University of Manitoba Section 16160 Req. #

advertisement
University of Manitoba
PANELBOARDS
Section 16160
Req. #
1.1
Page 1
RELATED WORK
.1
Basic Electrical Materials
and Methods
.2
Conduit
.3
Circuit Breakers
Section 16050
Section 16111
Section 16182
1.2
SUBMITTALS
.1
Submit shop drawings in accordance with Section 16050.
.2
Drawings shall include electrical detail of panel, branch breaker type, quantity, ampacity and
enclosure dimension.
1.3
PLANT ASSEMBLY
.1
Install circuit breakers in panelboards before shipment.
.2
In addition to CSA requirements, manufacturer’s nameplate shall show fault current that
panel, including breakers, has been built to withstand.
2.1
PANELBOARDS
.1
Panelboards: to CSA C22.2 No.29-M1989.
.2
CDP panels: to CSA22.2 No.29-M1989 and shall be manufactured to allow installation of two
200a frame breakers adjacent to each other - horizontally.
.3
Panelboards shall be product of one manufacture throughout project.
.4
250V branch circuit panelboards: bus and breakers rated for 10kA symmetrical interrupting
capacity minimum, or as indicated.
.5
600V branch circuit panelboards: bus and breakers rated for 18 kA symmetrical interrupting
capacity, unless otherwise indicated.
.6
250V CDP panelboards: bus and breakers rated for 25 kA symmetrical interrupting capacity,
unless otherwise indicated. CDP panels shall be complete with doors.
.7
600V CDP panelboards: bus and breakers rated for 22 kA symmetrical interrupting capacity,
unless otherwise indicated. CDP panels shall be complete with doors.
.8
Sequence phase bussing such that circuit breakers shall be numbered vertically in
consecutive order. Each breaker shall be identified by permanent number identification as to
circuit number.
.9
Panelboards: mains, number of circuits, and number and size of branch circuit breakers as
indicated.
.10
Two keys for each panelboard and key panelboards alike.
.11
Copper bus with full size neutral.
.12
Flush or surface-mounted tubs as shown.
.13
Finish trim and door baked grey enamel.
.14
CDP-type panelboards (breakers or fusible) shall be provided with a minimum of 6-200 amp,
3-pole, frame spaces each complete with mounting hardware.
.15
All panelboards and CDP’s shall have “sprinklerproof” enclosures in sprinklered areas, and all
shall have lockable doors and isolated ground bus.
.16
Panelboard mains shall be suitable for bolt-on circuit breakers, and all spaces shall be
provided with mounting hardware.
.17
Panelboards and CDP’s fed from Emergency power shall be painted Red.
2.2
CUSTOM BUILT PANELBOARD ASSEMBLIES
.1
Double section panels as indicated.
.2
Feed through lugs as indicated.
.3
Weatherproof enclosure as indicated.
.4
Built-in contactors as indicated.
.5
L.V. relay sections as indicated.
2.3
BREAKERS
.1
Breakers in Section 16182.
.2
Breakers with thermal magnetic tripping to panelboards, except as indicated otherwise.
Date revised December 18, 2012
University of Manitoba
PANELBOARDS
Req. #
Section 16160
Page 2
.3
.4
.5
Main breaker: mounted on top or bottom of panel to suit cable entry.
Lock-on devices for fire alarm, emergency, door supervisory, intercom, stairway, exit light,
and night light circuits.
Branch circuit breakers shall be 15A single-pole, unless otherwise indicated on drawings.
2.4
EQUIPMENT IDENTIFICATION
.1
Provide equipment identification in accordance with Section 16050.
.2
Size 3 nameplate for each Panelboard and CDP.
Line 1 – Panel ID.
Line 2 – Amp of Feeder, Breaker, Voltage & Wire.
Line 3 – Fed from Panel & Room Number.
.3
Size 2 nameplate for each breaker in CDP Panelboards
Line 1 – Panel ID.
Line 2 – Panel location (Room #).
.4
Complete circuit directory with typewritten legend showing location and load of each circuit.
2.5
MANUFACTURERS
.1
Acceptable manufacturers: Cutler Hammer / Square D.
3.1
INSTALLATION
.1
Locate panelboards as indicated and mount securely, plumb, true and square, to adjoining
surfaces.
.2
Install surface-mounted panelboards on U-channels. Where practical, group panelboards on
common length of U-channel.
.3
Mount panelboards to height indicated in Section 16050, unless otherwise indicated.
.4
Connect loads to circuits as indicated.
.5
Provide a separate neutral for each branch circuit with the exception of:
a)
split wired parking or kitchen countertop receptacles.
b)
balanced three-phase lighting circuits feeding fluorescent and/or incandescent
sources only.
c)
Convenience receptacle circuits in corridors or stairwells. Where a common neutral
is acceptable (a, b, or c above), they shall be shared by vertically adjacent breakers.
Neutral conductors shall be identified with Mylar/cloth wire markers showing the
circuit number of all circuits sharing the neutral. Wire markers for each phase
conductor shall be provided.
.6
Install spare conduits from recessed panelboards in accordance with Section 16111.
.7
Connect isolated ground bus in panelboards to main building ground source with #2/0 AWG,
green insulated ground wire, in conduit unless otherwise noted.
.8
Wiring in panelboards shall be neat and set in as if laced. All neutral conductors shall be
identified in the panel with their associated circuit numbers by means of Brady Markers.
.9
All panelboards throughout the building shall be phased together such that the left hand,
centre, and right hand panelboard busses represent Phases A, B and C, respectively. All
indicating meters shall be identified to this sequence.
.10
Panels shall be complete with 10% spare breakers and 10% space (and mounting hardware)
based on Panel capacity for future breakers.
Date revised December 18, 2012
Download