Florida Public Schools Annual Fire Safety Report Tom Gallagher Chief Financial Officer State Fire Marshal Produced by Florida Division of State Fire Marshal Prepared by the Bureau of Economic and Business Research University of Florida Table of Contents Letter from the State Fire Marshal..................................... 3 Overview of Law.............................................................. 5 School Inspections Success Stories.................................... 7 Inspection Summary........................................................ 8 2 CHIEF FINANCIAL OFFICER STATE OF FLORIDA TOM GALLAGHER Dear Floridians, This is the third annual report by the State Fire Marshal’s Office on the status of fire safety inspections in Florida’s public schools. Statewide, the school districts conducted 97 percent of required inspections, while the local fire districts conducted 90 percent of required inspections. Fire safety inspections are critical to ensure the safety of our school children and educators. Nothing short of 100-percent compliance is acceptable. This report was provided to the Legislature and is available on the Division of State Fire Marshal’s website, at www.fldfs.com/sfm. Florida law requires that each local school district and each local fire department annually inspect every public school and ancillary facility within its jurisdiction. I applaud those school districts and fire departments that did their duty under the law. To those school districts and fire departments that did not, they are forewarned: if we learn that serious violations of the fire code are not being addressed, steps will be taken to protect teachers and school children from unsafe areas. The Division of State Fire Marshal is continually working to improve the inspection reporting system. In conjunction with the University of Florida, the division has developed an internetbased school-inspection reporting system that will be implemented with the current fiscal year. In accordance with Rule Chapter 69A-58, Uniform Fire Safety Standard for Educational Facilities, all reports must now be submitted via the electronic school reporting system. If a school district or local fire district chooses not to enter the report directly into the system, all reports must be coded using the database coding system prior to forwarding to the division. Our goal is to provide school districts and local fire officials with a tool to improve and simplify reporting and ensure inspection reports are complete, consistent, and accurate. Full instructions, including the Master Coding List, will be available on the division’s website on April 1, 2006. Our teachers deserve a safe place to teach and our children deserve a safe environment in which to learn. Each of us plays a critical role in that goal. Let’s keep that as our focus. Sincerely, Tom Gallagher DEPARTMENT OF FINANCIAL SERVICES OFFICE OF COMMUNICATIONS 200 EAST GAINES STREET • TALLAHASSEE, FLORIDA 32399-0302 (850) 413-2842 • FACSIMILE (850) 413-4993 ■■■ Affirmative Action / Equal Opportunity Employer Overview of Law Overview of the Requirements of Section 1013.12, Florida Statutes The firesafety inspections referred to in the statute above are applicable to all buildings owned, leased, or being lease-purchased by the school board, including all permanent and re-locatable buildings. In addition, they must begin not sooner than one year after a new building has been occupied. They must be performed each fiscal year in accordance with any applicable code or standard, such as NFPA 101, as adopted in Rule 69A-3.012, Florida Administrative Code, or any other applicable code or standard which has been adopted in Rule Chapter 69A-58, Florida Administrative Code. Finally, the subject inspections are not applicable to new construction or new buildings which are subject to and controlled by Section 1013.38, Florida Statutes. Each firesafety inspection report and plan of correction must contain, at a minimum, the name of the school district or community college, the name of the local fire authority having jurisdiction (that is, the municipality, county, or special district), the name of the facility inspected, the type of facility inspected (that is, K-5, 6-9, 1012, community colleges, other), the facility address, the number of the facility as listed in the Florida Inventory of School Houses (FISH#), the name, address, and phone number of each inspector and the designation of whether such inspector is a special fire safety inspector or a municipal fire safety inspector, the date of the inspection, and each violation or deficiency noted during an inspection. Reports of the inspections must be filed with the local school board and the local site administrator. A plan and schedule for correction of any deficiency in the inspection report must be developed by any fire safety Continued on page 6 Overview of Law continued inspector finding a deficiency in conjunction with the school board and that plan and schedule then must be adopted and complied with by the school board. Furthermore, each violation or deficiency report must contain the Building name or number and, if applicable, the room number of the building in which the violation was noted; a description of the violation or deficiency and the number of times this violation or deficiency has been cited. In addition, the estimated correction date, total number of violations or deficiencies cited not involving serious life safety hazards and the total number of violations or deficiencies cited involving serious life safety hazards. Finally, the date of the scheduled re-inspection, a statement that the district has or has not complied with 1013.12(1)(c), a statement that the local authority having jurisdiction has or has not complied with 1013.12(2) c), including verification that the required fire drills have been completed. The report must include the signature of the district inspector if the inspection was made by the school district, or the signature of the local fire official if the local authority having jurisdiction made the inspection. If joint inspections were performed, both the school district fire safety inspector and the local fire official must each sign the report. When the violation or deficiency has been corrected, the school board must notify the division of such correction. The inspection reports noted above together with the plan and schedule for correction of any deficiency must be submitted to the division by June 30, of each year. . Continued on page 7 School Inspections Success Stories The SFM’s Inspection Reporting System is Now Available The Division has been working in conjunction with the University of Florida to create a web-based firesafety inspection reporting system. This system was designed specifically to eliminate the need for school districts to copy reports and forward them physically to the Division as required by section 1013(1)(b), Florida Statutes. The system allows school districts and fire officials to personally enter firesafety data as it relates to inspections performed on each school and ancillary facility. This ensures that data collected during any particular fiscal year is complete, consistent, and accurate information and allows school districts and local fire authorities to comply with the submission requirements in 1013(1)(b), Florida Statutes. “I found the New Public School Reporting System to be functional and easy to use. Registering to use the new system was very simple, and if any problems arose, I had direct access to the project manager, database manager and programmer, and also the State Fire Marshal’s office. This system is very user friendly and is definitely an advantage when doing school inspections.” Archie Strickland, Fire Inspector Madison County Fire Rescue Continued on page 8 Inspection Summary (Statewide) Florida School District Inspections Total number of schools and ancillary facilities Number of schools and ancillary facilities Percentage reporting Top five violations: Smoke detectors inoperable or missing Emergency lights not operational Fire extinguisher requires inspection Exit access not maintained Improper use of multistrips/extension cords ESCAMBIA SANTA RO SA HOLMES O KALOO SA WALTO N 3,460 3,355 97% JACKSON WASHINGTON LEO N CALHOUN NASSAU JEFFERSON GADSDEN MADISON BAY HAMILTON DUVAL BAKER SUWANNEE LIBERTY WAKULL A COLUMBIA TAYLOR CLAY UNION GULF LAFAYETTE ST. JOHNS BRADFORD FRANKLIN GILCHRIST DIXIE ALACHU A PUTNAM FLAGLER LEVY MARION VOLUSIA LAKE CITRUS SEMINOLE SUMTER HERNANDO ORANGE BREVARD PASCO Less than 75.0 OSCEO LA HILLSBOROUGH POLK 75.0 to 89.9 PINELLAS INDIAN RIVER 90.0 to 99.9 MANATEE HARDEE OKEECHOBEE HIGHLANDS 100.0 SARASO TA MARTIN CHARLOTTE G LADES LEE HEND RY COLLIER MONROE MONROE Percentage of Schools and Facilities Inspected by School Districts 8 ST. LUCIE DESO TO PALM BEACH BRO WARD MIAMI-DADE Inspection Summary (Statewide) Florida Local Fire Authority Inspections Total number of schools and ancillary facilities Number of schools and ancillary facilities Percentage reporting Top five violations: Emergency lights not operational Exit access not maintained Smoke detectors inoperable or missing Fire extinguisher requires inspection Inadequate fire resistance ESCAMBIA SANTA RO SA HOLMES O KALOO SA WALTO N 3,460 3,129 90% JACKSON WASHINGTON LEO N CALHOUN NASSAU JEFFERSON GADSDEN MADISON BAY HAMILTON DUVAL BAKER SUWANNEE LIBERTY WAKULL A COLUMBIA TAYLOR CLAY UNION GULF LAFAYETTE ST. JOHNS BRADFORD FRANKLIN GILCHRIST DIXIE ALACHU A PUTNAM FLAGLER LEVY MARION VOLUSIA LAKE CITRUS SEMINOLE SUMTER HERNANDO ORANGE BREVARD PASCO Less than 75.0 OSCEO LA HILLSBOROUGH POLK 75.0 to 89.9 PINELLAS INDIAN RIVER 90.0 to 99.9 MANATEE HARDEE OKEECHOBEE HIGHLANDS 100.0 SARASO TA MARTIN CHARLOTTE G LADES LEE HEND RY COLLIER MONROE MONROE Percentage of Schools and Facilities Inspected by Local Fire Authorities 9 ST. LUCIE DESO TO PALM BEACH BRO WARD MIAMI-DADE Inspection Summary (County-by-County) Alachua Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Improper use of multistrips/extension cords Penetration protection missing or inadequate Ground Fault Circuit Interrupter (GFCI) not installed in wet locations 68 68 100% 65 96% Baker Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Penetration protection missing or inadequate Exit access not maintained Missing or broken receptacle/faceplate 9 8 89% 3 33% Bay Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Fire extinguisher requires inspection Blocked or locked exits 10 42 41 98% 38 90% Inspection Summary (County-by-County) Bradford Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Penetration protection missing or inadequate Accumulation of combustible materials Fire alarm system not properly inspected/maintained 11 11 100% 4 36% Brevard Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Improper use of multistrips/extension cords Inadequate fire resistance 105 105 100% 103 98% Broward Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Smoke detectors inoperable or missing Accumulation of combustible materials Inadequate fire resistance 11 259 259 100% 259 100% Inspection Summary (County-by-County) Calhoun Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Accumulation of combustible materials Blocked or locked exits Extinguisher access obstructed 8 8 100% 8 100% Charlotte Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Exit lights inoperable in emergency mode Inadequate fire resistance 19 19 100% 19 100% Citrus Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Exit access not maintained Fire extinguisher requires inspection 12 24 24 100% 24 100% Inspection Summary (County-by-County) Clay Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Improper use of multistrips/extension cords Exit lights inoperable in normal mode 40 40 100% 40 100% Collier Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Fire alarm violations, general Means of egress violations, general Missing or broken receptacle/faceplate 53 53 100% 45 85% Columbia Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Inadequate fire resistance Emergency lights not operational Ground Fault Circuit Interrupter (GFCI) not installed in wet locations 13 15 15 100% 9 60% Inspection Summary (County-by-County) DeSoto Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Fire extinguisher requires inspection Exit lights inoperable in normal mode Exit lights inoperable in emergency mode 13 13 100% 13 100% Dixie Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Compressed gas cylinders not secured 6 6 100% 6 100% Duval Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Fire extinguisher requires inspection Blocked or locked exits Fire evacuation plan(s) not posted 14 168 168 100% 160 95% Inspection Summary (County-by-County) Escambia Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit access not maintained Missing or broken receptacle/faceplate Blocked or locked exits Fire safety inspection reports were not received for the following: Brownsville Middle C. A. Weis Elementary Escambia Superintendent's Office Eseal Center Hellen Caro Elementary Jim Allen Elementary John A. Gibson Headstart Program Judy Andrews School Pine Forest Senior High Roy L. Hyatt Environmental Center 66 52 79% 17 26% Flagler Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Smoke detectors inoperable or missing Emergency lights not operational Blocked or locked exits 15 13 13 100% 13 100% Inspection Summary (County-by-County) Franklin Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Accumulation of combustible materials Means of egress violations, general Protection violations, general 6 6 100% 6 100% Gadsden Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Accumulation of combustible materials Exit lights inoperable in emergency mode Blocked or locked exits Fire safety inspection reports were not received for the following: James A. Shanks Senior High Quincy Educational Center 19 17 89% 12 63% Gilchrist Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: General requirements violations Exit access not maintained Emergency lights not operational 16 6 6 100% 6 100% Inspection Summary (County-by-County) Glades Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Fire alarm system not properly inspected/maintained Emergency lighting not tested/records maintained Exit lights inoperable in normal mode 5 5 100% 5 100% Gulf Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Accumulation of combustible materials Emergency lights not operational Fire extinguisher requires inspection 6 6 100% 0 0% Hamilton Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit access not maintained Emergency lights not operational Accumulation of combustible materials 17 8 8 100% 7 88% Inspection Summary (County-by-County) Hardee Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Exit lights inoperable in emergency mode 11 10 91% 9 82% Hendry Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Means of egress violations, general Exit lights inoperable in emergency mode Fire safety inspection reports were not received for the following: Clewiston Administrative Offices 15 14 93% 14 93% Hernando Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Means of egress violations, general Fire extinguisher requires inspection Emergency lights not operational 18 25 25 100% 25 100% Inspection Summary (County-by-County) Highlands Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operatonal Missing or broken receptacle/faceplate Improper storage 18 17 94% 18 100% Hillsborough Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit access not maintained Fire extinguisher requires inspection Emergency lights not operational 247 247 100% 243 98% Holmes Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Fire extinguisher requires inspection Blocked or locked exits Combustible material improperly stored 19 10 10 100% 8 80% Inspection Summary (County-by-County) Indian River Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Improper use of multistrips/extension cords Fire evacuation plan(s) not posted Smoke detectors inoperable or missing 24 24 100% 24 100% Jackson Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Fire extinguisher requires inspection Fire safety inspection reports were not received for the following: Administrative Building Cottondale Elementary Cottondale Senior High Family Services Center Graceville Elementary Graceville Senior High Grand Ridge Senior High Head Start Hope School/CACL/ACE Jackson Academy of Applied Technology Maintenance Yard Malone Senior High Marianna Adult Education Center Marianna Middle Marianna Senior High Riverside Elementary Sneads Elementary Sneads Senior High Transportation Center 20 20 0 0% 1 5% Inspection Summary (County-by-County) Jefferson Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit lights inoperable in normal mode Emergency lights not operational Improper use of multistrips/extension cords 9 0 0% 9 100% Lafayette Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Means of egress violations, general Utilities violations, general Emergency lights not operational 5 5 100% 5 100% Lake Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Fire extinguisher requires inspection Exit lights inoperable in normal mode 21 58 58 100% 49 84% Inspection Summary (County-by-County) Lee Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit access not maintained Smoke detectors inoperable or missing Emergency lights not operational 83 81 98% 72 87% Leon Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Accumulation of combustible materials Blocked or locked exits Exit lights inoperable in normal mode Fire safety inspection reports were not received for the following: Odyssey Science Center 61 60 98% 58 95% Levy Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Exit lights inoperable in normal mode Horn/strobe device inadequate or inoperable 22 15 15 100% 15 100% Inspection Summary (County-by-County) Liberty Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit lights inoperable in normal mode Building address/I.D. not present or not visible Emergency lights not operational 7 7 100% 7 100% Madison Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Fire extinguisher requires inspection Blocked or locked exits General requirements violations Exit lights inoperable in normal mode 7 7 100% 7 100% Manatee Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit lights inoperable in normal mode Extension cords not rated for use Emergency lights not operational 23 53 53 100% 53 100% Inspection Summary (County-by-County) Marion Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Fire extinguisher requires inspection Missing or broken receptacle/faceplate 60 60 100% 57 95% Martin Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit access not maintained Penetration protection missing or inadequate Accumulation of combustible materials 24 26 26 100% 26 100% Inspection Summary (County-by-County) Miami-Dade Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit access not maintained Inadequate fire resistance Exit lights inoperable in normal mode Fire safety inspection reports were not received for the following: Aventura Elementary Charter School Doral Academy Charter High School Maintenance Operations; South Central Satellite Miami Carol City Senior High Miami Edison Middle North County Charter School Ronald W. Reagan/Doral Senior High Rosa Parks Charter School Ryder Elementary Charter School Spiral Tech Elementary Student Services and Attendance Center Youth Co-Op Charter School 394 366 93% 321 81% Monroe Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Blocked or locked exits Fire extinguisher requires inspection Smoke detectors inoperable or missing 25 15 15 100% 15 100% Inspection Summary (County-by-County) Nassau Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Smoke detectors inoperable or missing Monthly inspections not done/recorded 21 21 100% 18 86% Okaloosa Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Exit lights inoperable in normal mode Extinguisher missing from location 51 51 100% 51 100% Okeechobee Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Missing or broken receptacle/faceplate Emergency lights not operational Exit lights inoperable in normal mode 26 11 11 100% 11 100% Inspection Summary (County-by-County) Orange Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Inadequate fire resistance Improper use of multistrips/extension cords Exit access not maintained 198 198 100% 198 100% Osceola Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Accumulation of combustible materials Exit access not maintained Horn/strobe device inadequate or inoperable 43 43 100% 43 100% Palm Beach Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit access not maintained Smoke detectors inoperable or missing Rated openings not maintained Fire safety inspection reports were not received for the following: Howell L. Watkins Middle S. D. Spady Elementary South Area Middle School of Choice 27 223 220 99% 220 99% Inspection Summary (County-by-County) Pasco Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit access not maintained Emergency lights not operational Extension cords not rated for use 78 78 100% 77 99% Pinellas Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Extension cords not rated for use Emergency lights not operational Inadequate fire resistance 150 150 100% 145 97% Polk Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Penetration protection missing or inadequate Emergency lights not operational Smoke detectors inoperable or missing 28 139 129 93% 89 64% Inspection Summary (County-by-County) Putnam Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Dangerous condition exists Improper use of multistrips/extension cords Inadequate fire resistance 26 26 100% 26 100% St. Johns Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Accumulation of combustible materials Blocked or locked exits Improper use of multistrips/extension cords 36 36 100% 36 100% St. Lucie Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Accumulation of combustible materials Extinguisher missing from location Blocked or locked exits 29 40 40 100% 36 90% Inspection Summary (County-by-County) Santa Rosa Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Blocked or locked exits Fire extinguisher requires inspection Emergency lights not operational 33 33 100% 24 73% Sarasota Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Improper storage Blocked or locked exits Inadequate fire resistance Fire safety inspection reports were not received for the following: Taylor Ranch Bus Depot 47 41 87% 44 94% Seminole Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Fire extinguisher requires inspection Smoke detectors inoperable or missing Emergency lights not operational 30 64 64 100% 64 100% Inspection Summary (County-by-County) Sumter Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Inadequate clearance below sprinkler heads Fire extinguisher requires inspection Improper use of multistrips/extension cords Fire safety inspection reports were not received for the following: Administrative Complex 26 25 96% 24 92% Suwannee Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Exit lights inoperable in normal mode Monthly sprinkler system inspection not done/recorded Extinguisher missing from location 11 11 100% 11 100% Taylor Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Accumulation of combustible materials Inadequate fire resistance Blocked or locked exits 31 9 9 100% 1 11% Inspection Summary (County-by-County) Union Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Accumulation of combustible materials Penetration protection missing or inadequate 8 8 100% 8 100% Volusia Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Fire extinguisher requires inspection Improper use of multistrips/extension cords Emergency lights not operational Fire safety inspection reports were not received for the following: Bicentennial Park Ridgewood South 79 77 97% 74 94% Wakulla Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit lights inoperable in normal mode Fire extinguisher requires inspection Rated openings not maintained 32 10 10 100% 10 100% Inspection Summary (County-by-County) Walton Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Exit lights inoperable in normal mode Missing or broken receptacle/faceplate Fire extinguisher requires inspection Fire safety inspection reports were not received for the following: Freeport Senior High 14 13 93% 10 71% Washington Total number of schools and ancillary facilities School District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Fire extinguisher requires inspection Hood system needs inspection or maintenance Improper storage in electrical or mechanical rooms 33 11 11 100% 11 100% Inspection Summary Community Colleges Total number of schools and ancillary facilities College District Number of schools and ancillary facilities inspected Percentage inspected Local Fire Authority Number of schools and ancillary facilities inspected Percentage inspected Top violations: Emergency lights not operational Dangerous condition exists Extinguisher missing from location Brevard - No reports Broward Top violations: Penetration protection missing or inadequate Fire extinguisher requires inspection Sprinkler system needs inspection/test/maintenance Central Florida Top violations: Smoke detectors inoperable or missing Flammable atmosphere present Building services violations, other Means of egress violations, other Chipola Top violations: Improper storage in electrical or mechanical rooms Exit lights inoperable in emergency mode FACP indicates trouble condition General requirements violations, other Daytona Beach Top violations: Improper use of multistrips/extension cords Extension cords not rated for use Fire extinguisher requires inspection Edison Top violations: Fire extinguisher requires inspection Fire alarm system not properly inspected/maintained Improper storage in electrical or mechanical rooms Smoke detectors inoperable or missing Fire alarm control panel indicates trouble condition 34 133 130 98% 42 32% Inspection Summary Community Colleges continued Florida Community College at Jacksonville Top violations: Sprinkler system needs inspection/test/maintenance General requirements violations, other Post Indicator Valve (PIV) not locked/supervised Florida Keys Top violations: Occupancy load exceeded or not posted Means of egress violations, other Blocked or locked exits Extinguisher missing from location Accumulation of combustible materials Gulf Coast Top violations: Emergency lights not operational Exit lights inoperable in normal mode Protection violations, other Hillsborough Top violations: Improper storage in electrical or mechanical rooms Rated openings not maintained Fire extinguisher requires inspection Accumulation of combustible materials Emergency lights not operational Indian River Top violations: Means of egress violations, other Smoke detectors inoperable or missing FACP indicates trouble condition Penetration protection missing or inadequate Fire extinguisher requires inspection Lake City Top violations: Means of egress violations, other Smoke detectors inoperable or missing Fire extinguisher requires inspection Lake-Sumter Top violations: Fire extinguisher requires inspection Penetration protection missing or inadequate Fire alarm system requires inspection Blocked or locked exits 35 Inspection Summary Community Colleges continued Manatee Top violations: Means of egress violations, other Improper use of multistrips/extension cords Exit access not maintained Miami-Dade Top violations: Fire extinguisher requires inspection Missing or broken receptacle/faceplate Fire evacuation plan(s) not posted North Florida Top violations: Fire extinguisher requires inspection Exit lights inoperable in normal mode Means of egress violations, other Utilities violations, other Okaloosa-Walton Top violations: Exit lights inoperable in normal mode Monthly sprinkler system inspection not done/recorded Penetration protection missing or inadequate Palm Beach Top violations: Fire extinguisher requires inspection Blocked or locked exits Emergency lights not operational Pasco-Hernando Top violations: Accumulation of combustible materials Emergency lights not operational Extinguisher missing from location Pensacola Top violations: Rated openings not maintained Exit lights inoperable in normal mode Smoke detectors inoperable or missing 36 Inspection Summary Community Colleges continued Polk Top violations: Penetration protection missing or inadequate Missing or broken receptacle/faceplate Improper use of multistrips/extension cords St. Johns River Top violations: Fire alarm needs inspection Fire extinguisher requires inspection FACP indicates trouble condition Means of egress violations, other St. Petersburg Top violations: Means of egress violations, other Emergency lights not operational Utilities violations, other Santa Fe Top violations: Fire extinguisher requires inspection Penetration protection missing or inadequate Inadequate clearance below sprinkler heads Seminole Top violations: Exit lights inoperable in normal mode Fire alarm system needs inspection Fire extinguisher missing from location Means of egress violations, other South Florida Top violations: Penetration protection missing or inadequate Exit access not maintained FACP indicates trouble condition Tallahassee Top violations: Means of egress violations, other Improper use of multistrips/extension cords Valencia Top violations: Penetration protection missing or inadequate Smoke detectors inoperable or missing Utilities violations, other 37