LE CHI HOANG TRUNG I. INTRODUCTION II. SCADA IN VIET NAM III. SCADA IN DONG NAI POWER COMPANY III. CONCLUSION SCADA SYSTEM was installed in Viet Nam from 2000. Up to now, mostly province in Viet Nam has owned SCADA system. Many experts criticized the safety in operation of SCADA system in Area Centers like A0, A1, A2. Many systems after having installed can not go to operation in the reality. All of them just looked as Training System SCADA system is used to supervise and control plans, factories, or equipments in industry such as: telecommunication, waste system, energy system, oil filtering system, transportation., etc. The system transfer data from master unit in SCADA center and some RTU - Remote Terminal Unit) or PLC - Programable Logic Controller) SCADA consist of 3 levels of controlling: Level 1: controlling, supervising for respectively equipments. The most common device is protective relay and RTU Level 2: Collecting data from IEDs and save in order to serve for the data reading. Level 3: The Controlling Center of all system, where data come from Substation Server, and then is calculated, judged status of distribution system and predict for the loads in the future Level 1 Level 2 Level 3 Trạm Long Bình Trạm Tân Hòa Trạm Đồng Nai Trạm cắt KCN Trạm cắt Hóa An Trạm hợp bộ, Recloser và LBS •406.125Mhz, 406.175Mhz •409.800Mhz, 409.875Mhz •414.225Mhz •Dây điện thọai dùng để dự phòng Trạm Biên Hòa MCC Trạm Tân Mai Trạm cắt Tân Phong Number of node using in controlling and supervising: MCC and 48 positions (05 medium voltage stations), 03 breaker stations, 20 compacts, 10 Recloser and 10 LBS) National SCADA/EMS Regional SCADA/EMS Substation Generation G Substation G G RTU G SCADA RTU Transmission SCADA Distribution RTU RTU Substation Substation Regional SCADA/EMS At compact, LBS, Recloser: functions: Adding RTU 232 with -Receiving and processing command form MSC, transferring these commands to equipments - Being processed and transferring status signals, measurement signal from equipments to MSC. - Managing information system between MSC and RTU. - Saving events of faults of not linking between MSC and RTU and transferring these data to MSC. Compact station Some compacts are chosen to be the separated nodes between lines Here, some power poles 20m were installed with antenna CA400Y At the low-voltage room, installing one Transducer TRIAD to collect current, pressure, and active power signal Signals were transfer to RTU 211 to transform into wireless signals. And then, these signal will be transferred to antenna to go to Control Center. LBS, Recloser: Using power poles to install antenna CA400Y Installing more DLUs to collect current, voltage signal. DLUs will supply these signals to Control Center (MCC) Data were transfer to MCC through Telemodem 32/485 At the station 110/ 220KV: The current stations were installed more devices such as: - Radiator VHF with 4 chanels - Transmission line PSTN. - Information tower - RTU 560 One channel UHF is used to collect data from 4 breaker station with protocol Master/Slaver between SCADA and RTU in high voltage station Data is transferred in the possible shortest time delay, about 5 seconds – even in the emergency cases The high voltage stations were installed information cabin, named Marshall. Information from Relay, and transducer were transferred to RTU 232 Data were transformed into the proper protocol (from RP570 to IEC 870-5-101) and transfer to MCC through dial modem Telecommunication system substation MV/LV, Recloser, LBS were controlled in remote by UHF. System UHF was configured to be suitable with the operation of SCADA. Substation will transfer data to breaker station/ high voltage station and wait for a moment to reply. To limit the data transferring, maximum 4 breaker station/ high voltage station will be collected data in a circulation by a receiver in the Control Center. Telecommunication Line - Two respective frequencies are used to transfer and receive (dual UHF). - Protocol: using protocol IEC 60870-5-101 Telecommunication system System VHF available can support the voice communication. So, all 4 channels can be used concluding as follow 142.65 MHz cho caùc hoaït ñoäng ñieàu ñoä. 143.15 MHz for distribution application 143.25 MHz for maintenance application 143.45 MHz for maintenance application The main characteristic of current VHF is: one-way transferring. The distance between channels is 12.2/25kHz, transferred power is 40W max. Signal type: voice. Control Center MCC Computer for dispatchers to operate: - 2 master computer SYS1 and SYS2 with dual application (main and back-up ) were used to supervise, collect, and remote control. - 1 master computer DMS (Distribution Management System) to serve for operating the system by real map Caùc thieát bò phuïc vuï cho chuyeân vieân Scada : - Maùy chuû MDW (Management Development Workstation) vaø EW (Engineering Workstation) daønh rieâng ñeå phuïc vuï ñaøo taïo, môû roäng vaø nghieân cöùu. - Maùy chuû AS (Archive Server)ï: ghi nhaän, löu tröõ, taùi naïp caùc thoâng tin quùa khöù vaø khôûi taïo caùc baùo bieåu. - Maùy chuû EW phuïc vuï trao ñoåi döõ lieäu vôùi caùc trung taâm ñieàu khieån khaùc. Server AS PC. DMS PC. SyS 1 PC. SyS 2 PC.EW Overview ACC Máy in Laser A4 Sys 1 Máy tính điều khiển Máy tính chủ Lýu dữ liệu (AS) 22” 22” Sys 2 Máy tính điều khiển 22” 22” 22” Đồng bộ thời gian Máy chiếu 22” Máy in kim Truyền thông dự phòng 22” 22” Máy tính chủ DMS GPS M SW A LAN 1 HP Jetdirect LAN 1 LAN 2 LAN 2 HUB SW B Cisco 1605R 17” M RAS 22” 22” Máy tính chủ (MDW) dïng ®Ó nghiªn cøu vµ më réng 22” Máy tính chủ (Com 1) thu thập dữ liệu chính Fall Back Switch Máy tính chủ (Com 2) thu thập dữ liệu dự phòng 22” 22” 22” Nối với Công ty Điện lực 2 (Remote Console) Máy tính chủ chính (EW) để đào tạo nghiên cứu và mở rộng hệ thống Trạm Tân Mai Trạm Biên Hoà TC. Hóa An TC. KCN Trạm Đồng Nai Long Bình Tân Hoà TC.Tân Phong Các trạm hợp bộ, Recloser và LBS Designing of SCADA/DMS Application is designed based on the software of SCADA and OPERA, running on WINDOWS Core software language is SCIL (Supervisory Control Implementary Language) - Collecting and processing data from RTU. - Calculating from data were transferred from RTU. - Supervising and controlling in remote Breaker, Recloser, LBS and Compact Station. - Creating and managing alarm clocks of faults. - Recording the event - Report : Receiving, showing the value of measurement, giving charts from these data.. - Report : Receiving, showing the measurement and drawing charts according the real time. - Event list : Recording and events in the past time can be reviewed by the dispatchers. - Alarm list : Recording and highlighting temporary faults or permanent faults. - Note : Creating notes on the breakers (for more information) Modulation of Dong Nai power line 1. Modulation Opera ++ 2. Modulation DMS User screen of SCADA/DMS -At MCC, we can not confirm weather breaker in compact station 22KV or in the high voltage station is in the operation position or out of operation position. - When the breaker is not in the ready operation position, dispatchers can control them, DMS show the change of status but no measurements were recognized. - Breaker is in the remote position, but operator can open/close it. - When doing the contract, Dong Nai power company didn’t require ABB to supply Sources of Scada vaø DMS. In the future, when there is any fault to SYS1 and SYS2 , the system can not be used - Because Mini-Scada TP.Bieân Hoøa was designed from 1997 so that the data was transfer by UHF, the back-up is tele-line, so that the area to control and supervise is limited by 20Km from MCC. XIN CHAÂN THAØNH CAÛM ÔN YÙ KIEÁN CUÛA THAÀY VAØ CAÙC BAÏN