ±1° ∠VaVb,∠VaVc ∠VaIa, ∠VbIb, ∠VcIc Active power Pa(ab), Pb(bc), Pc(ca), P kW 1kW~99,999kW ±3% Reactive power Qa(ab), Qb(bc), Qc(ca), Q kVar 1kVar~99,999kVar ±3% 1kVA~99,999kVA ±3% 1kWh~9999.99MWh ±3% 1kVarh~9999.99MVarh ±3% 1kWh ~9999.99MWh ±3% Sa(ab), Sb(bc), Sc(ca), S kVA WHa(ab), WHb(bc), kWh WHc(ca), WH MWh VARHa(ab), VARHb(bc), kVarh VARHc(ca), VARH Mvarh Reverse active rWHa(ab), rWHb(bc), kWh energy rWHc(ca), rWH MWh Frequency F Hz 45~65Hz Power factor(PF) PFa(ab), PFb(bc), PFc(ca), PF Unbalance rate Iunalance, Vunbalance % 0.0~100.0 Peak demand kW 1kW~99999kW Current demand Peak demand A 80A~65,535A Voltage 1st~63th harmonics of harmonics Va(ab),Vb(bc),Vc(ca) V 60~690V Current harmonics 1st~63th harmonics of Ia,Ib,Ic A 80A~65,535A THD, TDD % 0.0~100.0 K-Factor - 0.0~100.0 +: Lead, -: Lag For P and S type Trip relay, separate voltage module is necessary to measure other element besides current (Seperate purchase is needed) - Voltage input range: AC 60~690V Vr Vs Vt Vn Vr Vs Vt Voltage module 3P4W wiring 36 13 14 15 16 17 18 19 20 V1 V2 V3 Vn 1 2 3 4 5 6 7 8 9 10 11 12 ±1° ±1° Voltage module 1 2 3 4 5 6 7 8 9 10 11 12 ±1% Phase-to-phase demand Harmonics 80A~65,535A Phase-to-current Active power Demand Accuracy ±1% Normal voltage Reactive energy Power factor Display range A Line voltage Active energy Freq. Unit ±3% Phase voltage Apparent power Energy Detailed element Voltage module 3P3W wiring 13 14 15 16 17 18 19 20 V1 V2 V3 Vn Trip relays Man machine interface Measurement display Initial display 1000 A M R S T N Setting display 100% 1. H/W set 2. Relay set 3. Events 1. Wiring 1. OCR 1. Event 2. Comm 2. OCGR 2. Clear All 3. Password 3. OVR/UVR 3. Fault 4. Time-RTC 4. Unbal 4. Clear All 5. PT Ratio 5. rP/OPR 6. Demand 6. OFR/UFR 5. L/R (L) 4. Sys info 50% Initial display 7. Data Rst Max Power Demand Energy CB Count Run Time 8. DO Setup 9. Language 10. Option An example of graphic LCD display 1000 A 1000 A R S T R N S T N Ir .7 .8 Ir = .9 .6 1 100% 50% .5 100% .4 1000 A ×In 50% Ir adjustment knob Displayed screen when changing Ir value into 1.0 (After 3 sec, return to initial display) Initial display tg (S) .4 .4 Tg = .3 .3 .2 .1 .2 .1 .05 on 2 off I t 200 ms [I2t](Off) tg adjustment knob Displayed screen when changing tg value into 0.2 (After 3sec, return to initial display) 37 Trip relays Protection element setting Initial display 1000 A R S T Setting display M N 100% 50% PASSWORD 1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L] XXXX 1.OCR 2.OCGR 3.OVR/UVR 4.Unbal 5.rP/OPR Password input Relay setting display 1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L] Find adjustment of protection setting current Find adjustment of long-time delay OCR-L, S, I I2T [Off] 800 A EIT 6400 A Find adjustment of short-time delay Find adjustment of Instantaneous 15000 A OCR-L, S, I I2T [Off] OCR-L, S, I 800 A EIT 6400 A I2T [Off] 800 A EIT 6400 A 15000 A 1.OCR 2.OCGR 3.OVR/UVR 4.Unbal 5.rP/OPR 15000 A � Relay setting display 38 OVR/UVR Set Pick Up Delay Action Pick Up Delay Action Protection setting display 1.OCR 2.OCGR 3.OVR/UVR 4.Unbal 5.rP/OPR �OCR and OCGR's current setting is basically controlled by knob's setting values. �The fine current that cannot be controlled by knob is adjustable by using , key. �Fine adjustment is only adjustable in the present knob and next knob's setting range, when moving knob, the adjusted data becomes reset state. Select one IDTM characteristic curve among DT, SIT, VIT and EIT : 724 V : 1.2 s : None : 150 V : 1.2 s : D01 OVR/UVR setting � rPower Pick Up Delay Action Pick Up Delay Action OCR-L, S, I I2T [Off] 800 A EIT 6401 A 15000 A 1.OCR 2.OCGR 3.OVR/UVR 4.Unbal 5.rP/OPR � 6.OFR/UFR Relay setting display Unbal V/I Pick Up Delay Action Pick Up Delay Action Relay setting display :100 kW : 10.0 s : D02 : 2400 kW : 0.2 s : TRIP Reverse power setting �The setting method of OCGR is same with OCR's, fine adjustment is available. : 6% : 10.0 s : D02 : 12 % : 10.0 s : D03 Unbalance setting � OFR/UFR Set Pick Up Delay Action Pick Up Delay Action : 65 Hz : 10.0 s : D01 : 55 Hz : 10.0 s : None Frequency setting Trip relays Measurement element display Load current 1000 A R S N T 100% 50% �� Measurement overview Metering Overview Demand Current [A] Max Power [kW] VR 220 V∠0.0 R : 1000 987 IR 1000 A∠330.0 S : 1000 2007/05/14 P 986 kW T : 1000 10:00:00 Q 589 kVar PF 0.866 F 60.0 Max Demand [kW] 986 EP 56 kWh 2007/05/14 EQ 32 kVarh 11:15:00 �� Voltage/Current vector diagram Vector Diagram Vt It Vr Is Ir Vs VOLTGAE [V] VR : 220∠ 0.0 VS : 220∠240.0 VT : 220∠120.0 V unbal 3Phase Vpos : 220 V CURRENT [A] IR : 1000∠330.0 IS : 1000∠210.0 IT : 1000∠ 90.0 IN : 0 I unbal 3Phase Active Power [kW] Apparent [kVA] R : 328 Total R : 379 Total S : 328 986 S : 379 1139 T : 379 Vneg : 0 V Unbal : 0.0 % Ipos : 1000 A Ineg : 0 A Unbal : 0.0 % �� Power and power factor Power Diagram P=986 Q=589 T : 328 Reactive [kVar] kW 1000 kVar 2000 Power Factor R : 189 Total R : 0.87 Total S : 189 589 S : 0.87 0.866 T : 189 T : 0.87 �� Energy Forward Energy Forward P [kWh] Reverse P [kWh] P+ R : 360 Total R : 0 Total S : 360 1080 S : 0 0 Q+ 1051 kWh 607 kVarh T : Reverse Energy 360 Forward Q [kVarh] T : 0 Reverse Q [kVarh] P- 0 kWh R : 210 Total R : 0 Total Q- S : 210 630 S : 0 0 0 kVarh T : 210 T : 0 �� Voltage/Current harmonics (S type) Volt Wave & FFT [%] THD[S] : 25.0 I R S S Volt Harmonics [V] S Volt Harmonics [V] S Volt Harmonics [V] H1 220 H8 0 H15 0 H22 0 H57 0 H2 0 H9 0 H16 0 H23 0 H58 0 H3 55 H10 0 H17 55 H24 0 H59 0 H4 0 H11 0 H18 0 H25 0 H60 0 H5 0 H12 0 H19 0 H26 0 H61 0 H6 0 H13 0 H20 0 H27 0 H62 0 H7 0 H14 0 H21 0 H28 0 H63 0 �� Curr Wave & FFT [%] THD[R] : 3.0 T R Curr Harmonics [A] R Curr Harmonics [A] TDD 3Phase H1 1000 H8 0 H15 1 H22 0 H57 0 R : 0.1 % H2 0 H9 3 H16 0 H23 1 H58 0 S : 0.1 % H3 15 H10 0 H17 1 H24 0 H59 0 T : 0.1 % H4 0 H11 1 H18 0 H25 1 H60 0 Current K - Factor R Curr Harmonics [A] H5 20 H12 0 H19 1 H26 0 H61 0 R : 1.2 R H6 0 H13 1 H20 0 H27 1 H62 0 S : 1.2 S H7 0 H14 0 H21 1 H28 0 H63 0 T : 1.3 39 Trip relays Characteristics curves Long-time delay (L) 5000 2000 Ir = 0.4...1 In 1000 500 200 100 50 40 30 tr = 0.5...20s 20 20 12 10 t(s) 8 5 4 3 4 2 2 1 1 0.5 0.4 0.3 0.2 0.1 0.05 × Ir 40 20 10 7 5 4 3 2 1 0.7 0.01 0.5 0.02 Trip relays 5000 2000 1000 500 Isd = 1.5...10 Ir 200 100 50 40 30 20 10 t(s) 5 4 3 2 1 0.4 0.3 0.4 0.2 0.2 I2t ON 0.4 0.3 0.3 0.2 I2t OFF 0.1 0.1 0.1 0.05 0.05 20 10 7 5 4 3 2 1 0.01 0.7 0.02 0.5 Short-time delay (S) × Ir 41 Trip relays Characteristics curves Instantaneous (I) Ground fault (G) 100 50 40 30 20 Ig = 0.2...1 In 10 5 4 3 2 t(s) 1 I2t ON 0.4 0.4 0.3 0.3 0.2 0.2 0.2 0.1 I2t OFF 0.1 0.1 0.4 0.3 0.05 0.05 Ii = 2...15 In 42 × In 3 2 10 7 4 5 3 2 1 0.7 0.4 0.5 0.3 0.2 0.1 0.07 0.01 0.05 0.02 Trip relays 10000 5000 2000 EIT 1000 500 VIT 200 100 SIT t(s) 50 20 DT 10 5 2 20 10 7 5 4 3 2 1 0.05 0.7 1 0.5 IDMTL × Ir 43 Trip relays Characteristics curves Pre Trip Alarm 500 200 100 50 40 35 30 20 15 10 5 5 4 3 t(s) 2 1 1 0.4 0.3 0.2 0.1 0.05 × Ip 44 30 20 10 7 5 4 3 2 1 0.7 0.01 0.5 0.02 Trip relays ZSI - Zone Selective Interlocking (A, P, S type) Zone-selective interlocking drops delay time that eliminates faults for breakers. It minimizes the shock that all kinds of electric machineries get under fault conditions. 1. In case of that short time-delay or ground fault accident occurs at ZSI built in system, the breaker at accident site sends ZSI signal to halt upstream breaker’s operation. 2. To eliminate a breakdown, trip relay of ACB at accident site activates trip operation without time delay. 3. The upstream breaker that received ZSI signal adhere to pre-set short time-delay or ground fault time-delay for protective coordination in the system. However upstream breaker that did not receive its signal will trip instantaneously. 4. For ordinary ZSI operation, it should arrange operation time accordingly so that downstream circuit breakers will react before upstream ones under overcurrent/short time delay/ ground fault situations. 5. ZSI connecting line needs to be Max. 3m. ① Z4 Z3 Z2 Z1 ZSI input Fault A ② Z4 Z3 Z2 Z1 ZSI output ZSI input Fault B Z4 Z4 Z4 Z3 Z3 Z3 Z2 Z2 Z2 Z1 Z1 Z1 1) Occurrence of fault A - Only breaker ① performs instantaneous trip operation. 2) Occurrence of fault B - Breaker ② performs instantaneous trip operation, breaker ① performs trip operation after prearranged delay time - But if breaker ② did not break the fault normally, breaker ① performs instantaneous trip operation to protect system. 45 Trip relays Remote reset and digital I/O (A, P, S type) In case of that ACB operates due to accidents or over current, Trip relay indicates the information of the accident through the LED and LCD. Trip relay A, P and S type is possible to perform the remote reset by digital input, and have 3 DO(Digital output). 1. Methods to reset Trip relay is to push the Reset button on the frontal side and to use the remote reset. 2. Digital input - [R11-R22] input: Remote reset - [Z1-Z2] Input: ZSI input - [E1-E2] Input: ZCT for earth leakage detection or external CT input ※All DI are dry contact that has 3.3V of recognition voltage. When inputting close by SSR(Solid State Relay) or open-collector, connect collector(Drain) to R11. V1 V2 V3 Vn E1 Z3 Z1 Common Reset ZCT ZSI input Voltage module ZSI output 3. Digital output 3a(524, 534, 544-513) - Fault output: Long/Short time delay, Instantaneous, Ground fault, UVR, OVR, UFR, OFR, rPower, Vunbal, Iunbal (Maintains state as Latch form until user pushes reset.) - General DO: when setting L/R as remote, it is available to control close/open remotely by using communication. 485+ R11 R22 513 544 534 524 Power supply R2 R1 485- Trip Relay Digital Output LTD Z2 GTD Z4 S/I Trip relay Long Short Instantaneous Ground Overload OVR UVR rPower Vunbal Iunbal OFR UFR OPR Alarm time time DO1(524) P, S DO2(534) type DO3(544) ● ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ● ● ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ● ○ ○ ○ ○ ○ ○ ○ ○ ○ DO1(524) ● × × × A type DO2(534) × ● ● × DO3(544) × × × ● 46 Not available Note Programmable Fixed Trip relays Communication Modbus/RS-485 �Operation mode: Differential �Distance: Max. 1.2km �Cable : General RS-485 shielded twist 2-pair cable �Baud rate : 9600bps, 19200bps, 38400bps �Transmission method: Half-Duplex �Termination: 100Ω SCADA system Modbus/RS-485 Profibus-DP �Profibus-DP module is installed separately (Option) �Operation mode: Differential �Distance: Max. 1.2km �Cable : Profibus-DP shielded twist 2-pair cable �Baud rate: 9600bps~12Mbps �Transmission method: Half-Duplex �Termination resistor: 100Ω �Standard: EN 50170 / DIN 19245 Ethernet/TCP/IP Area controller TCP/IP/Ethernet TCP/IP CNC Profibus-FMS PC DCS PLC Profibus-DP Profibus-DP communication module (Option) Profibus-DP communication module (Option) PLC Modbus/RS-485 47 Trip relays Event & fault recording (P, S type) When there are events such as setting change, Info. change, error of self-diagnose, state change, P and S type record Max. up to 256 information of the events in accordance with time(ms). In addition, they can record Max. up to 256(up to 10 for A type) information of the faults such as fault cause, fault phase, fault value and so on in accordance with time(ms). Event information display Initial display Setting display 1000 A R S T M N 100% 50% Password input 1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L] 1.Event 2.Clear All 3.Fault 4.Clear All 1. Event-L 2007/05/15 20:29:41 Sta Change 10. Event-L 2007/04/15 10:11:24 Cfg Change Power On Comm Set up Fault information display Initial display Setting display 1000 A R S T M N 100% 50% Password input 1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L] 1.Event 2.Clear All 3.Fault 4.Clear All 1. Trip 2007/04/26 08:35:52 OCR-Short 9. Trip 2007/04/11 09:11:32 UVR Phase T Phase R 930A System information P and S type can indicate information as followings with the information of the ACB. - Present time: year/month/date/hour/minute/ms - ACB current ratings - N-phase current ratings: 100% - Frequency information: 60Hz / 50Hz - Closing numbers of breaker: CB ON numbers - Trip relay operating time: OCR ON time - ON time of breaker: CB ON time - F/W ver. information System information display Initial display Setting display 1000 A R 100% 50% 48 S T N M 1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L] Password input System Info Date Time 2007/05/15 21:23:30 Rating 1000 A Ex-Func 4POCGR Freq 60 Hz CB ON# 23 Ver-Arm 1.5 System Info Date Time 2007/05/15 21:23:30 Rating 1000 A Ex-Func 4POCGR T-OPER 220 h T-CB ON 180 h Ver-Msp 4.01A OV Trip relays System block diagram R S T N ACB Trip ACB Vcc/+9V/-9V CN2-1 CN2-11 Filter Amp. CN2-3 CN2-13 Signal CT CN2-5 CN2-15 Vcc CPU Output Power PCB Ass’y +5V +24V Display (LED, LCD) Main PCB Ass’y MTD CN2-6 Output CN2-8 Main PCB Ass’y CN2-7 CN2-16 CN2-14 Setting part GND 24 CN2-4 Vcc Self power RY0 (K1) CN4-2 GTD contact +24V GND+24V Power CT Main PCB Ass’y RY1 (K2) CN4-4 STD/INST contact +5V RY2 (K3) -5V CN4-6 LTD contact CN2-2 CN4-9 SMPS CN4-10 Power PCB Ass’y Trip relay Additional source AC/DC 100~250V DC 24~60V CN4-8 Common contact CN1-1 ZSI output+ terminal CN1-2 ZSI output- terminal CN1-3 ZSI input+ terminal CN1-4 ZSI input- terminal CN1-9 CN1-10 VDM CN1-11 CN1-12 CN1-5 Remote reset+ terminal CN1-6 Remote reset- terminal CN1-7 Earth CN1-8 CN1-7 Earth leakage+ terminal Input signal(R phase) CN3-2 Input signal(S phase) CN3-4 CN1-8 Earth leakage- terminal Input signal(T phase) CN3-6 Input signal(N phase) CN3-8 DC 24V CN3-5 UTXO CN3-1 URXO CN3-3 GND 24V CN3-7/9 AD GND CN3-10 Test Main PCB Ass’y Comm. Power PCB Ass’y CN4-1 485+ terminal CN4-3 485- terminal 49 Accessories Mounting Accessories AH Standard ● SHT1 Shunt Coil M CS1 Internal ● 54 Motor ● 55 Charge Switch ● 55 CS2 Charge Switch Communication ** ○ 55 UVT Under Voltage Trip Device ○ 56 Trip Alarm Contact ** ○ 57 MRB Manual Reset Button ** ○ 57 RES ○ 58 ○ 58 AL C Remote Reset Switch ● Counter 65 AX Auxiliary Switch ○ 59 TM Temperature Alarm ** ○ 74 K1 Key Lock ○ 60 K2 Key Interlock Set ○ 60 K3 Double Key Lock ○ 61 B On/Off Button lock ○ 61 Lifting Hook ○ 62 CTD Condenser Trip Device * ○ 62 ATS Automatic Transfer Switch Controller * ○ 63 DC Dust Cover ○ 65 DF Door Frame ○ 68 OT OCR Tester ○ 64 LH * * Non UL Listed. ** Separate purchasing is not allowed. Each item should be purchased with the main body. 50 53 Closing Coil RCS Ready to Close Switch External Page 52 ○ SHT2 Double Shunt Coil CC Option Accessories Mounting Accessories Page 26 A A type ○ 28 P P type ○ 30 32 S type ○ VM Voltage Module ○ SBC Shorting "b" Contact * ○ MI Mechanical Interlock ** ○ 67 ST Safety Shutter ○ 68 MIP Miss Insertion Prevent Device ○ 72 MOC Mechanical Operated Cell Switch ○ 66 CEL Cell Switch ○ 69 Door Interlock ○ 67 Body Supporter ○ 70 ○ 70 DI BSP Other Option ○ S Cradle Standard N type N Trip relay AH RI Racking Interlock PL Pad Lock/ Position Lock ● 71 UDC UVT Time Delay Controller ○ 73 RCO Remote I/O ○ 75 PC Profibus-DP comm. module ○ * Non UL Listed. ** Separate purchasing is not allowed. Each item should be purchased with the main body. *** Voltage module should be purchased with P/S type trip relay. **** It is available only when the control block is in the mode of auto-connection. ***** Trip unit P type & S type are under development, coming soon. 51 Accessories Shunt Coil [SHT1] �SHT1 is a control device which trips a circuit breaker from remote place, when applying voltage continuously or instantaneously over 200ms to coil terminals(C1, C2). Shunt coil 1 �When UVT coil is installed, its location is changed. 1. Rated voltage and characteristics of Trip coil Rated voltage [Vn] DC [V] AC [V] Power consumption (VA or W) Operating voltage range [V] 24~30 - 14 ~ 33 48~60 48 28 ~ 66 100~125 100~125 70 ~ 140 200~250 200~250 140 ~ 280 - 380~480 * 266 ~ 528 Inrush Steady-state 200 5 Trip time [ms] Opening order Less 40ms 2. Specification of the wire �Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] Wire type Operating voltage 52 SHT1 C2 Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn). * Non UL Listed. DC 24~30 [V] C1 than DC/AC 48 [V] #14 AWG #16 AWG #14 AWG #16 AWG (2.08mm2) (1.31mm2) (2.08mm2) (1.31mm2) 100% 95.7m 61m 457.8m 287.7m 85% 62.5m 38.4m 291.7m 183.2m * 점선은 The dotted to Userline 배선임 be made by the Wiring Diagram customer Wiring Diagram Accessories Double Shunt Coil [SHT2] �SHT2 is a control device which trips a circuit breaker doubly from the outside. When SHT1 doesn’t operate normally, it can trip a circuit breaker safely. Shunt coil 1 Shunt coil 2 �Shunt coil 1: Install it at existing location. �Shunt coil 2: Install it on the right side of the Shunt coil 1 �It is not available with UVT coil when installing double shunt coil. 1. Rated voltage and characteristics of Trip coil Rated voltage [Vn] DC [V] AC [V] Power consumption (VA or W) Operating voltage range [V] 24~30 - 14 ~ 33 48~60 48 28 ~ 66 100~125 100~125 70 ~ 140 200~250 200~250 140 ~ 280 - 380~480 * 266 ~ 528 Inrush Steady-state 200 5 Trip time [ms] Less Opening order C11 than 40ms SHT2 C12 Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn). * Non UL Listed. 2. Specification of the wire �Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. * The dotted line to be made by the customer Wiring Diagram The maximum wire length Rated voltage [Vn] DC 24~30 [V] Wire type Operating voltage DC/AC 48 [V] #14 AWG #16 AWG #14 AWG #16 AWG (2.08mm2) (1.31mm2) (2.08mm2) (1.31mm2) 100% 95.7m 61m 457.8m 287.7m 85% 62.5m 38.4m 291.7m 183.2m 53 Accessories Closing Coil [CC] �It is a control device which closes a circuit breaker, when the voltage is applied continuously or instantaneously over 200ms to the coil terminals (A1, A2). Closing coil 1. Rated voltage and characteristics of Closing coil Rated voltage [Vn] DC [V] AC [V] Power consumption (VA or W) Operating voltage range [V] 24~30 - 14 ~ 33 48~60 48 28 ~ 66 100~125 100~125 70 ~ 140 200~250 200~250 140 ~ 280 - 380~480 * 266 ~ 528 Inrush Steady-state 200 5 Close time [ms] Less 2. Specification of the wire �Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] Operating voltage 54 CC A2 Note) Operating voltage range is the min. rated standard for each rated voltage (Vh). * Non UL Listed. ** Close time of G frame (3200~5000A) is less than 95ms. Wire type A1 than 80ms ** DC 24~30 [V] Closing order DC/AC 48 [V] #14 AWG #16 AWG #14 AWG #16 AWG (2.08mm2) (1.31mm2) (2.08mm2) (1.31mm2) 100% 95.7m 61m 457.8m 287.7m 85% 62.5m 38.4m 291.7m 183.2m * The dotted line to be made by the customer Wiring Diagram Accessories Motor [M] �Charge the closing spring of a circuit breaker by the external power source. Without the external power source, charge manually. Motor �Operating voltage range 85%~110%Vn Gear Main axis Input voltage(V) Load current(max.) DC 24~30V AC/DC 48~60V AC/DC 100~130V AC/DC 200~250V 5A 3A 1A 0.5A Starting current(Max.) 5 times of load current Load rpm(Motor) 15000 ~ 19000 rpm Charge time AC 380V * AC 440~480V * 0.3A 0.3A Less than 5sec. Dielectric strength 2kV/min Using temperature range -20。 ~ 60。 Using humidity range Max. RH 80% (No dew condensation) Endurance 15,000 cycle (Load connection, 2 times/min) Charge switch 10A at 250VAC * Non UL Listed. Charge Switch [CS1] Charge Switch Communication [CS2] �It is a built-in contact which sends the signal to the outside, when motor charging is completed. (2a) �It has a “1a” contact for communication and the other “1a” contact for complete charging. �When using an extra communication module (Remote I/O), the state of contacts can be displayed through the network. Classification Contactor Capacity Standard Remark 250/125 Vac 10 A 250 Vdc 0.3 A 125 Vdc 0.6 A 48 Vdc 3A 24 Vdc 5A 55 Accessories Under Voltage Trip device [UVT] �If the voltage of the main or the control power is under voltage, UVT which is installed inside of the breaker breaks the circuit automatically. Please connect with UVT time-delay device in order to present the timedelay function because UVT is technically instantaneous type. UVT coil Shunt coil �The closing of a circuit breaker is impossible mechanically or electrically if control power not supplied to UVT. To close the circuit breaker, 65~85% of rated voltage should be applied to both terminals of UVT coil (D1, D2). Closing coil �When using UVT coil, the double trip coil can not be used, and the location of trip coil is changed. 1. Rated voltage and characteristics of UVT coil Rated voltage [Vn] DC [V] AC [V] 24~30 - 48~60 48 100~130 100~130 200~250 200~250 - 380~480 Operating voltage range [V] Power consumption (VA or W) Pick up Drop out Inrush Steady-state 0.65~0.85 Vn 0.3~0.6 Vn 200 5 Trip time [ms] Less than 50ms Note) Operating voltage range is the min. rated standard for each rated voltage (Vh). 2. Specification of the wire �Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length Rated voltage [Vn] DC 24~30 [V] #16 AWG #14 AWG #16 AWG (2.08mm2) (1.31mm2) (2.08mm2) (1.31mm2) 100% 48.5m 30.5m 233.2m 143.9m 85% 13.4m 8.8m 62.5m 39.3m Wire type Operating voltage Note) In case of using UVT coil, the location of Shunt coil is changed. 56 DC/AC 48 [V] #14 AWG Accessories Trip Alarm Contact [AL] �When a circuit breaker is tripped by OCR which operates against the fault current (Over Current Relay), Trip Alarm switch provides the information regarding the trip of circuit breaker by sending the electrical signal from the mechanical indicator on front cover of main circuit breaker or internal auxiliary switch. (Installed at the inside of circuit breaker) AL1, 1a AL2, 1a �When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops out from the front cover and the switch (AL) which sends control signal electrically is conducted to output the information occurred from fault circuit breaker. �MRB and AL can be operated only when tripping by OCR, but doesn’t be operated by Off button and OFF operation of trip coil. �To re-close a circuit breaker after a trip, press MRB to reset it for closing. �2pcs of electrical trip switch (AL1, AL2, 1a) are provided (Option) �Trip alarm contact and MRB(Manual reset bottom) need to be purchased together. 1. Electrical characteristics of trip alarm contact Classification Contactor Capacity Standard Remark 250/125 Vac 10 A 250 Vdc 0.3 A 125 Vdc 0.6 A 48 Vdc 3A 24 Vdc 5A Manual Reset Button [MRB] �It is a function which resets a circuit breaker manually when a circuit breaker is tripped by OCR. �When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops out from the front cover and the switch(AL) which sends control signal electrically is conducted to output the information occurred from fault circuit breaker. �MRB can be operated only by OCR but not by OFF operation of circuit breaker. To re-close a circuit breaker after a trip, press MRB to reset it for closing. Manual reset button MRB reset lever Manual reset button Note) The manual reset button is protruded in the event of trip. 57 Accessories Remote Reset Switch [RES] �Following tripping, this function resets the "fault trip" alarm contacts(AL) and the mechanical indicator(MRB) and enables circuit breaker closing. Push button switch : AC 125V 10A, AC 250V 6A, DC 110V 2.2A, DC 220V 1.1A Resistive load �In case of auto reset type circuit breaker Following tripping, a reset of Manual Reset Button(MRB) or Remote Reset Switch(RES) is no longer required to enable circuit breaker closing. The mechanical indicator(MRB) and electrical indicator(AL) remain in fault position until the reset button is pressed. �AL2 and RES are alternative. 1. Rated voltage and rated current of RES Rated voltage Operating current(Max.) AC/DC 100~130V AC/DC 200~250V AC 6A DC 5A AC 3A DC 2.5A Operating time Wire spec. #14 AWG (2.08 mm2) Less 40ms #16 AWG (1.31 mm ) 2 Reset order 183 Connect to inner micro switch RES 184 Connect to AL2 / RES * The dotted line to be made by the customer Wiring Diagram Ready to Close Switch [RCS] �It interlocks with mechanism of circuit breaker. �It indicates the status that the circuit breaker is ready to do closing operation. �When mechanism is in OFF position or in Charge, contact is output with “ON” and it indicates that mechanism can be closed. Classification Standard Ready to close switch Remark 250/125 Vac 10 A Contactor Capacity 58 250 Vdc 0.3 A 125 Vdc 0.6 A 48 Vdc 3A 24 Vdc 5A “A” contact Contact part Accessories Auxiliary switch [AX] �It is a contact used to monitor ON/OFF position of ACB from remote place. AUX. contact & charging types AX Standard OFF charge 3a3b AC Standard ON charge 3a3b BX Standard OFF charge 5a5b BC Standard ON charge 5a5b HX High capacity OFF charge 5a5b HC High capacity ON charge 5a5b Standard CC Standard ON charge 6a6b JC High capacity ON Charge 6a6b High capacity Standard classification Standard 2000, 5000AF High capacity 4000, 6300AF Classification Standard Contactor Capacity No. of Contact that can be used 2000, 5000AF 4000, 6300AF High capacity 250/125 Vac 10 A 250/125 Vac 10 A 250 Vdc 0.3 A 250 Vdc 3A 125 Vdc 0.6 A 125 Vdc 5A 48 Vdc 3A 48 Vdc 10 A 24 Vdc 5A 24 Vdc 10 A AX 3a3b - BX 5a5b - HX - 5a5b AC 3a3b - BC 5a5b - CC 6a6b - HC - 5a5b JC - 6a6b Remark Standard charging type Rapid autoreclosing charging type 59 Accessories Key Lock [K1] �It is a device for locking which prevents a certain circuit breaker from being operated by user‘s discretion when two or more circuit breakers are used at the same time. �K1: Preventing mechanical closing K1 Key Interlock Set [K2] �3 circuit breakers can be arranged for the continuous power supply to the load side and be interlocked mutually by using Key Lock embedded in each circuit breaker. ACB-1 ACB-2 ACB-3 ● ● ● Wiring Status LOAD1 LOAD2 ● OFF OFF ○ ○ ON ON ○ ● ○ ON ON ○ ○ ● ON ON ● ● ○ OFF OFF ● ○ ● OFF ON ○ ● ● ON OFF ACB1 ACB2 ○: Release ●: Lock ACB3 Load 1 60 Load 2 Accessories Double Key Lock [K3] �When only two keys are released at the same time, circuit breakers operate. Handling method is same as K1. Key interlock double ON/OFF Button Lock [B] �It is to prevent manual operation of ACB’s closing/tripping button due to user’s wrong handling. �It is not possible to handle ON/OFF operation under the “Button lock” status. Note) Padlocks(∅5 ~ ∅6) are not supplied. ON/OFF button lock 61 Accessories Lifting Hook [LH] �It is a device to make an ACB easy to shift. �Please hang it to both handles of the arc cover. Condenser Trip Device [CTD] Ratings �It gets a circuit breaker tripped electrically within regular time when control power supply is broken down and is used with Shunt coil, SHT. In case there is no DC power, It can be used as the rectifier which supplies DC power to a circuit breaker by rectifying AC power. External dimension 131 118 Ratings Specification Model CTD-100 Rated input voltage (V) AC 100/110 CTD-200 AC 200/220 ㎐) Frequency (㎐ 50/60 50/60 Rated charge voltage (V) 140/155 280/310 Charging time Within 5S Within 5S Trip possible time Over 3 min. Over 2 min. Range of Input voltage (%) 85~110 85~111 Condenser capacity ㎌ 400㎌ ㎌ 160㎌ Circuit diagram 7.5 15 AC input 108 75 75 Side view * Non UL Listed. Rear view 62 Front view DC output Accessories Automatic Transfer Switch Controller [ATS] Ratings Model type ATSC-110 ATSC-220 Rated voltage AC 110V AC 220V Voltage range AC 93.5(±5%) ~126.5V(±5%) AC 187(±5%) ~ 253V(±5%) Frequency 50Hz/60Hz Power consumption (apparent power) 15.4W 4-location switch (stop, N, R, Auto) � � Test function � � Generator control function � � N power source setting (phase-to-phase/ 3phases) � � Time setting (T1~T6) � � Fault function (OCR/Circuit breaker trouble) � � Output contact (Auto, Load burden) � � - - Communication function (RS-485) �T1: The delayed time from when UN (power supply of electric company) is tripped to when generator start-up signal contact is closed. (t1: 0.2, 0.5, 1, 2, 4, 8, 15, 30, 40, 50secs) �T2: The delayed time from when UN is closed to when ACB2 is tripped. (t2: 0.2, 1, 2, 4, 8, 15, 30, 60, 120, 240secs) �T3: The delayed time from when ACB1 is tripped to when ACB2 is closed. (t3: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs) �T4: The delayed time from when ACB2 is tripped to when ACB1 is closed. (t4: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs) �T5: The delayed time when ACB1 is closed to when generator start-up signal contact is opened. (t5: 60, 120, 180, 240, 300, 360, 420, 480, 540, 600secs) �Stop-mode: This mode is for compulsory trip of ACB1(electric power company) or ACB2 (power station) when UN (power supply of electric power company) or UR (power supply of power station) is available *UN or UR should be kept in ON position �N-mode: This mode is for compulsory closing of ACB1 when UN is available. * it does not matter to be ON or OFF position of UR and if converting to N-mode while using UR, generator start-up signal contact is opened. �R-mode: This mode is for compulsory closing of ACB2 during the use of UR regardless of that UN is available or not. �Auto-mode: This mode is for transferring a circuit breaker automatically to available power supply of UN or UR. In short, it trips the circuit breaker where power supply is not available and it close the circuit breaker where power supply is available. * Non UL Listed. 63 Accessories OCR Tester [OT] �It is a device which can test for the operation of Trip Relay under no power condition. 1. Maximum 17 times rated current can be inputted. 2. It is possible to enter the current value and phase on each of R/S/T/N 3. Frequency is adjustable. 4. It is available to test for long time delay/short time delay/instantaneous /ground fault. OCR tester Configuration R S T N R, S, T, N phase signal input Increase/Decrease signal input ENT. ESC START STOP Signal setting/Delete Waveform generation/Stop 50Hz 60Hz Hz * Non UL Listed. 64 Select frequency Accessories Dust Cover [DC] �Attach it to the door frame. �It protects the product against the dust (IP5X) which may cause fault operation and enhances the sealing degree by being mounted to protrude type of panel. �It is transparent so that the front side of ACB is visible and the Cover can be opened/closed even if ACB is drawn out to until TEST position. Panel door Dust cover Door frame Counter [C] �It displays the total number of ON/OFF operation of ACB. Counter 65 Accessories Mechanical Operated Cell Switch [MOC] a1 a2 a3 a4 a5 b1 b2 b3 b4 b5 a1 a2 a3 a4 a5 b1 b2 b3 b4 b5 13 23 33 43 53 11 21 31 41 51 13 23 33 43 53 11 21 31 41 51 14 24 34 44 54 12 22 32 42 52 14 24 34 44 54 12 22 32 42 52 AUX S/W AUX S/W �It is the contact (10a10b) which displays the ON/OFF condition of ACB. It mechanically operates only when the breaker is “CONNECTED” position. A standard type and a high capacity type is available. �The contact capacity is as same as the ratings of aux. contacts. �When MOC link is installed to cradle, MOC can be equipped with the inside of panel. 66 Accessories Mechanical Interlock [MI] �It is used to interlock closing and trip between two or three breakers mechanically so as to prevent unintended operation at the same time. �Wire type interlock can be applied upto 3 breakers Door Interlock [DI] �It is a safety device which does not allow the panel door to open when a circuit breaker is in the “ON” position. Install on the door of panel Install on the side plate of ACB cradle 67 Accessories Safety Shutter [ST] �It is the automatic safety device to protect the connectors of main circuit by cutting off dangerous contact from outside while the breaker is drawn out. When the ACB is drawn in, the shutter is automatically opened. �There are 4 types of Safety Shutter and they are divided as shown in figure below. The types of safety shutter plate 1600AF, 3P 1600AF, 4P 3200AF, 3P 3200AF, 4P Safety shutter 5000AF, 4P 5000AF, 4P Door Frame [DF] �When structuring the embedded type of ACB panel, it protects the protrude front of ACB and the cutting side of panel door by attaching it to the panel door. Fixed type Door frame Panel door Draw-out type 68 Accessories Cell Switch [CEL] �It is a contact which indicates the present position of ACB.(CONNECTED, TEST, DISCONNECTED) Cell switch <Contact configuration> 4C: 1Disconnected +1Test +2Connected ※ Contact configuration can be changeable if necessary. ACB position Draw-in and draw-out position DISCONNECTED DISCONNECTED CONNECTED TEST CONNECTED ON CL-C (Connected) Contact OFF CL-T operation (Test) ON OFF ON CL-D OFF (Disconnected) Classification Standard 250/125 Vac 10 A Contact 250 Vdc 0.3 A capacity 125 Vdc 0.6 A 48 Vdc 3A 24 Vdc Contact number 5A 4C 69 Accessories Body Supporter [BSP] �It interlocks the main body of circuit breaker and cradle mechanically to fix the former in connected position. Therefore, all draw-in/outs are not available. Body supporter * Non UL Listed. Racking Interlock [RI] Door plate Handle inserting hole Racking interlock �When panel door is opened, Draw in/out handle doesn’t be inserted. Thus, panel handle can be inserted only when panel door is closed. 70 Accessories Pad Lock / Position Lock [PL] Draw-in button Pad lock ACB is subject to restriction regarding moving in connected, test, disconnected when drawing in or out. If main body of ACB is placed in 3 positions, it is locked and stopped when drawing in or out. �As shown in the figure, if draw-in/out button pops out, it means locking is operating. �To continue Draw-in/out operation, release lock by pushing Draw-in/out button �In case it is locked as shown in the figure above, main body of ACB can not be drawn in or out into the cradle. �For the lock device, user has to purchase it. (∅5 ~ ∅6) 71 Accessories Miss Insertion Prevent Device [MIP] C E G 1 2 A B 3 4 D 5 6 F 7 Cradle ACB body �When the main body of ACB is inserted to the cradle, if the ratings of ACB does not match with cradle, it mechanically prevents ACB from being inserted into cradle of ACB. �The installation method is variable according to ratings. 72 Cradle ACB ABCD 567 ABCE 467 ABCF 457 ABCG Cradle ACB Cradle ACB Cradle ACB ADEF 237 ABEG 346 BCEG 146 ADEG 236 ABFG 345 BDEF 137 ADFG 235 ACDE 267 BDEG 136 456 AEFG 234 ACDF 257 BDFG 135 ABDE 367 BCDE 167 ACDG 256 CDEF 127 ABDF 357 BCDF 157 ACEF 247 CDEG 126 ABDG 356 BCDG 156 ACEG 246 CEFG 124 ABEF 347 BCEF 147 ACFG 245 DEFG 123 Accessories UVT Time Delay Controller [UDC] �UVT is a device which makes ACB tripped automatically to prevent the accident on load side due to under voltage or power breakdown. There are two types, Instantaneous type and time delay type. �It can be installed on the rail or to the cradle. �Instantaneous type: only available with UVT coil. �Time delay type: available by connecting UVT coil and UVT time delay controller. �Common use for the all types. UVT time delay controller 1. The rated voltage and characteristic of UVT time delay controller Rated voltage [Vn] DC [V] Operating voltage range [V] AC [V] 48~60 48 100~130 100~130 200~250 200~250 - 380~480 Power consumption (VA or W) Pick up Drop out Inrush Steady-state 0.65~0.85 Vn 0.4~0.6 5Vn 200 5 Trip time[s] 0.5, 1, 1.5, 3 Note) Operating voltage range is the min. rated standard for each rated voltage (Vh). 2. Wiring 1. Wiring for general type 2. Wiring for special type Rated voltage (Vn) Rated voltage (Vn) Delay trip function 5 7 5 7 14 16 14 16 D2 Instantaneous trip function D1 D2 D1 ACB ACB Rated voltage (Vn) Rated voltage (Vn) * The wiring presented with red color should be set by uesers. 73 Accessories Temperature Alarm [TM] �Temperature Alarm Unit is a device to show the temperature through a sensor inside of ACB. Temperature alarm �The temperature sensor can be installed up to 2 and the output is connected to control terminal blocks. �It displays the maximum temperature of them and transmits through a network. �If the temperature is higher than a standard, an alarm can occur. �Temperature alarm unit communicates with Modbus / RS-485 basically, Profibus-DP need to be purchased separately. �Temperature alarm unit is installed on the cradle or the inside of panel. Control power AC/DC 110/220V 1 2 Power 24V 24V GND 5V 5V GND 13 14 15 3 16 4 5 Relay 3 DO control 17 18 6 Temperature alarm Temperature Alarm(+) Temperature Alarm(-) 7 Temp. Sensor input 1 8 9 RS-485(-) 19 10 RS-485(+) 20 Temp. Sensor input 2 Temp. Sensor input 3 Temp. Sensor input 4 Temp_COM 11 12 Temperature LED(℃): 10 ~150℃, Warning (Indicates the maximum value) 74 * RS-485 MODBUS Profibus-DP *In case of using Profibus-DP communication, it needs to communicate with ACB trip relay. Accessories Remote I/O Unit [RCO] Control Power AC/DC 110/220V 1 Power 2 CB ON 3 CB OFF 4 General DI 1 24V 24V GND 5V 5V GND Relay 0 CB close 13 14 CB ON(+) CB ON(-) 15 Relay 1 CB open CB OFF(+) 16 CB OFF(-) Remote I/O Unit 5 General DI 2 6 DI_COM 7 8 RS-485(-) 19 RS-485(+) 20 9 10 11 RS-485 12 Alarm MODBUS Profibus-DP *In case of using Profibus-DP communication, it needs to communicate with ACB trip relay. Classification CB control * Applied range Contact switching capacity Remarks AC230V 16A / DC30V 16A Max. switching capacity 3680VA, 480W Contact switching capacity AC230V 6A / DC25V 6A Max. switching capacity 1880VA, 150W Induction load (cos∅=0.4, L/R=7ms) �Remote I/O unit has the I/O contact which can trip or close the ACB from the remote site by communication. �For the General DO, the output of DI1 or DI2 is selectable. �Remote I/O Unit communicates with Modbus / RS-485 communication basically, Profibus-DP need to be purchased separately. �It supports SBO (Select Before Operation) function and guarantees the control reliability. �Remote I/O Unit can be installed on the cradle of ACB or the inside of panel. - Baud rate setting - Comm. address setting - Temperature setting LED 1 Status DI1 Indicates digital Input #1condition 2 DI2 Indicates digital Input #2condition 3 DO ON Indicates temperature alarm output is ON 4 DO OFF Indicates temperature alarm output is OFF 5 CB ON Indicates circuit break close condition 6 CB OFF Indicates circuit break open condition 7 RUN LED 8 CB ERROR Indicates unit run condition Indicates circuit break terminal Disconnection / control Err condition 75 Electrical diagram V2 V3 VN E1 Z3 Z1 485+ R11 R22 513 R2 R1 251 83 183 /RES(+) Trip relay D1 C11 ON OFF Power supply OFF Common Reset ZCT V1 ZSI Input Voltage module ZSI Output This diagram is based on “CONNECTED” position of a circuit breaker and Opening, Motor charging, Releasing of locking plate should be normal condition. C1 UVT SHT2 SHT1 A1 CC 485- 544 534 524 LTD Z2 252 Digital trip relay 84 184 /RES(-) D2 C12 Ready to close Secondary trip coil Terminal code description 13 14 ~ 63 64 Auxiliary switch “a” D1 D2 Voltage input terminal of UVT 11 12 ~ 61 62 84 Alarm1 “a” Auxiliary switch “b” 83 413 414 Charged signal 183 184 Alarm2 “a” 423 424 Charged signal communication 251 252 Ready to close switch U1 U2 Motor charging R1 Control power A1 A2 Closing coil 513 ~ 544 Alarm contact C1 C2 Shunt trip R11 R22 Alarm reset (Trip cause LED, Alarm contact) 2nd shunt trip 485+ 485- RS-485 communication C11 C12 R2 Note) 1. The diagram is shown with circuits de-energized, all devices open, connected and charged and relays in normal position 2. Relay is normal condition and charging type is "ON-Charging" 3. The standard of auxiliary contact is 3a3b. The auxiliary switch in above diagram is composed of 5a5b. See 48 page for more detail on auxiliary switches. 4. Option - Ready to close contact, Trip alarm contact, UVT coil, Fully charged contact, secondary trip coil - Cell switch, Temperature module, Voltage module, Remote close-open module, ZCT, ZSI 5. Please consult us for the use of ZSI (Zone selective Interlocking). 6. Refer to the page 33 for the connection of Trip relay and the page 43 for UVT. 7. For connecting RS-485 verify if the polarity is correct 76 C2 A2 Electric operatio circuit Fault trip UVT Main circuit Z4 STD/Inst E2 GTD or n Temperature Module 41 31 21 11 53 43 33 23 13 T1 TC1 TC2 341 331 321 311 Temperature Sensor-2 CL Axa Axa Axa Axa Axa Axb Axb Axb Axb Axb Temperature Sensor-1 T2 CL 51 CL 423 CL 413 Axb U1 52 42 32 22 12 54 44 34 24 Charge completion contact 14 342 344 332 334 322 324 312 314 ON 424 OFF 414 Charged U2 Charged M Thermal, communication remote control module Auxiliary switch Cell switch Accessory code description ZSI input Z1 Z2 Z3 Z4 ZSI output E1 E2 ZCT VN ~ V3 TC1 , TC2 ~ T1 311 ~ 344 Voltage module , T2 Temperature module Position switch Ax LTD STD/Inst GTD CL M Auxiliary switch Internal wiring Long time delay trip indicator External wiring (by customer) Short time delay/instantaneous Ground fault trip indicator Cell switch Motor CC Closing coil SHT1 Shunt tripping device 1 SHT2 Shunt tripping device 2 UVT UVT coil Connector of the control circuit terminal of drawout type 77 Dimensions Fixed type 800~1600A (UAS-08/16D) Side view 15.16 (385) 11.81 (300) 11.02 (280) 11.02 (280) 5.51 (140) 5.51 (140) Operating panel center 10.63 (270) 12.6 (320) 2.56 (65) 0.47 (12) 9.84 (250) 6.50 (165) 17.28 (439) 13.94 (354) 3P 1.46 (37) 4P Vertical-con Vertical Operating panel center Operating panel center Ø0.55(Ø14) (Mounting Hole) Ø0.55(Ø14) (Mounting Hole) Ø0.55(Ø14) (Earthing Hole) Ø0.55(Ø14) (Earthing Hole) 3.15 (80) 3.35 (85) 3.15 (80) 6.50 (165) 3.35 (85) 6.50 (165) Back view 6.50 (165) Side view 0.49 (12.5) 1.97 (50) 0.98 (25) 5.24 (133) 3.62 (92) 78 0.79 (20) 12.99 (330) 1.65 (42) 11.81 (300) Ø0.55 (Ø14) 13.94 (353.6) 0.59 (15) 3.35 (85) 1.91 (48.5) 13.52 (343.5) 4.88 (124) 0.98 (25) 0.59 (15) 3.35 (85) 6.50 (165) 3.19 (81) 0.98 (25) 6.99 (177.5) 6.99 (177.5) 2.34 (59.5) 2.34 (59.5) Vertical type_3P 0.79 (20) 0.79 (20) 6.50 (165) 6.50 (165) 0.47 (12) 1.38 (35) 2.64 (67) 10.63 (270) 10.63 (270) 11.81 (300) 12.60 (320) Operating panel center 5.24 (133) Front view 11.81 (300) 12.60 (320) Front view 6.5 (165) 13.52 (343.5) 2.83 (72) 3.35 (85) Dimensions Vertical-con Vertical Operating panel center Operating panel center Ø0.55(Ø14) (Mounting Hole) Ø0.55(Ø14) (Earthing Hole) Ø0.55(Ø14) (Earthing Hole) 2.34 (59.5) Ø0.55(Ø14) (Mounting Hole) 3.15 (80) 3.35 (85) 3.35 (85) 3.35 (85) 6.50 (165) 4.88 (124) 0.98 (25) 3.91 (81) 0.98 (25) 6.99 (177.5) 6.99 (177.5) 2.34 (59.5) Vertical type_4P 0.59 (15) 3.15 (80) 9.84 (250) 3.35 (85) 3.35 (85) 6.50 (165) Back view 3.35 (85) 0.59 (15) 9.84 (250) Side view 0.49 (12.5) 1.97 (50) 0.98 (25) 5.24 (133) 3.62 (92) 1.91 (48.5) 0.79 (20) 16.34 (415) 3.62 (42) 11.83 (300) Ø0.55 (Ø14) 13.52 (343.5) 17.28 (438.6) Horizontal-con Horizontal Operating panel center Operating panel center Ø0.55(Ø14) (Mounting Hole) Ø0.55(Ø14) (Mounting Hole) Ø0.55(Ø14) (Earthing Hole) Ø0.55(Ø14) (Earthing Hole) 3.35 (85) 2.66 (67.5) 6.50 (165) 1.77 (45) Ø0.55(Ø14) 3.15 (80) 6.50 (165) 3.35 (85) 6.99 (177.5) 3.35 (85) 6.50 (165) 6.50 (165) Side view 5.24 (133) 2.64 (67) 11.81 (300) 0.59 (15) Back view 4.88 (124) 0.98 (25) 1.75 (44.5) Ø0.55 (Ø14) 0.49 (12.5) 0.98 (25) 3.35 (85) 0.75 (19) 3.19 (81) 6.99 (177.5) 59.5 (2.34) 2.34 (59.5) 0.98 (25) 1.97 (50) 12.99 (330) 13.94 (353.6) 0.79 (20) Horizontal type_3P 1.91 (48.5) 13.52 (343.5) 79 Dimensions Fixed type 800~1600A (UAS-08/16D) Operating panel center Ø0.55(Ø14) (Mounting Hole) Horizontal-con Operating panel center Ø0.55(Ø14) (Mounting Hole) Ø0.55(Ø14) (Earthing Hole) Ø0.55(Ø14) (Earthing Hole) 6.99 (177.5) 2.34 (59.5) 0.98 (25) 6.99 (177.5) 3.19 (81) 0.98 (25) 2.66 (67.5) 3.35 (85) 3.35 (85) 3.35 (85) 6.50 (165) 1.75 (44.5) Ø0.55 (Ø14) Ø0.55 (Ø14) 1.77 (45) 3.15 (80) 9.84 (250) 3.35 (85) 3.35 (85) 6.50 (165) 3.35 (85) 9.84 (250) Side view 5.24 (133) 2.64 (67) 11.81 (300) 0.59 (15) Back view 0.75 (19) 0.98 (25) 0.49 (12.5) 1.97 (50) 4.88 (124) Horizontal 2.34 (59.5) Horizontal type_4P 0.79 (20) 16.34 (415) 1.91 (48.5) 13.52 (343.5) 17.28 (438.6) Top view Operating panel center Ø0.55(Ø14) (Mounting Hole) Ø0.55(Ø14) (Mounting Hole) Ø0.55(Ø14) (Earthing Hole) Ø0.55(Ø14) (Earthing Hole) 2.34 (59.5) 0.98 (25) 6.99 (177.5) 6.50 (165) 6.50 (165) 3P 6.50 (165) 9.84 (250) 4P 7.97 (202.5) 19.90 (505.5) 9.21 (234) Side view 0.98 (25) 80 1.50 (38) 1.50 (38) 0.98 (25) 3.15 (80) 3.15 (80) 11.83 (300.5) 6.99 (177.5) Operating panel center 2.34 (59.5) Front connection type Dimensions Draw-out type 800~1600A (UAS-08/16D) Front view Operating panel center Operating panel center 5.51 (140) 5.51 (140) 2.56 (65) 2.56 (65) 10.63 (270) 16.93 (430) 8.46(215) 10.63 (270) 5.51 (140) 10.24(260) 3.35(85) 10.24(260) 13.15(334) 16.50(419) 3P 4P Vertical-con Bottom view 1.77 (45) 3.35 (85) 1.77 (45) 3.35 (85) 3.35 (85) 3.35 (85) 0.59 (15) 3.94 (100) 3.94 (100) 3.94 (100) 7.76 (197.3) 9.45 (240.3) 0.59 (15) 3.94 (100) 10.24 (260) 10.24 (260) Ø0.51(Ø13) (Mounting Hole) Back view Ø0.51(Ø13) (Mounting Hole) Side view 0.49 (12.5) 13.14 (334) 16.93 (430) 0.99 (25) 2.83 (72) 5.23 (133) 1.97 (50) Ø0.55(Ø14) 4.80 (122) Vertical type_3P 16.93 (430) Front view 23.82 (60.5) 18.39 (467.3) 81 Dimensions Draw-out type 800~1600A (UAS-08/16D) Bottom view Vertical-con 3.35 (85) 3.35 (85) 3.35 (85) 0.59 (15) 1.77 (45) 3.35 (85) 3.35 (85) 3.35 (85) 0.59 (15) 9.45 (240.3) 1.77 (45) 3.93 (100) 3.94 (100) 3.93 (100) 3.94 (100) 7.76 (197.3) Vertical type_4P 13.59 (345) 13.58 (345) Ø0.51(Ø13) (Mounting Hole) Back view Ø0.51(Ø13) (Mounting Hole) Side view 0.49 (12.5) 16.92 (430) 2.83 (72) 4.80 (122) 5.23 (133) 1.97 (50) 0.98 (25) Ø0.55(Ø14) 23.82 (60.5) 16.50 (419) Horizontal type_3P Bottom view 1.28 (32.5) 18.39 (467.3) Vertical-con 3.35 (85) 1.97 (50) 3.35 (85) 1.77 (45) 0.98 (25) 3.35 (85) 3.35 (85) 1.77 (45) Ø0.55(Ø14) 9.45 (240.3) 0.75 (19) 3.94 (100) 0.49 (12.5) 7.76 (197.3) 3.94 (100) 3.94 (100) 3.94 (100) 10.24 (260) 1.77 (44.5) Ø0.55(Ø14) 10.24 (260) Ø0.51(Ø13) (Mounting Hole) Side view 3.82 (97) 5.24 (133) 16.93 (430) 0.59 (15) Back view Ø0.51(Ø13) (Mounting Hole) 13.15 (334) 82 23.82 (60.5) 18.39 (467.3) Dimensions Vertical-con 3.35 (85) 3.35 (85) 3.35 (85) 1.28 (32.5) 3.35 (85) 1.77 (45) 1.97 (50) 0.98 (25) 3.35 (85) 1.77 (45) Ø0.55(Ø14) Ø0.55(Ø14) 3.35 (85) 0.75 (19) Botttom view 9.45 (240.3) 3.94 (100) 7.76 (197.3) 3.94 (100) 3.94 (100) 3.94 (100) 0.49 (12.5) 1.75 (44.5) Horizontal type_4P 13.58 (345) 13.58 (345) Ø0.51(Ø13) (Mounting Hole) Side view 3.81 (97) 5.23 (133) 16.93 (430) 0.60 (15) Back view Ø0.51(Ø13) (Mounting Hole) 16.50 (419) 18.39 (467.3) Bottom view 1.77(45) 3.94 (100) 3.94 (100) 3.94 (100) 3.94 (100) 6.38 (162) 6.38 (162.3) 1.77(45) 10.24(260) 13.58(345) Ø0.51(Ø13) (Mounting Hole) 3P 4P Ø0.51(Ø13) (Mounting Hole) Side view 0.98 (25) 1.77 (45) 3.35 (85) 2.89 (73.5) 1.63 (41.5) Ø0.55(Ø14) 7.97 (202.5) 19.90 (505.5) 16.93 (430) 9.21 (234) 1.26 (32) Back view 1.26 (32) Front connection type 23.82 (60.5) 0.98 (25) 2.26 (57.5) 17.00 (432.3) 3.35 (85) 13.15(334) 83 Dimensions Fixed type 800~2000A (UAH-08~20E) 19.41 (493) 11.97 (304) 0.47 (12) 17.01 (432) 0.47 (12) 3P 8.03 (204) 21.54 (547) 10.63 (270) 1.38 (35) 12.56 (319) 0.47 (12) 1.91 (56.5) 4P 2.83 (72) 13.52 (343.5) Side view Top view Operating panel center Operating panel center Ø0.55 (Ø14) 6.99 (177.5) 0.98 (25) 6.99 (177.5) 3.19 (81) 0.98 (25) 2.34 (59.5) 2.34 (59.5) Ø0.55 (Ø14) 3.50 (89) 0.79 (20) 4.53 (115) 4.53 (115) 8.03 (204) 8.03 (204) 3P 0.75 (19) 1.16 (29.5) 4.11 (104.5) 2.95 (75) 1.75 (44.5) Ø0.55 (Ø14) 5.24 (133) 4.53 (115) 4.53 (115) 8.03 (204) 1.91 (48.5) 13.52 (343.5) 4.53 (115) 12.56 (319) 4P Side view 84 3.50 (89) 0.75 (20) 3.19 (81) Vertical type 10.63 (270) 11.81 (300) 0.79 (20) 8.03 (204) 10.63 (270) 12.60 (320) 8.03 (204) 0.47 (12) 1.38 (35) 0.79 (20) 11.81 (300) Operating panel center 0.59 (15) 7.44 (189) 11.02 (280) Operating panel center 11.02 (280) 0.79 (20) 7.44 (189) 12.60 (320) 14.88 (378) 7.44 (189) 1.38 (35) Front view Dimensions Top view Operating panel center Operating panel center Ø0.55 (Ø14) 2.64 (67) 1.75 (44.5) 2.95 (75) 4.53 (115) 4.53 (115) 8.03 (204) 1.75 (44.5) 2.95 (75) Ø0.55 (Ø14) 2.64 (67) 8.03 (204) 4.53 (115) 4.53 (115) 4.53 (115) 8.03 (204) 3P 6.99 (177.5) 2.34 (59.5) 0.75 (19) 0.98 (25) 6.99 (177.5) 0.75 (19) 3.19 (81) 0.98 (25) 2.34 (59.5) Ø0.55 (Ø14) 3.19 (81) Horizontal type Ø0.55 (Ø14) 12.56 (319) 4P 2.64 (67) 5.26 (133.5) 0.79 (20) Side view 1.91 (48.5) Top view Operating panel center Operating panel center Ø0.55(Ø14) 3.50 (89) 4.53 (115) 8.03 (204) 6.99 (177.5) 0.98 (25) 1.50 (38) 0.98 (25) 1.50 (38) 6.99 (177.5) 2.34 (59.5) 2.34 (59.5) Ø0.55(Ø14) 3.50 (89) 8.03 (204) 3P 12.56 (319) 8.03 (204) 4P 19.92 (506) 9.21 (234) Side view 7.97 (202.5) Front connection type 13.19 (343.5) 0.98 (25) 11.83 (300.5) 85 Dimensions Fixed type 2500A (UAH-25E) Vertical type Top view Operating panel center Operating panel center Ø0.55(Ø14) 3.50 (89) 0.79 (20) 4.53 (115) 4.53 (115) 4.53 (115) 3.50 (89) 8.03 (204) 8.03 (204) 5.08 (129) 5.08 (129) 0.98 (25) 0.98 (25) 6.99 (177.5) 6.99 (177.5) 2.34 (59.5) 2.34 (59.5) Ø0.55(Ø14) 4.53 (115) 4.53 (115) 0.79 (20) 12.56 (319) 8.03 (204) 4P 3P Side view 17.01 (432) 21.54 (547) 3P 4P 1.75 (44.5) 1.26 (32) 1.75 (44.5) 2.95 (75) 1.16 (29.5) 4.11 (104.5) 5.26 (133.5) Ø0.55(Ø14) 3.80 (96.5) 15.41 (391.5) 86 20.59 (523) 0.79 (20) 0.79 (20) 16.06 (408) 11.81 (300) 11.81 (300) Back view Dimensions Operating panel center Operating panel center Ø0.55 (Ø14) 2.64 (67) 0.98 (25) 6.99 (177.5) 6.99 (177.5) 1.75 (44.5) 4.53 (115) 8.03 (204) 8.03 (204) 8.03 (204) 2.95 (75) 4.53 (115) 2.64 (67) 4.53 (115) 4.53 (115) Ø0.55 (Ø14) Ø0.55 (Ø14) 3P 1.75 (44.5) 1.26 (32) 1.75 (44.5) 2.95 (75) 5.08 (129) 1.26 1.75 (32) (44.5) 0.98 (25) 2.34 (59.5) 2.34 (59.5) Ø0.55 (Ø14) 5.08 (129) Top view 4.53 (115) 12.56 (319) 4P 20.59 (523) 17.01 (432) 21.54 (547) 3P 4P 0.79 (20) 0.79 (20) 16.06 (408) 11.81 (300) 11.81 (300) Back view 5.26 (133.5) 0.79 (20) Side view 2.64 (67) Horizontal type 3.80 (96.5) 15.41 (391.5) 87 Dimensions Fixed type 3200A (UAH-32E) Vertical type Top view Operating panel center Operating panel center Ø0.55 (Ø14) 8.88 (225.5) 8.88 (225.5) 0.98 (25) 0.98 (25) 6.99 (177.5) 6.99 (177.5) 2.34 (59.5) 2.34 (59.5) Ø0.55 (Ø14) 0.20 (5) 4.53 (115) 4.53 (115) 8.03 (204) 0.79 (20) 4.53 (115) 4.53 (115) 0.20 (5) 8.03 (204) 8.03 (204) 12.56 (319) 20.98 (533) 3P 4P 16.46 (418) 20.98 (533) 3P 4P Back view Side view 1.75 (44.5) 0.44 (11.2) 15.14 (384.5) 3.07 (78) 7.76 (197) 1.75 (44.5) 0.62 (15.7) Ø0.55 (Ø14) 1.76 (44.8) 0.62 (15.7) 1.75 (44.5) 5.12 (130) Ø0.95(Ø19) 1.75 (44.5) 7.60 (193) 19.21 (488) 88 0.79 (20) Dimensions Draw-out type 800~2000A (UAH-08~20E) Front view Operating panel center 5.51 (140) 12.57 (319.3) Operating panel center 5.51 (140) 5.51 (140) 5.51 (140) 2.95 (75) 2.36 (60) Disconnected Disconnected & Test 3P 10.63 (270) 1.85 (47) 7.87 (200) 13.38 (339.8) 5.12 (130) 14.76 (375) 20.75 (527) 17.65 (448.3) 4P Side view 2.56 (65) 14.23 (361.5) 5.24 (133) 3.82 (97) 2.56 (65) 9.65 (245) 10.24 (260) 16.22 (412) 2.36 (60) Bottom view 4.53 (115) 4.53 (115) 0.59 (15) 0.79 (20) 4.53 (115) 4.53 (115) 0.79 (20) 3.94 (100) 3.94 (100) 3.94 (100) 3.94 (100) 10.24 (260) 4.53 (115) 8.15 (207) 8.15 (207) 0.59 (15) 14.76 (375) Ø0.51 (Ø13) 3P Ø0.51 (Ø13) 4P Back view 16.22 (412) 20.75 (527) 3P 4P Side view 0.75 (19) 16.93 (430) 2.95 (75) 1.75 (44.5) 3.00 (75) 5.30 (134.5) 5.24 (133) Ø0.55 (Ø14) 2.34 (59.5) Vertical type 16.93 (430) 10.63 (270) 16.93 (430) 2.56 (65) 10.63 (270) 1.97 (50) 2.78 (70.5) 18.78 (477) 89 Dimensions Draw-out type 800~2000A (UAH-08~20E) Bottom view 4.53 (115) 2.95 (75) 1.75 (44.5) 2.83 (7.2) Ø0.55 (Ø14) 4.53 (115) 4.53 (115) 2.95 (75) Ø0.55 (Ø14) 8.15 (207) 3.94 (100) 14.76 (375) Ø0.51 (Ø13) 3P 4P 16.22 (412) 20.75 (527) 3P 4P Back view 3.82 (97) 5.24 (133) 16.93 (430) 0.79 (20) Side view 2.78 (70.5) 18.78 (477) 90 1.75 (44.5) 3.94 (100) 8.15 (207) 3.94 (100) 3.94 (100) 10.24 (260) 4.53 (115) 0.75 (19) 4.53 (115) 0.29 (7.3) 0.75 (19) Horizontal type Ø0.51 (Ø13) Dimensions Bottom view 0.59 (15) 3.94 (100) 3.94 (100) 3.94 (100) 3.94 (100) 6.46 (164) 6.46 (164) 0.59 (15) 10.24 (260) 14.76 (375) Ø13(0.51) (Mounting Hole) 3P Ø0.51(Ø13) 4P Ø0.55 (Ø14) Ø0.55 (Ø14) 4.53 (115) 20.75 (527) 4.53 (115) 4.53 (115) 4.53 (115) 1.26 (32) 4.53 (115) 1.26 (32) 17.6 (44.5) 2.95 (75) 1.63 (41.5) 1.63 (41.5) 19.90 (505.5) 1.26 (32) 1.26 (32) Back view 16.22 (412) 3P 4P 19.90 (505.5) 16.93 (430) 9.21 (234) Side view 2.89 (73.5) 7.97 (202.5) Front connection type 0.98 (25) 17.09 (434) 91 Dimensions Draw-out type 2500A (UAH-25E) Bottom view 4.53 (115) 0.59 (15) 4.53 (115) 4.53 (115) 0.79 (20) 4.53 (115) 0.59(15) 3.94 (100) 14.76 (375) Ø0.51 (Ø13) 3P 4P 16.22 (412) 20.75 (527) 3P 4P Back view Side view 1.75 (44.5) Ø0.55 (Ø14) 16.93 (430) 2.95 (75) 2.34 (59.5) 5.30 (134.5) 5.24 (133) 1.75 (44.5) 1.26 (32) 4.67 (118.5) 20.67 (525) 92 0.79 (20) 3.94 (100) 3.94 (100) 3.94 (100) 10.24 (260) 4.53 (115) 10.04 (255) 10.04 (255) Vertical type Ø0.51 (Ø13) Dimensions Bottom view 3.94 (100) 3.94 (100) 3.94 (100) 3.94 (100) 10.24 (260) 1.75 (44.5) 10.04 (255) Ø0.55(Ø14) 1.26 (32) 2.95 (75) 0.29 (7.3) Ø0.55(Ø14) 4.53 (115) 1.75 (44.5) 1.75 (44.5) 4.53 (115) 10.04 (255) 2.95 (75) 4.53 (115) 1.75 (44.5) 0.29 (7.3) 4.53 (115) 1.26 (32) 4.53 (115) 14.76 (375) Ø0.51 (Ø13) 3P 4P 16.22 (412) 20.75 (527) 3P 4P Ø0.51 (Ø13) Back view 16.93 (430) 0.79 (20) 5.24 (133) Side view 3.82 (97) Horizontal type 4.67 (118.5) 20.67 (525) 93 Dimensions Draw-out type 3200A (UAH-32E) Bottom view 16.46 (418) 9.06 (230) 0.79 (20) 3.11 (79.2) 3.94 (100) 3.94 (100) 3.94 (100) Ø0.51(Ø13) (Mounting Hole) 10.24 (260) 14.76 (375) 3P 4P 16.22 (412 ) 20.75 (527) 3P 4P Back view Side view 2.11 (53.5) 0.44 (11.2) 15.31 (389) 16.93 (430) 3.07 1.75 (78) (44.5) 7.76 (197) 0.62 (15.7) Ø0.55(Ø14) 0.20 (5) 0.62 (15.7) 1.75 (44.5) 5.31 (135) 1.75 (44.8) Ø0.75(Ø19) 1.49 (38) 23.50 (597) 94 0.79 (20) 3.94 (100) 12.87 (327) 3.13 (79.2) 20.98 (533) 13.58 (345) 4.53 (115) 12.87 (327) Vertical type Ø0.51(Ø13) (Mounting Hole) Dimensions Fixed type 3200~5200A (UAH-32~50G) Front view 29.57(751) 22.13(562) 38.62(981) 7.44(189) 31.18(792) 7.44(189) 11.02(280) 11.02(280) 8.03(204) 22.72(577) 0.47(12) 0.47(12) 31.69(805) 1.38 (35) 10.63 (270) 12.60 (320) 11.81(300) 0.79 (20) 0.79 (20) 1.38 (35) 12.60 (320) Operating panel center 10.63 (270) 11.81(300) Operating panel center 31.77(807) 0.47(12) 8.03(204) 3P 4P Top view Operating panel center Operating panel center Ø0.55 (Ø14) 2.99 (76) 9.61 (244) 0.79 (20) 0.79 (20) 2.99 (76) 9.61 (244) 9.61 (244) 3P 6.99 (177.5) 6.65 (169) 0.98 (25) 6.99 (177.5) 6.65 (169) 0.98 (25) 2.34 (59.5) 2.34 (59.5) Ø0.55 (Ø14) 9.61 (244) 9.61 (244) 4P 0.79 (20) 30.75 (781) 31.69 (805) 3P Side view 1.26 (32) 11.81 (300) 39.80 (1011) 40.75 (1035) 0.79 (20) 11.81 (300) Back view 4P 0.55 (44.5) 1.75 (44.5) 2.95 (75) 5.24 (133) Ø0.55 (Ø14) 1.16 (29.5) 4.11 (104.5) Vertical type 0.47(12) 40.75(1035) 5.37 (136.5) 16.99 (431.5) 95 Dimensions Fixed type 3200~5200A (UAH-32~50G) Operating panel center Operating panel center Ø0.55 (Ø14) 2.34 0.98 (59.5) (25) 6.99 (177.5) Ø0.55 (Ø14) 9.61 (244) 9.61 (244) 1.75 (44.5) Ø0.55 (Ø14) Ø0.55 (Ø14) 3P 1.75 (44.5) 9.61 (244) 5.94 (151) 9.61 (244) 1.25 (31.7) 1.26 (32) 1.25 (31.7) 6.65 (169) 1.75 (44.5) 5.95 (151.2) 1.26 (32) 1.75 (44.5) 6.65 (169) Top view 2.34 0.98 (59.5) (25) 6.99 (177.5) Horizontal type 9.61 (244) 4P 3P 2.64 (67) 5.24 (133) 0.79 (20) Side view 5.37 (136.5) 16.99 (431.5) 96 11.81 (300) 39.80 (1011) 40.75 (1035) 4P 0.79 (20) 30.75 (781) 31.77 (805) 0.79 (20) 11.81 (300) Back view Dimensions Draw-out type 3200~5200A (UAH-32~50G) Front view Operating panel center Operating panel center 5.51 (140) 5.51 (140) 10.24 (260) 4.45 (113) 18.11 (460) 10.24 (733) 18.11 (460) 19.8 (503) 10.24 (260) 10.24 (260) 13.5 (343) 39.96 (1015) 30.91 (785) 4P 3P Bottom view 9.61(244) 9.61(244) 9.61(244) 3 (76.2) 9.61(244) 9.61(244) 2.99 (76.2) 0.79 (20) 1.36 (34.6) 10.24 (260) 5.24 (113) 10.24 (260) 3P 7.87 (200) 7.87 (200) 10.83 (275.3) 10.83 (275.3) 0.79 (20) 1.09 (27.6) Ø0.51(Ø13) (Mounting Hole) 10.24 (260) 13.5 (343) 4P 10.24 (260) Ø0.51(Ø13) (Mounting Hole) 0.59 (15) 28.11 (714) 39.96 (1015) 30.91 (785) Ø0.31(Ø8) (Earthing Hole) 3P Side view Ø0.31(Ø8) (Earthing Hole) 2.95 (75) 1.75 (44.5) 1.75 (44.5) 3.52 (89.5) 5.24 (133) 4P Ø0.55 (Ø14) 1.26 (32) 6.48 (164.5) 37.01 (940) 0.59 (15) 18.11 (460) 18.11 (460) Back view 17.05 (433) Vertical type 10.24 (260) 5.45(138.5) 21.47 (545.3) 97 Dimensions Draw-out type 3200~5200A (UAH-32~50G) 9.61 (244) Ø0.55(Ø14) 3 (76.2) 1.75 (44.5) 3 (76.2) 9.61 (244) 1.75 (44.5) 1.25 (31.7) 1.36 (34.6) 10.24 (260) 5.24 (113) 10.24 (260) Ø0.51(Ø13) (Mounting Hole) 3P 7.87 (200) 7.87 (200) 10.83 (275.3) 1.25 (31.7) 9.61 (244) 5.94(151.2) 1.26 (32) 9.61 (244) 5.94(151.2) 1.75 (44.5) 9.61 (244) 10.83 (275.3) Bottom view 1.26 (32) Horizontal type 1.09 (27.6) 10.24 (260) 13.50 (343) 10.24 (260) Ø0.51(Ø13) (Mounting Hole) 4P 0.59 (15) 28.11 (714) 30.91 (785) Ø0.31(Ø8) (Earthing Hole) 3P 4.61 (117) 17.05 (433) 5.24 (133) 0.79 (20) Side view 5.45 (138.5) 21.56 (545.3) 98 37.01 (940) 39.96 (1015) 4P 0.59 (15) 18.11 (460) 18.11 (460) Back view Ø0.31(Ø8) (Earthing Hole) � For your safety, please read user's manual thoroughly before operating. � Contact the nearest authorized service facility for examination, repair, or adjustment. � Please contact a qualified service technician when you need maintenance. Do not disassemble or repair by yourself! Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned. ⓒ 2011.9 LSIS Co.,Ltd. All rights reserved. � HEAD OFFICE LS-ro 127 (Hogye-dong) dongan-gu Anyang-si Gyeonggi-do Korea Tel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648 www.lsis.com � Global Network �LSIS (Middle East) FZE � �Dubai, U.A.E. Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: dhleef@lsis.biz �Dalian LSIS Co., Ltd. � �Dalian, China Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: tangyh@lsis.com.cn �LSIS (Wuxi) Co., Ltd. � �Wuxi, China Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: luw@lsis.com.cn � CHEONG-JU PLANT Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea �LSIS-VINA Co., Ltd. � �Hanoi, Vietnam Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: sjbaik@lsis.biz �LSIS-VINA Co., Ltd. � �Hochiminh , Vietnam Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: hjchoid@lsis.biz �LSIS Shanghai Office � �Shanghai, China Address: Room 32 floors of the Great Wall Building, No. 3000 North Zhongshan Road, Putuo District, Shanghai, China Tel: 86-21-5237-9977 Fax: 89-21-5237-7189 e-mail: baijh@lsis.com.cn �LSIS Beijing Office � �Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: sunmj@lsis.com.cn �LSIS Guangzhou Office � �Guangzhou, China Address: Room 1403, 14/F, New Poly Tower, No.2 Zhongshan Liu Road, Guangzhou 510180, P.R. China Tel: 020-8326-6754 Fax: 020-8326-6287 e-mail: chenxs@lsis.com.cn �LSIS Chengdu Office � �Chengdu, China Address: Room 1701 17Floor, huamin hanjun internationnal Building, No1 Fuxing Road Chengdu, 610016, P.R. China Tel: 86-28-8670-3201 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn �LSIS Qingdao Office � �Qingdao, China Address: Room 2001,20/F,7B40, Galaxy Building, No.29 Shandong Road, Shinan District, Qingdao 266071, P.R. China Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 e-mail: wangzy@lsis.com.cn �LSIS NETHERLANDS Co.Ltd � �Schiphol-Rijk, Netherlands Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: junshickp@lsis.biz Specifications in this catalog are subject to change without notice due to continuous product development and improvement. 2013. 11 �LSIS Gurgaon Office � �Gurgaon ,India Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, India e-mail: hwyim@lsis.biz Susol UL Air Circuit Breakers (E) 2011. 09/(03) 2013. 11 Printed in Korea STAFF