Whole Building Design Guide Biodiesel Fueled Cogeneration Systems for a Building Fred Betz, PhD. David Archer, PhD. Center for Building Performance and Diagnostics School of Architecture College of Fine Arts Carnegie Mellon University Pittsburgh, Pennsylvania May 29, 2009 Table of Contents Whole Building Design Guide ............................................................................................ 1 Biodiesel Fueled Cogeneration Systems for a Building ..................................................... 1 Table of Contents ................................................................................................................ 2 List of Figures ..................................................................................................................... 4 List of Tables ...................................................................................................................... 5 Nomenclature ...................................................................................................................... 6 1.0 Preliminary Design Guide............................................................................................. 7 1.1 Generic Design Steps ................................................................................................ 7 1.1.1 Loads .................................................................................................................. 7 1.1.2 Fuel Selection..................................................................................................... 8 1.1.3 Energy Grids ...................................................................................................... 8 1.1.4 Prime Movers ..................................................................................................... 9 1.1.5 Auxiliary and Heat Recovery Equipment .......................................................... 9 1.1.6 Operating Strategy ........................................................................................... 10 1.1.7 CHP System Evaluation ................................................................................... 11 2.0 Design of Biodiesel Fueled CHP System ................................................................... 12 2.1 Load Profiles ........................................................................................................... 12 2.2 Fuel Selection.......................................................................................................... 12 2.3 Energy Grids ........................................................................................................... 13 2.4 Prime Movers .......................................................................................................... 13 2.5 Auxiliary and Heat Recovery Equipment ............................................................... 14 2.6 Operations ............................................................................................................... 15 2.7 Evaluation ............................................................................................................... 16 2.8 Submittals ............................................................................................................... 16 Appendix A: Background ................................................................................................. 18 A.1 Fuels ....................................................................................................................... 18 A.2 Energy Grids .......................................................................................................... 19 A.3 Prime Movers ......................................................................................................... 20 A.3.1 Central Power Plants ....................................................................................... 20 A.3.2 Boilers and Steam Turbines ............................................................................ 20 A.3.3 Gas Turbine ..................................................................................................... 20 A.3.4 Internal Combustion Engines .......................................................................... 20 A.3.5 Fuel Cells ........................................................................................................ 21 A.3.6 Prime Mover Summary ................................................................................... 21 A.4 Heat Loads ............................................................................................................. 21 A.4.1 Space Heating ................................................................................................. 22 A.4.2 Absorption Cooling ......................................................................................... 22 A.4.3 Desiccant Regeneration................................................................................... 22 A.4.4 Other Heat Loads ............................................................................................ 23 A.4.5 Storage ............................................................................................................ 23 A.4.6 Heat Loads Summary ...................................................................................... 23 Appendix B: Biodiesel Fueled CHP system ..................................................................... 24 B.1.1 System Components ........................................................................................ 24 B.1.2 Input / Output .................................................................................................. 31 2 B.1.3 Operating Description and Results .................................................................. 32 B.1.3.1 Engine: Measured Data versus Manufacturer’s Specifications................ 34 B.1.3.1 Pressure – Time – Crank Angle Measurements ....................................... 35 B.1.3.2 Turbocharger Analysis ............................................................................. 37 B.1.3.3 Combustion Gas and Emissions Analysis ................................................ 38 B.1.3.4 Heat Recovery Analysis ........................................................................... 41 Appendix C ....................................................................................................................... 44 Appendix D: Steam System Schematics ........................................................................... 45 References ......................................................................................................................... 46 3 List of Figures Figure 1: IW Heating and Cooling System Flow Diagram\ ............................................. 14 Figure 2: Basic CHP Flow Diagram ................................................................................. 24 Figure 3: CHP System Components ................................................................................. 25 Figure 4: Baldor Engine Generator ................................................................................... 25 Figure 5: ATS/SLC with Screen Shot Operating at 18kWe and exporting 12 kWe......... 26 Figure 6: Assembled Components: Engine Generator (Left), Steam Generator (Right) .. 27 Figure 7: Steam - Hot Water Converter ............................................................................ 28 Figure 8: Coolant Heat Exchanger with Piping before Insulation .................................... 29 Figure 9: Remote Mounted Radiator ................................................................................ 29 Figure 10: Engine Generator Onboard Interface .............................................................. 30 Figure 11: Engine Generator Onboard Interface .............................................................. 30 Figure 12: Automated Logic CHP User Interface for the Heat Recovery/Rejection System ........................................................................................................................................... 32 Figure 13: Pressure vs. Time for One Cylinder at 12 kWe using Low Sulfur Diesel Fuel ........................................................................................................................................... 36 Figure 14: Pressure vs. Time for One Cylinder at 12 kWe using Low Sulfur Diesel Fuel ........................................................................................................................................... 37 Figure 15: Turbocharger Compressor Map [] ................................................................... 38 Figure 16: Summer Operation of the Steam Generator T-Q Diagram.............................. 42 Figure 17: T-Q Diagram for Coolant Heat Exchanger at 25 kWe .................................... 43 4 List of Tables Table 1: Typical U.S. Commercial Building Loads ........................................................... 8 Table 2: Prime Mover Performance Summary ................................................................... 9 Table 3: Prime Mover Performance Summary ................................................................. 21 Table 4: Averaged Summer Diesel Commissioning and Experimental CHP Results ...... 33 Table 5: Averaged Winter Diesel Commissioning and Experimental CHP Results ........ 33 Table 6: Averaged Winter Biodiesel Experimental Results ............................................. 33 Table 7: Diesel Engine Generator Measured Data vs. Manufacturer Specifications ....... 34 Table 8: Biodiesel Engine Generator Data vs. Manufacturer Specifications ................... 35 Table 9: Average Gaseous Emissions vs. Load with Low Sulfur Diesel Fuel ................. 38 Table 10: Average Gaseous Emissions vs. Load with Soy Biodiesel Fuel ...................... 39 5 Nomenclature BAPP: Building As Power Plant CHP: Combined Heat and Power, also known as cogeneration CCHP: Combined Cooling Heat and Power, also known as trigeneration CMU: Carnegie Mellon University CBPD: Center for Building Performance and Diagnostics DG: Distributed Generation IC: Internal Combustion IW: Intelligent Workplace IWESS: Intelligent Workplace Energy Supply System kW: kilowatt kWc: kilowatt chemical (fuel energy) kWe: kilowatt electric kWt: kilowatt thermal 6 1.0 Preliminary Design Guide This guide provides a generic approach to the preliminary design of a cogeneration system that will provide power, cooling, heating, and ventilation to a building. A specific example of design based on the biodiesel fueled CHP system designed, installed, operated and evaluated at Carnegie Mellon University. The design process is iterative; however seven steps in sequence are recommended. Throughout the design process engineers should be aware of local code requirements as they affect decisions. 1.1 Generic Design Steps The general procedure for designing a CHP system is to: determine the electrical and thermal loads of the building, load profiles and the required flow rates and temperatures of cooling and heating streams. determine which fuel types are locally available, how they are distributed, and their cost. determine what energy grids for power, natural gas, steam, chilled water, etc. are available, what their operating conditions and costs are, and if it is possible to interface with them. select a prime mover that best fits the load profile and load proportions. select auxiliary and heat recovery equipment to match the prime mover and the fluids used to transfer energy. choose an operating strategy (thermal or electrical load follow, base load operation, etc.) evaluate design options on the basis of capital, operating, and environmental cost. As these steps are carried out the following documents should be created: a flow diagram. material and energy balances. equipment descriptions. operating descriptions. a process and instrumentation diagram. a preliminary layout of equipment cost estimates for the equipment and its installation These documents provide the basis for equipment procurement, detailed design, installation, and operation of a cogeneration system for a building. 1.1.1 Loads The first task is to identify the energy loads for the CHP system. These include, but are not limited to: electrical (lighting, pumps, fans, computers, etc.), space cooling and heating, ventilation, dehumidification, and process energy. Lawrence Berkley National Labs (LBNL) publishes generic annual load values for U.S. buildings on a square foot basis shown in Table 1. 7 U.S. Commercial Office Building Energy Intensity (kBTU/ft2-year) Space Water Office Cooling Cooking Ventilation Lighting Refrigeration Heating Heating Equipment 33.2 11.0 11.4* 1.4 6.1 18.9 0.3 11.1 *Electrical energy for operation of a vapor compression chiller. Table 1: Typical U.S. Commercial Building Loads Other 7.8 Table 1 shows thermal and electrical loads assuming average furnace and chiller efficiencies of 80% and COP = 3.2 respectively. The cooking load is not specified as an electrical or thermal load in the LBNL report. Ventilation energy is assumed to be for a forced air system that delivers the heating, cooling, and fresh air. The information in Table 1 gives annual energy demands; however, to properly size and evaluate a CHP system, peak and base loads and annual hourly load profiles are required. Hourly load data can come from metered data or from building energy simulations. Simulation data should be used carefully and it is reasonable to add a safety factor of 1.1 when sizing the system; metered data is best. Over sizing systems will lead to inefficiency. Reality dictates that metered data are not always readily available. When analyzing hourly data it important to find the peak (maximum) and base (minimum) electrical and thermal loads. Details about these loads such as voltage, temperatures, flow rates, and pressures should be determined as appropriate. 1.1.2 Fuel Selection There are many fuels available for the operation of CHP systems including: natural gas, petroleum products (gasoline, Diesel fuel, etc.), biomass (biogas, biodiesel, ethanol, solids), coal, and waste fuels (waste coal, garbage, etc.). Many of these fuels are associated with a particular type of prime mover. They vary in energy content, cost, availability, and emissions. The CHP system designer must determine what options are available based on this list of criteria and tabulate them to assist in the selection of a prime mover, and in the estimation of the operating costs of the system. 1.1.3 Energy Grids The availability of energy grids is an important consideration in the design of a CHP system for a building. Energy grids can come in many forms; electrical, natural gas, steam, chilled water, heated water, compressed air, etc. The most common energy grid is the electric utility grid. The interface with the electric utility grid must be coordinated with the local electric utility, which will have individual requirements governing the operation of CHP systems that detail voltages, power quality requirements, and cost structures for providing and accepting power. Larger systems may be required to generate a certain amount of power. Thermal grids (steam, chilled water, etc.) are operated by some large utilities or by smaller private entities. Similar to the electric utility grid, CHP system designers must contact the grid operators to determine if it is possible to interface with the grids. Typical performance requirements for interfacing with thermal grids include; temperatures, pressures, and flows. Furthermore, these temperatures, pressures, and flows may change throughout the year as thermal demands change throughout the year. 8 The ultimate goal of interfacing with energy grids is to have a source and sink for all the forms of energy generated by the CHP system and needed by the facility. Many types of commercial buildings have varying loads throughout the year, whereas CHP systems operate most efficiently at steady state. Energy grids provide the possibility to level the load on the CHP system by accepting or providing power or thermal energy so that it can operate independently of the local building loads. Also, importantly the energy grid can act as a back up in case of a plant failure. 1.1.4 Prime Movers The fourth step is to select a prime mover that will provide sufficient thermal and/or electrical energy at the proper conditions. Table 2 lists the prime movers most frequently considered for CHP systems in buildings along with some of their performance characteristics. Based on the building load profiles and the fuel data one or more prime movers will emerge as the best fit for a particular application. As previously stated, the design process is iterative. Therefore, prime mover options may be eliminated or identified in subsequent steps. Prime Mover Boiler + Steam Turbine Gas Turbine IC Engine -Diesel Fuels Nat. gas, coal, waste fuels, biomass Natural gas, biogas Diesel, biodiesel Gasoline, E85, natural gas Electrical Efficiency 10 - 15 % 15 - 25 % 30 - 40 % -Spark 20 - 30 % Fuel Cell -SOFC Natural gas 35 - 45 % -PEM Hydrogen 35 - 45 % Table 2: Prime Mover Performance Summary Recoverable Heat 45 - 65 % low quality steam 45 - 55 % 600oF exhaust 15 - 20 % 190oF coolant, 15 - 20 % 900oF exhaust 15 - 30 % 190oF coolant, 15 - 20 % 900oF exhaust 25 - 35 % 500oF exhaust 25 - 35 % 300oF exhaust CHP Efficiency Heat to Power Ratio 65 - 80 % 60 - 80 % 4.3 2.8 60 - 80 % 1.6 50 - 80 % 2.0 60 - 80 % 60 - 80 % 0.8 0.8 1.1.5 Auxiliary and Heat Recovery Equipment The fifth step in the design process is to select auxiliary heat recovery equipment that makes use of exhaust gas, coolant flow or steam to meet the desired loads. This equipment may include: heat exchangers absorption chillers (single and double effect) dehumidifiers thermal storage arrangements Appendix A further discusses the temperature and medium of these thermal outputs with respect to engine type. There are several ways of transferring heat and there are several types of heat exchangers that are tailored to particular mediums and applications. An important tool in selecting and designing equipment for recovery and utilization of thermal energy, heat, in CHP systems is the T-Q diagram as shown in Figures 16 and 17 in Appendix B. T-Q diagrams should be constructed for each exchange of thermal energy 9 in the system. It may be necessary to contact several manufacturers to determine the best match for the selected prime mover output and building load. At this point, it is possible to start to develop a preliminary flow diagram so that the CHP system designer can get an over view of the options thus far. There may be multiple flow diagrams at this point as a single prime mover and fuel may not have been selected yet, but there is sufficient information to get started. The preliminary flow diagrams allow the designer to visualize what forms of energy are available and what the loads are. As information becomes available and decisions are made in subsequent steps, the flow diagram is revised. Furthermore, it is prudent to develop multiple designs in parallel using different components and eliminating options as details become available. 1.1.6 Operating Strategy The sixth step in designing a CHP system is determining an operating strategy. There are many options available to engineers but they primarily include: steady state operation at the peak or at the base, minimum, loads of the system thermal or electrical load following operation Load following may be based on a thermal or electrical load and partially depends on the available auxiliary equipment and grid types. Electrical load follow is a mandatory operating method unless battery storage or a grid interconnection exists; more electricity can not be generated than is consumed, stored, or dissipated. Both battery storage and grid interconnection may be expensive, yet they allow the CHP system to operate much more efficiently allowing electricity to flow to and from the utility grid so the CHP operator only has to focus on effectively recovering and utilizing heat. Design operation typically takes on two forms: base loading and peak loading. Design operation is defined as operating the prime mover at a constant load for which it is designed and importing or exporting thermal and electrical energy as required. Base loading has the prime mover generating the minimum amount of thermal and/or electrical energy that will always be used by the building. The caveat to this mode of operation is that back up sources of heating, cooling, and electricity must be available to cover the load variability. These backups can come from standard boilers and chillers and/or the utility grids (electrical and thermal). Peak design operation on the other hand has the prime mover operating at a setting that will always generate sufficient electrical and thermal energy to meet any building load. The downside to this mode of operation is that excess amounts of thermal and electrical energy will have to be exported to an energy grid or rejected when loads are below peak values. Rejecting energy decreases over all efficiency, but extra equipment, boilers and chillers, will not be required to meet peaks. The decisions regarding operating strategies including startup and shut down will establish the requirements for the sensor, actuator and control system components and will provide the basis for the piping and instrumentation diagram. 10 1.1.7 CHP System Evaluation Evaluation serves multiple purposes. If multiple CHP system options exist the designer must weigh and select among these options on an engineering, economic, and environmental bases. The CHP system designer must also evaluate the efficiency, economic, and environmental performance as required by the conditions set by regulatory bodies, the system owner and the system operator. Regulatory bodies may want information on the quantity of emissions generated. Owners may be interested in how much money has been saved by operating the CHP system. CHP system operators may need information to diagnose problem and determine if the system is operating properly. The result of this step is to determine the best CHP system configuration and operating conditions to meet the economic demands of building operation. 11 2.0 Design of Biodiesel Fueled CHP System A biodiesel fueled CHP system was designed, installed, operated and evaluated according the design guide described above. 2.1 Load Profiles The thermal and electrical load profiles from the Intelligent Workplace (IW) were developed from a combination of metered and name plate data. A decision was made early on that the CHP system would be designed to meet the peak loads of the IW to demonstrate a facility that could be powered entirely by a renewable fuel and could export excess energy to neighboring buildings. Using data on existing HVAC, lighting, and plug loads a peak electrical demand of approximately 20 kWe was determined. Metered data for the double effect steam absorption chiller was available, which showed the peak demand as 16 kWt in the form of saturated steam at 87 psig (6 bar) with a flow rate of 65 lb/hr (29 kg/hr). Furthermore, metered data for the heating system showed a peak heating demand of approximately 40 kWt at 40oC (104oF). The heating load changes rapidly as the IW has a low thermal mass; therefore, outdoor temperature changes are felt in the building relatively quickly. The heating season typically lasts from early October to late March. The heating system was fed by the steam grid which operates at about 7 psig (0.5 bar) during the winter. The main steam supply pressure is 150 psig (10 bar) during the winter; this pressure is reduced inside the buildings on campus as appropriate. Regenerating the desiccant dehumidification wheel in the ventilation system is an additional heat load in the IW. Desiccant regeneration, like the chiller operation is also a seasonal load, however it is steadier than the chiller load. The metered data of the ventilation system showed a required temperature for regenerating the desiccant of approximately 195oF (95oC) with a peak demand of about 20 kWt. 2.2 Fuel Selection Local fuels that were available included natural gas and biodiesel fuel. As this was a demonstration facility, it was decided that using a renewable fuel was an important design consideration. Another group on the Carnegie Mellon University campus has commercialized a biodiesel fuel refining process. This new commercial entity agreed to donate the fuel for this system, which also made it the most economic fuel choice. Distribution of the biodiesel was not as simple as natural gas, which has a pipe line infrastructure in Pittsburgh, PA. Provision for filling fuel storage tanks had to be made, which was addressed during the detailed system design and equipment layout. 12 2.3 Energy Grids Carnegie Mellon’s campus has many energy grids including; electric, steam, and chilled water. These grids are connected to every building on campus; the steam and chilled water are generated at a central plant. The local utility, Duquesne Light, was contacted to determine their requirements for installing a utility paralleled engine generator with a capacity of between 20 and 30 kWe. Electricity enters the Carnegie Mellon campus at two points. Therefore, it is unlikely that the 20 to 30 kWe system would be noticed in a campus system that draws between 2 and 5 megawatts of electricity from Duquesne Light. Based on this information, Duquesne Light set no requirements for grid protection on this system. A grid outage would immediately over load the engine generator and cause it to shut down. Additional protections were provided in this demonstration facility, which will be discussed further during auxiliary equipment. The campus chilled water and steam grids are operated year round by Carnegie Mellon’s facilities management service. The university agreed to allow the CHP system to interface with the campus thermal grids to allow for importing and exporting of steam and chilled water. The chilled water operates year round at approximately 45oF (7oC). The steam grid also operates year round to prevent thermal expansion and contraction; the pressures vary from about 15 psig (1 bar) in the summer to 150 psig (10 bar) during the winter. The fall and spring pressures are approximately 40 psig (3 bar). Another smaller grid was available in the building: a hot water grid. This grid is not campus wide, but was considered as a possible outlet for thermal energy. The building hot water grid has an operating range of 26oC to 40oC (78oF to 105oF). 2.4 Prime Movers Three options were available, microturbines, Diesel engines, and fuel cells. Fuel cells were eliminated quickly as the cost was too high, approximately 100 times the cost of the microturbine and Diesel engines per kWe. The smallest microturbine available at the time was a 30 kWe unit, which corresponds to approximately 90 kWt at 530oF (270oC), much too large for this system. Diesel generator sets are available from many manufacturers that would provide about 20 kWt of high temperature exhaust. A 32 kWe Diesel engine generator was selected from John Deere. John Deere was ultimately selected for two reasons, it was locally supported and John Deere showed interest in the work. Next, as this is a prime power setup, as opposed to a backup power setup, the engine would not be operated at full power (32 kWe) for an extended period of time. An 80% power rating is reasonable for prime power applications or 25 kWe. Assuming that Diesel engines are about 33% electrically efficient, it was assumed that a Diesel engine operating at 25 kWe would produce approximately 25 kWt exhaust and coolant heat each. Based on this reasoning, a Diesel engine generator set was selected. Because of the high steam pressure and temperature required by the two stage absorption chiller the amount of exhaust energy used was closer to 18 kWt, and therefore diminished the heat recovered from the exhaust. Specification sheets from 13 engine manufacturers typically don’t include part load values or exact values for CHP systems. Conservative estimates are recommended. 2.5 Auxiliary and Heat Recovery Equipment Sizing the heat recovery equipment is where the first major difficulty arose for this system configuration, as there are no commercially available steam generators in the 1030 kWt size range. The smallest steam generator available for exhaust heat recovery was a 200 kWt unit from Vaporphase, Inc. The consequence of using a steam generator of this size is that the heat up time is very long, approximately nine hours from cold start to steady state, not including heating up the pipes. However, as a proof of concept, this was deemed an acceptable configuration. A high pressure hot water system would be recommended for a new system that would also include the purchase of an absorption chiller. Next, the thermal energy from the engine coolant needs to be recovered. A plate and frame heat exchanger was selected to transfer this energy to water that is utilized in the IW’s heating system. The configuration of the IW’s existing heating system allowed for the dual use of the hot water pipes for space heating in the winter and regenerating desiccant in the summer as the loads are not simultaneously active. It should be noted that this is not a common system configuration. Many buildings use what is called a four pipe heating system in which hot and cold water is available to the heating and cooling system as many buildings have to heat and cool at the same time, especially during the spring and fall. The passive design of the IW allows for the use of what is incorrectly assumed to be an inferior two pipe system. The IW does not require heating and cooling at the same time, and therefore an entire set of pipes can be eliminated as shown in Figure 1 below. Intelligent Workplace Chilled Water Supply Mullions Radiant Panels Fan Coils Chilled Water Return Hot Water Supply Regeneration Air Desiccant Regeneration Wheel Heat Exchanger Hot Water Return Outside Air Figure 1: IW Heating and Cooling System Flow Diagram\ 14 The coolant energy has a use during the summer for regenerating the desiccant and in the winter for space heating, however there are no reliable loads in the spring and fall. Therefore, a remotely mounted radiator is used to dump excess coolant energy to the atmosphere as there must always be an outlet for the coolant energy to prevent the engine from over heating. An alternative to this would have been to purchase a single effect absorption chiller to generate additional chilled water that could be exported to the chilled water grid, or to make a connection with the domestic hot water system of the building. Finally, the electrical energy needs to be sent to the power grid. The advantage of connecting power to the utility grid is that it allows operational freedom to produce the reject heat in the quantity required. If a CHP system does not have the flexibility to export electricity, the prime mover must always match the electrical demand. As electrical and thermal demands don’t necessarily coincide, too much waste heat could be generated, or not enough. The requirements of the utility paralleling gear (Automatic Transfer Switch / Soft Load Controller ATS/SLC) are determined by the local utility. Typically for very small systems, less than 100 kWe, the utility’s requirements are minimal. However, as this is a demonstration facility, a much more complex ATS/SLC was selected, which could provide additional operational flexibility and realism for larger systems. Based on all of this information several flow diagrams were generated and frequently revised as details emerged on equipment, pipe sizes, and sensor and actuator requirements. Due to the scattered nature of this CHP installation, the heat recovery equipment had to be placed in a relatively distant location from the absorption chiller. Therefore, piping losses (thermal and pressure) had to be considered as the piping distance is about 220 feet (67 meters) including a 70 foot (21 meter) vertical rise. A pressure drop of 5 psi (0.3 bar) and a thermal loss of 2.5 kWt were calculated based on these estimates as shown in Appendix C. Therefore, a minimum of 18.5 kWt was needed to drive the absorption chiller. It was decided to add a safety factor to this number and to set the requirements to 20 kWt. 2.6 Operations A specific operational strategy was not designated for this project as one of the research goals of this project is to compare operational strategies. The control system and infrastructure in place for this system allow the system to operate in various modes: thermal load follow, electrical load follow, base load, and peak load. There is an extra cost associated with this decision, but as a demonstration facility cost was not a driving factor. The extra costs come from additional controls programming as well as having actuators modulate their position rather than having two position valves. 15 2.7 Evaluation The fuel type, prime mover, and auxiliary equipment were selected relatively quickly for this application as there were a lot of constraints on equipment selection between the existing chiller and ventilation systems, the energy grids, and the demands of the building. The long term evaluation of all facets of this system was the primary focus of this project, and is outlined in section 3. The evaluation of this system was meant to satisfy CHP system designers, builders, operators, owners, and regulators as well as educational entities. Therefore, there is a great emphasis on data acquisition and dissemination. Over 200 data points are continuously measured and made available on the web. 2.8 Submittals Flow diagrams, material and energy balances, equipment descriptions, operating descriptions, process and instrumentation diagrams, preliminary layout, and cost estimates for equipment were all created and submitted to an engineering firm for detailed evaluation and the creation of construction drawings. The engineering firm created a detailed flow diagram, and a layout which balanced educational/scientific goals. The detailed flow diagram and the layout went through several iterations as the educational and scientific goals weren’t always understood by the engineering firm. Code requirements often clashed with scientific requirements, however eventually a compromise was met. For example, to accurately measure fuel consumption, a weigh tank is typically used, however code requirements indicate that tanks must be fastened to the floor. Therefore, the fuel tanks are fastened to the floor, and extra piping provisions were made to bypass the main fuel system so a separate fuel tank on a weigh scale could be used. Upon completion of the construction drawings, bids were sought and awarded for placing and connecting the equipment, installing instrumentation and controls, and commissioning the system. Details on the construction process can be viewed on the project website: http://www.cmu.edu/iwess/components/biodiesel_engine/installation/index.html 16 3.0 Conclusions, Recommendations, Future Work 17 Appendix A: Background Section two covers background information for each of step of the design guide. A.1 Fuels There are many fuels available for the operation of CHP systems including: natural gas, petroleum products (gasoline, Diesel, etc.), biomass (biogas, biodiesel, ethanol, solids), coal, and waste fuels (waste coal, garbage, etc.). Many of these fuels are associated with a particular type of prime mover and vary in energy content, cost, availability, and emissions. Natural gas is by far the most common fuel type accounting for about 75% of all CHP systems in operation in the U.S. [1]. The reason for this is that the fuel is readily available with a nationwide distribution network, the cost per unit of energy is relatively low, and the emissions are relatively clean. However, it should be noted that while the cost of natural gas is relatively low as compared to many other common fuels, the price is very volatile making operating costs projections problematic. Diesel fuel is the most common petroleum product used for CHP systems as Diesel engines provide a high electrical efficiency. Furthermore, Diesel fuels can be stored relatively easily adding a margin of security in case of a power outage, which may also affect the flow of natural gas. The cost is relatively high as Diesel fuel for CHP applications must still compete with Diesel fuel used for transportation, which is on average three times as expensive as natural gas per unit energy. Renewable fuels such as biomass are gaining market share due to their emissions characteristics and public appeal. Biomass can come in a gaseous, liquid or solid form. Biogas often comes from landfills and waste water treatment facilities. The first cost of treatment systems for the fuel is high; however operational costs are very low. Biogas is typically difficult to distribute, therefore it is often used on site or in nearby locations. Biodiesel on the other hand has a growing distribution network yet is being primarily used for transportation rather than power and heat generation. Biodiesel is typically made from soybean oil in the U.S., but can be made from many different plant oils and animal fats. The cost is relatively high as biodiesel is primarily used as a transportation fuel and does divert feed stocks from the food supply. Ethanol, which is typically made from corn is the most common liquid biofuel in the U.S. and is typically used for transportation, but would work in gasoline fueled engine generators that have been modified to operate with E85, or a gasoline-ethanol mixture that is 85% ethanol. Corn based ethanol is a controversial fuel, which may or may not provide energy independence or a net energy gain, as well as diverting a food source to fuel production. Ethanol from cellulose (corn husks, grass clippings, etc.) may solve the issue of diverting food production to fuel production and would be relatively inexpensive, however cellulosic ethanol is not commercially available yet. Finally, ethanol is a 18 problematic fuel from an engineering point of view. Ethanol is hygroscopic, meaning it absorbs water, it has a relatively low energy density, and requires the modification of engines to run on E85. Cellulosic butanol may be the best of both worlds providing a fuel that is very similar to gasoline in energy density and performance, while not requiring engines to be significantly altered [2]. Cellulosic butanol is still in the laboratory scale development and will not be commercially available for several years. Solid fuels, referred to as biomass include wood chips, saw dust, grass clippings and any other solid biological material can be burned in an incinerator to generate steam and drive a turbine to generate electricity. Biomass is considered a relatively crude fuel and is somewhat difficult to distribute, however it is usually inexpensive. The emissions vary, and care must be taken when using biomass to fuel a CHP system, but it can be clean. Coal is typically used in larger CHP systems and carries with it negative emissions characteristics including high CO2, particulates, SO2, NOX, heavy metals, etc.. However, the distribution system is relatively good and the cost is relatively low and steady. The emissions characteristics of coal systems are highly regulated by the EPA and getting permits may be difficult, especially in urban environments. Finally, waste fuels such as waste coal, garbage and heavy oils can be used in CHP systems; however such systems typically require significant emissions controls. Garbage presents an interesting challenge as the actual fuel composition on site is unknown; however it can be successfully implemented in a CHP system. For example, the Hennepin Energy Recovery Center in downtown Minneapolis, MN burns garbage providing electricity and heat to the downtown area [3]. A.2 Energy Grids There are several types of energy grids, most commonly the electric utility grid. This grid is nationwide and offers some flexibility to operators of CHP systems. Each utility grid operator has different sets of rules and regulations; therefore it is important to contact the utility when considering the installation of a CHP system. Thermal grids are sometimes available for CHP operators such as steam, hot water and chilled water. These grids can provide sources and sinks for thermal energy. Energy grids enable CHP operators to manage both excess and shortages of energy. Buildings typically have varying loads over the course of a day as occupants come and go and as the weather changes. Furthermore, various energy loads may not be coincident. There may be a large electrical load and a low heating load during the day as the sun is shining and people are present on a fall day. However at night, the temperature drops and additional heating is required but there is little demand for electricity. CHP systems tend to operate better with steady conditions simultaneously generating electricity and heating that should be used. Some energy grids allow CHP systems to operate flexibly giving and taking a variety of forms of energy as they are needed or not needed depending on the regulations set by the primary grid operator. Furthermore, energy grids provide a great backup source of energy in case the CHP system fails. 19 Energy grids found on college campuses are particularly effective, providing electricity, heating, and cooling to a mix of institutional and residential applications. As students are preparing for the day they are using energy in their dormitories, then they move to laboratories, classrooms, and offices and continue to use energy. In the evening they return to their dormitories to study, eat dinner, and enjoy recreation, all of which can use the same CHP system. A.3 Prime Movers Prime movers are defined as the device that consumes the fuel, delivers power, and rejects heat; such as a boiler with a steam turbine, a Diesel engine, or a gas turbine. A.3.1 Central Power Plants Many central power plants are of the boiler – steam turbine type and burn coal to generate steam in a boiler, and then send that high pressure steam through a turbine to generate electricity. Furthermore, these central power plants typically have very large generating capacity, in excess of 500 MW and sometimes greater than 1,000 MW. The efficiency of these plants appears to have reached a maximum at about 35%, although 38% efficiency is possible with very sophisticated and expensive equipment [Error! Bookmark not defined.]. Nuclear power plants operate in a similar way with the exception of using enriched uranium as a fuel to provide heat rather than coal. Note, a combination of boiler and steam turbine can be used on a smaller scale, and are often used with low grade fuels making them cheap to operate. A.3.2 Boilers and Steam Turbines The combination of a boilers and steam turbines is an effective way of using low quality, inexpensive fuels such as biomass and waste fuels to generate electricity and heat. The electrical efficiency of these systems is relatively low, 10% to 15%; however a lot of low quality steam is available for a variety of applications. The emissions generated from this type of system vary, and will require detailed study for permitting. These systems come in a variety of sizes, typically 100 kWe and up. A.3.3 Gas Turbine Gas turbines for power generation typically use natural gas, however examples of turbines using kerosene, jet fuel, biogas, and biodiesel among others can be found. Gas turbines come in a variety of sizes from 30 kW up to 50 MW. The efficiencies of gas turbines can vary based on the technology used. A simple gas turbine can have an electrical efficiency as low as 15%, but as high as 45% [Error! Bookmark not defined.]. This difference is primarily based on the use of a regenerator to preheat incoming air or the use of a combined cycle process that captures waste heat to generate steam and drive an additional turbine. Distributed Generation systems typical operate around 15-25% electrical efficiency. A.3.4 Internal Combustion Engines Internal combustion (IC) engines can use multiple types of fuel but typically use natural gas, Diesel, or gasoline for operation. Biodiesel and biogas have also been frequently 20 used, but are much less common. Efficiencies also vary for reciprocating engines based on the technology but a natural gas fired IC engine would have a high efficiency of 25%, whereas a very efficient Diesel engine can reach an efficiency of 40%. A.3.5 Fuel Cells Fuel cells have taken on a variety of forms, fuel types, and efficiencies. While fuel cells are arguably the most efficient form of generating electricity, the high cost both in raw materials and manufacturing has not allowed them to become a mainstream prime mover in the last century. Therefore, fuel cells will not be considered in this paper as possible DG source, although the future potential of this technology is considerable. A.3.6 Prime Mover Summary In a CHP system it should be noted that none of these prime movers is inherently better than another on an energy basis. If each CHP system achieves an efficiency of 80%, then the factors that vary are the proportion of electricity to heat, and the ability to use the various fuels effectively. As the goal is to use as much reject heat as possible, a CHP operator will have to be aware of many issues, including how much heat and electricity are demanded by the building and its surrounding facilities and how much is available and in what forms. First costs, cost of fuel, cost of heat and electricity, and maintenance costs will all vary and need to be accounted for. Also, while there isn’t necessarily a cost associated with emissions, this too may be regulated in the future. Furthermore, the EPA has designated some locations as non-attainment zones for sulfur oxides, nitrogen oxides, and particulates, etc. that may have a mitigation cost associated with it. A summary of prime movers, fuels, and performance is shown in Table 3. Prime Mover Boiler + Steam Turbine Gas Turbine IC Engine -Diesel Fuels Nat. gas, coal, waste fuels, biomass Natural gas, biogas Diesel, biodiesel Gasoline, E85, natural gas Electrical Efficiency 10 - 15 % 15 - 25 % 30 - 40 % -Spark 20 - 30 % Fuel Cell -SOFC Natural gas 35 - 45 % -PEM Hydrogen 35 - 45 % Table 3: Prime Mover Performance Summary Recoverable Heat 45 - 65 % low quality steam 45 - 55 % 600oF exhaust 15 - 20 % 190oF coolant, 15 - 20 % 900oF exhaust 15 - 30 % 190oF coolant, 15 - 20 % 900oF exhaust 25 - 35 % 500oF exhaust 25 - 35 % 300oF exhaust CHP Efficiency Heat to Power Ratio 65 - 80 % 60 - 80 % 4.3 2.8 60 - 80 % 1.6 50 - 80 % 2.0 60 - 80 % 60 - 80 % 0.8 0.8 A.4 Heat Loads The earliest use for reject heat from power generation facilities was in the 1880s with Thomas Edison’s Pearl street power plant in New York [4]. The plant was only about 8% efficient and Edison recognized that he could improve his bottom line by selling the excess heat to neighboring buildings in the winter for space heating [4]. 21 Over the last century additional uses for reject have been found and implemented to varying degrees around the world, many of which are found in the Intelligent Workplace. Reject heat temperatures vary greatly depending on the type of prime mover; however ball park temperatures are available. A Diesel engine would supply exhaust at temperatures in excess of 900oF (482oC) and coolant at 195oF (91oC). A microturbine might provide exhaust around 600oF (316oC). All of these heat sources provide a high enough temperature for many applications, which will be discussed below. A.4.1 Space Heating Space heating is probably the most common application for reject heat utilization. This heat can be utilized using radiant and convective systems typically found in many buildings. Space heat is particularly effective as the temperature is relatively low with a wide range of useful temperature possible. Operating temperatures range between 90oF (32oC) for the radiant surfaces in the Intelligent Workplace to 120oF (49oC) common for air handling units. A.4.2 Absorption Cooling A heat pump is a technology that enables the transfer of heat from a low temperature to a high temperature [5]. Heat pumps can be mechanical driven using electricity and a motor or by heat. Absorption chillers are heat driven heat pumps [5]. Absorption chillers come in three common types based on the type of refrigerant that they use; ammonia and water, lithium-bromide and water, and lithium-bromide, water, and hydrogen [5]. The types of chillers used as part of IWESS are both lithium-bromide and water. Furthermore, different configurations of absorption chillers are available; single effect, double effect and triple effect [5]. The higher the number of chiller stages, the higher the overall efficiency [5]. However, the control system becomes more expensive and there is an increased cost per unit of cooling. A typical single effect chiller will have a coefficient of performance (COP) of around 0.5 to 0.7, whereas a double effect chiller can reach a COP of 1.2. It should be noted that normal chillers have a COP of 3.2 on average or greater [6]. However, the electricity used to drive the chiller must be paid for, whereas the heat used to drive the absorption chiller is nearly free in the form of solar energy or engine exhaust as demonstrated in the IWESS project. A.4.3 Desiccant Regeneration A common method of humidity control in buildings is to cool incoming outside air to a temperature at which the water vapor in the air condenses and is removed from the air stream, and then to reheat the air to the desired set point temperature. Needless to say this is an energy intensive process that can be accomplished more efficiently using a desiccant to absorb moisture [7]. As the desiccant absorbs water from the incoming air it becomes saturated overtime. Therefore, the desiccant needs to be regenerated using a hot air stream, which could come from a natural gas burner as is presently the case in IWESS or from a hot water heating coil in the future [7]. 22 A.4.4 Other Heat Loads There are many other places to utilize waste heat such as domestic hot water, which is found in almost every building. Additional heat demands include, but are not limited to; heating pools, drying laundry, process energy, and thawing sidewalks and streets as is done at Sierra Nevada College in Incline Village, Nevada. Research is being conducted into additional usages of reject heat; however the ones stated above are currently employed. A.4.5 Storage As discussed in section A.3 CHP systems tend to operate best in steady modes while buildings operate in dynamic modes. When an energy grid is not available to import and export energy, storage is an option to be considered by the engineer. While the electric grid is almost always available, banks of batteries have been used for electrical storage as well as using electrical resistance heaters to generate hot water or vapor compression chillers to generate chilled water. Thermal storage is most commonly used for domestic hot water in most businesses and homes. The same concept can be used for chilled and hot water, which can provide a buffer between the CHP system’s outputs and the buildings demands. Based on the loads an engineer must decide if storage should last for an hour or a day or longer. Ice storage is a common way of storing large amounts of cooling energy. An absorption chiller can be used to generate ice, however it must be an ammonia water chiller as lithium-bromide absorption chillers can only achieve a minimum of 3oC, which is insufficient to create ice. A.4.6 Heat Loads Summary As stated in the previous section that there are a number of possible heat sinks that can provide a use for reject heat from a CHP system. The overall goal is to have a steady demand for heat year round, which improves the economics of the CHP system. Some technologies are applied year round, some in a heating season and some in the cooling season; it is up to the CHP system designer to use the given building and site loads to find the proper balance. 23 Appendix B: Biodiesel Fueled CHP system The biodiesel fueled engine generator with heat recovery system has been operating for over a year achieving a maximum efficiency of 76%, and efficiency comparable to other CHP systems. B.1.1 System Components There are four major components in the biodiesel CHP system shown in Figure 2: engine generator, steam generator, coolant heat exchanger, and automatic transfer switch (ATS) / soft load controller (SLC) Power to IW/Grid ATS / SLC Exhaust Muffler Generator Absorption Chiller Steam Diesel Engine Radiator Exhaust Exhaust Gas Diversion Valve To Condensate Tank Steam Generator Hot Water Converter Coolant Loop Condensate Tank Coolant Heat Exchanger Chilled Water Supply and Return (IW/Grid) To CMU Campus Steam Grid Hot Water Supply and Return (IW/Grid) To CMU Campus Condensate Grid Regen Exhaust Condensate from Exhaust Air Absorption Chiller/Grid Regen Coil Hot Water Supply and Return (IW/Grid) Ventilation System Regen Air Return Air Outside Air Dehumidified Air to IW Figure 2: Basic CHP Flow Diagram Expanding upon Figure 2, Figure 3 shows the complexity of the CHP system with parts from no less than twenty-three direct suppliers, manufacturers, and integrators. Furthermore, this list does not include the installers for the piping, placing the equipment, masonry work, electrical connections, instrumentation, and programming. 24 Coolant Heat Exchanger Biodiesel Diesel Fill Station 2 Fill Station 1 Fuel Tank 2 Fuel Tank 1 VFD Motor Valve 5 Valve 6 Motor Radiator Fan Motor Motor Pump Starter Valve 4 Motor Motor Valve 3 Engine-Generator Fuel Pump 1 Day Tank 1 Engine Generator Fuel Pump 2 Day Tank 2 Turbocharger Air Controler Electric Grid Automatic Transfer Switch Intelligent Workplace Mullion Steam Generator Bypass Tee Muffler Blowdown Separator Steam Generator Back Pressure Valve Control Column Steam Converter Motor Valve 2 Fan Coil Supplier/Manf/Integrator Baldor John Deere Stamford Intelligen ASCO Vaporphase Kickham Broad ITT Pryco Magnetek BorgWarner Belimo Bell & Gossett Highland Tank Marathon Penn Separator Corp. Thermoflo General Electric Siemens Nelson Pomeco OPW Marathon Electric Campus Steam Grid Motor Valve 1 Absorption Chiller Radiant Panel Cool Wave Feed Water Valve Condensate Pumps (2) Motor (2) Condensate Receiver w/ Controller Figure 3: CHP System Components The engine generator is a standard engine generator assembled by Baldor Electric Company shown in Figure 4. It uses a 43 hp (33kW) four cylinder, 2.4 L John Deere Diesel Engine and a Stamford, Inc. generator. It includes a standard engine generator controller made by IntelliGen, Inc. Figure 4: Baldor Engine Generator The engine generator is connected to the grid via an ASCO 7000 automatic transfer switch (ATS) and soft load controller (SLC) shown in Figure 5. The ATS/SLC allows the engine generator system to deliver excess power to the grid during operation, while 25 allowing the grid to power the mechanical room when the system is off. The operation of the ATS/SLC is fully automated, and once a power level is set and the start command given, the engine generator is started and paralleled to the utility in less than five seconds. Figure 5: ATS/SLC with Screen Shot Operating at 18kWe and exporting 12 kWe. The steam generator made by Vaporphase, Inc. shown in Figure 6 is essentially a double pass fire tube boiler without a burner. In lieu of a burner, the high temperature exhaust is routed from the engine to the steam generator. The steam generator also acts as an exhaust silencer, however the silencing effects are lost if the exhaust is bypassed; therefore an extra muffler has been installed. Steam is generated at 87 psig (6 bar) in the summer at 68 pounds per hour (31 kg/hr) for the absorption chiller and at 30 psig (2 bar) and 65 pounds per hour (29 kg/hr) in the winter, spring, and fall for space heating the IW and exporting to the campus steam grid. 26 Figure 6: Assembled Components: Engine Generator (Left), Steam Generator (Right) While there is about 18 kWt of heat recovered from the exhaust, the system is greatly oversized and can handle up to 250 kWt of heat transfer. This unit was selected because it is the smallest commercially available exhaust heat recovery steam generator. A steam generator was required for this project as the absorption chiller used in this project is steam driven. For new systems, direct firing of an absorption chiller and/or high pressure hot water heat recovery can be considered to achieve space and cost savings. To deliver hot water to the IW, a steam – hot water converter is used that can use steam from the steam generator or the campus grid. The converter is shown in Figure 7. 27 Figure 7: Steam - Hot Water Converter The coolant heat exchanger shown in Figure 8 is a standard plate and frame heat exchanger made by ITT, Inc. The heat exchanger operates in parallel with a standard engine generator radiator, which has been moved outside of the mechanical room shown in Figure 9. 28 Figure 8: Coolant Heat Exchanger with Piping before Insulation Figure 9: Remote Mounted Radiator 29 There are several control loops within this CHP system that allow for robust control of the system while also assuring safe operations. The engine controller monitors status, power level, oil pressure, coolant temperature and level, battery conditions, etc. on an engine mounted interface shown Figures 10 and 11. Figure 10: Engine Generator Onboard Interface Figure 11: Engine Generator Onboard Interface The Soft Load Controller (SLC) and the Automatic Transfer Switch (ATS) takes over control of the governor in the engine, which was initially controlled by the Intelligen controller to vary the speed to aid in paralleling the engine to the grid. The SLC/ATS monitors the grid’s voltage and phase so that the generator output frequency, phase, and voltage match the grid. The SLC/ATS monitors any disruptions in the grid or the engine and protects both the grid and the generator from severe damage. If there is a failure the ATS/SLC will separate the engine generator from the grid and will send a shutdown order to the engine. The engine will continue to operate for five minutes powering lights, ventilation, etc. so that occupants have enough time to vacate the lab. Then the engine will go into its standard shutdown procedure, which includes a five minute cool down. 30 The steam generator has its own stand alone pneumatic control system that has three principal tasks. First, it supplies condensate to the steam generator so that it does not run dry. Hot exhaust gases can warp the coils if the heat is not dissipated by steam generation. It calls for makeup water based on the output of a low level alarm and if makeup water is not available, it bypasses the exhaust gases around the steam generator. The second task for the pneumatic controller is to maintain the set point pressure inside the steam generator using a back pressure control valve. The steam pressure is measured inside the steam generator and downstream from the back pressure valve. If the pressure inside the steam generator drops below the set point, the back pressure control valve will restrict the flow of steam to maintain the pressure. The purpose of this control function is to prevent a sudden drop in steam pressure, which causes swelling and carry over of the liquid contained in the generator. The third task is to match heat input to the output steam flow. The exhaust gas flow to the steam generator is modulated by the bypass control valve to maintain a set point pressure of the output steam flow. This arrangement allows the steam generator to operate at partial loads, while the engine operates at full power. The routing and control of the steam flow is accomplished through a series of two position valves and pressure reduction valves. During the summer, two two-position valves block flow to the grid/hot water converter and route the steam flow to the absorption chiller. During the rest of the year the flow to the chiller is blocked and directed towards the grid and hot water converter. A pressure reduction valve reduces the steam supply pressure to the hot water converter to 9 psig (0.6 bar) and the steam from the grid is reduced to 7 psig (0.5 bar) with another pressure reduction valve. The steam from the CHP system is prioritized over the steam from the grid because the 9 psig steam will prevent the 7 psig pressure reduction valve from opening as the pressure on the outlet side is too high. If there is a short fall of pressure from the CHP system, the steam grid will start to makeup the difference once the pressure falls below 7 psig (0.5 bar). Schematics from the steam system are shown in Appendix D. The coolant system controller is designed to prevent the engine from over-heating. This is accomplished by removing heat either through a plate and frame heat recovery exchanger or a remotely mounted radiator with a fan. The coolant controller has two modulating valves which allow the controller to proportion flows to control the amount of heat removed. This arrangement allows the engine to operate at full power, while only recovering a portion of the coolant energy. This controller is a part of the overall Webbased building automation system (BAS). The BAS operates the overall dispatch of the CHP system and logs all of the sensor data. The previously mentioned controllers all function together to allow the system to address varying thermal and electrical energy demands. B.1.2 Input / Output The Inputs for this system include: fuel (Diesel or biodiesel) 31 air (fresh air for combustion) condensate hot water return The outputs for this system include: electricity (208 V, 3 phase) exhaust steam hot water data (Modbus, 4-20mA, 0-5 V converted to BACNET and available on the web) Data inputs and outputs from sensors and actuators in the heat recovery system are compiled in the Automated Logic web based user interface shown in Figure 12. Figure 12: Automated Logic CHP User Interface for the Heat Recovery/Rejection System B.1.3 Operating Description and Results The core of the biodiesel fueled engine generator with heat recovery is the engine generator, which burns fuel in order to generate electricity which is sent to the grid, and generates heat in the forms of high temperature exhaust at 160oC (360oF) and lower temperature engine coolant at 90oC (190oF). The high temperature exhaust can be rejected to atmosphere or recovered using a steam generator, which can generate steam at varying pressure levels. The steam can be used to heat the IW in the winter or drive an absorption chiller in the summer. Furthermore, the steam system is connected to a campus grid system, which allows for excess steam to be exported to the grid. The coolant energy is recovered through another heat exchanger to heat water or rejected through a radiator. The hot water is used in the winter for space heating in the IW. 32 Tables 2 through 4 show the compiled commissioning and experimental results, from the operation of the engine generator, the heat recovery systems (exhaust and coolant), and the integration with the Intelligent Workplace and campus systems. Summer CHP Diesel Results Power Output Fuel Input Plant Power Coolant Heat Exhaust Heat (kWe) (kWc) (kWe) Recovered (kWt) Recovered (kWt) 6 25 3 6 3 12 43 3 9 7 18 57 3 12 12 25 76 3 18 18 Table 4: Averaged Summer Diesel Commissioning and Experimental CHP Results CHP Efficiency 47% 59% 68% 76% Winter CHP Diesel Results Power Output Fuel Input Plant Power Coolant Heat Exhaust Heat (kWe) (kWc) (kWe) Recovered (kWt) Recovered (kWt) 6 25 4 6 4 12 43 4 11 7 18 57 4 14 12 25 76 4 18 17 Table 5: Averaged Winter Diesel Commissioning and Experimental CHP Results CHP Efficiency 49% 61% 70% 74% Winter CHP Biodiesel Results Power Output Fuel Input Plant Power Coolant Heat (kWe) (kWc) (kWe) Recovered (kWt) 6 26 4 8 12 42 4 10 18 59 4 14 25 76 4 18 Table 6: Averaged Winter Biodiesel Experimental Results CHP Efficiency 54% 65% 68% 76% Exhaust Heat Recovered (kWt) 4 9 13 18 The results shown in Tables 4 through 6 show average plant efficiency between 47% and 76%, consistent with typical CHP efficiencies. There is a substantial fall off in efficiency as the power level drops, which indicates that the system operates more efficiently at full load than part load. This is not surprising as engine efficiency usually peaks at about 80% of the maximum engine rating, or 25 kWe of 33kWe. Furthermore, the power required to operate pumps and fans, plant power, remains constant, and becomes a larger percentage of the total power at the lower loads. 33 B.1.3.1 Engine: Measured Data versus Manufacturer’s Specifications It has been difficult to precisely compare all of the engine’s specifications with the measured data as the manufacturer’s specifications are written for operation at 32 kWe, whereas the engine has been operated at part loads from 6 kWe to 25 kWe electrical. Note, the specification column is written for the maximum engine rating of 32kWe using No.2 low sulfur Diesel fuel. System Air System Specification Data Notes Max. temp. rise, amb. to inlet 15 F (8C) ~15 F Varies due to room air temperature Steady increase in flow rate with power (6 kW = 64 CFM, 12kW = 68 CFM, 18kW = 74 CFM) Engine Air Flow 99 CFM (2.8 m3/min) 83 CFM at 25 kWe Intake Manifold Pressure 9 psig (64 kPa) 0.4psi (6kWe), 0.9psi (12kWe), 1.6psi (18kWe), 2.3psi (25kWe) Total Fuel Flow 185 lb/hr (84 kg/hr) NA Fuel Consumption (6 kWe) 4.7 lb/hr (2.1 kg/hr) 4.6 lb/hr (2.1 kg/hr) Fuel Consumption (12 kWe) 7.0 lb/hr (3.2 kg/hr) 7.9 lb/hr (3.6 kg/hr) Fuel Consumption (18 kWe) 9.8 lb/hr (4.4 kg/hr) Fuel Consumption (25 kWe) 13.3 lb/hr (6.1 kg/hr) Fuel Consumption (32 kWb) 17.9 lb/hr (8.1 kg/hr) NA Engine Heat Rejection 1303 BTU/min (23 kW) 18 kW at 25 kWe Coolant Flow 24 GPM (91 L/min) 10.2 GPM Thermostatic Valve start to open 185 F (82 C) Verified by comparing start of coolant flow and coolant temperature Thermostatic Valve fully open 201 F (94 C) Verified by comparing by observing steady flow above 201 F Fuel System 10.6 lb/hr (4.8 kg/hr) 14.1 lb/hr (6.4 kg/hr) The individual fuel flow meters do not provide independent outputs. Verified with weigh tank measurement Verified with weigh tank measurement Verified with weigh tank measurement Verified with weigh tank measurement Soft load controller will allow a maximum power of 25 kW Cooling System Spec assumes radiator attached to engine Exhaust Exhaust Temperature 963 F (517 C) 930 F (499 C) at 25 kWe Max allowable back pressure 30 in-H2O (7.5 kPa) 14 in-H2O at 25 kWe Used a pressure gauge mounted between the engine exhaust and steam generator Table 7: Diesel Engine Generator Measured Data vs. Manufacturer Specifications Table 7 shows that the measured data corresponds well to the manufacturer’s specifications; however, there is a small margin of error. This margin of error probably comes from minor differences between engines during manufacturing and the sensors used by the manufacturer and the IWESS team during testing. Table 8 shows similar results to Table 7 for biodiesel fuel. 34 System Air System Max. temp. rise, amb. to inlet Engine Air Flow Intake Manifold Pressure Fuel System Total Fuel Flow Fuel Consumption (6 kW) Fuel Consumption (12 kW) Fuel Consumption (18 kW) Fuel Consumption (25 kW) Fuel Consumption (32 kW) Cooling System Engine Heat Rejection Coolant Flow Thermostatic Valve start to open Thermostatic Valve fully open Exhaust Exhaust Temperature Max allowable back pressure Specification Data Notes 15 F (8C) 99 CFM (2.8 m3/min) 79 CFM at 25 kWe 9 psig (64 kPa) 1.7psi (6kWe), 2.15psi (12kWe), 2.84psi (18kWe), 3.67psi (25kWe) 185 lb/hr (84 kg/hr) No Measurement Available 4.7 lb/hr (2.1 kg/hr) 7.0 lb/hr (3.2 kg/hr) 9.8 lb/hr (4.4 kg/hr) 13.3 lb/hr (6.1 kg/hr) 17.9 lb/hr (8.1 kg/hr) 1303 BTU/min (23 kW) 24 GPM (91 L/min) Steady increase in flow rate with power (6 kW = 64 CFM, 12kW = 68 CFM, 18kW = 74 CFM) Verified with weigh tank measurement 8.8 lb/hr (4.0 kg/hr) 12.6 lb/hr (5.7 kg/hr) 16.1 lb/hr (7.3 kg/hr) NA Verified with weigh tank measurement Verified with weigh tank measurement Verified with weigh tank measurement Soft load controller will allow a maximum power of 25 kW 16 kW at 25 kWe 10.2 GPM Spec assumes radiator attached to engine 185 F (82 C) Verified by comparing start of coolant flow and coolant temperature 201 F (94 C) Verified by comparing by observing steady flow above 201 F 963 F (517 C) 890 F (477 C) at 25 kWe Biodiesel experiments only conducted during winter at this time, may cause low temp. 30 in-H2O (7.5 kPa) 14 in-H2O at 25 kWe Used a pressure gauge mounted between the engine exhaust and steam generator Table 8: Biodiesel Engine Generator Data vs. Manufacturer Specifications As shown in Tables 7 and 8, the primary difference between Diesel fuel and biodiesel fuel is that the fuel flow rate is greater for biodiesel fuel. The reason for this is that the energy density of biodiesel is lower than Diesel fuel, thus the engine controller naturally increases the fuel demand to meet power demand. As the engine operates below its maximum, prime power operation, the fuel pump has no problem meeting this challenge. B.1.3.1 Pressure – Time – Crank Angle Measurements Pressure sensors have been installed in each engine cylinder to obtain information on how the combustion process changes when using different fuels. In combination with a crank angle encoder, the pressure measurements are collected using a high speed data acquisition system, and plotted as shown in Figure 13. 35 Figure 13: Pressure vs. Time for One Cylinder at 12 kWe using Low Sulfur Diesel Fuel Figure 13 shows the pressure vs. crank angle curve, and shows injection combustion taking place around top dead center (TDC). 36 Figure 14: Pressure vs. Time for One Cylinder at 12 kWe using Low Sulfur Diesel Fuel As can be observed in Figure 14, the wave forms shifts soon after start up from injection and combustion at TDC to a delayed combustion of about 15 degrees after TDC. The effect of a delayed combustion is that the peak combustion temperature is reduced. The purpose of reducing the peak temperature is to reduce NOX formation to meet U.S. Environmental Protection Agency regulations. An additional effect of this control strategy is the reduction of engine capacity and efficiency. Further analysis on these wave forms is under way to compare the performance of the various fuels. B.1.3.2 Turbocharger Analysis The engine’s turbocharger was completely instrumented with temperature, pressure and flow sensors. The data collected from the turbocharger indicates a mass flow rate of 0.053 kg/sec and a maximum compression ratio of 1.25 at 25kWe. These data are plotted in Figure 15, the compressor map provided in by the turbocharger manufacturer. They show that this turbocharger is not suited for this engine operating under the specified conditions. 37 Figure 15: Turbocharger Compressor Map [8] While the turbocharger is not effective for the duty cycle of this engine, it may operate more efficiently at 33 kWe, the power level for which the turbocharger was designed. CHP system designers should be aware of this fact and request a turbocharger that will operate more effectively in the appropriate range. B.1.3.3 Combustion Gas and Emissions Analysis Emissions of gas-phase pollutants [carbon dioxide (CO2), carbon monoxide (CO), nitrogen dioxide (NO2), nitrogen oxide (NO), unburned hydrocarbons (UHC), and oxygen (O2)] have been measured over four loads using both low sulfur Diesel fuel and soy based biodiesel fuel. Load (kWe) 6 12 18 25 % O2 16.1 13.9 11.6 9.6 % CO 0.0 0.1 0.1 0.1 % CO2 3.7 5.2 6.8 8.2 UHC (PPM) 4 9 11 12 NO (PPM) 251 424 466 502 NO2 (PPM) 4 6 5 4 Table 9: Average Gaseous Emissions vs. Load with Low Sulfur Diesel Fuel 38 Load (kWe) 6 12 18 25 % O2 16.3 13.9 11.5 9.7 % CO 0.0 0.0 0.0 0.0 % CO2 3.8 5.4 7.1 8.4 UHC (PPM) 0 1 2 3 NO (PPM) 224 357 450 498 NO2 (PPM) 5 8 10 9 Table 10: Average Gaseous Emissions vs. Load with Soy Biodiesel Fuel The data in Tables 9 and 10 agree with published results [9, 10, 11] with significant reductions in CO, and UHC. However, typically soy based biodiesel has resulted in more NOX, and the averaged data does not reflect that. The NOX emissions for this engine are reduced due to the engine timing adjustments to meet emissions requirements, which may account for the similar levels of NOX. Further research into the emissions is warranted if large scale use of biodiesel in CHP systems is to be achieved as emissions must be understood to meet EPA regulations. A combustion analysis has been conducted for the engine generator operating at 25 kWe using Diesel fuel. The stoichiometric material balance for Diesel fuel. C12 H 23 aO2 3.76 N 2 bCO2 cH 2O dN 2 C: 12 = b(1) b = 12 H: 23 = c(2) c = 11.5 O: a(2) = b(2) + c(1) 2a = 2x12 + 11.5 = 35.5 a = 17.75 N: a(3.76)(2) = d(2) d = 66.7 C12 H 23 17.75O2 3.76 N 2 12CO2 11.5H 2O 66.7 N 2 Determine the molar air to fuel ratio. moles _ O2 moles _ N 2 17.75 17.753.76 AFR 84.5 mole _ Fuel 1 Determine quantity of excess air. AFRMeasured m air m fuel 165kg / hr 25.8 6.4kg / hr MWFuel 167 25.8 AFR Measured AFRMeasured 148.6 29 MW Air moles _ O2 moles _ N 2 17.75 17.753.76 AFR 84.5 mole _ Fuel 1 EA AFR Measured 148.6 1.76 84.5 AFR 39 The material balance C12 H 23 1.7617.75O2 3.76 N 2 aCO2 bH 2O cN 2 dO2 C: 12 = a(1) a = 12 H: 23 = b(2) b = 11.5 O: 1.76 x 17.75 x 2 = a(2) + b(1) + d(2) 62.5 = 2a + b + 2d 62.5 = 24 + 11.5 + 2d 27 = 2d d = 13.5 N: 1.76 x 17.75 x 3.76 x 2 = c(2) 235 = 2c c = 117.5 C12 H 23 31.2O2 3.76 N 2 12CO2 11.5H 2O 117.5N 2 13.5O2 The percentage of the emissions on a molar basis of O2 and CO2 and compare to the results in Table 9 on a dry basis. Calculated Percentage of CO2 = 8.4% Calculated Percentage of O2 = 9.4% Both the CO2 and O2 emissions are consistent with the measured data in Table 9. The heat release from the engine has been calculated. Q W nf hP hR nf o o o o h P n CO 2 h f h CO 2 n H 2O h f h H 2O n N 2 h f h N 2 nO 2 h f h O 2 o o o h R n f h f h f n N 2 h f h N 2 nO 2 h f h O 2 The number of moles shown below and the necessary enthalpy values with the units of kJ/kg-mol C12 H 23 31.2O2 3.76 N 2 12CO2 11.5H 2O 117.5N 2 13.5O2 40 12 393,520 31,154 9,364CO 2 11.5 241,820 27,125 9,904H 2O hP 117.50 23,085 8,669N 2 13.50 23,850 8,682O 2 h P 12 371,730CO 2 11.5 224,599H 2O 117.514,416N 2 13.515,168O 2 h P 4,460,760 2,582,888.5 1,693,880 204,768 h P 5,145,000.5kJ / kg mol h R 1 7,014,000 0 f 117.50 0 N 2 31.20 0 O 2 h R 7,014,000kJ / kg mol kg 6.4 mf kg mol kg mol hr nf 0.0383 1.065 105 MW f kg hr sec 167 kg mol W W Electric Generator Q W nf 25kWe kJ 28.4 0.88 sec hP hR nf Q W n f hP hR kJ kg mol 5,145,000.5 7,014,000 kJ Q 28.4 1.065 10 5 sec sec kg mol kJ kg mol 1,868,999.5 kJ Q 28.4 1.065 10 5 sec sec kg mol kJ kJ Q 28.4 19.9 sec sec kJ Q 48.3 48.3kWt sec The amount of heat captured by the heat recovery system is approximately 36 kWt from Tables 2, 3, and 4, which leaves about 12 kWt for radiant and convective losses to the space from the engine and losses in the pipes and heat exchangers, which is realistic. B.1.3.4 Heat Recovery Analysis The steam generator and the coolant heat exchanger have been analyzed using temperature – heat transfer or T-Q diagrams. T-Q diagrams are an effective way of 41 describing the operation of heat exchangers by showing the stream temperatures versus heat transfer between them. The required area for heat transfer between the streams, A, can be calculated from the following function: dq A , U T where U = heat transfer coefficient, dq = heat transfer, T = temperature difference between the two streams Steam Generate T-Q Diagram 1000 900 Temperature (oF) 800 700 Exhaust at 25 kWe 600 500 Exhaust at 6 kWe 400 Saturated Steam (87psig) 300 Condensate 200 Domestic Hot Water 100 0 0 5 10 15 Heat Transfer (kWt) 20 25 Figure 16: Summer Operation of the Steam Generator T-Q Diagram Figure 16 shows the T-Q diagram for the steam generator during summer operation with exhaust entering on the left at a high temperature. The heat in the exhaust is transferred to the water inside the steam generator, which evaporates at a rate of 65 lbs/hr (28 kg/hr) at 87 psig (6 bar) or 18 kWt. This steam generator uses a pool of water, which is directly replenished rather than preheating make up condensate, however condensate entering at 212oF (100oC) could be preheated. As shown on the right side of the T-Q diagram, additional energy is available from the exhaust which leaves the steam generator at approximately 360oF (160oC). Domestic Hot water is typically delivered at 140oF (60oC), and is supplied from city water at 50oF (10oC). Recovering additional heat from the exhaust (8 kWt) to heat domestic hot water represents approximately a 40% increase in the heat recovery potential, and would increase the CHP efficiency from 78% to 87%. 42 However, the downside of reducing the exhaust temperature down to below 100oC is that the moisture in the exhaust will condense, which can form rust in the exhaust pipes. Therefore, it is necessary to build these sections out of stainless steel. Additionally, Figure 16 shows the operation of the steam generator when the engine generator is operating at 6 kWe. The effect of operating at lower loads is that the exhaust temperature and flow rate are lower, thus reducing steam production. Figure 17 shows the T-Q diagram for the coolant heat exchanger during both summer and winter operation. Using engine coolant heat to heat the water used for space heating in the winter is somewhat problematic as the required temperatures are relatively low, which forces the temperature of the engine coolant to the relatively low temperature of 185oF, where as an ideal temperature would be about 195oF as shown in Figure 17. During winter operation the water side of the exchanger typical has a flow rate of four gallons per minute with an inlet temperature of 95oF and an outlet temperature of 110oF. During the summer, a higher temperature is desired for the regeneration of a solid desiccant, and therefore a higher over all temperature is maintained. Coolant Heat Exchanger T-Q Diagram at 25kWe 210 Temperature (oF) Coolant (12 GPM) 190 Summer Operation Water (12 GPM) 170 150 130 Coolant (2 GPM) 110 Water (4 GPM) Winter Operation 90 0 5 10 Heat Transfer (kWt) 15 20 Figure 17: T-Q Diagram for Coolant Heat Exchanger at 25 kWe To remedy the relatively low coolant operating temperatures during the winter, two options exist. First, the water flow rate could be further reduced with an improved control system, which would shift the winter operation water line up to a higher temperature. The second, option is to bypass some of the water around the coolant heat exchanger essentially reducing the flow. The two flows would then be mixed and the desired temperature achieved. 43 Appendix C Insert in PDF version. 44 Appendix D: Steam System Schematics Insert pages in PDF version 45 References 1 U.S. Department of Energy, Oak Ridge National Laboratory, and Energy and Environmental Analysis, Inc. Combined Heat and Power Installation Database. http://www.eea-inc.com/chpdata/ 2 Discussion with Dr. Marc Portnoff. Director, Center for Advanced Fuel Technology, Carnegie Mellon University. 3 Hennepin Energy Recovery Center (HERC): http://www.co.hennepin.mn.us/portal/site/HCInternet/menuitem.3f94db53874f9b6f68ce1e10b1466498/?vg nextoid=aad2c95fa29fc010VgnVCM1000000f094689RCRD 4 Casten, Thomas R. “Turning Off The Heat: Why American Must Double Energy Efficiency to Save Money and Reduce Global Warming”. Prometheus Books, Amherst, New Yok, 1998. 5 Herold, Keith E., Reinhard Radermacher, and Sanford A. Klein. “Absorption Chillers and Heat Pumps”. CRC Press. 1996. 6 U.S. Department of Energy, Energy Efficiency and Renewable Energy. “Appliances and Commerical Equipment Standards: Commercial Unitary Air Conditioners and Heat Pumps”. http://www.eere.energy.gov/buildings/appliance_standards/commercial/ac_hp.html 7 Zhai, Chaoqin, David H. Archer, and John C. Fisher. “Integration Of The Active Desiccant Wheel In CHP System Design ”. Proceedings of the 2008 ASME Energy Sustainability Conference. Jacksonville, FL August 2008. ES2008-54190. 8 Guider, T. P. Characterization of Engine Performance with Biodiesel Fuels. Masters Thesis, Lehigh University. December 2008. 9 Department of Energy, Office of Energy Efficiency and Renewable Energy. 2004 Biodiesel Handling and Use Guidelines. 10 National Biodiesel Board Published Biodiesel Emissions. www.biodiesel.org/pdf_files/fuelfactsheets/emissions.PDF 11 Brown, Jack. Producing Biodiesel from Brassica Crops in the Pacific Northwest. National Biodiesel Conference, San Diego, CA. February 6, 2006. 46