CHT- Project Carl Roth Determine the Capacity of a Lubricating Oil Sump Tank Heater TABLE OF CONTENTS ITEM NO. DESCRIPTION PAGE 1 Statement of Problem 1 2 Summary of Results and Conclusions 1 3 Background 1 4 Nomenclature 1 5 Assumptions and Given Data 2 6 Calculation Method 2 7 Input Values 4 8 Equations and Source 4 9 Analysis 6 10 Results/Conclusions 9 11 References 9 12 Appendices 10 A-1 Figure 1: Sump Tank Geometry 11 A-2 Figure 2: Pump BHP vs. Oil Temperature 12 A-3 Figure 3: Heat transfer diagram and equivalent circuit 13 A-4 Figure 4: Tabulation of Sump Tank Parameters 14 A-5 Figure 5: Sump tank heater temp vs. time 15 A-6 Figure 6: Results of Sump Tank Heater Bank Capacity Calculation 16 Carl Roth CHT- Term Project Page 1 of 16 1. Statement of Problem: The purpose of this calculation is to determine the sump tank heater bank capacity to raise the typical shipboard lubricating oil sump from 40F to 90F in two hours with one two-speed pump operating at slow speed. 2. Summary of Results and Conclusions: Based on the following analysis of the current sump tank geometry and computer model, 83 kW is the minimum heater size required that would bring the oil temperature in the tank from 40F to 90F in two hours. Figure (5) shows a plot of sump tank temperature vs. time for the sump heating operation. It is recommended to install 5 units to provide a total heating capacity of 100kW to add design margin for heating the oil in the sump in the time required. The 100 kW heater will heat the sump from 40F to 90F in 103 minutes. 3. Background: Typically, lubricating oil sump tanks aboard ships have heater banks installed within the sump tank to heat the oil for plant start-up under cold conditions. These tanks store the oil for use in lubricating and cooling system components such as bearings and gears. Oil is circulated throughout this system via electric pumps, lined-up for a closed loop recirculation to the sump tank for the heating operation. 4. Nomenclature: Qtk – energy stored within sump tank, BTU/hr Qin – rate of energy flowing into control volume, BTU/hr Qout – Rate of energy flowing from control volume, BTU/hr Qheater – energy input from heater, BTU/hr Qpump – energy input from pump, BTU/hr d/dt – derivative with respect to time woil, wsteel – weight of oil and steel respectively, lb cp, oil cp, steel – specific heat of oil and steel respectively, BTU/lbF Toil, Tsteel – average temperature of oil and steel respectively, F U – overall heat transfer coefficient, BTU/hr ft2F A – surface area, ft2 P – perimeter, ft T – temperature difference, F hoil, hair – convective heat transfer coefficient for oil and air respectively, BTU/hrft2F Koil, Ksteel – thermal conductivity of oil and steel plate respectively, BTU/hrftF Lsteel – thickness of steel plate, ft t – time, min, hours Carl Roth CHT- Term Project Page 2 of 19 5. Assumptions and Given Data: 5.1 Assume that the oil and all tank surfaces are initially at 40 5.3 Tank will be constructed from ¾ inch HTS. 5.4 The volume of the sump tank is small compared to the volume of the Engine Room (ER), and heat lost from the tank to the engine room during warm-up will not significantly effect the ER air temperature. The ER air temperature will be assumed constant at 40F. 5.5 The sump tank heaters are electrical immersion heaters. This type of heater will develop its full rated capacity within a matter of seconds. Therefore the time-lag between heater activation and full heater output will be assumed to be negligible. 5.6 Pump heat input to the sump tank is assumed to be from one two-speed electric lubricating oil pump running in slow speed. 5.7 Assume oil and tank walls are at the same temperature. 5.8 Natural convection occurs at the exterior tank walls, assuming the engine room air will not be subjected to flow. 6. Calculation Method: The calculation method used employs basic thermodynamic analysis provided in Reference (a) to estimate the heat transfer within the sump tank control volume. Warming up the sump tank is a transient process in which the inflow of energy exceeds the outflow, resulting in an increase of the stored energy within the tank. To model this process a control volume is drawn around the tank as is shown below: Sump Tank Control Volume Qin in Qtk Applying the law of conservation of energy to the control volume gives: Qout Carl Roth CHT- Term Project Page 3 of 19 Qtk = Qin - Qout The rate of energy storage is Qtk = [(woilcp, oil Toil)/dt] + [(wsteelcp, steel Tsteel)/dt] This equation would require two separate control volumes to solve for the two unknown temperatures. A simplifying, yet conservative approximation can be used that eliminates the need for two control volumes: Qtk = [(wcp)cv](Toil/dt), where (wcp)cv = woilcp, oil + wsteelcp, steel This equation sets Toil and Tsteel equal to each other (assumption 5.7), although Toil is actually greater than Tsteel. This equation implies that the steel will absorb more energy than it actually will, resulting in a conservative rate of heat transfer out of the tank. The energy input term is associated with the rate of change of energy into the control volume in the form of heat from the heaters and one pump operating in slow speed. Qin = Qheater + Qpump The heat input from the heater is assumed to be a constant value based on the heater rating. Qheater = Qheater(W) / 0.2931 BTU/hr/W The heat input to the sump tank with one two-speed pump running in slow speed is considered. The lubricating oil pump recirculates oil to the sump tank by manually jacking open relief valves and ensuring that the pump discharge valves are closed. This is essentially a closed loop process. It is therefore assumed that all of the pump energy (BHP) will be converted to heat and will be input to the oil. Qout can be described with an overall heat transfer coefficient, U. To simplify the problem, the heat transfer from the oil to the steel of the tank is neglected and the surface resistance for air is used as the driving force for the heat transfer. The equation used is below: Qout = [UAT] Carl Roth CHT- Term Project Page 4 of 19 Substituting the above terms into the energy balance equation yields, ((wcp)cv)dToil/dt = Qin - [UAT] dToil/dt = Qin/((wcp)cv - [UAT]/ ((wcp)cv = Qin/((wcp)cv - [UAToil]/ ((wcp)cv + [UATair]/ ((wcp)cv Let [UA]/ ((wcp)cv = K2 dToil/dt = Qin/((wcp)cv - K2Toil + K2Tair Let Qin/((wcp)cv + K2Tair = K1 dToil/dt = K1- K2Toil dToil = (K1- K2Toil)dt Toil (t) = Toil(t-dt) + dToil 7. Input Values: 7.1 Total oil volume is 3350 gal 7.2 Oil properties based on temperature are calculated based on curvefit of data from Reference (b) 7.3 The estimated discharge pressure of the lubricating oil pump varies from 40 to 27 psig based on the piping arrangement, resulting in BHP decreasing with Temperature due to the less viscous effects from the oil at higher temperatures. Based on the head loss in the current suction and discharge piping arrangement. This data is plotted in Figure (2). 8. Equations and Source: 8.1 Pump Energy The following expression was developed from the Figure (2) plot to determine the pump HP input over the range from 40F to 90F Qpump(HP) = 0.0051T2 – 0.9119T + 69.015 This horsepower value is then converted to BTU/hr: Qpump(BTU/hr) = (Qpump(HP))(42.44 BTU min-1/HP)(60 min/hr) 8.2 Sump Tank Parameters Carl Roth CHT- Term Project Page 5 of 19 Since the sump tank is basically a rectangle, the overall heat transfer coefficient, U, and the surface area A must be determined for each plate. Figure (3 ) shows the typical resistive network that models the sump tank control volume. For simplification, the temperature of the oil and the steel are assumed to be the same; there is no change in temperature between the two materials. The value of U for each surface is determined using the following equation: U = 1/[Lsteel/Ksteel + 1/h] where h = combined convective coefficient for air and radiation. The surface resistance used is from the Reference (c), which is summarized below: Position of Surface Horizontal Horizontal Vertical Direction of Heat Flow Upward Downward Horizontal h 1.63 1.08 1.46 Although the value of Ksteel varies with temperature, the variation over the temperature range of 40F to 90F is small and a good approximation may be made by taking its value at the average temperature of 65F. The steel used will be HTS, and therefore @ 65F, the value for Ksteel = 31.5 BTU/h ft F, per Reference (d). 8.3 Determination of specific heats and oil weight The specific heat of the HTS steel has been interpolated from Reference (d) at a temperature of 65F. cpsteel = 0.107 BTU/lbF The specific heat of the oil is determined from an equation that is a curvefit of the values for oil based on Reference (b) : cpoil = 0.4143 + [0.000485(Toil)] The weight of the oil is determined from an equation that is a curvefit of the density values for oil listed in Reference (b). The density is multiplied by the volume of oil in the tank and a conversion factor of 0.13368 ft3/gal: woil = [56.556 – {0.021774(Toil)}](Tank Volume)(0.13368) Carl Roth CHT- Term Project Page 6 of 19 8.4 Solving for the Temperature difference where K2 = [UAT]/ ((wcp)cv dToil/dt = K1- K2Toil and K1 = Qin/((wcp)cv + K2Tair dToil = (K1- K2Toil)dt Toil(t) = Toil(t-dt) + dToil 9. Analysis: Sample calculations using 40F oil are presented to complete the first iteration and check the results of the computer solution. The computer solution iterated the heater capacity to obtain a final temperature of 90F in two hours. The resultant capacity was 83.32 kW. 9.1 Input Energy Heater Energy Qheater = Qheater(W) / 0.2931 BTU/hr/W Qheater = 83,000 / 0.2931 BTU/hr/W Qheater = 283,179.8 BTU/hr Pump Energy Qpump(HP) = 0.0051Toil2 – 0.9119Toil + 69.015 = 0.0051(40F)2 – 0.9119(40F) + 69.015 Qpump(HP) = 40.85 HP This horsepower value is then converted to BTU/hr: Qpump(BTU/hr) = (Qpump(HP))(42.44 BTU min-1/HP)(60 min/hr) = (40.85 HP)(42.44 BTU min-1/HP)(60 min/hr) Qpump(BTU/hr) = 103,635.9 BTU/hr Carl Roth CHT- Term Project Page 7 of 19 9.2 Sump tank parameters Figure (1) shows the sump tank configuration and dimensions, and parameters for each plate are determined below: Plate 1: Aft Tank Face Orientation: Vertical A = (17.3 ft)(10.4 ft) = 179.92 ft2 Plate 2: Tank Top Orientation: Horizontal A = (7.33 ft)(17.3 ft) = 126.8 ft2 P = 2(17.3 ft) + 2(7.33) = 49.2 ft Plate 3: Starboard Side Orientation: Vertical A = (7.33 ft)(10.4 ft) = 76.2 ft2 Plate 4: Port Side Orientation: Vertical A = (7.33 ft)(10.4 ft) = 76.2 ft2 Plate 5: Bottom Orientation: Horizontal A = (7.33 ft)(17.3 ft) = 126.8 ft2 P = 2(17.3 ft) + 2(7.33) = 49.2 ft Plate 6: Front Orientation: Vertical A = (17.3 ft)(10.4 ft) = 179.92 ft2 Determining the Overall Heat Transfer Coefficient, U U = 1/[Lsteel/Ksteel + 1/h) where Lsteel = 0.75 in = .0625 ft Ksteel = 31.5 BTU/hr ft F h varies based on the plate orientation and direction of heat flow per Reference (c), as shown in Figure (4). For Plate 1, h = 1.46, U = 1/[0.0625 ft/31.5 BTU/hr ft F + 1/1.46 BTU/hr ft2 F U = 1.46 BTU/hr ft2 F The area of plate 1 = 179.92 ft2, so Carl Roth CHT- Term Project Page 8 of 19 UA = 1.46 BTU/hr ft2 F * 179.92 ft2 UA = 261.92 BTU/hr F The subsequent UA terms are now determined for the remaining plates, and are combined to give an overall heat transfer coefficient for the entire surface area of the tank. These values are tabulated in Figure (4). 9.3 Determination of Specific Heats and Weights Based on rationale presented in section 8.3, cpsteel = 0.107 BTU/lbF wsteel = 23,409.64 lb, from Figure (4) The specific heat of the oil at 40F, cpoil = 0.4143 + [0.000485(Toil)] = 0.4143 + [0.000485(40)] cpoil = 0.4337 BTU/lbF The weight of the oil at 40F: woil = [56.556 – {0.021774(Toil)}](Tank Volume)(0.13368) woil = [56.556 lb/ft3 – {0.021774(40F)}](3350 gal)(0.13368 ft3/gal) woil = 24,937.32 lb 9.4 Solving for the temperature difference dToil/dt = K1- K2Toil where K2 = [UA]/ ((wcp)cv = [(1088.5 BTU/hr F)]/[( 23,409.64 lb*0.107 BTU/lbF) + ( 24,937.32 lb*0.4337 BTU/lbF)] K2 = 0.0817 at 40F and K1 = Qin/((wcp)cv + K2Tair Carl Roth CHT- Term Project Page 9 of 19 = (103,635.9 BTU/hr + 283,179.8 BTU/hr)/[( 23,409.64 lb*0.107 BTU/lbF)* (24,937.32 lb*0.4337 BTU/lbF)] + 0.0817*40F K1= 32.39 at 40F Therefore, dToil = (K1- K2Toil)dt where dt = 1 min = (32.39 – 0.0817*40F)(1 min)(1 hr/60 min) dToil = 0.486 So the temperature at t = 1 minute will be Toil + dToil , 40F + 0.486 = 40.486F. This value is consistent with the value calculated with the numerical analysis, and thus validates the computer model. 10. Results/Conclusions: Based on the analysis of the sump tank model, 83 kW is the minimum heater bank size required that would bring the oil temperature in the tank from 40F to 90F in 2 hrs. Figure (5) shows the sump tank temperature vs. time for the sump heating operation. It is recommended to install 5 units to provide a total heating capacity of 100kW. This adds design margin for heating the oil in the sump in the time required. The resultant curve for temperature vs. time is basically linear since most of the heat input is from the steady source of the heater. This process is exponential in nature, however the heater input tends to overpower the inherent system losses and pump input, thereby producing a plot that is more or less linear. 11. References: a. Ozisik, Heat Conduction, 2nd ed. John Wiley and Sons, New York, 1993. b. Product Bulletin for Gulf Harmony 78 EP, Gulf Oil Company Marketing Department, dated August, 1993. c. ASHRAE Fundamentals, 1981 ed, Table 1, Chapter 23, Design Heat Transmission Coefficients d. Structural Design Basis 63 (SDB-63), Rev. 22, Table II-1-2.3, Physical and Mechanical Properties of Low Carbon – Magnese High Tensile (HT) Steel, dated May 1993. 12. Appendices: Carl Roth CHT- Term Project Figure 1: Sump Tank Geometry Figure 2: Pump BHP vs. Oil Temperature Figure 3: Heat Transfer diagram and equivalent heat transfer circuit Figure 4: Tabulation of Sump Tank Parameters Figure 5: Sump Tank Temperature vs. Time Figure 6: Results of Sump Tank Heater Bank Capacity Calculation Page 10 of 19 Carl Roth CHT- Term Project Page 11 of 19 Figure 1: Sump Tank Geometry 2 (Top) 10.4 ft 6 (fwd face) 4 3 1 (aft face) 5 (Bottom) 7.33 ft FWD 17.3 ft Carl Roth CHT- Term Project Page 12 of 19 Figure 2: Pump BHP vs. Oil Temperature BHP vs Oil Temp 45 BHP 40 y = 0.0051x2 - 0.9119x + 69.015 35 30 25 20 30 40 50 60 70 Temp (deg F) 80 90 100 Carl Roth CHT- Term Project Page 13 of 19 Figure 3: Tank Wall Thermal Circuit qx qx Steel qx = Heat transfer through wall Equivalent Thermal Circuit for Wall: 1/hair Lsteel/Ksteel q qx 1/hrad x Toil = Ts,1 Tair Ts,2 Carl Roth CHT- Term Project Page 14 of 19 Figure 4: Tabulation of Sump Tank Parameters ASHRAE Avg (@65F) Plate No 1 2 3 4 5 6 Direction of Orientation Heat Flow Length Width Height thick Vertical Horizontal Vertical Vertical Horizontal Vertical Horizontal Upward Horizontal Horizontal Downward Horizontal ft N/A 7.33 7.33 7.33 7.33 N/A ft 17.3 17.3 N/A N/A 17.3 17.3 ft 10.4 N/A 10.4 10.4 N/A 10.4 Totals in 0.75 0.75 0.75 0.75 0.75 0.75 Area 2 ft 179.92 126.81 76.23 76.23 126.81 179.92 765.92 Perimeter Volume ft 55.40 49.26 35.46 35.46 49.26 55.40 3 Density 3 in lb/in 19431.36 0.28 13695.37 0.28 8233.06 0.28 8233.06 0.28 13695.37 0.28 19431.36 0.28 82719.58 Weight lb 5499.07 3875.79 2329.95 2329.95 3875.79 5499.07 23409.64 h 2 BTU/hr ft F 1.46 1.63 1.46 1.46 1.08 1.46 K Rt BTU/hr ft F 31.5 0.68692 31.5 0.61548 31.5 0.68692 31.5 0.68692 31.5 0.92791 31.5 0.68692 UA BTU/hr F 261.9245 206.0323 110.9772 110.9772 136.6609 261.9245 1088.497 Carl Roth CHT- Term Project Figure 5: Sump Tank Heater Temperature vs. Time Page 15 of 19 Carl Roth CHT- Term Project Page 16 of 19 Figure 6: Results of Sump Tank Heater Bank Capacity Calculation Carl Roth CHT- Term Project Page 17 of 19 Sump Tank Heater Bank Capacity Calculation Heater Rating 83.3199 kW Time Q heater Qpump Qin wcp_steel wcp_oil sum wcp (min) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 (BTU/hr) 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 (BTU/hr) 103635.9 103016.2 102404.6 101801 101205.3 100617.5 100037.6 99465.31 98900.72 98343.71 97794.22 97252.18 96717.51 96190.17 95670.07 95157.15 94651.35 94152.61 93660.87 93176.05 92698.11 92226.98 91762.6 91304.91 90853.87 90409.4 89971.46 89539.98 89114.92 88696.22 88283.83 87877.69 87477.76 87083.97 86696.29 86314.66 85939.03 85569.36 85205.59 84847.68 84495.59 84149.26 83808.65 83473.72 83144.42 82820.71 82502.54 82189.88 81882.67 81580.89 81284.48 80993.42 80707.65 80427.14 80151.85 79881.74 (BTU/hr) 387907.2 387287.4 386675.8 386072.2 385476.6 384888.8 384308.8 383736.5 383172 382614.9 382065.5 381523.4 380988.7 380461.4 379941.3 379428.4 378922.6 378423.8 377932.1 377447.3 376969.3 376498.2 376033.8 375576.1 375125.1 374680.6 374242.7 373811.2 373386.2 372967.5 372555.1 372148.9 371749 371355.2 370967.5 370585.9 370210.3 369840.6 369476.8 369118.9 368766.8 368420.5 368079.9 367745 367415.7 367091.9 366773.8 366461.1 366153.9 365852.1 365555.7 365264.7 364978.9 364698.4 364423.1 364153 BTU/degF 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 BTU/degF 10815.32 10819.13 10822.93 10826.72 10830.49 10834.25 10838 10841.73 10845.45 10849.15 10852.84 10856.52 10860.18 10863.83 10867.46 10871.09 10874.7 10878.3 10881.88 10885.45 10889.01 10892.56 10896.1 10899.62 10903.13 10906.63 10910.12 10913.59 10917.06 10920.51 10923.95 10927.38 10930.8 10934.2 10937.6 10940.99 10944.36 10947.72 10951.08 10954.42 10957.75 10961.07 10964.38 10967.68 10970.97 10974.25 10977.52 10980.78 10984.03 10987.27 10990.51 10993.73 10996.94 11000.14 11003.33 11006.52 BTU/degF 13320.15 13323.96 13327.77 13331.55 13335.33 13339.09 13342.83 13346.56 13350.28 13353.98 13357.67 13361.35 13365.01 13368.66 13372.3 13375.92 13379.53 13383.13 13386.71 13390.28 13393.84 13397.39 13400.93 13404.45 13407.96 13411.46 13414.95 13418.42 13421.89 13425.34 13428.78 13432.21 13435.63 13439.04 13442.43 13445.82 13449.19 13452.55 13455.91 13459.25 13462.58 13465.9 13469.21 13472.51 13475.8 13479.08 13482.35 13485.62 13488.87 13492.11 13495.34 13498.56 13501.77 13504.97 13508.17 13511.35 sum UA BTU/h deg F 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 K2 K1 dt Tair dToil Toil 1/hr 0.0817 0.0817 0.0817 0.0816 0.0816 0.0816 0.0816 0.0816 0.0815 0.0815 0.0815 0.0815 0.0814 0.0814 0.0814 0.0814 0.0814 0.0813 0.0813 0.0813 0.0813 0.0812 0.0812 0.0812 0.0812 0.0812 0.0811 0.0811 0.0811 0.0811 0.0811 0.0810 0.0810 0.0810 0.0810 0.0810 0.0809 0.0809 0.0809 0.0809 0.0809 0.0808 0.0808 0.0808 0.0808 0.0808 0.0807 0.0807 0.0807 0.0807 0.0807 0.0806 0.0806 0.0806 0.0806 0.0806 deg F/hr 32.39 32.33 32.28 32.23 32.17 32.12 32.07 32.01 31.96 31.91 31.86 31.81 31.76 31.72 31.67 31.62 31.58 31.53 31.48 31.44 31.40 31.35 31.31 31.27 31.23 31.18 31.14 31.10 31.06 31.02 30.99 30.95 30.91 30.87 30.84 30.80 30.76 30.73 30.69 30.66 30.63 30.59 30.56 30.53 30.50 30.46 30.43 30.40 30.37 30.34 30.31 30.29 30.26 30.23 30.20 30.17 min 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 deg F 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 deg F 0.000 0.485 0.484 0.482 0.481 0.479 0.478 0.476 0.475 0.473 0.472 0.470 0.469 0.467 0.466 0.465 0.463 0.462 0.460 0.459 0.458 0.456 0.455 0.454 0.452 0.451 0.450 0.449 0.447 0.446 0.445 0.444 0.442 0.441 0.440 0.439 0.438 0.436 0.435 0.434 0.433 0.432 0.431 0.430 0.429 0.427 0.426 0.425 0.424 0.423 0.422 0.421 0.420 0.419 0.418 0.417 deg F 40.000 40.485 40.969 41.451 41.932 42.411 42.889 43.365 43.840 44.313 44.784 45.255 45.723 46.191 46.657 47.121 47.584 48.046 48.506 48.965 49.423 49.879 50.334 50.788 51.240 51.691 52.141 52.590 53.037 53.483 53.928 54.371 54.814 55.255 55.695 56.134 56.571 57.008 57.443 57.877 58.310 58.742 59.173 59.602 60.031 60.458 60.885 61.310 61.734 62.157 62.580 63.001 63.421 63.840 64.258 64.675 Carl Roth CHT- Term Project Page 18 of 19 Sump Tank Heater Bank Capacity Calculation Heater Rating 83.3199 kW Time Q heater Qpump Qin wcp_steel wcp_oil sum wcp (min) 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 (BTU/hr) 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 (BTU/hr) 79616.77 79356.91 79102.12 78852.37 78607.61 78367.81 78132.94 77902.96 77677.83 77457.54 77242.03 77031.28 76825.26 76623.93 76427.26 76235.22 76047.78 75864.92 75686.59 75512.77 75343.44 75178.55 75018.09 74862.02 74710.33 74562.97 74419.92 74281.16 74146.67 74016.4 73890.35 73768.48 73650.76 73537.18 73427.71 73322.33 73221.01 73123.72 73030.45 72941.17 72855.86 72774.5 72697.07 72623.54 72553.89 72488.11 72426.16 72368.04 72313.72 72263.18 72216.39 72173.36 72134.04 72098.43 72066.5 (BTU/hr) 363888 363628.1 363373.4 363123.6 362878.8 362639 362404.2 362174.2 361949.1 361728.8 361513.3 361302.5 361096.5 360895.2 360698.5 360506.5 360319 360136.2 359957.8 359784 359614.7 359449.8 359289.3 359133.3 358981.6 358834.2 358691.2 358552.4 358417.9 358287.6 358161.6 358039.7 357922 357808.4 357698.9 357593.6 357492.2 357395 357301.7 357212.4 357127.1 357045.7 356968.3 356894.8 356825.1 356759.3 356697.4 356639.3 356585 356534.4 356487.6 356444.6 356405.3 356369.7 356337.7 BTU/degF 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 BTU/degF 11009.69 11012.86 11016.02 11019.16 11022.3 11025.43 11028.55 11031.66 11034.77 11037.86 11040.95 11044.03 11047.1 11050.16 11053.21 11056.26 11059.3 11062.32 11065.35 11068.36 11071.37 11074.36 11077.35 11080.34 11083.31 11086.28 11089.24 11092.19 11095.14 11098.07 11101.01 11103.93 11106.85 11109.76 11112.66 11115.55 11118.44 11121.33 11124.2 11127.07 11129.93 11132.79 11135.64 11138.48 11141.32 11144.15 11146.97 11149.79 11152.6 11155.4 11158.2 11160.99 11163.78 11166.56 11169.34 BTU/degF 13514.52 13517.69 13520.85 13523.99 13527.13 13530.26 13533.38 13536.5 13539.6 13542.69 13545.78 13548.86 13551.93 13554.99 13558.04 13561.09 13564.13 13567.16 13570.18 13573.19 13576.2 13579.19 13582.18 13585.17 13588.14 13591.11 13594.07 13597.02 13599.97 13602.91 13605.84 13608.76 13611.68 13614.59 13617.49 13620.39 13623.27 13626.16 13629.03 13631.9 13634.76 13637.62 13640.47 13643.31 13646.15 13648.98 13651.8 13654.62 13657.43 13660.23 13663.03 13665.83 13668.61 13671.39 13674.17 sum UA BTU/h deg F 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 K2 K1 dt Tair dToil Toil 1/hr 0.0805 0.0805 0.0805 0.0805 0.0805 0.0804 0.0804 0.0804 0.0804 0.0804 0.0804 0.0803 0.0803 0.0803 0.0803 0.0803 0.0802 0.0802 0.0802 0.0802 0.0802 0.0802 0.0801 0.0801 0.0801 0.0801 0.0801 0.0801 0.0800 0.0800 0.0800 0.0800 0.0800 0.0800 0.0799 0.0799 0.0799 0.0799 0.0799 0.0798 0.0798 0.0798 0.0798 0.0798 0.0798 0.0797 0.0797 0.0797 0.0797 0.0797 0.0797 0.0797 0.0796 0.0796 0.0796 deg F/hr 30.15 30.12 30.10 30.07 30.04 30.02 30.00 29.97 29.95 29.93 29.90 29.88 29.86 29.84 29.82 29.79 29.77 29.75 29.73 29.71 29.70 29.68 29.66 29.64 29.62 29.61 29.59 29.57 29.56 29.54 29.52 29.51 29.49 29.48 29.46 29.45 29.44 29.42 29.41 29.40 29.39 29.37 29.36 29.35 29.34 29.33 29.32 29.31 29.30 29.29 29.28 29.27 29.26 29.25 29.24 min 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 deg F 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 deg F 0.416 0.415 0.414 0.413 0.412 0.411 0.410 0.409 0.408 0.408 0.407 0.406 0.405 0.404 0.403 0.402 0.401 0.400 0.400 0.399 0.398 0.397 0.396 0.395 0.395 0.394 0.393 0.392 0.391 0.391 0.390 0.389 0.388 0.388 0.387 0.386 0.386 0.385 0.384 0.383 0.383 0.382 0.381 0.381 0.380 0.379 0.379 0.378 0.377 0.377 0.376 0.375 0.375 0.374 0.374 deg F 65.091 65.506 65.920 66.333 66.745 67.157 67.567 67.976 68.385 68.792 69.199 69.605 70.009 70.413 70.816 71.218 71.620 72.020 72.420 72.819 73.217 73.614 74.010 74.405 74.800 75.194 75.587 75.979 76.371 76.761 77.151 77.541 77.929 78.317 78.704 79.090 79.475 79.860 80.244 80.628 81.010 81.392 81.774 82.154 82.534 82.913 83.292 83.670 84.047 84.424 84.800 85.175 85.550 85.924 86.298 Carl Roth CHT- Term Project Page 19 of 19 Sump Tank Heater Bank Capacity Calculation Heater Rating 83.3199 kW Time Q heater Qpump Qin wcp_steel wcp_oil sum wcp (min) 111 112 113 114 115 116 117 118 119 120 (BTU/hr) 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 284271.23 (BTU/hr) 72038.24 72013.62 71992.64 71975.27 71961.5 71951.31 71944.67 71941.59 71942.03 71945.99 (BTU/hr) 356309.5 356284.9 356263.9 356246.5 356232.7 356222.5 356215.9 356212.8 356213.3 356217.2 BTU/degF 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 2504.831 BTU/degF 11172.11 11174.87 11177.63 11180.38 11183.12 11185.86 11188.6 11191.33 11194.05 11196.77 BTU/degF 13676.94 13679.7 13682.46 13685.21 13687.96 13690.7 13693.43 13696.16 13698.88 13701.6 sum UA BTU/h deg F 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 1088.497 K2 K1 dt Tair dToil Toil 1/hr 0.0796 0.0796 0.0796 0.0795 0.0795 0.0795 0.0795 0.0795 0.0795 0.0794 deg F/hr 29.24 29.23 29.22 29.21 29.21 29.20 29.19 29.19 29.18 29.18 min 1 1 1 1 1 1 1 1 1 1 deg F 40 40 40 40 40 40 40 40 40 40 deg F 0.373 0.372 0.372 0.371 0.371 0.370 0.369 0.369 0.368 0.368 deg F 86.670 87.043 87.414 87.786 88.156 88.526 88.895 89.264 89.632 90.000