Lecture Notes ELE A6 Ramadan El-Shatshat Three Phase circuits 9/12/2006 ELE A6 Three-phase Circuits 1 Three-phase Circuits 9/12/2006 ELE A6 Three-phase Circuits 2 Advantages of Three-phase Circuits • Smooth flow of power (instantaneous power is constant). • Constant torque (reduced vibrations). • The power delivery capacity tripled (increased by 200%) by increasing the number of conductors from 2 to 3 (increased by 50%). 9/12/2006 ELE A6 Three-phase Circuits 3 Three-phase Circuits Wye-Connected System • The neutral point is grounded • The three-phase voltages have equal magnitude. • The phase-shift between the voltages is 120 degrees. Van = V ∠0 ° = V Vbn = V ∠ − 120 ° Vcn = V ∠ − 240 ° 9/12/2006 ELE A6 Three-phase Circuits 4 Three-phase Circuits Wye-Connected System • Line-to-line voltages are the difference of the phase voltages Vab = Van - Vbn = 3 V ∠30 Vbc = Vbn - Vcn = 3 V ∠ - 90 Vca = Vcn - Van = 3 V∠150 9/12/2006 ELE A6 Three-phase Circuits 5 Three-phase Circuits Wye-Connected System • • • • • Phasor diagram is used to visualize the system voltages Wye system has two type of voltages: Line-to-neutral, and line-to-line. The line-to-neutral voltages are shifted with 120o The line-to-line voltage leads the line to neutral voltage with 30o The line-to-line voltage is 3 times the line-to-neutral voltage 9/12/2006 ELE A6 Three-phase Circuits 6 Three-phase Circuits Wye-Connected Loaded System • The load is a balanced load and each one = Z • Each phase voltage drives current through the load. • The phase current expressions are: Vcn Van Vbn Ia = , Ib = , Ic = z z z 9/12/2006 ELE A6 Three-phase Circuits 7 Three-phase Circuits Wye-Connected Loaded System • Since the load is balanced (Za = Zb = Zc) then: Neutral current = 0 Van Za a Ia • This case single phase equivalent circuit can be used (phase a, for instance, only) • Phase b and c are eliminated n Io 9/12/2006 ELE A6 Three-phase Circuits 8 Three-phase Circuits Wye-Connected System with balanced load • A single-phase equivalent circuit is used • Only phase a is drawn, because the magnitude of currents and voltages are the same in each phase. Only the phase angles are different (-120o phase shift) • The supply voltage is the line to neutral voltage. • The single phase loads are connected to neutral or ground. V 9/12/2006 ln Load ELE A6 Three-phase Circuits 9 Three-phase Circuits Balanced Delta-Connected System • The system has only one voltage : the line-to-line voltage ( VLL ) • The system has two currents : – line current – phase current • The phase currents are: Vab Ia = z 9/12/2006 ELE A6 Three-phase Circuits 10 Three-phase Circuits Delta-Connected System The line currents are: Ia= Iab − Ica Ib= Ibc − Iab Ic = Ica − Ibc • In a balanced case the line currents are: I line = 9/12/2006 3I phase ∠ − 30 ELE A6 Three-phase Circuits 11 Three-phase Circuit Delta-Connected System • The phasor diagram is used to visualize the system currents • The system has two type of currents: line and phase currents. • The delta system has only line-toline voltages, that are shifted by • The phase currents lead the line currents by 30 ° • The line current is 3 times the phase current and shifted by 30 degree. 9/12/2006 ELE A6 Three-phase Circuits 12 Three-phase Circuit • Circuit conversions – A delta circuit can be converted to an equivalent wye circuit. The equation for phase a is (will not be used for this course): Za = Z ab Z ca Z ab + Z bc + Z ca – Conversion equation for a balanced system is: Za = 9/12/2006 Z ab 3 ELE A6 Three-phase Circuits 13 Three-phase Circuit Power Calculation • The three phase power is equal the sum of the phase powers P = Pa + Pb + Pc • If the load is balanced: P = 3 Pphase = 3 Vphase I phase cos (φ ) • • Wye system: Vphase = VLN I phase = I L VLL = P = 3 Vphase I phase cos (φ ) = 3 VLL I L cos (φ ) Delta system: I Line = 3 I phase VLL = Vphase P = 3 Vphase I phase cos (φ ) = 9/12/2006 3 VLN 3 VLL I L cos (φ ) ELE A6 Three-phase Circuits 14 Three-phase Circuit Power measurement • In a four-wire system (3 phases and a neutral) the real power is measured using three singlephase watt-meters. • In a three-wire system (three phases without neutral) the power is measured using only two single-phase watt-meters. - The watt-meters are supplied by the line current and the line-to-line voltage. 9/12/2006 ELE A6 Three-phase Circuits 15 Three-phase Circuit Load Watt meter 1 Power measurement a b • The total power is the algebraic sum of Wattmeter 2 the two watt-meters reading. W1 = Vab I a cos(θ vab − θ Ia ) c W2 = Vcb I c cos(θ vcb − θ Ic ) PT = W1 + W2 = 3VL I L cos(θ ) 9/12/2006 ELE A6 Three-phase Circuits 16 Three-phase Circuits Example 1 A 345 kV, three phase transmission line delivers 500 MVA, 0.866 power factor lagging, to a three phase load connected to its receiving end terminals. Assume the load is Y connected and the voltage at the receiving end is 345 kV, find: • The load impedance per phase. • The line and phase currents. • The total real and reactive power. 9/12/2006 ELE A6 Three-phase Circuits 17 (a ) Zφ = Vφ Iφ 345kV S 500 MVA Vφ = ∠0V , Iφ = = = 836.7 A 3 3VL 3 345kV Iφ = 836.7∠ − cos −1 (0.866) = 836.7∠ − 30 Zφ = 238∠30 = 206 + j119 (b) I L = Iφ = 836.7∠ − 30 (c) P = 3VL I L cos(θ ) = 433 MW Q = 3VL I L sin(θ ) = 249.9 MVAR 9/12/2006 ELE A6 Three-phase Circuits 18 Three-phase Circuits Example 2 Repeat example 2 assuming the load is Delta connected. 9/12/2006 ELE A6 Three-phase Circuits 19 (a ) Vφ = VL = 345kV∠0V , S 500MVA Iφ = = = 483.1A 3VL 3 * 345kV Iφ = 483.1∠ − cos −1 (0.866) = 483.1∠ − 30 Zφ = Vφ Iφ = 714∠30 = 618.3 + j 357 (b) I L = 3Iφ ∠ − 30 = 836.7∠ − 60 (c) P = 3VL I L cos(θ ) = 433 MW Q = 3VL I L sin(θ ) = 249.9 MVAR 9/12/2006 ELE A6 Three-phase Circuits 20 Power factor correction • Power factor (p.f.) correction is the process of making P.f. = 1. • In order to correct the power factor in any system, a reactive (either inductive or capacitive) will be added to the load. • If the load is inductive, then a capacitance is added. – Note: Correcting the P.f. WILL NOT affect the active power, why? 9/12/2006 ELE A6 Three-phase Circuits 21 Three-phase Circuits Example 3 A 3-phase load draws 120 kW at a power factor of 0.85 lagging from a 440 V bus. In parallel with this load, a three phase capacitor bank that is rated 50 kVAR is inserted, find: • The line current without the capacitor bank. • The line current with the capacitor bank. • The P.F. without the capacitor bank. • The P.F. with the capacitor bank. 9/12/2006 ELE A6 Three-phase Circuits 22 3V L I L cos( θ ) (a ) P = IL = 120 * 10 3 = 185 . 25 A 3 440 ( 0 . 85 ) I L = 185 . 25 ∠ − cos ( b ) Q capacitor = −1 ( 0 . 85 ) = 185 . 2 ∠ − 31 . 8 , 3V L I L sin( θ ) Since we have pure capacitor sin( θ ) = 1 Q capacitor = I L ( capacitor I L ( capacitor 3V L I L ( capacitor ) 50 * 10 3 = = 65 . 6 A ) 3 440 = 65 . 6 ∠ 90 ) I L ( new ) = I L + I L ( capacitor ( c ) P .F. (no capacitor) = 160 . 6 ∠ − 11 . 49 ) = 0.85 ( d ) P .F. (with capacitor) 9/12/2006 load = c os (11 . 49 ) = 0 . 98 ELE A6 Three-phase Circuits 23 Home Work 9/12/2006 ELE A6 Three-phase Circuits 24 Home Work 9/12/2006 ELE A6 Three-phase Circuits 25