Design Guidelines and Standards Manual University of Cincinnati 15250D - MECHANICAL INSULATION A. SECTION INCLUDES 1. 2. 3. B. GENERAL DESIGN CRITERIA 1. 2. 3. C. Piping Ductwork Equipment Internal duct insulation and lining is not permitted unless it is required because of acoustical concerns within the space. Where needed for acoustics, a flexible elastomer cellular insulation such as AP Armaflex SA by Armstrong is acceptable. Specify vapor barrier on cold surfaces (temp < 60F); and emphasize importance of preserving the integrity of the barrier, particularly during construction when it is most susceptible to damage. Specify insulation where required on hot surfaces, to prevent burning hazard to people. INSULATION MATERIAL 1. Symbol Legend a. INSULATION TYPE TYPE Glass Fiber Performed SYMBOL GFP Glass Fiber Board Glass Fiber Block Cellular Glass GFB GFBL CG b. SYMBOL FEC CS UR INSULATION JACKET, FIELD APPLIED DESCRIPTION Foil and Paper Plastic (Polyvinyl chloride) Aluminum c. TYPE Flexible Elastomeric Cellular Calcium Silicate Urethane SYMBOL FP PVC Stainless Steel SS DESCRIPTION Drinking Fountain Drain SYMBOL DFD A PIPING SYSTEMS DESCRIPTION Boiler Blowdown MECHANICAL INSULATION SYMBOL BBD 15250 - D1 5/18/2000 Design Guidelines and Standards Manual University of Cincinnati 2. Boiler Feedwater Boiler Flue Brine Supply Brine Return Chilled Water Supply Chilled Water Return Condenser Water Supply BFW BF BS BR CHS CHR CWS Condenser Water Return CWR Cooling Coil Condensate Drains Domestic Cold Water Domestic Hot Water Supply Domestic Hot Water Return CCD Engine Exhaust, Diesel EE Heating Hot Water Supply Heating Hot Water Return Roof Storm Drain Sanitary Drains, Fixtures Steam, Low Pressure (0-15 psig) Steam, High Pressure (P>15 psig) Steam Condensate Return HWS HWR RSD SAN LPS HPS CR DCW DHS DHR Insulation Schedule ITEM GLASS FIBER (GF) Temperature Range Material -20 to +450F, Jacket: 150F Max Inorganic Glass Fiber, Bonded Type Rigid Molded Semi-Rigid Board Block Blanket C 547 Class 1(Mold) C 612 Class 2(Brd) C C 553 Type II Class F-1 (Blanket) 0.26 Ave @ 75F Mean Temp 10 - 12 PCF ASTM Thermal Conductivity Density MECHANICAL INSULATION CELLULAR GLASS (CG) -450 to +800 F Jacket: 150F Max Inorganic Foamed or Cellulated Glass, Annealed, Rigid, Hermetically Sealed Cells, Incombustible Block Performed Pipe Special Shapes FLEXIBLE ELASTOMERIC CELLULAR (FEC) -40 to +200F Flexible, Expanded Closed-Cell Structure, Smooth Skin, Both Sides. Max 5% Shrinkage @ 200F for 7 Days Tubular Sheet C 552: Type I (Boards) Type II-Class 2 (Performed) Type III (Special) C 354, Type I (Tubular) C 354, Type II (Sheet) 0.38 Ave @ 75F Mean Temp 7 PCF (Min) 0.30 Ave @ 75F 15250 - D2 5/18/2000 Design Guidelines and Standards Manual University of Cincinnati 9.5 PCF (Max) MECHANICAL INSULATION 15250 - D3 5/18/2000 Design Guidelines and Standards Manual University of Cincinnati Moisture Absorption Jacket < 0.2% By Volume Factory Applied, Flame Retardant, White Kraft Paper Vapor Barrier, Bonded to Alum Foil, Glass Fiber Reinforced, 0.02 Perm [3%][6%] Max by Wt. Factory Applied ASTM C 921, Type 1, Laminated Foil, Flame Retardant, Vinyl Facing Features Water Based Latex Enamel 0.2 Perm Max Flame: Self Extinguishing Misc. ITEM Temperature Range Material Type ASTM Thermal Conductivity Density Moisture Absorption Jacket Features MECHANICAL INSULATION CALCIUM SILICATE (CS) +100 TO +1600F URETHANE (UR) (Outdoor Use Only) -60 to +220F Inorganic Hydrous Calcium Silicate, Fibrous Reinforcement (Non-Asbestos) Incombustible Molded Block Curved Block Performed Pipe C 533, Type I 0.60 @ 500 F Cellular Foam, Plastic (Urethane) Molded for Pipe 0.16 @ 100F 15 PCF Max Flame Spread: 0 Smoke Developed: 0 UL ASTM E 84 Test ASJ Vapor Barrier: 0.02 Perm Puncture Resistance: 50 Beach Units Flame Spread: 75 Max UL ASTM E 84 Test 15250 - D4 5/18/2000 Design Guidelines and Standards Manual University of Cincinnati Shrinkage: 2% Max @ 150F for 7 Days Compressive Strength: 30.6 psi, ASTM D 1621-73, Proc A Misc. E. PIPE INSULATION APPLICATION 1. Schedule TEMP 35 to 55 100 TO 250 250 TO 350 350 TO 900 SERVICE 1/2 to 2 PIPE SIZE 2 1/2 to 4 5 to 10 12 to 18 GF (P) FEC 1 1/2 3/4 1 1/2 3/4 2 --- 2 --- 1 1 2 2 1/2 3/4 1 1/2 1 1/2 1 1/2 1 1/2 2 --1 1/2 1 1/2 1 1/2 1 1/2 2 1/2 --2 1/2 2 2 2 3 1/2 --3 2 1/2 2 1/2 2 1/2 4 HPS CR BBD BFW EE GF(P), FEC, CG, CS SAME SAME SAME SAME SAME GF(P),CG CS SAME SAME SAME SAME CG, CS 2 1 1/2 1 1/2 1 1/2 3 2 1/2 2 2 2 3 1/2 3 3 3 3 4 3 1/2 3 1/2 3 1/2 3 1/2 5 BF SAME 4 4 CHS & R DCW CCD DFD RSD HWS & R LPS CR BBD BFW DHWS&R HWS & R MECHANICAL INSULATION INSUL 15250 - D5 5/18/2000 Design Guidelines and Standards Manual University of Cincinnati F. DUCT INSULATION APPLICATION 1. Schedule SERVICE INSULATION THICKNESS Interior Concealed HVAC Supply and Return Ducts and Plenums Interior Exposed HVAC Supply and Return Ducts and Plenums Exterior Concealed HVAC Supply and Return Ducts and Plenums GFBL 1 1/2 VAPOR FIELD BARRIER APPLIED JACKET YES NO GFB GFP GFB GFP 1 1/2 YES NO 3 YES NO FEC GFB GFP 2 3 YES YES NO YES Interior Exposed HVAC Supply Fans, AHU’s, Casings, & Plenums Interior Exposed Range Hood Exhaust Ducts GFB 2 YES NO CS NO SS Interior Concealed Range Hood Exhaust Ducts CS NO NO Interior Exposed Oven and Dishwasher Exhaust Ducts Interior Concealed Oven and Dishwasher Exhaust Ducts GFB CS GFB THKNS for 2 HR Rating THKNS for 2 HR Rating 2 NO SS 2 NO NO Exterior Exposed, HVAC Supply and Return Ducts and Plenums G. EQUIPMENT INSULATION APPLICATION 1. Schedule SERVICE INSULATION THICKNESS Interior Exposed DCW Equipment, Tanks, & Pumps GFB 1 VAPOR FIELD BARRIER APPLIED JACKET YES P/K/A/SS CG 1 1/2 YES MECHANICAL INSULATION P/K/A/SS 15250 - D6 5/18/2000 Design Guidelines and Standards Manual University of Cincinnati Interior Exposed DHW Equipment, Tanks, & Pumps Interior Exposed Low Temp Brine Equipment, Tanks, Pumps & Heat Exchangers (0 to 34 F) Interior Exposed Chilled and Dual-Temp Water Equip., Tanks, Pumps, and Heat Exchangers (35 to 100 F) Interior Exposed Refrigerated Drinking Water Equipment, Tanks, Pumps, and Heat Exchangers Interior Exposed Heating Water Equip, Tanks, Pumps and Heat Exchangers (100 to 250 F) Interior Exposed High-Temp Heating Water Equip, Tanks, Pumps and HX’s (250 to 350 F) Interior Exposed Boiler Flues and Breeching FEC GFBL 3/4 2 YES NO NO A/SS CG (BLK) CS (BLK) GFBL 2 2 4 NO NO YES A/SS A/SS A/SS CG (BLK) GFBL 5 2 1/2 YES YES A/SS A/SS CG (BLK) GFBL 3 2 YES YES A/SS P CG GFB or GFBL 2 2 YES NO P A/SS CG (BLK) CS GFB GFBL 2 2 4 NO NO NO A/SS A/SS A/SS CG (BLK) CS (BLK) CS (BLK) 5 4 4 NO NO NO A/SS A/SS A/SS END MECHANICAL INSULATION 15250 - D7 5/18/2000