L-OBS-03x LAT Observatory Level EPS Performance Outline 10 November 06 v4 Initial Configuration / Entrance Criteria: REVISION SUMMARY Vers Date 0 1 10/23/06 10/31/06 Initial Draft Modify sequence per GFSC input. 2 11/2/06 Incorporate comments from table top. 3 11/6/06 Incorporate review comments. 4 11/10/06 Incorporate review comments. 1. LICOS can send commands to AstroRT and receive science and telemetry data from Spacecraft Integration & Test (SCIT) console. 2. Spacecraft is on and operating in the selected redundancy configuration. 3. The spacecraft is providing valid 1PPS, Timetone, Spacecraft Position, and Spacecraft Attitude data. 4. The SSR is active and the SC_Ready line is enabled. 5. AstroRT is displaying and archiving SC collected LAT telemetry and LAT related voltages and currents. Description of Change Purpose: The L-OBS-03x procedure powers on the LAT from a fully off state, with support from the Spacecraft, while providing pauses and opportunities to repeat steps to enable LAT power transients to be measured using breakout boxes (BoBs) on the various LAT feeds and test instrumentation. Final Configuration / Exit Criteria: 1. The SIU and EPUs are running in application mode and providing secondary boot telemetry. 2. The GASU and PDU specified in the selected redundancy configuration are on and operating. 3. All 16 towers are powered. 4. All 12 ACD Free boards are powered. 5. All ACD, CAL, and TKR HVBS are at their operational levels. 6. SIU, PDU, TKR-15, and TKR-10 power on transients were captured. Description: At the start of L-OBS-03x the Spacecraft energizes the SIU feed consistent with the redundancy configuration shown in Table 1 below. At this time the SIU power on transient is measured. If the test instrumentation fails to capture the SIU power on transient, power is removed from the SIU feed by the SC and the step is repeated. After the SIU feed is energized the SIU will autonomously perform primary boot. The SIU is left in primary boot, the SC enables the DAQ feed, and Primary Boot Code (PBC) commands are used to power the PDU and GASU. The PDU power on transient on the DAQ feed is measured. If test instrumentation fails to capture the PDU power on transient, the PDU is powered off and the step is repeated. The LAT then performs a secondary boot of the SIU and the LIMMAINFEEDON command is issued. LAT then powers and executes secondary boot on the two EPUs, configures all 16 towers, the ACD FREE boards, and sets the Detector HVBSs to operational levels. Pauses are placed after each TEM, CAL, and TKR is powered to allow power on transients to be measured at any time. Nominally power on transients will be made for TKR-4 and TKR-15. The script does provide the ability to repeat the power on of TKR-15 if test instrumentation fails to capture the power on transient. The script does NOT check any LAT related telemetry read by the Spacecraft. Those checks must be performed by AstroRT or by procedure. GLAST Constraints: 1. All telemetry check and command execution failures must be coordinated with Systems Engineering before proceeding. Relevant Modes of Operation: QUIESCENT Estimated Duration: 180 minutes 1 L-OBS-03x STEP 1. OWNER SC LAT Observatory Level EPS Performance Outline DESCRIPTION SC verifies the initial test configuration and the ability of Astro RT to read, display, and archive SC read LAT telemetry. ACTION a. Connect the in-line Breakout Boxes on the SIU and DAQ feeds. b. Initialize AstroRT on the TC Console. c. Start the AstroRT LICOS interface console on AstroRT. d. Verify SC and LAT telemetry are received by AstroRT. e. Verify the SC is in the configuration required for the selected LAT configuration. f. Verify the SC read LAT telemetry points are all being read, displayed, and archived properly and g. Verify the 1553B bus is active and the SC is supplying valid 1PPS, Timetone, Spacecraft Position, and Spacecraft Attitude data to the LAT. h. Verify the SSR is enabled and the SC_Ready line is set to ready. i. Verify LAT feed voltages are in range. EXPECTED RESPONSE a. b. c. d. e. f. g. 2. LAT Set up the LICOS-AstroRT Proxy on the LAT Workstation. a. b. GLAST 10 November 06 v4 COMMENTS AstroRT is displaying telemetry. Verify the SC is in the required configuration per Table 1. For SC A-Side SD_AA_CPUA = 1 SD_AB_CPUA = 1 SC_AA_CPUB = 0 SC_AB_CPUB = 0 For SC B-Side SD_AA_CPUA = 1 SD_AB_CPUA = 1 SC_AA_CPUB = 0 SC_AB_CPUB = 0 Verify the 1553B bus is active and the SC is supplying valid 1PPS, Timetone, Spacecraft Position, and Spacecraft Attitude data. SBCRTENBLLAT = 1 SACFLAGLATINSAA = 0 VSBCPBUSLAT = 0 (A-Side), 1 (B-Side) Verify the SSR is enabled and the SC_Ready line is set to ready. STWRENBL_SSRSCI = 1 STWRENBL_SSRTLM = 1 SIU feed voltages are in range: SE_PRU_P_SIU_V = 0.0±1.0V SE_PRU_R_SIU_V = 0.0±1.0V L_DAQ_P_RSF_V = 0.0±1.0V L_DAQ_R_RSF_V = 0.0±1.0V DAQ feed voltage is in range: SE_PRU_P_DAQ_V = 0.0±1.0V SE_PRU_R_DAQ_V = 0.0±1.0V SIU temp is in range: L_DAQ_P_SIU_T = 10.0 to 35.0 °C L_DAQ_R_SIU_T = 10.0 to 35.0 °C Verify the LICOS/Astro-RT Proxy socket connection to the SASS Test Network. In the LICOS Proxy Window, the indicator shows “Not Ready”. 2 L-OBS-03x STEP LAT Observatory Level EPS Performance Outline OWNER DESCRIPTION ACTION 3. LAT Start LatPowerOnSuite script when instructed to do so by the Observatory test conductor. 4. SC Measure NEB_4 current prior to SC enabling of the SIU feed and LAT Power on so that LAT power consumption can be measured. Select the LatPowerOnSuite script from the LICOS script window and chose the LatEpsPowerOn.cfg configuration file . Measure the SC NEB_4 current using SC telemetry (SE_PDUA_SW_L4_I or SE_PDUB_SW_L4_I) and the test instrumentation prior to SIU power on. 5. SC 6. SC GLAST Verify the SIU feed is instrumented to measure the SIU power on transient. Enable the SIU feed. Primary or redundant feed selected per the required redundancy configuration and Table 1. Enable SIU feed. 10 November 06 v4 EXPECTED RESPONSE COMMENTS LatPowerOnSuite is running. Record spacecraft NEB_4 current prior to LAT power on SE_PDUA_SW_L4_I = A SE_PDUB_SW_L4_I = A Clean room personnel indicate test instrumentation is ready to capture SIU power on transient. a. Verify the SIU Feed PDU Inhibits are OFF For PRU A-Side SE_PAL4_SIU_INH = OFF SE_PBL4_SIU_INH = ON For PRU B-Side SE_PAL4_SIU_INH = ON SE_PBL4_SIU_INH = OFF b. Verify SIU Feed switch positions For PRU A-Side SE_PAL3_SIU_SW = ON For PRU B-Side SE_PBL3_SIU_SW = ON c. Verify PRU output voltages For PRU A-Side SE_PRU_P_SIU_V = 28.0±1.0V SE_PRU_R_SIU_V = 0.0±1.0V For PRU B-Side SE_PRU_P_SIU_V = 0.0±1.0V SE_PRU_R_SIU_V = 28.0±1.0V d. Verify SIU voltages in range: For SIU A-Side L_DAQ_P_SIU_V = 1.7 to 2.1 V For SIU B-Side L_DAQ_R_SIU_V = 1.7 to 2.1 V 3 L-OBS-03x STEP 7. LAT Observatory Level EPS Performance Outline OWNER DESCRIPTION SC Verify SIU Primary Boot, record the NEB 4 current delta, and calculate SIU power consumption. ACTION Verify SIU Memory and Communication checks passed. b. Verify SIU Health c. Record the NEB 4 and calculate the NEB 4 current delta due to SIU power on using both SC telemetry and the test instrumentation. a. EXPECTED RESPONSE a. b. c. d. e. 8. SC 9. SC GLAST Verify the SIU feed test instrumentation captured the SIU power on transient. If the SIU power on transient was successfully captured, proceed to step 11, if not perform step 10. 10 November 06 v4 COMMENTS SIU Memory Check: PASS For SIU A-Side SLGIOLACTRLB06 = 0 [APID 0x26, PID5 = 0] For SIU B-Side SLGIOLACTRLB08 = 0 [APID 0x26, PID8 = 0] SIU Comm. Check: PASS For SIU A-Side SLGIOLACTRLB07 = 0 [APID 0x26, PID6 = 0] For SIU B-Side SLGIOLACTRLB09 = 0 [APID 0x26, PID9 = 0] Verify SIU temp is in range: L_DAQ_P_SIU_T = 10.0 to 35.0 °C L_DAQ_R_SIU_T = 10.0 to 35.0 °C LAT SIU Feed power consumption is <32W. NEB 4 current delta <1.25 A. Clean room personnel indicate test instrumentation captured the SIU power on transient. 4 L-OBS-03x STEP OWNER 10. SC 11. LAT 12. SC GLAST LAT Observatory Level EPS Performance Outline DESCRIPTION OPTIONAL STEP: If the SIU power on transient was NOT captured, Disable the SIU Feed, and repeat steps 4-9. Verify SIU Primary Boot Verify the DAQ feed is instrumented to measure the voltage transient when the DAQ feed is enabled. ACTION Disable SIU Feed EXPECTED RESPONSE 10 November 06 v4 COMMENTS Verify SIU Feed switch positions For PRU A-Side SE_PAL3_SIU_SW = OFF For PRU B-Side SE_PBL3_SIU_SW = OFF b. Verify PRU output voltages For PRU A-Side SE_PRU_P_SIU_V = 0.0±1.0V SE_PRU_R_SIU_V = 0.0±1.0V For PRU B-Side SE_PRU_P_SIU_V = 0.0±1.0V SE_PRU_R_SIU_V = 0.0±1.0V c. Verify SIU voltages in range: For SIU A-Side L_DAQ_P_SIU_V = 0.0±1.0V For SIU B-Side L_DAQ_R_SIU_V = 0.0±1.0V a. SIU boot telemetry is present [LAT telemetry - LBTHKP] and boot mode in interactive mode ready for commands LPBCBOOTSTAT = 2 (BOOT_MODE_COMMAND). Clean room personnel indicate test instrumentation is ready to capture DAQ feed voltage transient. a. 5 L-OBS-03x STEP 13. OWNER SC LAT Observatory Level EPS Performance Outline DESCRIPTION Enable the DAQ feed. ACTION Enable DAQ feed EXPECTED RESPONSE 10 November 06 v4 COMMENTS Verify the DAQ Feed PDU Inhibit is OFF For SC A-Side SE_PAL4_DAQ_INH = OFF SE_PBL4_DAQ_INH = ON For SC B-Side SE_PAL4_DAQ_INH = ON SE_PBL4_DAQ_INH = OFF b. Verify PRU output voltages For SC A-Side SE_PRU_P_DAQ_V = 28.0 ± 1.0V SE_PRU_R_DAQ_V = 0.0 ± 1.0V For SC B-Side SE_PRU_P_DAQ_V = 0.0 ± 1.0V SE_PRU_R_DAQ_V = 28.0 ± 1.0V c. Record spacecraft NEB_4 current following DAQ power feed enable a. SE_PDUA_SW_L4_I = _______ Amps SE_PDUB_SW_L4_I = _______ Amps 14. SC 15. SC 16. LAT 17. SC GLAST Verify the DAQ feed test instrumentation captured the DAQ feed power on voltage transient. If not, disable the DAQ feed and repeat steps 12-13. Enable LAT Commanding Verify LAT Command path is operational. Verify the DAQ feed is instrumented to measure the PDU power on transient. Clean room personnel indicate test instrumentation captured the DAQ feed power on voltage transient. In AstroRT commanding window select: Options OTCC Ready? Ready Send no-op command to PBC LPBCSTART In LICOS Proxy Window, indicator shows “Ready”. LPBCLASTAPID = 1600 LPBCLASTFUNC = 0 LPBCTCRECVCNT increments LPBCTCACCCNT increments Clean room personnel indicate test instrumentation is ready to capture DAQ power on transient. 6 L-OBS-03x STEP 18. OWNER LAT GLAST LAT Observatory Level EPS Performance Outline DESCRIPTION Use PBC to power on the PDU. ACTION PBC power on PDU LMEMLOADMEM LMEMADDRESSHI=0xc000 LMEMADDRESSLO=0x8 LMEMDATA00HI=0x0 LMEMDATA00LO=0x18 LMEMDATA01HI=0x0 LMEMDATA01LO=0x0 LMEMDATA02HI=0x0 LMEMDATA02LO=0x0 LMEMDATA03HI=0x0 LMEMDATA03LO=0x0 LMEMDATA04HI=0x0 LMEMDATA04LO=0x0 LMEMDATA05HI=0x0 LMEMDATA05LO=0x0 LMEMDATA06HI=0x0 LMEMDATA06LO=0x0 LMEMDATA07HI=0x0 LMEMDATA07LO=0x0 LMEMDATA08HI=0x0 LMEMDATA08LO=0x0 LMEMDATA09HI=0x0 LMEMDATA09LO=0x0 LMEMDATA10HI=0x0 LMEMDATA10LO=0x0 LMEMLATUNIT=0x0 LMEMSIZE=0x1 LMEMTRANID=0xeee EXPECTED RESPONSE a. [Need PBC verifiers] 10 November 06 v4 COMMENTS Note for all subsequent steps: All LAT commands and monitors shown are for prime units, but actual monitors used are dependent on the LAT configuration. 7 L-OBS-03x STEP 19. LAT Observatory Level EPS Performance Outline OWNER DESCRIPTION SC Verify PDU power on, record NEB 4 delta current that resulted from PDU power on, and calculate PDU power consumption using the test instrumentation and telemetry. ACTION EXPECTED RESPONSE a. b. c. f. g. 20. SC 21. SC GLAST Verify the DAQ feed test instrumentation captured the PDU power on transient. If the PDU power on transient was successfully captured, proceed to step 21, if not perform steps 18-20. Verify PRU output voltages For SC A-Side SE_PRU_P_DAQ_V = 28.0 ± 1.0V SE_PRU_R_DAQ_V = 0.0 ± 1.0V For SC B-Side SE_PRU_P_DAQ_V = 0.0 ± 1.0V SE_PRU_R_DAQ_V = 28.0 ± 1.0V PDU temp is in range L_DAQ_P_PDU_T = 10.0 to 35.0 °C PDU 3.3V is in range L_DAQ_P_PDU_V = 3.0 – 3.6V PDU power consumption is <20W. NEB 4 current delta <1.0 A. 10 November 06 v4 COMMENTS Note for all subsequent steps: All LAT monitors shown are for prime units, but actual monitors used are dependent on the LAT configuration. Clean room personnel indicate test instrumentation captured the PDU power on transient. 8 L-OBS-03x STEP LAT Observatory Level EPS Performance Outline OWNER DESCRIPTION 22. LAT OPTIONAL STEP: If the PDU power on transient was NOT captured, use PBC to power off the PDU. 23. SC OPTIONAL STEP: Verify the PDU is off and then repeat steps 17-21. ACTION PBC power off the PDU LMEMLOADMEM LMEMADDRESSHI=0xc000 LMEMADDRESSLO=0x8 LMEMDATA00HI=0x0 LMEMDATA00LO=0x0 LMEMDATA01HI=0x0 LMEMDATA01LO=0x0 LMEMDATA02HI=0x0 LMEMDATA02LO=0x0 LMEMDATA03HI=0x0 LMEMDATA03LO=0x0 LMEMDATA04HI=0x0 LMEMDATA04LO=0x0 LMEMDATA05HI=0x0 LMEMDATA05LO=0x0 LMEMDATA06HI=0x0 LMEMDATA06LO=0x0 LMEMDATA07HI=0x0 LMEMDATA07LO=0x0 LMEMDATA08HI=0x0 LMEMDATA08LO=0x0 LMEMDATA09HI=0x0 LMEMDATA09LO=0x0 LMEMDATA10HI=0x0 LMEMDATA10LO=0x0 LMEMLATUNIT=0x0 LMEMSIZE=0x1 LMEMTRANID=0xeee EXPECTED RESPONSE COMMENTS [Need PBC verifiers] Note for all subsequent steps: All LAT monitors shown are for prime units, but actual monitors used are dependent on the LAT configuration. PDU temp is in range L_DAQ_P_PDU_T = 10.0 to 35.0 °C b. PDU 3.3V is in range L_DAQ_P_PDU_V = 0.0 ± 1.0V Note for all subsequent steps: All LAT monitors shown are for prime units, but actual monitors used are dependent on the LAT configuration. a. c. GLAST 10 November 06 v4 9 L-OBS-03x STEP LAT Observatory Level EPS Performance Outline OWNER DESCRIPTION 24. LAT 25. LAT LICOS operator proceeds with GASU power on with no other action when prompted to determine if High bay personnel are ready for GASU power on. Use PBC to power on the GASU. GLAST ACTION EXPECTED RESPONSE 10 November 06 v4 COMMENTS Step left in script to minimize LICOS script changes. PBC power on the GASU LMEMLOADMEM LMEMADDRESSHI=0xc000 LMEMADDRESSLO=0x8 LMEMDATA00HI=0x0 LMEMDATA00LO=0x1A LMEMDATA01HI=0x0 LMEMDATA01LO=0x0 LMEMDATA02HI=0x0 LMEMDATA02LO=0x0 LMEMDATA03HI=0x0 LMEMDATA03LO=0x0 LMEMDATA04HI=0x0 LMEMDATA04LO=0x0 LMEMDATA05HI=0x0 LMEMDATA05LO=0x0 LMEMDATA06HI=0x0 LMEMDATA06LO=0x0 LMEMDATA07HI=0x0 LMEMDATA07LO=0x0 LMEMDATA08HI=0x0 LMEMDATA08LO=0x0 LMEMDATA09HI=0x0 LMEMDATA09LO=0x0 LMEMDATA10HI=0x0 LMEMDATA10LO=0x0 LMEMLATUNIT=0x0 LMEMSIZE=0x1 LMEMTRANID=0xeef a. [Need PBC verifiers] Note for all subsequent steps: All LAT monitors shown are for prime units, but actual monitors used are dependent on the LAT configuration. 10 L-OBS-03x STEP 26. OWNER SC LAT Observatory Level EPS Performance Outline DESCRIPTION ACTION Verify GASU power on, record NEB 4 delta current that resulted due to GASU power on, and compute the GASU power consumption using the test instrumentation and telemetry. EXPECTED RESPONSE a. b. c. d. e. 27. LAT LICOS operator declines option to retry GASU power on. 28. LAT Initiate SIU secondary boot 29. LAT GLAST Dwell on the telemetry packet SiuStats at 2 Hz through next action Verify PRU output voltages For SC A-Side SE_PRU_P_DAQ_V = 28.0 ± 1.0V SE_PRU_R_DAQ_V = 0.0 ± 1.0V For SC B-Side SE_PRU_P_DAQ_V = 0.0 ± 1.0V SE_PRU_R_DAQ_V = 28.0 ± 1.0V GASU temp is in range L_DAQ_P_GASU_T= 10.0 to 35.0 °C GASU voltages are in range L_DAQ_P_EBM33_V = 3.1 – 3.5V L_DAQ_P_EBM25_V = 2.3 – 2.7V L_DAQ_P_GEM33_V = 3.1 – 3.5V L_DAQ_P_GEM25_V = 2.3 – 2.7V GASU power consumption is <30W. NEB 4 current delta <1.25 A. 10 November 06 v4 COMMENTS Note for all subsequent steps: All LAT monitors shown are for prime units, but actual monitors used are dependent on the LAT configuration. Step left in script to minimize LICOS script changes. Initiate secondary SIU-1 boot LPBCRTOSEXEC LPBCLATUNIT = 0 LPBCPAD1 = 0x0 LPBCPAD2 = 0x0 LPBCSBCFLAGSHI = 0x5400 (upper bank) LPBCSBCFLAGSLO = 0xC000 (EEPROM) Dwell on telemetry LHKREQDIAGPKT LHKDIAGAPID=0x22A LHKDIAGCOUNT=1024 LHKDIAGINTERVAL=500 (set to 8min 32 seconds max duration at 2Hz) Verify LAT state: LIMTOPMODE = LIM_OP_MODE_TERMINAL (0) b. Verify secondary boot is complete by the presence of LAT HK telemetry: H554SECONDS increases a. c. a. DiagSiuStats packet is detected in the Diagnostic Telemetry stream at 2 Hz. b. Check tlm in range [LAT telemetry: SiuStats] LHKSIUCPUAVLDM = 0 – 10% LHKSIUCPUJTEMP < 75°C c. 11 L-OBS-03x STEP OWNER LAT Observatory Level EPS Performance Outline DESCRIPTION ACTION 30. SC 31. LAT Stop dwell on SiuStats telemetry Stop Dwelling on the SiuStats telemetry packet LHKSTOPDIAG 32. LAT Reset housekeeping system to receive PDU, EPU-0, and EPU-1 telemetry Reset housekeeping system to a config file with the CPU metrics enabled for PDU, EPU-0, and EPU-1: LHKSYSRESET LHKCFGFILE0 = ??? LHKCFGFILE1 = 0 33. LAT Send Main Feed On command Send LIM Main Feed On command LIMMAINFEEDON LIMSIUPAD0 = 0 LIMSUIID = 1 LIMSIUSSRRED = 0 LIMSIUGBMRED = 0 LIMSIUPPSRED = 0 LIMSIUPPSINT = 0 LIMSIUPDU0 = 1 LIMSIUPDU1 = 0 LIMSIUMFPRI = 1 LIMSIUDABPRI = 1 LIMSIUDABRED = 0 GLAST Verify SIU health following Secondary boot. EXPECTED RESPONSE 10 November 06 v4 COMMENTS a. Verify SIU voltages in range: For SIU A-Side L_DAQ_P_RSF_V = 28.0 ± 1.0V L_DAQ_P_SIU_V = 1.7 to 2.1 V For SIU B-Side L_DAQ_R_RSF_V = 28.0 ± 1.0V L_DAQ_R_SIU_V = 1.7 to 2.1 V b. Verify SIU voltages in range: L_DAQ_P_SIU_T = 10.0 to 35.0 °C L_DAQ_R_SIU_T = 10.0 to 35.0 °C a. The DiagSiuStats packet is no longer detected in the Diagnostic Telemetry stream b. Wait for an Ops GO indicating the SIU is performing nominally and that the dwell can be canceled a. ??? [LAT needs to provide file ID, device, directory, file number] 12 L-OBS-03x STEP OWNER LAT Observatory Level EPS Performance Outline DESCRIPTION 34. LAT 35. SC 36. LAT Verify LAT Operations Mode. 37. LAT Verify EPU-0 health prior to unit power on. 38. LAT Power on EPU-0 GLAST Power on the AEM ACTION Turn on the AEM LIMPOWERON LIMPWRACDSEL = 1 LIMPWRACDPDU = 0 LIMPWRACDSUPRED = 0 (all other fields set to zero) Verify GASU health and status and AEM power on, record NEB 4 delta current that resulted from AEM power on, and calculate AEM power consumption using the test instrumentation and telemetry. Verify EPU-0 temperature and input voltage. b. Dwell on PduEnv0 at 4 Hz: LHKREQDIAGPKT LHKDIAGAPID=0x21E LHKDIAGCOUNT=1024; LHKDIAGINTERVAL=250 (4min 16sec at 4Hz max) LIMPOWERON LIMPWREPUSEL00 = 1 LIMPWREPUPDU00 = 0 (all other fields set to zero) a. 10 November 06 v4 EXPECTED RESPONSE COMMENTS a. GASU AEM/EBM, GEM 3.3 and AEM/EBM, GEM 2.5 voltages are in range: L_DAQ_P_EBM33_V = 3.1 – 3.5 V L_DAQ_P_EBM25_V = 2.3 – 2.7 V L_DAQ_P_GEM33_V = 3.1 – 3.5 V L_DAQ_P_GEM25_V = 2.3 – 2.7 V b. GASU temp is in range L_DAQ_P_GASU_T= 10.0 to 35.0 °C c. AEM power consumption is <15W. d. NEB 4 current delta <0.75 A. LIMTOPMODE = LIM_OP_MODE_QUIESCENT (1) Note for all subsequent steps: All LAT monitors shown are for prime units, but actual monitors used are dependent on the LAT configuration. The DiagPduEnv0 packet is detected in the Diagnostic Telemetry stream at 4 Hz. b. EPU-0 temperature is in range LHKP0EPU0TST = 0 LHKP0EPU0T = 10.0 to 35.0 °C Step assumes Config 1, EPU-0 may be replaced by EPU-1 or EPU-2 in other configurations. a. a. Verify LAT state tlm: LIMTACTION = LIM_ACTION_POWER_ON (4) LIMTSTATUS = (even number) b. EPU-0 3.3V voltage is in range LHKP0EPU033VST = 0 LHKP0EPU033V = 1.7 – 2.1V c. EPU-0 boot telemetry (0x261) is present, LPBC0BOOTSTAT = BOOT_MODE_COMMAND d. EPU-0 temperature is in range LHKP0EPU0TST = 0 LHKP0EPU0T = 10.0 to 35.0 °C a. 13 L-OBS-03x STEP OWNER LAT Observatory Level EPS Performance Outline DESCRIPTION 39. LAT 40. SC Measure and record the NEB 4 delta current that resulted from EPU-0 power on and calculate EPU-0 power consumption using the test instrumentation and telemetry. 41. LAT Initiate secondary boot for EPU-0 GLAST End dwell on EPU-0 telemetry ACTION Stop Dwelling on EPU-0 telemetry packet PduEnv0 LHKSTOPDIAG EXPECTED RESPONSE a. Initiate secondary boot for EPU-0 LPBCRTOSEXEC LPBCLATUNIT = 1 LPBCPAD1 = 0 LPBCPAD2 = 0 LPBCSBCFLAGSHI = 0x5400 (upper bank) LPBCSBCFLAGSLO = 0xC000 (EEPROM) COMMENTS The DiagPduEnv0 packet is no longer detected in the Diagnostic Telemetry stream Verify PRU output voltages For PRU A-Side SE_PRU_P_DAQ_V = 28.0 ± 1.0V SE_PRU_R_DAQ_V = 0.0 ± 1.0V For PRU B-Side SE_PRU_P_DAQ_V = 0.0 ± 1.0V SE_PRU_R_DAQ_V = 28.0 ± 1.0V b. EPU-0 power consumption is <35W. c. NEB 4 current delta <1.5 A. a. EPU-0 temperature is in range LHKP0EPU0TST = 0 LHKP0EPU0T = 10.0 to 35.0 °C a. 10 November 06 v4 Step assumes Config 1, EPU-0 may be replaced by EPU-1 or EPU-2 in other configurations. 14 L-OBS-03x STEP OWNER LAT Observatory Level EPS Performance Outline DESCRIPTION 42. LAT Verify EPU-1 health prior to unit power on. 43. LAT Power on EPU-1 ACTION Verify EPU-1 temperature and input voltage. b. Dwell on PduEnv0 at 4 Hz: LHKREQDIAGPKT LHKDIAGAPID=0x21E LHKDIAGCOUNT=1024; LHKDIAGINTERVAL=250 (4min 16sec at 4Hz max) LIMPOWERON LIMPWREPUSEL01 = 1 LIMPWREPUPDU01 = 0 (all other fields set to zero) a. EXPECTED RESPONSE The DiagPduEnv0 packet is detected in the Diagnostic Telemetry stream at 4 Hz. b. EPU-1 temperature is in range LHKP0EPU1TST = 0 LHKP0EPU1T = 10.0 to 35.0 °C a. a. b. c. d. 44. LAT 45. SC GLAST End dwell on EPU-1 telemetry Measure and record the NEB 4 delta current that resulted from EPU-1 power on and calculate EPU-1 power consumption using the test instrumentation and telemetry. Stop Dwelling on EPU-1 telemetry packet PduEnv0 LHKSTOPDIAG a. COMMENTS Step assumes Config 1, EPU-1 may be replaced by EPU-0 or EPU-2 in other configurations. Verify LAT state tlm: LIMTACTION = LIM_ACTION_POWER_ON (4) LIMTSTATUS = (even number) EPU-1 3.3V voltage is in range LHKP0EPU133VST = 0 LHKP0EPU133V = 1.7 – 2.1V EPU-1 boot telemetry (0x261) is present, LPBC1BOOTSTAT = BOOT_MODE_COMMAND EPU-1 temperature is in range LHKP0EPU1TST = 0 LHKP0EPU1T = 10.0 to 35.0 °C The DiagPduEnv0 packet is no longer detected in the Diagnostic Telemetry stream Verify PRU output voltages For PRU A-Side SE_PRU_P_DAQ_V = 28.0 ± 1.0V SE_PRU_R_DAQ_V = 0.0 ± 1.0V For PRU B-Side SE_PRU_P_DAQ_V = 0.0 ± 1.0V SE_PRU_R_DAQ_V = 28.0 ± 1.0V b. EPU-1 power consumption is <35W. c. NEB 4 current delta <1.5 A. a. 10 November 06 v4 Step assumes Config 1, EPU-1 may be replaced by EPU-0 or EPU-2 in other configurations. 15 L-OBS-03x STEP OWNER LAT Observatory Level EPS Performance Outline DESCRIPTION 46. LAT Initiate secondary boot for EPU-1 47. LAT Verifying TEM-y health prior to power on: For y = 0 – 15, executed in the following order: 0, 3, 12, 15, 14, 8, 1, 7, 11, 13, 4, 2, 5, 6, 9 and 10. Steps 38 –46 will be repeated to turn on the components for all towers. Use two digit values for the variable y in commands. For instance tower 5 would be 05. Use single digit hex values 0 – F for the variable y in telemetry. Start with tower 0 GLAST ACTION Initiate secondary boot for EPU-1 LPBCRTOSEXEC LPBCLATUNIT = 2 LPBCPAD1 = 0 LPBCPAD2 = 0 LPBCSBCFLAGSHI = 0x5400 (upper bank) LPBCSBCFLAGSLO = 0xC000 (EEPROM) Start monitoring TEM-y by Dwelling on the telemetry packet TemEnvPwry at 4 Hz. Send the Diagnostic Telemetry command to the SIU: LHKREQDIAGPKT LHKDIAGAPID=0x210 (TEM 02) LHKDIAGAPID=0x211 (TEM 35) LHKDIAGAPID=0x212 (TEM 68) LHKDIAGAPID=0x213 (TEM 911) LHKDIAGAPID=0x214(TEM 1214) LHKDIAGAPID=0x215 (TEM 15) LHKDIAGCOUNT=1024; LHKDIAGINTERVAL=250 (4min 16sec at 4Hz max) EXPECTED RESPONSE a. 10 November 06 v4 COMMENTS EPU-1 temperature is in range LHKP0EPU1TST = 0 LHKP0EPU1T = 10.0 to 35.0 °C The DiagTemEnvPwry packet is detected in the Diagnostic Telemetry stream at 4 Hz. b. DAQ board temperature is in range [LAT telemetry – PduEnv1 LHKP0TEMyPCTST = 0 LHKP0TEMyPCT = 10.0 to 35.0 °C c. TEM-y power supply temperature is in range PduEnv0: LHKP0TEMyPSTST = 0 LHKP0TEMyPST = 10.0 to 35.0 °C a. 16 L-OBS-03x STEP 48. OWNER LAT LAT Observatory Level EPS Performance Outline DESCRIPTION Power on TEM-y ACTION Power on TEM-y. LIMPOWERON LIMPWRTEMSELy = 1 LIMPWRTEMPDUy = 0 (all other fields set to zero) EXPECTED RESPONSE a. b. c. d. e. f. 49. LAT 50. SC GLAST End dwell on TEM telemetry Measure and record the NEB 4 delta current that resulted from TEM-y power on and calculate TEM-y power consumption using the test instrumentation and telemetry. Stop Dwelling on TEM-y telemetry packet TemEnvPwry LHKSTOPDIAG a. Verify LAT state tlm: LIMTACTION = LIM_ACTION_POWER_ON (4) LIMTSTATUS = (even number) TEM-y power supply voltage is in range – TemEnvPwr LHKTyTEM28V0ST = 0 LHKTyTEM28V0 = 25.5 – 29V LHKTyTEM28V1ST = 0 LHKTyTEM28V1 = 25.5 – 29V TEM-y power supply current is in range – TemEnvPwr LDETyTEM28I = 0.03 - 0.28 A TEM-y 3.3V voltage is in range LAT telemetry – TemEnvPwr LHKTyTEM33VST = 0 LHKTyTEM33V = 3.1 – 3.5V DAQ board temperature is in range LAT telemetry – PduEnv1: LHKP0TEMyPCTST = 0 LHKP0TEMyPCT = 10.0 to 35.0 °C TEM-y power supply temp is in range LAT telemetry PduEnv0: LHKP0TEMyPSTST = 0 LHKP0TEMyPST = 10.0 to 35.0 °C The DiagTemEnvPwry packet is no longer detected in the Diagnostic Telemetry stream 10 November 06 v4 COMMENTS There could be a telemetry delay after powering TEM 8 since it is usually the last to be powered on and may involve more actions than other TEMs to turn on. Verify PRU output voltages For PRU A-Side SE_PRU_P_DAQ_V = 28.0 ± 1.0V SE_PRU_R_DAQ_V = 0.0 ± 1.0V For PRU B-Side SE_PRU_P_DAQ_V = 0.0 ± 1.0V SE_PRU_R_DAQ_V = 28.0 ± 1.0V b. TEM-y power consumption is <5W. c. NEB 4 current delta <0.25 A. a. 17 L-OBS-03x STEP 51. 52. OWNER LAT LAT GLAST LAT Observatory Level EPS Performance Outline DESCRIPTION Verifying CAL-y health prior to power on. Power on the CAL-y ACTION EXPECTED RESPONSE Start monitoring CAL-y by Dwelling on the telemetry packet TemEnvPwri at 4 Hz. Send the Diagnostic Telemetry command to the SIU: a. LHKREQDIAGPKT; LHKDIAGAPID=0x210 (CAL 02) LHKDIAGAPID=0x211 (CAL 35) LHKDIAGAPID=0x212 (CAL 68) LHKDIAGAPID=0x213 (CAL 911) LHKDIAGAPID=0x214 (CAL 1214) LHKDIAGAPID=0x215 (CAL 15) LHKDIAGCOUNT=1024; LHKDIAGINTERVAL=250 (4min 16sec at 4Hz max) Power on the CAL-y LIMPOWERON LIMPWRTEMCALy to 1. (all other fields set to zero) d. b. c. e. 10 November 06 v4 COMMENTS The DiagTemEnvPwry packet is detected in the Diagnostic Telemetry stream at 4 Hz. TEM-y power supply temperature is in range PduEnv0: LHKP0TEMyPSTST = 0 LHKP0TEMyPST = 10.0 to 35.0 °C CAL-y base plate temperature is in range PduEnv1: LHKP0CALyBPTST = 0 LHKP0CALyBPT = 10.0 to 35.0 °C CAL-y AFEE temperatures are in range – TemEnvTemp: LHKTyCALAFzT1ST = 0 LHKTyCALAFzT1 = 10.0 to 35.0 °C (z = 0-3) LITCTASK = LIM (6) LITCCMDHDRAPID = 1635 LITCCMDHDRFNC = 6 Verify LAT state tlm: LIMTACTION = LIM_ACTION_POWER_ON (4) LIMTSTATUS = (even number) e. TEM-y power supply current is in range TemEnvPwr: LHKTyTEM28V0ST = 0 LHKTyTEM28V0 = 0.2 – 0.5 A LHKTyTEM28V1ST = 0 LHKTyTEM28V1 = 0.2 – 0.5 A f. CAL-y 3.3V analog and digital voltages are in range TemEnvPwri: LHKTyCAL33VDST = 0 LHKTyCAL33VD = 3.1 – 3.5 V LHKTyCAL33VAST = 0 LHKTyCAL33VA = 3.1 – 3.5 V a. b. c. d. 18 L-OBS-03x STEP OWNER LAT Observatory Level EPS Performance Outline DESCRIPTION ACTION EXPECTED RESPONSE g. h. i. j. 53. LAT 54. SC GLAST End dwell on CAL telemetry Measure and record the NEB 4 delta current that resulted from CAL-y power on and calculate CAL-y power consumption using the test instrumentation and telemetry. Stop Dwelling on CAL-y telemetry packet TemEnvPwry LHKSTOPDIAG a. 10 November 06 v4 COMMENTS CAL-y bias voltages are in range TemEnvPwr: LHKTyCALBSV0ST = 0 LHKTyCALBSV0 = -0.1 to 30.0 V LHKTyCALBSV1ST = 0 LHKTyCALBSV1 = -0.1 to 30.0 V CAL-y bias current is in range LDETyCALBIASI = (-0.1) - 0.1 A CAL-y base plate temperature is in range PduEnv1: LHKP0CALyBPTST = 0 LHKP0CALyBPT = 10.0 to 35.0 °C CAL-y AFEE temperatures are in range TemEnvTemp: LHKTyCALAFzT1ST = 0 LHKTyCALAFzT1 = 10.0 to 35.0 °C (z = 0-3) The DiagTemEnvPwry packet is no longer detected in the Diagnostic Tlm stream Verify PRU output voltages For PRU A-Side SE_PRU_P_DAQ_V = 28.0 ± 1.0V SE_PRU_R_DAQ_V = 0.0 ± 1.0V For PRU B-Side SE_PRU_P_DAQ_V = 0.0 ± 1.0V SE_PRU_R_DAQ_V = 28.0 ± 1.0V b. CAL-y power consumption is <5W. c. NEB 4 current delta <0.25 A. a. 19 L-OBS-03x STEP 55. OWNER LAT LAT Observatory Level EPS Performance Outline DESCRIPTION Verifying TKR-y health prior to power on. ACTION Start monitoring TKR-y by Dwelling on the telemetry packet TemEnvPwr at 4 Hz. Send the Diagnostic Telemetry command to the SIU: EXPECTED RESPONSE a. b. c. LHKREQDIAGPKT; d. LHKDIAGAPID=0x210 (TKR 02) e. LHKDIAGAPID=0x211 (TKR 35) LHKDIAGAPID=0x212 (TKR 68) LHKDIAGAPID=0x213 (TKR 911) LHKDIAGAPID=0x214 (TKR 1214) LHKDIAGAPID=0x215 (TKR 15) LHKDIAGCOUNT=1024; LHKDIAGINTERVAL=250 GLAST 10 November 06 v4 COMMENTS The DiagTemEnvPwr packet is detected in the Diagnostic Telemetry stream at 4 Hz. TEM-y power supply temperature is in range PduEnv0: LHKP0TEMyPSTST = 0 LHKP0TEMyPST = 10.0 to 35.0 °C TKR-y temperatures are in range TemEnvTemp: LHKTyTKRCzT0ST = 0 LHKTyTKRCzT0 = 10.0 to 35.0 °C LHKTyTKRCzT1ST = 0 LHKTyTKRCzT1 = 10.0 to 35.0 °C (z = 0-7) 20 L-OBS-03x STEP LAT Observatory Level EPS Performance Outline OWNER DESCRIPTION 56. SC 57. LAT OPTIONAL STEP: Prior to the turn on of TKR-15 (the 4th TKR powered on) and TKR-10 (the 16th TKR powered on) verify the DAQ feed is instrumented to measure the power on transient. Power on the TKR-y ACTION EXPECTED RESPONSE COMMENTS Clean room personnel indicate test instrumentation is ready to capture TKR power on transient. Power on the TKR-y LIMPOWERON LIMPWRTEMTKRy to 1. a. b. c. d. e. f. GLAST 10 November 06 v4 Verify LAT state tlm: LIMTACTION = LIM_ACTION_POWER_ON (4) LIMTSTATUS = (even number) TEM-y power supply current is in range TemEnvPwr: LHKTyTEM28V0ST = 0 LHKTyTEM28V0 = 0.6 – 1.1 A LHKTyTEM28V1ST = 0 LHKTyTEM28V1 = 0.6 – 1.1 A TKR-y 1.5V analog and 2.5V analog and digital voltages are in range TemEnvPwr: LHKTyTKR15VAAST = 0 LHKTyTKR15VAA = 1.3 – 1.7 V LHKTyTKR25VDST = 0 LHKTyTKR25VD = 2.3 – 3.0 V LHKTyTKR25VABST = 0 LHKTyTKR25VAB = 2.3 – 3.0 V TKR-y bias voltages are in range TemEnvPwr: LHKTyTKRBV0ST = 0 LHKTyTKRBV0 = -1.0 to 30.0 A LHKTyTKRBV1ST = 0 LHKTyTKRBV1 = -1.0 to 30.0 A TKR-y bias current is in range. LDETyTKRBIASI = -0.1 to 0.1 A TKR-y temperatures are in range TemEnvTemp: LHKTyTKRCzT0ST = 0 LHKTyTKRCzT0 = 10.0 to 35.0 °C LHKTyTKRCzT1ST = 0 LHKTyTKRCzT1 = 10.0 to 35.0 °C (z = 0-7) 21 L-OBS-03x STEP OWNER LAT Observatory Level EPS Performance Outline DESCRIPTION 58. LAT 59. SC Measure and record the NEB 4 delta current that resulted from TKR-y power on and calculate TKR-y power consumption using the test instrumentation and telemetry. 60. SC 61. SC OPTIONAL STEP: For TKR-15 and TKR-10 power on only, verify the DAQ feed test instrumentation captured the TKR power on transient. OPTIONAL STEP: If the TKR15 (the 4th tower) or TKR-10 (the last tower) power on transient was successfully captured, proceed to step 62, if not perform step 61. GLAST End dwell on TKR telemetry. ACTION Stop Dwelling on TKR-y telemetry packet TemEnvPwry LHKSTOPDIAG EXPECTED RESPONSE a. 10 November 06 v4 COMMENTS The DiagTemEnvPwry packet is no longer detected in the Diagnostic Telemetry stream Verify PRU output voltages For PRU A-Side SE_PRU_P_DAQ_V = 28.0 ± 1.0V SE_PRU_R_DAQ_V = 0.0 ± 1.0V For PRU B-Side SE_PRU_P_DAQ_V = 0.0 ± 1.0V SE_PRU_R_DAQ_V = 28.0 ± 1.0V b. TKR-y power consumption is <20W. c. NEB 4 current delta <1.0 A. Clean room personnel indicate test instrumentation captured the TKR power on transient. a. 22 L-OBS-03x STEP LAT Observatory Level EPS Performance Outline OWNER DESCRIPTION 62. LAT OPTIONAL STEP: If the TKR15 (the 4th tower) or TKR-10 power on transient was not captured (the last tower), power off the appropriate TKR (10 or 15) and then repeat steps 46-59. Power on the TKR-y LIMPOWEROFF LIMPWRTEMTKR10 to 1. 63. LAT Power on remaining towers. Repeat steps 47-62 for the next tower in the following order: 0, 3, 12, 15, 14, 8, 1, 7, 11, 13, 4, 2, 5, 6, 9 and 10. GLAST ACTION EXPECTED RESPONSE 10 November 06 v4 COMMENTS Verify LAT state tlm: LIMTACTION = LIM_ACTION_POWER_ON (4) LIMTSTATUS = (even number) b. TEM-10 power supply current is in range: LHKT10TEM28V0ST = 0 LHKT10TEM28V0 = 0.6 – 1.1 A LHKT10TEM28V1ST = 0 LHKT10TEM28V1 = 0.6 – 1.1 A c. TKR-10 1.5V analog and 2.5V analog and digital voltages are in range: LHKT10TKR15VAAST = 0 LHKT10TKR15VAA = 1.3 – 1.7 V LHKT10TKR25VDST = 0 LHKT10TKR25VD = 2.3 – 3.0 V LHKT10TKR25VABST = 0 LHKT10TKR25VAB = 2.3 – 3.0 V d. TKR-10 bias voltages are in range : LHKT10TKRBV0ST = 0 LHKT10TKRBV0 = -1.0 to 30.0 A LHKT10TKRBV1ST = 0 LHKT10TKRBV1 = -1.0 to 30.0 A e. TKR-10 bias current is in range. LDET10TKRBIASI = -0.1 to 0.1 A f. TKR-10 temperatures are in range: LHKT10TKRCzT0ST = 0 LHKT10TKRCzT0 = 10.0 to 35.0 °C LHKT10TKRCzT1ST = 0 LHKT10TKRCzT1 = 10.0 to 35.0 °C (z = 0-7) See expected response of steps 39-51. a. 23 L-OBS-03x STEP 64. OWNER LAT LAT Observatory Level EPS Performance Outline DESCRIPTION Verifying ACD FREE Board-f health prior to power on: For f = 0 – 11 Steps 64 through 68 will be repeated to turn on the components for all boards. Use two digit values for the variable f in commands. For instance board 5 would be 05. Use single digit values for f = 0-9 for telemetry. Start with free board 0 GLAST ACTION LHKREQDIAGPKT LHKDIAGAPID=0x226; LHKDIAGCOUNT=1024 LHKDIAGINTERVAL=250 (4min 16sec at 4Hz max) EXPECTED RESPONSE 10 November 06 v4 COMMENTS The DiagAemEnv0 packet is detected in the Diagnostic Telemetry stream at 4 Hz. b. ACD BEA grid temperatures are in range PduEnv3: LHKP0ACDBGT0ST = 0 LHKP0ACDBGT0 = 10.0 to 35.0 °C LHKP0ACDBGT1ST = 0 LHKP0ACDBGT1 = 10.0 to 35.0 °C c. LAT ACD PMT rail temps are in range PduEnv3: LHKP0ACDPRTyST = 0 LHKP0ACDPRTy = 10.0 to 35.0 °C (y = 0 – 3) a. 24 L-OBS-03x STEP OWNER 65. LAT 66. SC 67. LAT 68. SC GLAST LAT Observatory Level EPS Performance Outline DESCRIPTION Power on ACD Free board-f Verifying GASU health following FREE Board power-f on. For f = 0 – 11 Steps 64 through 68 will be repeated to turn on the components for all boards. End dwell on ACD Free board telemetry Measure and record the NEB 4 delta current that resulted from ACD FREE Board-f power on and calculate ACD FREE Board-f power consumption using the test instrumentation and telemetry. ACTION Power on Free board-f LIMPOWERON LIMPWRACDFREEf =1 Stop Dwelling on ACD Free board telemetry packet AemEnv0 LHKSTOPDIAG EXPECTED RESPONSE 10 November 06 v4 COMMENTS Verify LAT state tlm: LIMTACTION = LIM_ACTION_ POWER_ON (4) LIMTSTATUS = (even number) b. Free board-f voltage is in range AemEnv0: LHKAEMFRfVDST = 0 LHKAEMFRfVD = 3.1 – 3.5 V c. Free board-f 3.3 current sum delta is in range PduEnv0: LHKAFR33ISUMST = 0 LHKAFR33ISUM = 0.0 – 0.9 V d. Free board-f temperature is in range AemEnv0: LHKAEMFRfTST = 0 LHKAEMFRfT = 10.0 to 35.0 °C a. a. GASU AEM/EBM, GEM 3.3 and AEM/EBM, GEM 2.5 voltages are in range: L_DAQ_P_EBM33_V = 3.1 – 3.5 V L_DAQ_P_EBM25_V = 2.3 – 2.7 V L_DAQ_P_GEM33_V = 3.1 – 3.5 V L_DAQ_P_GEM25_V = 2.3 – 2.7 V a. The DiagAemEnv0 packet is no longer detected in the Diagnostic Telemetry stream ACD FREE Board-f power consumption is <5W. b. NEB 4 current delta <0.25 A. a. 25 L-OBS-03x STEP OWNER LAT Observatory Level EPS Performance Outline DESCRIPTION 69. LAT Power on ACD Free boards-1 through 11 70. LAT Verifying CAL HVBS-y health prior to power on. GLAST ACTION Repeat steps 64-68 to power on ACD Free boards 1 through 11. EXPECTED RESPONSE 10 November 06 v4 COMMENTS See expected response of steps 64 - 68. CAL-y 3.3V analog and digital voltages are in range TemEnvPwri: LHKTyCAL33VDST = 0 LHKTyCAL33VD = 3.1 – 3.5 LHKTyCAL33VAST = 0 LHKTyCAL33VA = 3.1 – 3.5 V b. CAL-y base plate temperature is in range PduEnv1: LHKP0CALyBPTST = 0 LHKP0CALyBPT = 10.0 to 30.0 °C c. CAL-y AFEE temperatures are in range TemEnvTemp: (z = 0-3) LHKTyCALAFzT1ST = 0 LHKTyCALAFzT1 = 10.0 to 30.0 °C a. 26 L-OBS-03x STEP 71. OWNER LAT LAT Observatory Level EPS Performance Outline DESCRIPTION Power on CAL HVBS-y For y = 0 – 15 This step will be repeated to power on all CAL high voltage supplies Use two digit values for the variable y in commands. For instance CAL 5 would be 05. Use single digit values for y = 0-9 for telemetry. Start with CAL 0 ACTION Power on TKR HVBS-y LIMBIASCAL LIMPAD = 0 LIMCALVALIDy = 1 LIMCALBIASy = 0x5800 (70 V) Repeat this step to power on all CAL high voltage supplies EXPECTED RESPONSE a. b. c. d. e. 72. SC Measure and record the NEB 4 delta current that resulted from CAL HVBS-y power on and calculate CAL HVBS-y power consumption using the test instrumentation and telemetry. a. b. c. GLAST 10 November 06 v4 COMMENTS Verify LAT state tlm: LIMTACTION = LIM_ACTION_BIAS_CAL LIMTSTATUS = (even number) CAL-y 3.3V analog and digital voltages are in range TemEnvPwri: LHKTyCAL33VDST = 0 LHKTyCAL33VD = 3.1 – 3.5 V LHKTyCAL33VAST = 0 LHKTyCAL33VA = 3.1 – 3.5 V CAL-y AFEE temperatures are in range TemEnvTemp: (z = 0-3) LHKTyCALAFzT1ST = 0 LHKTyCALAFzT1 = 10.0 to 30.0 °C CAL-y bias voltages are in range TemEnvPwr: LHKTyCALBSV0ST = 0 LHKTyCALBSV0 = 50.0 – 90.0 V LHKTyCALBSV1ST = 0 LHKTyCALBSV1 = 50.0 – 90.0 V CAL-y bias current is in range LDETyCALBIASI = -0.1 to 0.1 A Verify PRU output voltages For PRU A-Side SE_PRU_P_DAQ_V = 28.0 ± 1.0V SE_PRU_R_DAQ_V = 0.0 ± 1.0V For PRU B-Side SE_PRU_P_DAQ_V = 0.0 ± 1.0V SE_PRU_R_DAQ_V = 28.0 ± 1.0V CAL HVBS-y power consumption is <5W. NEB 4 current delta <0.25 A. 27 L-OBS-03x STEP 73. OWNER LAT LAT Observatory Level EPS Performance Outline DESCRIPTION ACTION Verifying TKR HVBS-y health prior to power on. EXPECTED RESPONSE a. b. 74. LAT Power on TKR HVBS-y For y = 0 – 15 This step will be repeated to power on all TKR high voltage supplies Use two digit values for the variable y in commands. For instance TKR 5 would be 05. Use single digit values for y = 0-9 for telemetry. Start with TKR 0 Power on TKR HVBS-y LIMBIASTKR LIMPAD = 0 LIMTKRVALIDy = 1 LIMTKRBIASy = 0x54fe (105 V) a. b. Repeat this step to power on all TKR high voltage supplies y = 1 – 15 c. d. e. GLAST 10 November 06 v4 COMMENTS TKR-y 1.5V analog and 2.5V analog and digital voltages are in range TemEnvPwr: LHKTyTKR15VAAST = 0 LHKTyTKR15VAA = 1.3 – 1.7 V LHKTyTKR25VDST = 0 LHKTyTKR25VD = 2.3 – 3.0 V LHKTyTKR25VABST = 0 LHKTyTKR25VAB = 2.3 – 3.0 V TKR-y temperatures are in range TemEnvTemp: (z = 0-7) LHKTyTKRCzT0ST = 0 LHKTyTKRCzT0 = 10.0 to 30.0 °C LHKTyTKRCzT1ST = 0 LHKTyTKRCzT1 = 10.0 to 30.0 °C Verify LAT state tlm LIMTACTION = LIM_ACTION_BIAS_ TKR LIMTSTATUS = (even number) TKR-y 1.5V analog and 2.5V analog and digital voltages are in range TemEnvPwr: LHKTyTKR15VAAST = 0 LHKTyTKR15VAA = 1.3 – 1.7 V LHKTyTKR25VDST = 0 LHKTyTKR25VD = 2.3 – 3.0 V LHKTyTKR25VABST = 0 LHKTyTKR25VAB = 2.3 – 3.0 V TKR-y temperatures are in range TemEnvTemp: (z = 0-7) LHKTyTKRCzT0ST = 0 LHKTyTKRCzT0 = 10.0 to 30.0 °C LHKTyTKRCzT1ST = 0 LHKTyTKRCzT1 = 10.0 to 30.0 °C TKR-y bias voltages are in range TemEnvPwr: LHKTyTKRBV0ST = 0 LHKTyTKRBV0 = 50 – 110 V 28 L-OBS-03x STEP 75. OWNER SC LAT Observatory Level EPS Performance Outline DESCRIPTION Measure and record the NEB 4 delta current that resulted from TKR HVBS-y power on and calculate TKR HVBS-y power consumption using the test instrumentation and telemetry. ACTION EXPECTED RESPONSE a. b. c. 76. LAT Verifying ACD Free board HV-f health prior to power on. a. b. c. GLAST 10 November 06 v4 COMMENTS Verify PRU output voltages For PRU A-Side SE_PRU_P_DAQ_V = 28.0 ± 1.0V SE_PRU_R_DAQ_V = 0.0 ± 1.0V For PRU B-Side SE_PRU_P_DAQ_V = 0.0 ± 1.0V SE_PRU_R_DAQ_V = 28.0 ± 1.0V TKR HVBS-y power consumption is <5W. NEB 4 current delta <0.25 A. LAT ACD PMT rail temps are in range PduEnv3: (y=0-3) LHKP0ACDPRTyST = 0 LHKP0ACDPRTy = 10.0 to 30.0 °C Free board-f voltage HV-f is in range AemEnv0: (f=0-11) LHKAEMFRfV1ST = 0 LHKAEMFRfV1 = -0.5 to 80.0 V Free board 3.3 current sum delta is in range PduEnv0: LHKAFR33ISUMST = 0 LHKAFR33ISUM = -1.0 to 10.0A 29 L-OBS-03x STEP 77. OWNER LAT LAT Observatory Level EPS Performance Outline DESCRIPTION Turn on and configure the ACD Free board-f HV bias voltages For f = 0 – 11 This step will be repeated to configure all ACD free board HV bias voltages Use two digit values for the variable f in commands. For instance board 5 would be 05. Use single digit values for y = 0-9 for telemetry. Start with board 0 ACTION Configure Free board bias voltages LIMBIASACD LIMARCSAAVALIDf = 1 LIMARCVETOENAf = 1 LIMARCVETOENBf = 0 LIMARCSAAPADf = 0 LIMARCSAABIASf = 945 LIMARCHVVALIDf = 1 LIMARCHV1BSf to 1 LIMARCHV2BSf to 0 LIMARCHVPADf = 0 LIMARCHVBIASf = [2331,2394,2268,2299,2252, 2346,2583,2520,2378,2331,239 4,2346] EXPECTED RESPONSE 10 November 06 v4 COMMENTS Verify LAT state tlm: LIMTACTION = LIM_ACTION_BIAS_ ACD (56) LIMTSTATUS = (even number) b. LAT ACD PMT rail temps are in range PduEnv3: (y=0-3) LHKP0ACDPRTyST = 0 LHKP0ACDPRTy = 10.0 to 30.0 °C c. Free board-f voltage HV-f is in range AemEnv0: (f=0-11) LHKAEMFRfV1ST = 0 LHKAEMFRfV1 = (-0.5) – 100.0 V d. Free board 3.3 current sum delta is in range PduEnv0: LHKAFR33ISUMST = 0 LHKAFR33ISUM = (-1.0) – 10.0A a. Repeat this step to configure all ACD free board HV bias voltages f = 1 – 11 78. SC GLAST Verifying GASU health following ACD FREE Board HVBS-f on. For f = 0 – 11 Steps 64 through 68 will be repeated to turn on the components for all boards. a. GASU AEM/EBM, GEM 3.3 and AEM/EBM, GEM 2.5 voltages are in range: L_DAQ_P_EBM33_V = 3.1 – 3.5 V L_DAQ_P_EBM25_V = 2.3 – 2.7 V L_DAQ_P_GEM33_V = 3.1 – 3.5 V L_DAQ_P_GEM25_V = 2.3 – 2.7 V 30 L-OBS-03x STEP 79. OWNER LAT LAT Observatory Level EPS Performance Outline DESCRIPTION Set ACD HVBS Free board bias voltage to SAA level ACTION 10 November 06 v4 EXPECTED RESPONSE Enable SAA bias voltage: LIMCONFIGHV LIMHVPAD1 = 0 LIMHVALLOW = 0 LIMHVPAD2 = 0 LIMHVVALID = 1 a. Free board-f voltage is in SAA range AemEnv0: (f=0-11) LHKAEMFRfV1ST = 0 LHKAEMFRfV1 = 270 – 330 V COMMENTS . b. 80. LAT Set ACD HVBS Free board bias voltage to Ops level Enable Ops ACD HVBS voltage: LIMCONFIGHV LIMHVPAD1 = 0 LIMHVALLOW = 1 LIMHVPAD2 = 0 LIMHVVALID = 1 a. 81. LAT Verify the final configuration is as expected 82. LAT Verify LAT is in Application Mode with LHK running. a. Check LIMTOPMODE telemetry b. Check if all steps of this procedure have been successfully completed. Verify telemetry 83. LAT Verify all telemetry is with in range. Enable LICOS power on limits a. LIMTOPMODE = LIM_OP_MODE_QUIESCENT (1) b. LTCRUNMODE = 1 (RUNNING) c. LTCCNTLMODE = 1 (ACTIVE control) a. Verify LAT mode: LIMTOPMODE = Active EPUs will LIM_OP_MODE_QUIESCENT (1) change with the b. Verify SIU is running: H0554SECONDS selected configuration. increases c. Verify EPU0 is running: H0555SECONDS increases d. Verify EPU1 is running: H0556SECONDS increases No LAT telemetry red or yellow limits are exceeded. 84. SC Measure the total power input to the LAT using both telemetry and the test instrumentation. a. 85. LAT Perform a 36 second muon run to verify LAT health and configuration. GLAST Calculate DAQ feed power by using NEB-4 current delta from step 15 to step 64 and multiply by the DAQ feed voltage. b. To item a) above add the power consumption from the SIU feed. Run LICOS script intSeApp_e2e_LAT-70x_0.01hr Free board-f voltage is in Ops range AemEnv0: (f=0-11) LHKAEMFRfV1ST = 0 LHKAEMFRfV1 = [666,814;684,836;648,792;657,803;643, 787;670,820;738,902;720,880;679,831;666, 814;684, 836;670,820] V (low, high) Total LAT power = 500 – 650 W LICOS indicates script PASSED. 31 L-OBS-03x STEP OWNER LAT Observatory Level EPS Performance Outline DESCRIPTION 86. SC Disable LAT Commanding 87. SC Dump Science and Housekeeping data from SSR. 88. LAT Verify Science and Housekeeping data dumped from SSR has been received. GLAST ACTION In AstroRT commanding window select: Options OTCC Ready? Not Ready EXPECTED RESPONSE 10 November 06 v4 COMMENTS In LICOS Proxy Window, indicator shows “Not Ready”. [Need SC verifiers for this item] [Is any LAT action required??] [Need LICOS verification for this item] 32