UNIVERSITY OF HOUSTON Campus Facilities Planning Committee Agenda Item Description Form 1. ITEM: Roy G. Cullen Fire Safety Renovations 2. REQUESTING DEPARTMENT: Minor and Planned Projects (MPP) 3. CONTACT NAMES & PHONE NUMBERS: Barry Simmons (713-743-9073) 4. PRESENTER: Barry Simmons 5. RECOMMENDATION/ ACTION REQUESTED: It is recommended to enclose stairwells and create new exit to the exterior to address the State Fire Marshall Violation for the Life Safety of the occupants of the building. 6. SUMMARY: The State Fire Marshal issued a Life Safety and Code Violation on 1/22/13 for the Roy G. Cullen Building. The Fire Protection Violation states that the 1st and 2nd Floors are unprotected vertical opening and lack of separation from remainder of building and discharge to the exterior at the level of discharge. The recommended remedy is to provide separation by adding walls and doors to create exit enclosures. Renovations of the building must be completed by 9/30/13. The open stairs in this building does not meet the current Life Safety Code requirements for smoke compartments. This project scope includes building rated walls and doors to enclose the stairs to meet this requirement. A new exit from the west stair will be created to exit directly to the exterior on the first floor. Openings between the 1st and 2nd floors will also be enclosed to create separation between floors. 7. PROPOSED START DATE: 8. SUPPORTING DOCUMENTATION: 9/30/13 or TBD State Fire Marshall Violation from 2/6/13. Conceptual Plans showing scope of renovations. Photograph/rendering of exterior of building that will be affected by creating new exit to the exterior. ROY G. CULLEN BUILDING PHOTO OF EXISTING NORTHWEST SIDE OF BUILDING ROY G. CULLEN BUILDING PROPOSED NEW EXIT DOORS PROPOSED NEW STAIRS PROPOSED NEW SIDEWALK PROPOSED LOCATION OF NEW EXIT AT NORTHWEST SIDE OF BUILDING Roy G Cullen Building (Building # 501) Life/Safety Renovations – Type 3 July 20, 2012 FINAL REPORT TABLE OF CONTENTS – 1 – Overview and Scope of Work 2 – Scope of Work Documents (SHW Group) 3 – Statement of Probable Cost Appendix A – Existing Condition Photos and Drawings 0 Overview and Scope of Work – 1 PROJECT DESCRIPTION This project is to address Life Safety and Code Violations identified by the State Fire Marshal Life Safety Violations Identified: 1. 2. Item # 1 - Means of Egress Violation: Third floor common path of travel exceeds the 75 feet maximum limitation per Life Safety Code and has access to only one stair Item # 2 - Means of Egress/Protection Violation: Open stairs between first and second floor create an unprotected vertical opening and lack required separation from remainder of building Proposed Remedy: 1. 2. Item # 1 - Third floor stair is to be separated from the remainder of the building (third floor classroom) by the construction of a 2-hour rated enclosure/walls including fire rated door, frame and hardware Item # 2 - Stairs are to be separated from remainder of building by the provision (construction) of 2-hour rated enclosures/walls including fire rated doors, frame and hardware. Includes providing a protected means of egress (new hallway) to exterior. Third Floor Stairs (to be enclosed) BUILDING INFORMATION The Roy G. Cullen building is a 45,729 square foot stone and glass building originally constructed in 1939. The primary functions of the building include classroom and administrative spaces for the College of Liberal Arts. The building has a below-grade basement and three upper floors. The third level is unoccupied other than one classroom, and is considered attic space by campus and occupants. The upper floor appears to have been abandoned some years ago and is in very poor condition, with convenience lighting and a fire alarm system. According to all available documentation, and meetings with UH staff, the building underwent an addition shortly after construction, which added the western part of the building. Subsequent renovations have included MEP modifications and finish replacements. In 1992, the windows were replaced and at the same time exterior façade was sealed. In 2008, the building had an interior renovation on the first floor which included ceilings, floors, walls, lights and technology. Scope of Work Documents (SHW Group) – 2 101C 245.53 sf 107 109 111 113 206.26 sf 486.81 sf 469.75 sf 647.66 sf 691.43 sf 103A 218.48 sf X 175.19 sf 121 135 121A 482.21 sf 232.73 sf 140.89 sf 1. 2 105C 39.97 sf 105D 103 Down 25.17 sf 72.49 sf 13.36 sf 140 349.74 sf 1101.20 sf 131 133 213.21 sf 212.65 sf 151 1443.78 sf 15.34 sf 95.42 sf 80.44 sf 140A 144 141B 139 129 127 3 143 2. 3. 65.84 sf 1358.27 sf 153 173.30 sf 4 1 155 337.03 sf 104A 100A 100B 373.63 sf 377.26 sf 126 3 27.56 sf 102 APPROX. 141 534.75 sf 2080 CFM TOTAL 152 693.29 sf 84.83 sf 74.61 sf 154 106 108 110 112 114 709.60 sf 519.03 sf 449.93 sf 318.83 sf 363.73 sf 116 104C 104B 60.01 sf 41.52 sf 1 118 264.92 sf 74.61 sf 71.88 sf 116B 116A 120 121.89 sf 120.07 sf 97.33 sf 142A 122 314.25 sf 691.62 sf 1 130 132 134 226.44 sf 225.43 sf 224.61 sf 4. 4 104 1959.78 sf DEMOLITION KEY NOTES: RELOCATE ANY LIGHT FIXTURES OR ELECTRICAL DEVICES THAT MAY INTERFERE WITH THE CONSTRUCTION OF THE NEW STAIR WALLS/ ENCLOSURE OR CORRIDOR. RELOCATE EXISTING THERMOSTAT. REMOVE EXISTING DIFFUSER AND ASSOCIATED DUCTWORK BACK TO MAIN AND CAP. RELOCATE MAIN AS NECESSARY TO BE OUTSIDE OF NEW STAIRWELL ENCLOSURE. PERFORM PRECONSTRUCTION AIR BALANCE OF AREA INDICATED AND OF ASSOCIATED AIR HANDLING UNIT PRIOR TO THE START OF DEMOLITION. NOT FOR BIDDING OR CONSTRUCTION 119 142 128.74 sf DATE: 07/20/12 101B 244.89 sf 706.22 sf 141A Up 101A 244.70 sf 115B 241.68 sf 164.31 sf 105A 188.49 sf 105 115A 241.52 sf ROY GUSTAV BUILDING FIRST FLOOR PLAN TYPE ITEM # 3 105B REFERENCE SHEET: 117 207.20 sf 103B 368.14 sf MECHANICAL AND ELECTRICAL FIRST FLOOR DEMOLITION PLAN 188.49 sf 105 101B 101C 244.89 sf 245.53 sf 141A 206.26 sf 706.22 sf 103A 218.48 sf 115B 241.68 sf 119 142 175.19 sf 107 109 111 113 486.81 sf 469.75 sf 647.66 sf 691.43 sf X 6 128.74 sf 121 135 121A 482.21 sf 1. 232.73 sf 140.89 sf 105C Up 101A 244.70 sf 115A 241.52 sf 39.97 sf 105D 103 Down 25.17 sf 72.49 sf 127 1 139 4 143 13.36 sf 144 141B 140 349.74 sf 1101.20 sf 140A 1443.78 sf 15.34 sf 7 80.44 sf 131 133 213.21 sf 212.65 sf 151 2. 65.84 sf 1358.27 sf 153 173.30 sf 100A 100B 373.63 sf 377.26 sf 102 152 693.29 sf 74.61 sf 104B APPROX. 2080 CFM 141 534.75 sf 5 154 106 108 110 112 114 709.60 sf 519.03 sf 449.93 sf 318.83 sf 363.73 sf 116 104C 60.01 sf 2 118 264.92 sf 74.61 sf 71.88 sf 116B 116A 120 121.89 sf 120.07 sf 97.33 sf 142A 122 314.25 sf 691.62 sf 3. 155 5 7 104A 27.56 sf 337.03 sf 130 132 134 226.44 sf 225.43 sf 224.61 sf 3 4. 5. 6. 41.52 sf 104 1959.78 sf 1 7. NEW CONSTRUCTION KEY NOTES: PROVIDE A FIRE ALARM PULL STATION AT DOORS, ALONG THE PATH OF EGRESS, AND TIE INTO THE EXISTING FIRE ALARM SYSTEM. PROVIDE NEW LIGHTING AND EXIT SIGNAGE IN EXIT CORRIDOR TO PROVIDE 20FC. PROVIDE POWER TO MECHANICAL UNIT FOR EXIT CORRIDOR. PROVIDE NEW EXIT SIGNAGE. PROVIDE NEW ELECTRIC CABINET UNIT HEATER TO SERVE THE STAIR/EGRESS CORRIDOR. RELOCATE EXISTING THERMOSTAT TO INSIDE ROOM 121. REBALANCE ASSOCIATED AIR HANDLING UNIT TO PRECONSTRUCTION AIR FLOW MINUS CFM INDICATED AT KEY NOTE. MECHANICAL AND ELECTRICAL FIRST FLOOR NEW WORK PLAN 1/32" = 1'-0" KEYPLAN PROJ NUMBER: 105B 164.31 sf 105A PROJECT NAME: 117 207.20 sf 103B 368.14 sf SCALE: 1/32" = 1'-0" 218B 77.36 sf 219 214 215 216 151.06 sf 109.03 sf 165.69 sf 217 342.45 sf T T 160.05 sf 218 191.96 sf Up 214C 221C 222B 222C 105.92 sf 148.07 sf 140.69 sf T 16.93 sf 219A 219B 13.44 sf 18.06 sf 237A 103.75 sf 221B 102.81 sf 218A 221A Down 214A 276.75 sf E D H 223B 113.32 sf 223C 224B 224C 137.06 sf 142.62 sf 116.65 sf T 221 221D 222A 121.82 sf 122.70 sf 75.14 sf 223 222D 223A 123.79 sf 113.27 sf T T 223D 224A 113.27 sf 115.02 sf 77.17 sf SA FAN #2 SA FAN #1 1 T 283.73 sf EDH EDH EDH 229 229A T 43.78 sf 32.31 sf 224D 237 3 2 229C T 156.88 sf 1610.87 sf 240A 250 999.48 sf 321.05 sf 237D E128.31 sf D H 241 T 210 209 208 207 174.79 sf 172.70 sf 168.30 sf 173.51 sf 206 204 134.20 sf 253.47 sf T 236 236A 235D 121.73 sf 122.39 sf 74.59 sf 235A 122.50 sf 235 75.25 sf E 234D 120.09 sf D H 234 T 234A 233D 112.19 sf 115.15 sf 75.04 sf 109.58 sf EDH E D H 252 EDH 232D 105.51 sf 236C 236B 235C 235B 147.69 sf 106.08 sf 147.72 sf 139.51 sf 318.38 sf E 234C 120.44 sf D H T T 76.10 sf T 234B 233C 233B 135.11 sf 136.55 sf 112.42 sf 3 3. 251 APPROX. 180 CFM 233A 233 2. 294.94 sf EDH 389.62 sf 1 2 232 T 232A 231 103.58 sf 131.67 sf DEMOLITION KEY NOTES: RELOCATE LIGHT FIXTURES OR ELECTRICAL DEVICES THAT MAY INTERFERE WITH THE CONSTRUCTION OF THE NEW STAIR WALLS/ ENCLOSURE. REMOVE EXISTING DIFFUSERS SERVING STAIRWELL AREA BACK TO MAIN AND CAP. PERFORM PRECONSTRUCTION AIR BALANCE OF AREA INDICATED AND ASSOCIATED AIR HANDLING UNIT PRIOR TO START OF DEMOLITION. 239.88 sf 227D 103.54 sf SA FAN #3 E D H 205 962.60 sf 203 84.70 sf 227A T 114.04 sf 213 314.39 sf 32.27 sf 76.70 sf 224 74.65 sf T 228 EDH 225A 1. 229D 254.84 sf 227 225 64.59 sf E D H 222 74.42 sf 131.22 sf 84.21 sf EDH E D H 230A 196.16 sf 74.33 sf E D H T 232C 232B 231A 136.43 sf 114.49 sf 116.31 sf 230B 401.51 sf 230AB 288.88 sf APPROX. 2300 CFM TOTAL FOR ALL DIFFUSERS NOT FOR BIDDING OR CONSTRUCTION DATE: 07/20/12 E D H 227C 133.24 sf ROY GUSTAV BUILDING SECOND FLOOR PLAN TYPE ITEM # 3 REFERENCE SHEET: X T 227B 198.33 sf MECHANICAL AND ELECTRICAL SECOND FLOOR DEMOLITION PLAN SCALE: SCALE: 1/32" = 1'-0" T 227B E D H 221B 218B 77.36 sf 219 214 215 216 276.75 sf 151.06 sf 109.03 sf 165.69 sf 218 191.96 sf 217 342.45 sf T T Up E D H 205 962.60 sf 203 84.70 sf T EDH 210 209 208 207 174.79 sf 172.70 sf 168.30 sf 173.51 sf 206 204 134.20 sf 253.47 sf 222B 222C 148.07 sf 140.69 sf 221 241 223C 224B 224C 137.06 sf 142.62 sf 116.65 sf 221D 222A 121.82 sf 122.70 sf 75.14 sf 223A 113.27 sf SA FAN #2 76.70 sf 227A 223D 224A 113.27 sf 115.02 sf 77.17 sf T 229D 239.88 sf 229C T 156.88 sf EDH 229A 32.31 sf EDH 229 T 43.78 sf 224D 114.04 sf 237 1610.87 sf 3 2 240A 251 999.48 sf 294.94 sf 1 250 321.05 sf 2 237D E128.31 sf D H T 236 236A 235D 121.73 sf 122.39 sf 74.59 sf 235A 235 122.50 sf 75.25 sf E 234D 120.09 sf D H 234 T 234A 233D 112.19 sf 115.15 sf 75.04 sf E D H 109.58 sf EDH EDH 232D 236B 235C 235B 147.69 sf 106.08 sf 147.72 sf 139.51 sf 318.38 sf E 234C 120.44 sf D H T APPROX. 180 CFM 233A 233 76.10 sf 105.51 sf 236C 2. 3. 283.73 sf 227D 103.54 sf EDH T 252 EDH 225A 32.27 sf 224 74.65 sf T T 228 254.84 sf 225 223 222D 123.79 sf T 133.24 sf 227 64.59 sf E D H 222 74.42 sf 131.22 sf SA FAN #1 389.62 sf 223B 113.32 sf T APPROX. 2,300 CFM 1 T 221C 105.92 sf 227C 198.33 sf SA FAN #3 3 213 221A E D H 84.21 sf EDH 314.39 sf T 218A 16.93 sf 219A 219B 13.44 sf 18.06 sf 237A 214C 103.75 sf 102.81 sf 160.05 sf Down 214A E D H NEW CONSTRUCTION KEY NOTES: PROVIDE A FIRE ALARM PULL STATION AT DOORS, ALONG THE PATH OF EGRESS, AND TIE INTO THE EXISTING FIRE ALARM SYSTEM. PROVIDE NEW EXIT SIGNAGE AT DOORS. REBALANCE ASSOCIATED AIR HANDLING UNIT TO PRECONSTRUCTION AIRFLOW MINUS ANTICIPATED AIRFLOW INDICATED AT NOTE. 234B 233C 233B 135.11 sf 136.55 sf 112.42 sf 232 T T 232A 231 103.58 sf 131.67 sf 230A 196.16 sf 74.33 sf E D H T 232C 232B 231A 136.43 sf 114.49 sf 116.31 sf 230B 401.51 sf 230AB 288.88 sf MECHANICAL AND ELECTRICAL SECOND FLOOR NEW WORK PLAN SCALE: 1/32" = 1'-0" KEY PLAN PROJ NUMBER: 1. PROJECT NAME: X 48x12 EXH 1. 301A 301B 301C 301D 40.92 sf 30.52 sf 24.67 sf 23.58 sf 2. APPROX. 300 CFM TOTAL 3. 301 352 788.28 sf 62.18 sf 1 DEMOLITION KEY NOTES: RELOCATE LIGHT FIXTURES OR ELECTRICAL DEVICES THAT MAY INTERFERE WITH THE CONSTRUCTION OF THE NEW STAIR WALLS/ ENCLOSURE. RELOCATE EXISTING DIFFUSERS TO OUTSIDE OF NEW STAIRWELL AREA. PERFORM PRECONSTRUCTION AIR BALANCE OF AREA INDICATED AND ASSOCIATED AIR HANDLING UNIT PRIOR TO START OF DEMOLITION. 3 2 NOT FOR BIDDING OR CONSTRUCTION X SA FAN #1 DATE: 07/20/12 302C 254.28 sf ROY GUSTAV BUILDING THIRD FLOOR PLAN TYPE ITEM # 3 46.72 sf 97.06 sf REFERENCE SHEET: 302B 302A MECHANICAL AND ELECTRICAL THIRD FLOOR DEMOLITION PLAN 1. 302C 254.28 sf SA FAN #1 48x12 EXH 301A 301B 301C 301D 40.92 sf 30.52 sf 24.67 sf 23.58 sf 2. 3. 4. NEW CONSTRUCTION KEY NOTES: PROVIDE A FIRE ALARM PULL STATION AT DOORS, ALONG THE PATH OF EGRESS, AND TIE INTO THE EXISTING FIRE ALARM SYSTEM. PROVIDE NEW EXIT SIGNAGE AT DOORS. REWORK LIGHTING CIRCUITRY FOR THREE LIGHTS IN NEW STAIRWAY ENCLOSURE. REBALANCE RELOCATED DIFFUSERS TO PRECONSTRUCTION AIRFLOW. APPROX. 300 CFM TOTAL 301 352 788.28 sf 62.18 sf 1 2 3 4 MECHANICAL AND ELECTRICAL THIRD FLOOR NEW WORK PLAN SCALE: 1/16" = 1'-0" KEY PLAN PROJ NUMBER: 46.72 sf PROJECT NAME: X 302B 302A 97.06 sf SCALE: SCALE: 1/16" = 1'-0" ROY G CULLEN FIRST FLOOR PLAN RESTROOM AREA TO UPDATE PER ADA Statement of Probable Cost – 3 COST BREAKDOWN The outline costs below represent the building modifications/revisions reflected in tab 2 (Scope of Work Documents), including possible hazardous material abatement and accessibility revisions. As these costs are conceptual at this time, additional budget information is provided by CCM Construction Services LLC to reflect a range of costs associated with the anticipated scope of work. Mechanical and Electrical cost detail is also provided. Item # 1 – Separate Third Floor Stairs 1. 3rd Floor – Enclose Stair, Add Door* 2. Subtotal $ 12,960 (approx. 216sf @ 60/sf ) *Includes $6,900 for MEP $18,144 (includes 40% Mark-Up) Hazardous Material Abatement: rd 3. 4. 3 Floor – Enclose Stairs Subtotal $1,554 (approx. 259sf @ 6/sf) $2,331 (includes 50% Contingency) 5. Total Project Cost (TPC) $20,475 Item #2 – Separate Stairs at All Floor Levels, Exit to Exterior st nd 1. 1 and 2 Floor - Enclose Stairs* Location A Location B 2. Subtotal $66,420 (approx. 1,107sf @ 60/sf) $89,550 (approx. 1,194sf @ 75/sf) *Includes $37,240 for MEP $218,358 (Includes 40% Mark-Up) Hazardous Material Abatement: 3. 4. st nd 1 and 2 Subtotal Floor – Enclose Stairs $16,567 (approx. 2,761sf @ 6/sf) $24,851(includes 50% Contingency) Accessibility: 5. 6. Modifications to Ground Floor Restrooms Subtotal $95,590 (approx. 869sf @$110/sf) $133,826 (Includes 40% Mark-Up) 7. Total Project Cost (TPC) $377,035 Note: Mark-Up includes contingency, GC’s overhead/profit, permits and bond University of Houston Building #501 ‐ Roy Gustav Cullen Building Item #3 Scope of Work ‐ Estimated Costs UniFormat C1010 Partitions C1020 Interior Doors C1020 Interior Doors C1030 Fittings C1030 Fittings C1030 Fittings C3010 Wall Finishes C3020 Floor Finishes D3090 Other HVAC Systems & Equipment D3090 Other HVAC Systems & Equipment D3090 Other HVAC Systems & Equipment D3090 Other HVAC Systems & Equipment D5020 Lighting and Branch Wiring D5020 Lighting and Branch Wiring D5020 Lighting and Branch Wiring D5020 Lighting and Branch Wiring D5030c Fire Alarm G1021a Building Demolition G1021a Building Demolition G1021a Building Demolition G1021a Building Demolition G1021a Building Demolition G1021a Building Demolition G1021a Building Demolition G1021b Mechanical Demo FIRST FLOOR Descripton New Interior Partition, Rated Door, 6x7 (PR), Wood, Rated, or Similar Door, 6x7, AL/GL, or Similar Handrail, at Ramp New Ramp, 5'‐6''‐6'‐0'' Wide Stone Stairs, Platform, Walls, March Existing Finish, 9'‐0'' x 10'‐0'' Rework Wall Finishes, Patch Rework Floor and Ceiling Finishes for New Layout Pre‐Construction Air Balance on Area Provide New Electric Cabinet Heater to Serve Stair/Egress Corridor Rebalance Associated AHU Relocate Existing Thermostat Provide New Exit Signage, Recircuit Lighting Provide New Lighting in Exit Corridor Provide Power to Mechanical Unit, at Exit Corridor Relocate Existing Light Fixtures and Electrical Devices, This Area Provide Fire Alarm Pull Station at Doors, Tie to Existing System Demo Ceiling, Lights, Diffusers Demo Exterior Wall for New Door, 6x7 Demo Furrdown or Similar Demo Interior Door, say 3x7 or Similar Demo Interior Partition Temporary Partitions, Dust Control (Large Area) Temporary Partitions, Dust Control (Small Area) Remove Existing Supply Diffuser w/Flex Duct, Cap Ductwork Total ‐ Direct Cost Add Mark‐Ups (Contingency, GCs/Overhead/Profit, Permits, Bond) Total ‐ Cost w/Mark‐Ups Approximate Area of Work UniFormat C1010 Partitions C1020 Interior Doors C3010 Wall Finishes C3020 Floor Finishes D3090 Other HVAC Systems & Equipment D3090 Other HVAC Systems & Equipment D5020 Lighting and Branch Wiring D5020 Lighting and Branch Wiring D5030c Fire Alarm G1021a Building Demolition G1021a Building Demolition G1021a Building Demolition G1021a Building Demolition G1021a Building Demolition G1021b Mechanical Demo SECOND FLOOR Descripton New Interior Partition, Rated Door, 6x7 (PR), Wood, Rated, or Similar Rework Wall Finishes, Patch Rework Floor and Ceiling Finishes for New Layout Pre‐Construction Air Balance on Area Rebalance Associated AHU Provide New Exit Signage, Recircuit Lighting Relocate Existing Light Fixtures and Electrical Devices, This Area Provide Fire Alarm Pull Station at Doors, Tie to Existing System Demo Ceiling, Lights, Diffusers Demo Interior Handrail Demo Interior Partition Temporary Partitions, Dust Control (Large Area) Temporary Partitions, Dust Control (Small Area) Remove Supply/Return Diffusers w/Flex Duct, Cap Ductwork, Clean/SFR Total ‐ Direct Cost Add Mark‐Ups (Contingency, GCs/Overhead/Profit, Permits, Bond) Total ‐ Cost w/Mark‐Ups Approximate Area of Work Prepared by: CCM Construction Services, LLC (214‐556‐4510) Page 7 of 10 Qty 2,520 1 1 67 36 1 3,720 2,331 1,932 1 2 1 2 1 1 1,932 2 824 1 12 4 650 1 1 4 UM SF EA EA LF LF EA SF SF SF EA EA EA EA LS EA SF EA SF EA LF EA SF EA EA EA Unit Cost $5.00 $3,600.00 $6,000.00 $50.00 $75.00 $4,000.00 $2.50 $8.00 $0.75 $2,000.00 $1,500.00 $300.00 $400.00 $1,600.00 $600.00 $4.00 $450.00 $2.00 $750.00 $8.00 $100.00 $3.00 $1,200.00 $600.00 $75.00 50.0% 1,489 SF Qty 2,025 3 4,845 1,590 1,681 2 2 1,681 2 458 57 710 1 1 1,681 UM SF PR SF SF SF EA EA SF EA SF LF SF EA EA SF Cost/SF Unit Cost $5.00 $3,600.00 $2.00 $8.00 $0.50 $750.00 $400.00 $4.00 $450.00 $2.00 $20.00 $3.00 $1,000.00 $600.00 $0.50 50.0% 1,590 SF Cost/SF Extended $12,600 $3,600 $6,000 $3,350 $2,700 $4,000 $9,300 $18,648 $1,449 $2,000 $3,000 $300 $800 $1,600 $600 $7,728 $900 $1,648 $750 $96 $400 $1,950 $1,200 $600 $300 $85,519 $42,760 $128,279 $86.15 Extended $10,125 $10,800 $9,690 $12,720 $841 $1,500 $800 $6,724 $900 $916 $1,140 $2,130 $1,000 $600 $841 $60,726 $30,363 $91,089 $57.29 7/23/2012 University of Houston Building #501 ‐ Roy Gustav Cullen Building Item #3 Scope of Work ‐ Estimated Costs UniFormat C1010 Partitions C3010 Wall Finishes C3020 Floor Finishes D3090 Other HVAC Systems & Equipment D3090 Other HVAC Systems & Equipment D5020 Lighting and Branch Wiring D5020 Lighting and Branch Wiring D5020 Lighting and Branch Wiring D5030c Fire Alarm G1021a Building Demolition G1021b Mechanical Demo THIRD FLOOR Descripton New Interior Partition, Rated Rework Wall Finishes, Patch Rework Floor and Ceiling Finishes for New Layout Pre‐Construction Air Balance on Area Rebalance Associated AHU Provide New Exit Signage, Recircuit Lighting Relocate Existing Light Fixtures and Electrical Devices, This Area Rework Lighting Circuitry for Light Fixture Provide Fire Alarm Pull Station at Doors, Tie to Existing System Temporary Partitions, Dust Control (Small Area) Remove Supply/Return Diffusers w/Flex Duct, Cap Ductwork, Clean/SFR Total ‐ Direct Cost Add Mark‐Ups (Contingency, GCs/Overhead/Profit, Permits, Bond) Total ‐ Cost w/Mark‐Ups Approximate Area of Work Prepared by: CCM Construction Services, LLC (214‐556‐4510) Page 8 of 10 Qty 480 1,215 484 1,173 1 1 1,173 3 1 1 1,173 UM SF SF SF SF EA EA SF EA EA EA SF Unit Cost $5.00 $2.00 $5.00 $0.50 $500.00 $400.00 $0.75 $275.00 $450.00 $600.00 $0.50 50.0% 484 SF Cost/SF Extended $2,400 $2,430 $2,420 $587 $500 $400 $880 $825 $450 $600 $587 $12,078 $6,039 $18,117 $37.43 7/23/2012 Existing Conditions Photos and Drawings – A FIRST FLOOR PLAN SECOND FLOOR PLAN