Harmonic Analysis for the Distribution System with Dispersed Generation Systems Cheng-Ting Hsu

advertisement

Harmonic Analysis for the Distribution

System with Dispersed Generation Systems

Cheng-Ting Hsu

Department of Electrical Engineering

Southern Taiwan University of Technology

Tainan, Taiwan

Outline

Introduction

Description of Distribution Feeder

Harmonic Analysis for the

Distribution System without PVGS

Description of PVGS

Harmonic Analysis for the

Distribution System with PVGS

Conclusion

Introduction

由於台灣自產能源不足及環保意識的抬頭,使

得在尖峰用電時刻電力不足。此外,為因應我

國之電業自由化,將來勢必會出現許多再生能

源發電系統及以天然氣為燃料的小型套裝氣渦

輪機。

這些分散式電源系統 (DGS) 因容量較小,故會

與電力公司之配電系統並聯運轉,對現有配電

系統之運轉與規劃會產生重大影響。

本計劃欲探討之內容包括配電系統之電壓控制

與電容器規劃、諧波、短路故障及保護協調、

孤島偵測與運轉可行性及電壓驟降等議題。

本年度之研究內容主要在分析 DGS 對配電系統

之電壓與諧波影響。

Description of Distribution Feeder and PVGS

7

8

5

6

Bus P(kW) Q(kvar)

2 0 0

3

4

427

684

140

224.82

534

534

1048

406

400.5

544.79

786

196.63

9

10

11

972 857.22

408 416.24

1487 921.56

Harmonic

Order

13

14

16

17

7

8

10

11

19

20

22

23

2

4

5

25

3

1.80

1.50

3.11

2.19

0.64

0.62

1.15

1.04

0.39

0.26

0.82

0.81

0.41

0.43

0.35

0.48

4

2.14

1.39

3.16

2.23

0.61

0.53

1.15

1.04

0.34

0.24

0.82

0.79

0.36

0.39

0.39

0.50

Harmonic current generated at each bus(%)

5

1.61

1.02

3.50

2.46

0.52

0.34

1.28

1.09

0.17

0.18

0.87

0.80

0.20

0.26

0.55

0.60

6

1.33

0.82

3.40

2.38

0.48

0.21

1.19

0.98

0.06

0.15

0.80

0.71

0.10

0.18

0.57

0.60

7

1.46

0.94

1.44

2.90

0.48

0.32

1.60

1.36

0.16

0.16

1.08

0.98

0.19

0.24

0.70

0.72

8

2.18

1.42

2.96

2.08

0.63

0.56

1.05

0.95

0.34

0.24

0.75

0.72

0.36

0.39

0.34

0.46

9

1.25

0.80

4.36

3.08

0.43

0.25

1.72

1.44

0.11

0.14

1.14

1.03

0.13

0.19

0.78

0.77

10

1.88

1.22

3.61

2.55

0.56

0.47

1.37

1.20

0.28

0.21

0.95

0.89

0.30

0.33

0.53

0.60

11

1.87

1.17

4.01

2.84

0.53

0.46

1.59

1.38

0.27

0.20

1.09

1.01

0.29

0.32

0.62

0.68

Harmonic Analysis for the

Distribution System without PVGS

利用表 2 配合日負載曲線與

自行研發撰寫之諧波潮流

程式,可算出各匯流排一

日 24 小時各級諧波失真與

等效阻抗。

執行右表中四種不同之事

例分析,由於諧波失真大

小與負載量成正比關係,

故僅列出最重載 ( 早上 11 點 )

與最輕載 ( 凌晨 4 點 ) 時各匯

流排之總諧波失真。

1

2

3

4

調整 OLTC

變壓器

Case 1

0.81

4.8%

In this case study, no capacitor and filter is installed on the distribution feeder and the voltage at Bus 1 is set by 1.0p.u. without adjusting the tap changer of the transformer. The voltage drop and total voltage harmonic distortion of each bus with the heavy and light load have been simulated as shown in the above figures. It is found that the bus voltage is dropped to the minimum value of 0.81p.u. and the total harmonic voltage distortion is increased to the maximum value of 4.8% at

Bus 11 by serving the heavy load.

Case 2

A capacitor bank with a total capacity of 1500kvar is installed at Bus

10 to provide the reactive power compensation for the feeder.

However, the voltage drop are still serious for many buses by serving the heavy load. The minimum voltage at Bus 11 has been increased from 0.81 to 0.87p.u. as compared to Case 1.

0.87

Case 2

Furthermore, the harmonic voltage will be amplified due to the resonant phenomenon, which occurs at frequency of 280Hz for the heavy load. The total voltage harmonic distortion at many buses are unacceptable. It reaches the maximum value of 11.6% at bus 10.

11.6

280Hz

Case 3

Both the capacitors and OLTC transformer have been used to provide the voltage regulation of the feeder . The voltage level of all buses along the feeder can be regulated within 4% around the base voltage of 1.0p.u as shown in the below figure. The total harmonic voltage distortion will be reduced slightly during the heavy load time period because the fundamental bus voltage along the feeder has been adjusted to be higher than 0.96p.u.

8.38%

0.96

Case 4

To improve the harmonic distortion, two passive filters with turning frequency at 282Hz and 408Hz have replaced the capacitor banks to bypass the 5th and

7th orders harmonic currents. The resonant frequencies have been shifted to the values of 210Hz and 370Hz. By this manner, the total voltage harmonic distortion of each bus will be suppressed to be smaller than 1.5% as shown in the figure.

1.5%

210 370

282 408

Description of PVGS

(a) Heavy Load (9kW)

(b) Middle Load (4.5kW)

(c) Light Load (2kW)

Harmonic

Order

2

3

4

5

6

7

8

9

10

11

12

13

Heavy

Load

(%)

0.288

0.328

0.106

0.384

0.053

1.141

0.327

0.043

0.057

0.108

0.021

0.073

Middle

Load

(%)

0.341

0.309

0.109

0.338

0.033

1.153

0.071

0.046

0.043

0.118

0.053

0.037

Light

Load

(%)

0.328

0.245

0.113

0.354

0.070

1.095

0.044

0.051

0.042

0.074

0.042

0.074

Harmonic

Order

14

15

16

17

18

19

20

21

22

23

24

25

Heavy

Load

(%)

0.040

0.031

0.031

0.054

0.033

0.047

0.022

0.040

0.028

0.036

0.021

0.018

Middle

Load

(%)

0.038

0.025

0.036

0.049

0.043

0.045

0.046

0.042

0.034

0.052

0.026

0.027

Light

Load

(%)

0.051

0.047

0.041

0.058

0.052

0.067

0.032

0.028

0.056

0.036

0.016

0.044

Harmonic Analysis for the

Distribution System with PVGS

5

6

7

8

事例 電容器 濾波器

9

10

調整 OLTC

變壓器分接頭

PVGS 容量與

發電模式

2MVA/1MW 定功率

10MVA/5MW 定功率

2MVA/1MW 定功率

10MVA/5MW 定功率

10MVA/ 功率隨

日照度變化

10MVA/ 功率隨

日照度變化

0.964

 0.978

Case 5

8.38

 8.13 %

事例 6

8.94%

Case 7

1.49

 1.46 %

0.75

0.76 %

Case 8

1.01

%

1.6

%

Conclusion

經本年度之計劃研究可知含交直流轉換器之分散

式電源所產生的諧波電流並不大,如經濾波器的

改善,對配電系統所造成的諧波污染亦不嚴重。

此外,分散式電源執行電壓控制可讓饋線各匯流

排的電壓獲得更佳的補償。

配電系統在離峰時發生電壓驟降較尖峰時嚴重。

配電系統裝置較大容量之分散式電源可改善電壓

驟降的現象。

未來本計劃將繼續研究分散式電源對配電系統運

轉與規劃所造成的影響,例如:短路故障及保護

協調 、 孤島偵測與運轉可行性 、 最佳電容器規劃

等議題。

Thank you

Download