Control of the Dynamic Voltage Restorer to Improve Voltage Quality Samet Biricik a,b, Shafiuzzaman K. Khadem c, Soydan Redif b, Malabika Basu a a b School of Electrical & Electronic Engineering, Dublin Institute of Technology, Ireland Department of Electrical & Electronic Engineering European University of Lefke, North Cyprus c School of Engineering, Trinity College Dublin, Ireland Abstract- In this study a method is proposed in order to improve the voltage compensation performance of Dynamic Voltage Restorer by using Self Tuning Filter. The proposed control method gives an adequate voltage compensating even for 50% voltage sag and distorted voltage conditions. The proposed DVR control method is modelled using MATLAB/Simulink and tested both in off-line and real-time environment. Results are then presented as a verification of the proposed method. The remainder of this paper has been organized as follows. The proposed control method with STF is discussed in details in section II. Development of a three phase system in MATLAB and results obtained by the simulation in presented in section III. Section IV shows the part of the results from real-time experimental result to verify the performance of the proposed method in real environment. II. Keywords - DVR; voltage sag; voltage harmonics; STF. I. INTRODUCTION Voltage distortions and fluctuations are frequently encountered in the weak grid network systems. The distorted currents cause non-sinusoidal voltage drops and as a result the network voltages become distorted. On the other hand, voltage sag and swell problems are usually caused by short-circuit current flowing into a fault. Voltage sag and swell are defined as a sudden reduction or rise of grid voltages which may vary from 10% to 90 % during sag and 110% to 180% during swell of its nominal value [1]. Therefore, dynamic voltage restorer (DVR) is used to solve such power quality problems. DVR was introduced by the end of the 1980s. It operates mainly as voltage regulator and as a harmonic isolator between the loads and the utility system. This type of filter is able to compensate the voltage related problems in the distribution system [2]. They can also be used to filter harmonic voltages, reduce voltage-flicker and regulate line voltage. However, DVR is less preferred to be used in industrial applications. Because it has to handle high load current which increases the losses. The DVR is represented as a controllable voltage source. It is controlled to present zero impedance at the fundamental frequency and a high resistance to the source or load harmonics. In order to improve the performance of the DVR a selftuning filter (STF) is used in this study. Presently, the STF is used as a part of filtering current harmonics in the controller of the three phase shunt active power filter (APF) [3- 9] and hybrid active power filter [10-11]. But till now, STF has not yet been applied to the control of DVR. In this study, we propose use of STF algorithm to increase the control performance of the DVR in the case of both non-ideal grid voltages and unbalanced voltage sag. Fig.1 shows the studied DVR topology. '978-1-4799-5115-4/14/$31.00 ©2014 IEEE' PROPOSED CONTROL METHOD The main aim of the DVR is to dynamically compensate the voltage sag/swell along with the voltage harmonics. Therefore, any kind of distortion in the instantaneous and fundamental supply voltage ( ) is defined by the error voltage ( ) which is calculated as ∆ 1 1 1 (1) 230 230 230 is where a, b, c subscripts represent the three phases. the rms of the supply voltage and 230 V is the standard or desired rms value of the supply voltage. The STF usually requires two inputs which should contain the phase and amplitude information of any system. Therefore, the calculated error signal is then transformed into two phase coordinate system using the Clarke (or α-β) transformation: 2 1 3 0 1 2 √3 2 1 2 √3 2 (2) The per unit α-β reference voltage for the compensation can then be obtained as: 230√2 (3) 230√2 In order to obtain undistorted and balanced waveform for the control circuit, the α-β of the distorted grid voltage is processed through the STF. In [3], the transfer function of the STF is obtained by integration of the synchronous reference frame and it is defined as: H (s) = Vxy (s) U xy (s) s + jω s 2 + ω2 = Kx (4) where V xy (t ) = e j ωt ∫ e − j ωt U xy (t )dt (5) The STF has a magnitude and phase response that is similar to those of a general band-pass filter. Apart from the integral effect on the input magnitude, the STF does not alter the phase of the input, i.e. the input Uxy(s) and output Vxy(s) have the same phase. Note that in order to have unit magnitude, i.e. |H(s)| = 0 dB, a constant KX is incorporated in to (4) [3], that is, H (s) = Vxy (s) U xy (s) = KX (s + K X ) + jω (s + K X ) 2 + ω 2 . (6) The signals generated by (3) are then transferred to the STF to generate the two phase instantaneous un-distorted signals in terms of α-β. . (7) . Then, the obtained un-distorted and balanced two phase voltages can be converted to the three phase system by using inverse Clark transformation as given by, 0 √3 3 2 2 √3 2 1 1 2 1 2 The phase information is also obtained by transferring the generated per unit error signals to the Phase-Locked-Loop (PLL). This angular position is then used to calculate the required un-distorted and balanced three phase reference voltages for the point of common coupling (PCC). This reference voltage is given as 2 . sin . √3. 230 3 2 . 3 1 sin 2 1 √3. . cos 2 √3 . 230 2 . 3 1 sin 2 1 √3. . cos 2 √3 . 230 Extracted reference signal for the PCC is then used to generate the reference signal for the sag/swell compensation. If there is no sag/swell/distortion then this signal (error = 0) is feed-forwarded to the PWM block to generate the gate pulses. Otherwise, this signal is compared with secondary voltage and then transferred to the proportional integrator (PI) controller to generate the required compensation current for the DVR controller. This reference current is then compared with the actual value to get the error in compensating current. A proportional gain is used to convert this error current to the appropriate voltage signal which is then added to the feed-forwarded signal and passed to the PWM block to generate the gate pulses. Fig. 2 shows the block diagram of the proposed controller. (8) Fig.1. Circuit Topology of the Dynamic Voltage Restorer '978-1-4799-5115-4/14/$31.00 ©2014 IEEE' (9) Fig.2. The block diagram of the DVR and proposed control method a-) b--) c-) d--) Fig.3. a-) Three phase unbalanced and distoorted (non-ideal) grid voltages, b-) Injected three phase voltaages by the DVR, c-) Three phase balanced and un-distorted (ideal) volttages at the load terminal. d-) Load (current) variation under ideal voltage condition III. SIMULATION RESULTS In order to evaluate the performance of the proposed control method, a power system structure has been developed in MATLAB/Simulink. The performance of the proposed control method is investigated for the case of o 50% three phase voltage sag with linear and non-linear load combinations. c Symbol vS f Load 1 Load 2 Load 3 Lc Udc fs TABLE I: PARAMETERS OF THE STUDIED D SYSTEM Value Quantity Ideal Grid L-N rms Voltage 230 V Grid Frequency 50 Hz 4Ω, 10 mH Linear Load Res. and Ind. 24Ω, 15 mH Non-Linear Load Res. and Ind. 7.5Ω, 45 mH Non-Linear Load Res. and Ind. 0.3 mH Filter Inductor 600 V dc- link Source Voltage 10 kHz Switching Frequency '978-1-4799-5115-4/14/$31.00 ©20114 IEEE' The proposed method, load l change has been also considered from 0.15s -0.20s. Load 1 is used to draw only active and reactive power from the grid. However, Load 2 and Load 3 draw both distorted cuurrents and reactive power. The block diagram representation of the simulated power and control systems are shown inn Figs 1 & 2 and the system parameters used in the simulaations are calculated from [12] and are given in Table I. Simulation is performed for the following cases and conditions; A. Grid side disturbances The system is operated unnder the non-ideal grid voltage condition (including harmonicss and unbalances) and it can be observed from Fig 3 (a). Thhe Total Harmonic Distortion (THD) of the grid voltages in each e phase are found as 9.06 %, 9.65 % and 7.39 %. The rms values v of the unbalanced phase voltages are 229.4V, 231.9V, 225.4V. 2 The simulation is run for 0.3 sec and 50% sag is applied between 0.05 to 0.1 sec. As a result the grid voltages are reduced to 1166.9 V, 116.9 V and 110.4 V. The performance of the proposed method m is observed in Fig 3 (b) where DVR injects the required voltage to compensate the voltage sag. The balancee and undistorted voltage at the load side is shown in Fig 3(cc). By this method, the voltage harmonics on the load terminall are reduced from 10 % around to 4 % and voltages are improvved from 116 V to 225 V. Because, of the losses on the injection transformers (series transformers) 5 V iss dropped on the injection transformer. Moreover, the load current harmonics create additional voltage harmonic on o the injection transformers impedances. B. Load side disturbance The THD of the load currents in eachh phase are found 17.91 %, 16.82 % and 17.68 % while the currrents are 107.9 A, 108.9 A, 107 A. Voltage change on the gridd side is created by reducing the grid current to 58.48 A, 58.75A A, 58.58 A. This is observed from 0.15 to 0.20 sec. However, thhe load groups are not affected from the voltage disturbance (see Fig 3 (d)). It is found that in full load condition, the total active a power (P) is 70 kW; the total reactive power (Q) is 26 kVAr. During the voltage sag condition, the consuming acttive power (P) is reduced to 38 kW; the total reactive powerr (Q) is reduced to 12 kVAr on the grid side (see Fig. 4, betw ween 0.05 to 0.10 sec). However, the proposed methhod dynamically compensated the active and reactivate poweer cause of voltage injection as presented in Fig. 5. As a result, the load groups do not observed any power changes during the voltage sag on the grid (see Fig.6, between 0.05 to 0.10 sec.)). In this study we also verified the system performance duringg the load changes. The load variation is applied between 0.15 too 0.20 sec. As can be seen in Figs. 4, 5 & 6 the performance of the system is not affected during the load variation. Fig. 6. Consumed Active and Reaactive powers from the load side. IV. RFORMANCE STUDY REAL-TIME PER The proposed control methood and power system then have been modelled in Simulink usinng RT-LAB real-time platform and associated tools to observee the performance in a real time environment. The system is then tested in software-in-the-loop (SIL) with hardware synchronization mode, which is similar to the hardware-in-the-loopp (HIL) test giving due consideration for delay in the real time measurement of actual signals and implementation of the t control signals [13]. Fig. 7 shows the real-tim me laboratory setup using the OPAL-RT (OP5600) platfo form, which manages the communications between the CPUs, FPGA architecture and the console PC (from whicch the global simulation is controlled). Fig. 7. Experimental seetup with the OPAL-RT Fig. 4. Consumed Active and Reactive powers from the grid Side. Figs. 8, 9 & 10 shows thhe real-time performance of the proposed method to obtain undistorted and balance grid voltage at PCC. Fig. 8 show ws the grid voltage waveforms through the real-time scope which are unbalanced and distorted. The injected voltagee by the DVR in real-time is observed in Fig. 9. Fig. 10 show ws the undistorted and balanced three-phase voltages at the loaad terminal which verifies the performance of the proposed method. m Fig. 5. Injected Active and Reactive powerrs by the DVR '978-1-4799-5115-4/14/$31.00 ©20114 IEEE' REFERENCES Fig. 8. Distorted and unbalanced grid voltages (93 V/div). Fig. 9. Injected voltages by the DVR (93 V/div). Fig. 10. The obtained un-distorted and balanced voltages at PCC terminal (93 V/div). V. CONCLUSION This paper shows the effectiveness of implementing STF in the traditional control method of DVR to compensate the distorted and unbalanced grid voltage condition as well as sudden drop or increase in grid voltage. Performance of the improved method is tested both in off-line and real-time mode. Results show that the proposed method can significantly improve the performance of the DVR and thus the load does not sense any kind of grid voltage disturbances. Moreover, the grid voltage harmonics are effectively suppressed on the load terminal. '978-1-4799-5115-4/14/$31.00 ©2014 IEEE' [1] M. Ramasamy, S. Thangavel, Experimental verification of PV based Dynamic Voltage Restorer With Significant Energy Conservation, Electrical Power and Energy Systems 49 (2013) 296-307. [2] O. S. Senturk, A. M Hava, "High-Performance Harmonic Isolation and Load Voltage Regulation of the Three-Phase Series Active Filter Utilizing the Waveform Reconstruction Method," IEEE Transactions on Industry Applications, vol.45, no.6, pp.2030,2038, Nov.-dec. 2009. [3] M. Abdusalam, P. Poure, S. Karimia, S. Saadate, "New Digital Reference Current Generation for Shunt Active Power Filter under Distorted Voltage Conditions", Electric Power Systems Research, vol. 79, pp 759-76, 2009. [5] A. Ghamri , M. T. Benchouia & A. Golea "Sliding-Mode Control Based Three-Phase Shunt Active Power Filter", Simulation and Experimentation, Electric Power Components and Systems, 40:4, 383398, Jan. 2012. [6] S. Biricik, S. Redif, O.C.Ozerdem, Malabika Basu, "Control of the Shunt Active Power Filter under Non-Ideal Grid Voltage and Unbalanced Load Conditions"48th International Universities Power Engineering Conference, UPEC 2013, 2-5 September, Dublin, Ireland. [7] S. S. Patnaik, A. K. Panda, "Real-Time Performance Analysis and Comparison of Various Control Schemes for Particle Swarm Optimization-Based Shunt Active Power Filters", Electrical Power and Energy Systems 52 (2013) 185–197. [8] S. Biricik, S. Redif, O.C.Ozerdem, S. K. Khadem, Malabika Basu, " Real-Time Control of Shunt Active Power Filter under Distorted Grid Voltage and Unbalanced Load Condition using Self Tuning Filter”, journal of IET Power Electronics (2014) [9] S. Biricik, O.C.Ozerdem, S. Redif and M.O.I. Kmail, “Performance Improvement of Active Power Filter under Distorted and Unbalanced Grid Voltage Conditions”, Journal of Electronics and Electrical Engineering, ISSN 1392 – 1215, Vol. 19, No.1, pp 35-39, 2013. [10] S.Biricik, O.C.Ozerdem, S.Redif and M.O.I.Kmail, “Novel Hybrid Active Power Filter Structure To Compensate Harmonic Currents and Reactive Power", 16th IEEE Mediterranean Electro-technical Conference -MELECON 2012, 25-28 Mart 2012, Tunisia. [11] S. Biricik, A Novel Hybrid Active Power Filter Topology for Harmonic Current Suppression and Reactive Power Compensation, PhD Thesis, NEU, April 2013 [12] S K Khadem, Power Quality Improvement of Distributed Generation Integrated Network using Unified Power Quality Conditioner, PhD Thesis, DIT, January 2013 [13] Real-time simulator, OPAL-RT, www.opal-rt.com