EQUIPMENT INSTALLATION DETAILS OF FANS, ROOM AIR CONDITIONERS & DESERT COOLERS

advertisement
EQUIPMENT INSTALLATION DETAILS OF
FANS, ROOM AIR CONDITIONERS &
DESERT COOLERS
IRANIAN PETROLEUM STANDARDS
C
B
NO REVISION PERMITTED UNLESS APPROVED BY STANDARD ORGANIZATION
A
REV.
DESCRIPTION
DATE
COVER SHEET
DATE
DRAWING No.
IPS-D-AR-014
SHT REV.
1
4
MOTOR OUT OF AIRSTREAM
ADJUSTABLE PITCH MOTOR SHEAVE
VIBRATION ELIMINATOR
DIRECT OR V-BELT DRIVEN
HOUSING WITH REMOVABLE
MOTOR DOME.
MANUAL RESET FIRESTAT
NON-FERROUS FASTENER
TO PERMIT DOME REMOVAL
FOR ACCESS TO MOTOR
BALL BEARING PERMANENTLY
LUBRICATED PILLOW BLOCKS
ALUMINUM BIRD SCREEN
UNFUSED DISCONNECT SWITCH
ALL AROUND
CENTRIFUGAL FAN WHEEL
BACKWARDLY INCLINED
ELECTRICAL CONDUIT GUIDE
STATIC PRESSURE PROBE
INLET VENTURI
6mm(1/4") TUBING
DISCHARGE APRON
PLASTIC CAP
SECURE FAN TO CURB WITH
S/M SCREWS 300mm(12")
O.C. ALL AROUND
CURB CAP
THERMAL-ACOUSTICAL
CURB SEE DETAIL
FOAM RUBBER GASKET APPLIED
UNDER SIDE OF FAN CRUB CAP
NOTE:
ROOF STRUCTURE-SEE ARCH.
AND STRUCTURAL PLANS FOR
DETAILS
LOUVERS
RUN POWER SUPPLY LEADS
IN CORNER INSIDE CURB
EXHAUST FAN DETAIL
CURBS AND FANS SHALL PREFERABLY BE
FROM THE SAME MANUFACTURER.
FAN CURB CAP
SECURE FAN TO CURB
WITH S/M SCREWS 300mm
(12") O.C. ALL AROUND
THERMAL INSULATION
CURB FASTENING FLANGE
ACOUSTICAL LINING
ALUMINIUM TWIN-SHELL CURB
ROOFING TO EXTEND UP AND
OVER TOP OF CURB AS SHOWN
SECRURE CURB TO ROOF
USING FASTENERS AT 300mm
(12") O.C. BEFORE APPLYING
ROOFING AND INSULATION
(IF REQUIRED)
300mm(12")
SECURE CURB TO ROOF
WITH S/M SCREWS,LAG
BOLTS OR OTHER METHOD
CONSISTANT WITH ROOF
CONSTRUCTION
ROOF STRUCTURE-SEE ARCH.
AND STRUCTURAL PLANS FOR
DETAILS
CONNECT DUCT TO CURB
SEE PLANS FOR DUCT
CONNECTION OR REGISTER
ROOF OPENING IN ACCORDANCE WITH
CONSULTANT'S APPROVED SHOP
DRAWINGS.
THERMAL-ACOUSTICAL CURB DETAIL
IRANIAN PETROLEUM STANDARDS
C
B
NO REVISION PERMITTED UNLESS APPROVED BY STANDARD ORGANIZATION
A
REV.
DESCRIPTION
TYPICAL POWER ROOF VENTILATOR(PRV)
DATE
INSTALLATION DETAIL
DATE
DRAWING No.
IPS-D-AR-014
SHT REV.
2
4
WOVEN ASBESTOS CLOTH
FLEXIBLE CONNECTION
1.3mm.(18 GAGE)
CASING
CASING
50x50x5
ANGLE ALL
AROUND
40x40x4
ANGLE
650mm. ACCESS DOOR
FAN ENCLOSURE
FAN INSIDE CASING
(AIR TIGHT)
SUCTION CHAMBER
DUCT
FLEXIBLE CONNECTION
AIR INTAKE DUCT SEE
PROJECTS PLANS FOR
SIZE AND CONTINUATION
FAN
MOTOR
CONCRETE PAD
FLEXIBLE CONNECTION
SIDE ELEVATION
RAILS
AIR DISCHARGE DUCT
CONC. ISOLATION PAD SEE PROJECT PLANS
FOR SIZE AND CONTINUATION
FLOOR LINE
MOTOR
1- ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
NOTED.
MOTOR MOUNTED ON
BELT GUARD
ADJUSTABLE TRACKS
PLAN
DETAILS OF FAN INSTALLED IN SHEET METAL HOUSING
NOTES:
MOTOR MOUNT
ADJUSTABLE SHEAVE
DRIVE PULLEY.
CONCRETE BASE
ON SPRINGS
AIR INLET
OIL RESISTANT V BELTS
TO SUIT HORSEPOWER
TRANSMITTED.
AIR
DOUBLE WIDTH
DOUBLE INLET
FAN
MOTOR
FLOW
FLANGED FAN
DISCHARGE OUTLET
SEE PLANS FOR
DUCT CONNECTION
BELT GUARD
INBOARD BEARING
CONCRETE ISOLATION PAD SHALL
BE 150mm. LARGER ALL AROUND
THAN EXTERMITIES OF FAN AND MOTOR
AIR
AIR INLET
SECURE BELT GUARD
TO FAN STRUCTURE
V BELTS
BACKWACK INCLINED OR
CONCRETE
PAD
FELT PAD
50
FLOW
BELT GUARD
MOTOR
THRU BOLTS
CONC. ISOLATION PAD
FLOOR LINE
MOTOR ADJUSTABLE
MOUNT RAIL TYPE
INLET SIDE ELEVATION
MOTOR END ELEVATION
AIRFOIL FAN WHEEL
FLANGED FAN
AIR
ISOLATORS (SEE DETAIL)
SET SLEEVES FOR
THRU BOLTS
DISCHARGE OUTLET
OIL RESISTANT
SPRING TYPE VIBRATION
FLOOR LINE
FLOW
PLAN
ADJUSTABLE RAIL TYPE
MOTOR MOUNT-BOLT TO
CONCRETE WITH THRU BOLTS
CONC. ISOLATION PAD
RUBBER
SOUND
PAD
FLANGED FAN DISCHARGE
OUTLET-SEE PROJECT PLANS
FOR DUCT CONTINUATION
4 No. AT 200 O.C. EACH
WAY TOP & BOTTOM
CEMENT ALL
PADS IN PLACE
BELT GUARD
25
FLOW
OIL RESISTANT V BELTS
AIR
50
AIR
BELT GUARD
FLOW
SPRING TYPE VIBRATION
ELIMINATION NUMBER AS
RECOMMENDED BY ISOLATOR
MANUFACTURER
C
B
A
REV.
DESCRIPTION
IRANIAN PETROLEUM STANDARDS
DATE
CONCRETE SLAB NO REVISION PERMITTED UNLESS APPROVED BY STANDARD ORGANIZATION
SPRING TYPE VIBRATION
ELIMINATOR DETAIL
SPRINGS (SEE
DETAIL)
FLOOR LINE
SPRING TYPE VIBRATION ELIMINATOR
FRONT ELEVATION
DOUBLE WIDTH DOUBLE INLET FAN
DATE
DRAWING No.
IPS-D-AR-014
SHEET REV.
3
4
EVAPORATIVE WATER COOLER
50x50x5mm. THICK
STEEL ANGLE
200x200x8mm. THICK
M.S. PLATE
200
300
DESERT COOLER FOR
COMMERICIAL USE
DATE
IPS-D-AR-014
DRAWING No.
4
4
SHT REV.
NO REVISION PERMITTED UNLESS APPROVED BY STANDARD ORGANIZATION
IRANIAN PETROLEUM STANDARDS
TYPICAL COOLER INSTALLATION DETAIL
APPROX.
TO SUIT COOLER SIZE
CANVAS
20x20x4mm. THICK ANGLE FRAME
260
COOLER OUTLET
REDUCING BEND
30
10
DATE
TO SUIT COOLER SIZE
50x5mm. THICK FLAT BAR
50x50x5mm. THICK
STEEL ANGLE FRAME
200x200x8mm. THICK
M.S. PLATE
DUCT
10
DESCRIPTION
550 APPROX.
SOLDERED
GALVD. SHEET
FOAM RUBBER
IN 1:3 C.S. MORTAR
A
B
C
220mm. BRICK WALL
1:3:6 C.S.S.
CONC.COPING
CEMENT PLASTER
ON WIRE MESH
GALVD. CHICKEN
WIRE MESH
F.R.L.
WATER PROOFING
150
150
TO SUIT COOLER SIZE
COOLER SUPPORT DETAIL
NOTE:
ALL DIMENSIONS ARE IN MILLIMETER.
REV.
150
100
200
50
100
TO SUIT COOLER SIZE
150
150