EQUIPMENT INSTALLATION DETAILS OF FANS, ROOM AIR CONDITIONERS & DESERT COOLERS IRANIAN PETROLEUM STANDARDS C B NO REVISION PERMITTED UNLESS APPROVED BY STANDARD ORGANIZATION A REV. DESCRIPTION DATE COVER SHEET DATE DRAWING No. IPS-D-AR-014 SHT REV. 1 4 MOTOR OUT OF AIRSTREAM ADJUSTABLE PITCH MOTOR SHEAVE VIBRATION ELIMINATOR DIRECT OR V-BELT DRIVEN HOUSING WITH REMOVABLE MOTOR DOME. MANUAL RESET FIRESTAT NON-FERROUS FASTENER TO PERMIT DOME REMOVAL FOR ACCESS TO MOTOR BALL BEARING PERMANENTLY LUBRICATED PILLOW BLOCKS ALUMINUM BIRD SCREEN UNFUSED DISCONNECT SWITCH ALL AROUND CENTRIFUGAL FAN WHEEL BACKWARDLY INCLINED ELECTRICAL CONDUIT GUIDE STATIC PRESSURE PROBE INLET VENTURI 6mm(1/4") TUBING DISCHARGE APRON PLASTIC CAP SECURE FAN TO CURB WITH S/M SCREWS 300mm(12") O.C. ALL AROUND CURB CAP THERMAL-ACOUSTICAL CURB SEE DETAIL FOAM RUBBER GASKET APPLIED UNDER SIDE OF FAN CRUB CAP NOTE: ROOF STRUCTURE-SEE ARCH. AND STRUCTURAL PLANS FOR DETAILS LOUVERS RUN POWER SUPPLY LEADS IN CORNER INSIDE CURB EXHAUST FAN DETAIL CURBS AND FANS SHALL PREFERABLY BE FROM THE SAME MANUFACTURER. FAN CURB CAP SECURE FAN TO CURB WITH S/M SCREWS 300mm (12") O.C. ALL AROUND THERMAL INSULATION CURB FASTENING FLANGE ACOUSTICAL LINING ALUMINIUM TWIN-SHELL CURB ROOFING TO EXTEND UP AND OVER TOP OF CURB AS SHOWN SECRURE CURB TO ROOF USING FASTENERS AT 300mm (12") O.C. BEFORE APPLYING ROOFING AND INSULATION (IF REQUIRED) 300mm(12") SECURE CURB TO ROOF WITH S/M SCREWS,LAG BOLTS OR OTHER METHOD CONSISTANT WITH ROOF CONSTRUCTION ROOF STRUCTURE-SEE ARCH. AND STRUCTURAL PLANS FOR DETAILS CONNECT DUCT TO CURB SEE PLANS FOR DUCT CONNECTION OR REGISTER ROOF OPENING IN ACCORDANCE WITH CONSULTANT'S APPROVED SHOP DRAWINGS. THERMAL-ACOUSTICAL CURB DETAIL IRANIAN PETROLEUM STANDARDS C B NO REVISION PERMITTED UNLESS APPROVED BY STANDARD ORGANIZATION A REV. DESCRIPTION TYPICAL POWER ROOF VENTILATOR(PRV) DATE INSTALLATION DETAIL DATE DRAWING No. IPS-D-AR-014 SHT REV. 2 4 WOVEN ASBESTOS CLOTH FLEXIBLE CONNECTION 1.3mm.(18 GAGE) CASING CASING 50x50x5 ANGLE ALL AROUND 40x40x4 ANGLE 650mm. ACCESS DOOR FAN ENCLOSURE FAN INSIDE CASING (AIR TIGHT) SUCTION CHAMBER DUCT FLEXIBLE CONNECTION AIR INTAKE DUCT SEE PROJECTS PLANS FOR SIZE AND CONTINUATION FAN MOTOR CONCRETE PAD FLEXIBLE CONNECTION SIDE ELEVATION RAILS AIR DISCHARGE DUCT CONC. ISOLATION PAD SEE PROJECT PLANS FOR SIZE AND CONTINUATION FLOOR LINE MOTOR 1- ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE NOTED. MOTOR MOUNTED ON BELT GUARD ADJUSTABLE TRACKS PLAN DETAILS OF FAN INSTALLED IN SHEET METAL HOUSING NOTES: MOTOR MOUNT ADJUSTABLE SHEAVE DRIVE PULLEY. CONCRETE BASE ON SPRINGS AIR INLET OIL RESISTANT V BELTS TO SUIT HORSEPOWER TRANSMITTED. AIR DOUBLE WIDTH DOUBLE INLET FAN MOTOR FLOW FLANGED FAN DISCHARGE OUTLET SEE PLANS FOR DUCT CONNECTION BELT GUARD INBOARD BEARING CONCRETE ISOLATION PAD SHALL BE 150mm. LARGER ALL AROUND THAN EXTERMITIES OF FAN AND MOTOR AIR AIR INLET SECURE BELT GUARD TO FAN STRUCTURE V BELTS BACKWACK INCLINED OR CONCRETE PAD FELT PAD 50 FLOW BELT GUARD MOTOR THRU BOLTS CONC. ISOLATION PAD FLOOR LINE MOTOR ADJUSTABLE MOUNT RAIL TYPE INLET SIDE ELEVATION MOTOR END ELEVATION AIRFOIL FAN WHEEL FLANGED FAN AIR ISOLATORS (SEE DETAIL) SET SLEEVES FOR THRU BOLTS DISCHARGE OUTLET OIL RESISTANT SPRING TYPE VIBRATION FLOOR LINE FLOW PLAN ADJUSTABLE RAIL TYPE MOTOR MOUNT-BOLT TO CONCRETE WITH THRU BOLTS CONC. ISOLATION PAD RUBBER SOUND PAD FLANGED FAN DISCHARGE OUTLET-SEE PROJECT PLANS FOR DUCT CONTINUATION 4 No. AT 200 O.C. EACH WAY TOP & BOTTOM CEMENT ALL PADS IN PLACE BELT GUARD 25 FLOW OIL RESISTANT V BELTS AIR 50 AIR BELT GUARD FLOW SPRING TYPE VIBRATION ELIMINATION NUMBER AS RECOMMENDED BY ISOLATOR MANUFACTURER C B A REV. DESCRIPTION IRANIAN PETROLEUM STANDARDS DATE CONCRETE SLAB NO REVISION PERMITTED UNLESS APPROVED BY STANDARD ORGANIZATION SPRING TYPE VIBRATION ELIMINATOR DETAIL SPRINGS (SEE DETAIL) FLOOR LINE SPRING TYPE VIBRATION ELIMINATOR FRONT ELEVATION DOUBLE WIDTH DOUBLE INLET FAN DATE DRAWING No. IPS-D-AR-014 SHEET REV. 3 4 EVAPORATIVE WATER COOLER 50x50x5mm. THICK STEEL ANGLE 200x200x8mm. THICK M.S. PLATE 200 300 DESERT COOLER FOR COMMERICIAL USE DATE IPS-D-AR-014 DRAWING No. 4 4 SHT REV. NO REVISION PERMITTED UNLESS APPROVED BY STANDARD ORGANIZATION IRANIAN PETROLEUM STANDARDS TYPICAL COOLER INSTALLATION DETAIL APPROX. TO SUIT COOLER SIZE CANVAS 20x20x4mm. THICK ANGLE FRAME 260 COOLER OUTLET REDUCING BEND 30 10 DATE TO SUIT COOLER SIZE 50x5mm. THICK FLAT BAR 50x50x5mm. THICK STEEL ANGLE FRAME 200x200x8mm. THICK M.S. PLATE DUCT 10 DESCRIPTION 550 APPROX. SOLDERED GALVD. SHEET FOAM RUBBER IN 1:3 C.S. MORTAR A B C 220mm. BRICK WALL 1:3:6 C.S.S. CONC.COPING CEMENT PLASTER ON WIRE MESH GALVD. CHICKEN WIRE MESH F.R.L. WATER PROOFING 150 150 TO SUIT COOLER SIZE COOLER SUPPORT DETAIL NOTE: ALL DIMENSIONS ARE IN MILLIMETER. REV. 150 100 200 50 100 TO SUIT COOLER SIZE 150 150