Stakeholder Comment Form AESO AUTHORITATIVE DOCUMENT PROCESS New ISO rules 501.3.1 Wind Generating Facilities Technical Requirements NOTE: The AESO is asking market participants to give an initial indication of their support for, or opposition to, the specific ISO rule changes referenced below. Such an initial indication assists in the AESO’s practical understanding of the receptivity of the industry to the proposed changes, and in that regard the AESO thanks in advance all market participants who choose to respond. With regard to the specific ISO rule changes and their implications, such responses are without prejudice to the rights of market participants under the Act, any regulations, or related decisions of the Commission. Date of Request for Comment: December 16, 2009 Period of Consultation: December 16, 2009 through January 22, 2010 Comments From: Date [yyyy/mm/dd]: Contact: Phone: E-mail: G1 Definitions to ISO Rules - New Definitions The following new definition hereby is incorporated in to Section G1 of the ISO rules: “generating facilities” means an aggregation of generating units, designated by the ISO, situated in the same proximate location. Reason for Stakeholder Positions: (mark with ”x”) Support Oppose No Comment Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 1 of 38 G1 Definitions to ISO Rules - New Definitions (cont’) The following new definition hereby is incorporated in to Section G1 of the ISO rules: (mark with ”x”) Support Oppose No Comment “maximum authorized MW” means, (i) (ii) for a generating unit, the maximum quantity (MW) that the generating unit is authorized by the ISO to deliver to its generator terminal; or for generating facilities with a collector bus, the maximum quantity (MW) that the generating units are authorized by the ISO to deliver to its collector bus. Reason for Stakeholder Positions: Alternate Proposal: G1 Definitions to ISO Rules - New Definitions (cont’) The following new definition hereby is incorporated in to Section G1 of the ISO rules: “operator” means a person given expressed authority by an owner to operate on the owner’s behalf any one or more of: (i) a generating unit; (ii) any generating facilities; (iii) a transmission facility; (iv) an electric distribution system; (v) an industrial system; or (vi) a load facility; (mark with ”x”) Support Oppose No Comment and includes the owner, if no such other person has been so authorized. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 2 of 38 G1 Definitions to ISO Rules - New Definitions (cont’) The following new definition hereby is incorporated in to Section G1 of the ISO rules: (mark with ”x”) Support Oppose No Comment “person” as defined in the Act includes an individual, unincorporated entity, partnership, association, corporation, trustee, executor, administrator or legal representative. Reason for Stakeholder Positions: Alternate Proposal: G1 Definitions to ISO Rules - New Definitions (cont’) The following new definition hereby is incorporated in to Section G1 of the ISO rules: “point of connection” means a point at which electric energy is transferred between a transmission facility that is not an industrial system, and: (i) the high voltage side of any generating facilities; (ii) an electric distribution system; (iii) an industrial system; or (iv) a load facility owned by a person who has arranged directly for system access service under Subsection 101(2) of the Act. (mark with ”x”) Support Oppose No Comment Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 3 of 38 G1 Definitions to ISO Rules - New Definitions (cont’) The following new definition hereby is incorporated in to Section G1 of the ISO rules: “transmission system” as defined in the Act means all transmission facilities in Alberta that are a part of the interconnected electric system. (mark with ”x”) Support Oppose No Comment Reason for Stakeholder Positions: Alternate Proposal: G1 Definitions to ISO Rules - New Definitions (cont’) The following new definition hereby is incorporated in to Section G1 of the ISO rules: “wind turbine generator” means the electric turbine generator component of a wind powered generating unit and includes a synchronous or asynchronous generator. (mark with ”x”) Support Oppose No Comment Reason for Stakeholder Positions: Alternate Proposal: G1 Definitions to ISO Rules - New Definitions (cont’) The following new definition hereby is incorporated in to Section G1 of the ISO rules: “voltage regulating system” means the equipment that automatically controls the reactive power devices to regulate the voltage level at the collector bus of wind generating facilities. (mark with ”x”) Support Oppose No Comment Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 4 of 38 (mark with ”x”) Support Oppose No Comment G1 Definitions to ISO Rules - Revised Definitions The following definition change hereby is incorporated in to Section G1 of the ISO rules: The definition of “owner” is deleted and the following is substituted “owner”, for the purpose of these ISO rules, means the person who has title to and ownership of any one or more of: (i) a generating unit; (ii) any generating facilities; (iii) a transmission facility; (iv) an electric distribution system; (v) an industrial system; or (vi) a load facility. Reason for Stakeholder Positions: Alternate Proposal: G1 Definitions to ISO Rules - Revised Definitions (cont’) The following definition change hereby is incorporated in to Section G1 of the ISO rules: (mark with ”x”) Support Oppose No Comment The definition of “gross MW” is deleted and the following is substituted: “gross MW” means a real power instantaneous measurement at a generator terminal or collector bus. Proposed New ISO Rule: 2009-12-16 Page 5 of 38 Reason for Stakeholder Positions: Alternate Proposal: ISO Rule 501.3.1 Wind Generating Facilities Technical Requirements 1. Applicability (mark with ”x”) Applicability 1(1) Section 501.3.1 applies to the ISO, and subject to the provisions of subsections 1(1), (2) and (3) to any: (i) new wind generating facilities and to its owner; and (ii) existing wind generating facilities and to its owner if such facilities connected to the transmission system under the Wind Power Facility Technical Requirements dated November 15, 2004. (2) Any wind generating facilities whose owner executed a Construction Commitment Agreement and completed the approval process of the ISO for connection to the transmission system under the Technical Requirements for connecting generators (1999) is exempt from this Section 501.3.1 but remains subject to the Technical Requirements for connecting generators (1999). (3) If any wind generating facilities referred to in subsection (2) undergo a facility addition or replacement such that the resulting accumulative MW capability is increased by an amount equal to or greater than five (5) MW, then the new or replaced facility will be subject to and must comply with the provisions of this Section 501.3.1 in its entirety. (4) Notwithstanding subsection (2) above, all wind generating facilities must be compliant with the provisions contained in subsections 32 and 36 below. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 6 of 38 Support Oppose No Comment 2. (mark with ”x”) Requirements Maximum authorized MW for Wind Generating Facilities 2(1) The owner of any wind generating facilities must submit to the ISO the maximum authorized MW for those facilities, and once approved of by the ISO this value will form part of the functional specifications for the wind generating facilities. (2) In accordance with Appendix 2, the ISO will determine the wind generating facilities’ requirements associated with reactive power capability of the wind generating facilities, based on the maximum authorized MW as submitted and approved. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 7 of 38 Support Oppose No Comment 2. Requirements (cont’) Voltage Ride Through Requirements 3(1) Wind generating facilities with a maximum authorized MW amount equal to or greater than five (5) MW and connected to the transmission system must meet the voltage ride through requirements specified in this subsection 3. (2) Each owner of wind generating facilities must ensure they are capable of continuous operation between ninety percent (90%) and one hundred and ten percent (110%) of the rated voltage at the point of connection. (3) Subject to subsection 3(4) below, wind generating facilities must not trip off line any loaded wind turbine generator due to voltage dips or post-transient voltage rises described in Appendix 1, resulting from normally cleared transmission faults on any phase or combination of phases at or beyond the point of connection. (4) Notwithstanding any other provision of this subsection 3, wind generating facilities are not required to ride through: (a) transmission system faults that cause a forced outage of a radial line to the wind generating facilities; (b) faults that occur on the wind generating facilities side of the point of connection, including the lower voltage network and the substation, or (c) transmission system faults that result in a transfer trip or anti-islanding protection scheme to activate at the wind generating facilities. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 8 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Voltage Regulation and Reactive Power 4(1) The ISO must assess voltage regulation and reactive power performance of wind generating facilities at the collector bus, and all reactive power requirements must be based on the rated voltage at the collector bus. (2) Wind generating facilities must be able to regulate their voltage at the voltage regulation system point of control under both non-disturbance and disturbance conditions. Reason for Stakeholder Positions: Alternate Proposal: 2. Requirements (cont’) (mark with ”x”) Wind Generating Facilities Reactive Power Capability 5(1) The reactive power capability of any wind generating facilities to supply reactive power must meet or exceed +0.9 power factor based on the gross MW of the wind generating facilities. (2) The reactive power capability of the wind generating facilities to absorb reactive power must meet or exceed -0.95 power factor based on the gross MW of the wind generating facilities. (3) Continuous reactive power capability referred to in subsections 6 and 7 below may be aggregated to meet the requirements set out in subsection 5(1) and subsection 5(2) above. (4) All reactive power devices used to vary the wind generating facilities’ output of reactive power within the requirements set out in subsection 5(1) and subsection 5(2) above must be under control of a voltage regulation system. (5) The operator must not intentionally, and the control systems of wind generating facilities must not be designed, to reduce the reactive power capability from the dynamic reactive devices described in subsection 6, or the non-dynamic reactive devices described in subsection 7. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 9 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Dynamic Reactive Power Capability 6(1) The dynamic reactive power capability of any wind generating facilities must meet or exceed plus zero point nine five (+0.95) power factor to minus zero point nine eight five (-0.985) power factor based on the gross MW of the wind generating facilities. (2) Wind generating facilities must have reactive power devices that are continuously acting and continuously variable under control of its voltage regulation system, and be able to respond to transmission system voltage fluctuations. (3) For the purposes of subsection 6(1), a short term reactive power capability for a period of up to one (1) second will be deemed to meet the dynamic reactive power capability set out in that subsection 6(1). (4) The short term reactive power capability referred to in this subsection 6 does not qualify for continuous reactive power described in subsection 5. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 10 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Non-Dynamic Reactive Power Capability 7(1) For any wind generating facilities, the MVAr size of the individual shunt reactive power devices under control of the voltage regulation system must not be larger than the total range of the continuous capability of dynamic reactive power set forth in subsection 6. (2) Any shunt reactive power device installed in any wind generating facilities must be capable of being switched on no later than five (5) minutes after having been switched off. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 11 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Voltage Regulation System 8(1) Wind generating facilities must have a continuously variable, continuously acting, closed loop centralized control voltage regulation system that measures voltage compared to a set point, and will control reactive devices such as wind turbine generators, static VAr devices, capacitor and reactor banks, or any or all of them. (2) The voltage regulation system must be continuously in service and controlling while the wind generating facilities are connected to the transmission system, and regardless of the quantity of actual MW output from the wind generating facilities. (3) The voltage regulation system set point must be adjustable by the operator of the wind generating facilities to between ninety five percent (95%) and one hundred and five percent (105%) of rated voltage. (4) The voltage regulation system must operate in a voltage set point control mode to the exclusion of any other modes. (5) The voltage regulation system must measure voltage that represents the overall voltage response of the wind generating facilities. (6) The voltage regulating system must be capable of: (a) adjustable gain, or reactive droop compensation adjustable from zero to ten percent (0 to 10%); and (b) reactive current compensation to compensate for the transmission system step-up transformer. (7) The combined settings of the voltage regulation system must be able to achieve a steady state voltage regulation of plus or minus zero point five percent (+/- 0.5%) of the voltage controlled by the voltage regulation system. (8) Prior to commissioning of any new wind generating facilities, the ISO will specify whether the reactive power compensation in the voltage regulation system must be implemented. (9) The ISO may, upon no less than ninety (90) days notice to the owner of any operational wind generating facilities, require a change to the setting of the reactive droop compensation gain or the reactive current compensation settings for those wind generation facilities. (10) The voltage regulation system must be calibrated such that a change in reactive power will achieve ninety five percent (95%) of its final value no sooner than zero point one (0.1) seconds and no later than one (1) second following a step change in voltage. Proposed New ISO Rule: 2009-12-16 Page 12 of 38 (11) When the voltage regulation system requires the switching of a shunt reactive device, the switching operation must be delayed by ten (10) seconds. Support Oppose No Comment Reason for Stakeholder Positions: Alternate Proposal: 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment External Voltage Regulation 9 No wind generating facilities may use or rely upon any voltage regulation system and reactive power that are external to the wind generating facilities without first having the ISO review and approve of the matter in writing. Reason for Stakeholder Positions: Alternate Proposal: 2. Requirements (cont’) (mark with ”x”) Operator Availability 10 The owner of wind generating facilities must have a designated and qualified operator available twenty four (24) hours a day every day for contact and communication with the ISO, in accordance with ISO rules and other communication policies and protocols. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 13 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment WECC Stability Control Requirements 11 If the ISO is required by any WECC standards or policies to use a power system stabilizer for any wind generating facilities using a synchronous wind turbine generator and connected directly to the transmission system, then the ISO in turn may require those wind generating facilities to use a power system stabilizer. Reason for Stakeholder Positions: Alternate Proposal: 2. Requirements (cont’) (mark with ”x”) Operating Voltage Requirements and Range 12 The owner of any wind generating facilities must submit to the ISO the following information and data which will form part of the functional specifications for those wind generating facilities: (a) a minimum through maximum transmission system voltage operating range; and (b) the value to be used for rated voltage of the transmission system at the point of connection, based on the normal operating voltage levels at the specific location of the wind generating facilities. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 14 of 38 Support Oppose No Comment 2. (mark with ”x”) Requirements (cont’) Transmission System Step-Up Transformer 13(1) The voltage ratio, tap changer type, range and step size specifications for any step-up transformer of any wind generating facilities must be such that the reactive power requirements specified in subsection 4 are fully available throughout the operating voltage range referred to in subsection 12. (2) The wind turbine generator step-up transformer and transmission system step-up transformer connection for any wind generating facilities must be designed to provide: (a) a favorable circuit to block the transmission of harmonic currents, and (b) isolation of transmission and wind turbine generator side ground fault current contributions. (3) The wind generating facilities must utilize an effectively and solidly grounded wye connection on the high side of the transmission system step up transformer. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 15 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Off Nominal Frequency Requirements 14(1) For wind generating facilities that have a requirement to protect equipment for off-nominal frequency operation, the owner must install protective relays so as to accommodate operation for the specified time frames shown in Appendix 3. (2) The trip setting of the protective relays must either: (a) be set to the requirements set out in Appendix 3 with respect to the frequency versus time setting; or (b) automatically trip load to match the anticipated generation loss and at comparable frequency levels. (3) The owner must only use solid state or microprocessor based frequency relays in wind generating facilities to provide off-nominal frequency protection. (4) Frequency relays must use the definite time characteristic and not be disabled for transmission system voltages that are eighty percent (80%) or higher of the rated voltage (5) The ISO first must approve in writing if the operator of wind generating facilities intends to permit a frequency relay to be automatically disabled if transmission system voltages fall below eighty percent (80%) of nominal. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 16 of 38 2. Requirements (cont’) (mark with ”x”) Over Frequency Control Requirements 15(1) Any wind generating facilities must have an over frequency control system that continuously monitors the frequency of the transmission system at a sample rate of thirty (30) per second and a resolution of zero point zero zero four (0.004) Hertz, and the frequency control system must automatically control the real power output of the wind generating facilities at all times. (2) The frequency control system may have an intentional deadband of up to zero point zero three six (0.036) Hertz. (3) The frequency control system must be designed and calibrated to reduce the real power output at the collector bus based on the real time capacity of all available wind turbine generators, and such reductions must be; (a) proportional to the frequency increase by a factor of thirty three percent (33%) per Hertz of the above capacity; (b) at a rate of five percent (5%) of the above capacity per second; and (c) with no intentional time delay added to the control system. (4) In accordance with subsection 14, for transmission system over frequency events greater than sixty one point seven (61.7) Hertz, wind generating facilities may trip due to the over frequency, but if the wind generating facilities remain connected to the transmission system then the frequency response system must continue to ramp down the active power output in accordance with provision of this subsection 15. (5) The over frequency control requirements of this subsection 15 must have control priority over the power limiting control function, and must reduce the real power output for an over frequency condition even when the requirements of this subsection 18 are in effect. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 17 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Wind Generating Facilities Disconnection 16(1) Wind generating facilities must have systems, controls and related procedures to electrically disconnect the wind generating facilities from the transmission system either at: (a) the point of connection; (b) the collector bus feeder breakers; or both of them, as applicable. (2) Wind generating facilities connecting to a transmission facility must provide the functionality and remote control capabilities to enable the operator of the transmission facility to open or trip any interconnecting breaker either at the point of connection or the collector bus feeder breakers, as applicable. (3) Once a connecting or feeder breaker of any wind generating facilities has been opened or tripped, then the operator may only electrically reconnect to the transmission facility after receiving approval from the ISO. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 18 of 38 2. Requirements (cont’) (mark with ”x”) Support Wind Generating Facilities Real Power and Ramp Rate Limitations 17(1) Wind generating facilities must have the control capability to limit the real power output at the point of connection in accordance with any limits or instructions contained in a directive, and in any event, that real power output must not exceed the tolerances described in this subsection 17. (2) The real power control limit of the wind generating facilities referred to in subsection 17(1) must be adjustable from the minimum operating output to the maximum authorized MW at an average resolution of one (1) MW. (3) When a real power limit at any wind generating facilities is in effect in accordance with a directive and wind speed conditions at the wind generating facilities are increasing, then subject to subsection 17(4) below, the power limiting controls of the wind generating facilities must be capable of keeping the one (1) minute average MW output from exceeding the wind generating facilities limit specified in the directive by two percent (2%) of the maximum authorized MW. (4) If a wind gust results in the real power control limit set out in the directive being instantaneously exceeded, the wind generating facilities will remain in compliance if the real power output at the point of connection does not exceed the real power control limit by more than five percent (5%) of the maximum authorized MW. (5) Wind generating facilities must be equipped with ramp rate limiting controls. (6) The ramp rate limiting controls must be capable of limiting the ramping up of any wind generating facilities, and must be adjustable such that the ramp rate does not exceed, in MW per minute, from five percent (5%) of the maximum authorized MW to twenty percent (20%) of the maximum authorized MW. (7) The default setting for the ramp rate limiting controls must be set at ten percent (10%) unless otherwise specified by the ISO. (8) Any difference in the real power at the point of connection and the collector bus must be compensated for in the real power limiting and ramp rate limiting controls. Proposed New ISO Rule: 2009-12-16 Page 19 of 38 Oppose No Comment Reason for Stakeholder Positions: Alternate Proposal: 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Wind Generating Facilities Protection Requirements 18(1) The owner of any wind generating facilities must comply with all provisions of the AIES Protection Standard Rev 0, December 1, 2004. (2) The protection requirements set out in subsection 18(1) extend to and include the wind turbine generator, any step-up transformer, collector facilities and any transmission system equipment required to connect the wind generating facilities to the transmission system. Reason for Stakeholder Positions: Alternate Proposal: 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Wind Generating Facilities Power Quality 19 Wind generating facilities must comply with all industry practices, standards and guidelines for electricity quality not otherwise specifically set out in this Section 501.3.1. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 20 of 38 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Voltage Flicker 20 The flicker for wind generating facilities must comply with either the maximum permissible voltage flicker limits as defined in Appendix 4, or in International Electrotechnical Commission 61000-3-7, Electromagnetic compatibility (EMC) – Part 3-7: Limits - Assessment of emission limits for the connection of fluctuating installations to MV, HV and EHV power systems , whichever is lower. Reason for Stakeholder Positions: Alternate Proposal: 2. (mark with ”x”) Requirements (cont’) Harmonics 21(1) Upon request from the owner of any wind generating facilities, the ISO will provide information describing the specific harmonic-impedance envelope at a proposed point of connection for those wind generating facilities. (2) The owner must mitigate any harmonic currents resulting from non-compliance with IEEE Standard 519-1992 Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 21 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Voltage Unbalance Avoidance 22(1) Wind generating facilities must not cause any voltage unbalance on the transmission system, calculated in accordance with subsection 22 (2), in excess of three percent (3%). (2) The voltage unbalance will be calculated using the following formula: Unbalance (%) = 100 x (deviation from average) (average) Reason for Stakeholder Positions: Alternate Proposal: 2. Requirements (cont’) (mark with ”x”) Avoidance of Undue Resonance 23. Any wind generating facilities must include systems and components designed to avoid introducing undue resonance into the transmission system, such design specifications to apply to self-excitation of induction machines, transformer ferroresonance, resonant effects of capacitor additions and the capacitance of the wind generating facilities’ collector cables. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 22 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Grounding 24. Any wind generating facilities must be designed and constructed to take in to account that the transmission system operates as an effectively and solidly grounded. Reason for Stakeholder Positions: Alternate Proposal: 2. Requirements (cont’) (mark with ”x”) Lightning Surge Protection 25. The lightning surge protection for any substation facilities associated with any wind generating facilities must be designed to take into account the average isokeraunic level for the site location of the wind generating facilities, and to be compatible with the connecting transmission facility to ensure coordination of insulation levels. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 23 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Clearance and Access 26(1) All energized facilities and installations of any wind generating facilities must be maintained at safe vertical and horizontal clearances and otherwise must meet the specifications and requirements set forth in this subsection 26. (2) The connecting facilities of any wind generating facilities at a point of connection must be designed and operate in compliance with the Canadian Electrical Code Part I. (3) The facilities and installations of any transmission facility connecting with the wind generating facilities at a point of connection must comply with The Alberta Electrical and Communication Utility Code. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 24 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Wind Power Facility Fault Interrupting Devices 27(1) The design of the connecting facilities of any wind generating facilities must: (a) account for the fault contributions from both the transmission system and the wind generating facilities; and (b) have fault interrupting and momentary withstand ratings that are adequate to meet the maximum expected fault levels, with a margin for future anticipated fault levels. (2) The wind generating facilities must not use or apply high voltage fuses at sixty nine (69) kilovolts or higher due to the risks of reduced reliability, increased outage times, single phasing and the possibility of ferroresonance. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 25 of 38 2. Requirements (cont’) (mark with ”x”) Wind Generating Facilities Isolating Devices 28(1) Any wind generating facilities must be designed and operate with manually operable isolation switches at all points of isolation designated by the ISO after consultation with the owner of the applicable transmission facility. (2) The isolation switches must permit visual verification of electrical isolation, and have the capability of being locked open with multiple locks. (3) All isolating switches of the wind generating facilities must be under the control of either the operator of the wind generating facilities, or the operator of the transmission facility. (4) If the wind generating facilities contain isolating switches owned by both the owner of the wind generating facilities and the owner of the transmission facility, then the owner of the wind generating facilities must agree in writing with the owner of the transmission facility as to who will control those isolating switches. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 26 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Special Interconnection Protections 29. The ISO, after consultations with the owner of any wind generating facilities, may require in writing additional, remedial action schemes and other specific protection and controls for the wind generating facilities at a proposed point of connection to ensure adequate, safe, efficient and reliable protection of the interconnected electric system and the wind generating facilities. Reason for Stakeholder Positions: Alternate Proposal: 2. Requirements (cont’) (mark with ”x”) Revenue Metering 30(1) Any wind generating facilities must have revenue electric meter facilities conforming to the AESO Measurement System Standard, to measure active energy and reactive energy flowing from the wind generating facilities to the transmission system, and for submission of the resulting data and records to the ISO. (2) The revenue electric metering facilities must include instrument transformers dedicated for metering purposes only, voltage transformers, current transformers, secondary wiring, test switches, meters and a communication interface. (3) All metering data must be submitted to the ISO in the format specified in the standard referenced in subsection 30(1). (4) At the point of connection, the meter installation facilities must be capable of measuring real power imports and exports. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 27 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Supervisory Control and Data Acquisition Requirements 31 In addition to complying with AESO SCADA Standard Rev 1 September 6, 2005 as amended from time to time, any wind generating facilities must provide the following additional data: (a) voltage regulation system set-point; (b) wind speed and direction, from a single point of measurement at the wind generating facilities; (c) potential MW capability, the real power that would have been produced at the point of connection without wind generating facilities curtailment and based on real time meteorological conditions at each available wind turbine generator; (d) real power limit, the MW limit used in the power limiting control system at the wind generating facilities; and (e) on / off status for the wind power limiting control system at the wind generating facilities. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 28 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Wind Power Data Collection Facility Requirements 32(1) Any wind generating facilities must have a data collection tower and related facilities installed in accordance with the provisions of this subsection 32. (2) The meteorological tower referred to in subsection 32(1) must be equipped with two (2) weather measurement devices, one taking measurements at the wind turbine generator hub height and another taking measurements at a height specified by the ISO. (3) The measurement devices must measure, on a ten (10) minute average value; (a) wind speed in meters per second (m/s), precision for instantaneous measurements to the nearest zero point one (0.1) meters per second; (b) wind direction in degrees from true north, precision for instantaneous measurements to the nearest one (1) degree; (c) barometric pressure in HectoPascals (HPa), precision for instantaneous measurements to the nearest six (6)-Pa; and (d) ambient temperature in degrees celsius (◦C), precision for instantaneous measurements to the nearest zero point one (0.1) degrees celsius. (4) The ISO will specify in writing whether the owner must submit the data described in subsection 32 for the wind generating facilities to the ISO by means of the systems referenced in subsection 31, or an alternative means or path. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 29 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Support Oppose No Comment Wind Power Facility Monitoring Equipment 33(1) Any wind generating facilities must have a monitor installed that complies with the AESO Requirements for Phasor Measurement Units. (2) The monitor must be capable of measuring all three (3) phase to ground voltages and currents at each collector bus of the wind generating facilities and for each transmission step-up transformer. (3) The monitor must be capable of measuring all three (3) phase to ground voltages and currents at each point of connection of the wind generating facilities. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 30 of 38 2. Requirements (cont’) (mark with ”x”) Support Wind Generating Facilities Testing Post Connection 34(1) Following connection of any wind generating facilities to the transmission system, those facilities must be tested by the owner in accordance with the provisions of subsection 34(2) below and the test results and report must be provided as per the ISO document “Requirements for Model Validation” no later than thirty (30) days following the date upon which wind speed conditions reasonably will allow for the tests to be conducted. (2) The following specific tests must be completed: (a) A voltage regulation system and reactive power response test, which demonstrates the ability of the wind generating facilities to control the collector and transmission system voltage in a stable manner, and which test consists of injecting a test signal to the voltage reference point of the voltage regulation system; (b) A reactive power capability test, which demonstrates the ability of the wind generating facilities to provide continuous reactive power in accordance with the any applicable standards set out in the ISO rules; (c) A voltage set-point capability test, which demonstrates the ability of the wind generating facilities to adjust the voltage set-point of the voltage regulation system to any applicable standards set out in the ISO rules; (d) A harmonic test as may be required by the ISO , which will demonstrate that harmonic levels for the wind generating facilities are within the limits of IEEE 519; and (e) A flicker test as may be required by the ISO, which will confirm that the flicker levels for the wind generating facilities are within the specifications set out in subsection 21. (3) The tests set out in this subsection 34 may be required to be re-conducted upon written request from the ISO, and in any event, such retests must be done due to a change in any applicable NERC or WECC policy or standards requirements. Proposed New ISO Rule: 2009-12-16 Page 31 of 38 Oppose No Comment Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 32 of 38 2. Requirements (cont’) (mark with ”x”) Provision of Modelling Information 35(1) In accordance with the Transmission Technical Modeling Requirements of the ISO, t he owner of any wind generating facilities must provide to the ISO all reasonably requested data and records to allow for the modeling of the wind turbine generators, transformers, collector systems, control systems and other installations of the wind generating facilities. (2) Where an appropriate model is not available within Siemens’ PSS/E software, the owner must supply a working user written PSS/E model. (3) If such a model is supplied to the ISO, then in addition, the owner must provide a written model and compiled code of the model, and maintain the user written model compatible with current and new releases of PSS/E until such time as a standard model is provided to the ISO. (4) Any model submitted by an owner under this section 35 may be resubmitted by the ISO to the WECC and its members for interconnected system studies. (5) The owner in addition must provide the ISO with power system studies which demonstrate that the wind generating facilities are capable of meeting the voltage ride through requirements specified in subsection 35(3). (6) The owner must provide the ISO with a wind turbine generator model with validated data demonstrated by a physical performance test, on a sixty (60) Hertz system, of at least one wind turbine generator for every type or model used at the wind generating facilities. (7) The owner in addition must provide a voltage regulation system model with validated data demonstrated by a physical performance test of at least one (1) voltage regulation system device used at the wind generating facilities. (8) The owner in addition must re-validate all model data from time to time as requested by the ISO. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 33 of 38 Support Oppose No Comment 2. Requirements (cont’) (mark with ”x”) Wind Power Data Facility Requirements 36(1) Any wind generating facilities must have equipment and installations so as provide to the service provider as designated by the ISO forecast data and records, which must include historical ten (10) minute averaged meteorological data, containing details on wind speed, wind direction, temperature and barometric pressure and which illustrate the height of the measurements. (3) Upon written request by the ISO, the owner of the wind generating facilities must provide historical data and records referenced in subsection 36(1) for up to two (2) calendar years prior to the commissioning period of the wind generating facilities. (4) The owner of the wind generating facilities must provide the ISO with wind turbine generator data and records, including hub height, turbine land coordinates, turbine power curves, high wind speed cutout, and any applicable temperature cut-outs. (5) The ISO will specify in writing how the owner must submit to the ISO the data and records specified in this subsection 36 for the wind generating facilities. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 34 of 38 Support Oppose No Comment 3. (mark with ”x”) Appendix 1 - Voltage Ride Through Requirements 120% Support Oppose No Comment Wind generating facilities may trip above high voltage requirement. Voltage (Point of Connection) Percent of Rated 100% Fault incidence at time = 0 second. 80% 60% Wind generating facilities may trip below low voltage requirement. 40% 20% 15% 0% -1 0 1 2 3 4 5 Time (Seconds) Low Voltage Requirement High Voltage Requirement Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 35 of 38 3. (mark with ”x”) Appendix 2 - Reactive Power Capability -0.985 power factor at maximum authorized MW +0.95 power factor at maximum authorized MW Continuous Reactive Power Capability Dynamic Reactive Power Capability -0.95 power factor at maximum authorized MW Support Oppose No Comment +0.9 power factor at maximum authorized MW 1.0 MW per unit 0.8 0.6 0.4 Absorbing MVArs per unit 0.6 0.484 0.4 0.2 0 0.2 0.4 0.328 0.6 0.2 Producing MVArs per unit Where 1 per unit is the maximum authorized MW Minimum continuous reactive capability Minimum dynamic reactive capability Continuous reactive power capability within the shaded area. Dynamic reactive power capability within the shaded area. Reason for Stakeholder Positions: Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 36 of 38 3. Appendix 3 - Trip Settings of Off-Nominal Frequency Protective Relays Frequency (Hz) Minimum Time Delay >61.7 Hz 0 seconds 61.6 Hz to 61.7 Hz 30 seconds 60.6 Hz to <61.6 Hz 3 minutes >59.4 Hz to <60.6 Hz Continuous Operation >58.4 Hz to 59.4 Hz 3 minutes >57.8 Hz to 58.4 Hz 30 seconds >57.3 Hz to 57.8 Hz 7.5 seconds >57.0 Hz to 57.3 Hz Reason for Stakeholder Positions: (mark with ”x”) Support Oppose No Comment 45 cycles Alternate Proposal: Proposed New ISO Rule: 2009-12-16 Page 37 of 38 3. (mark with ”x”) Appendix 4 - Voltage Flicker Limits Support Oppose No Comment Reason for Stakeholder Positions: Alternate Proposal: Please return this form with your comments by Friday, January 22, 2010 to: John Kehler, Operations and Reliability, john.kehler@aeso.ca, (403) 539-2622 or alternate, Kevin Wiens, kevin.wiens@aeso.ca (403) 539-2672 Proposed New ISO Rule: 2009-12-16 Page 38 of 38