IAQ Check List

advertisement
IAQ Check List
Building: Sarah Adams Elementary School
Date: February 1, 2012
IAQ Check List
Building Inspection Performed by: Lyle Erstad/Deny Armashov
Report Compiled by: Lyle Erstad
Check List
True False
N/A
1. Ground Level Indoor Inspection
a. Univents are on and air discharge grills are free of obstructions.
If false, send email to building principal and facilities director asking staff to be instructed to keep vents
clear at all times. Record locations here:
2. Ground Level Outdoor Inspection (weather permitting)
a. Univent air intakes are free of obstructions.
If false, record locations here:
b. Filters
i. Medium efficiency filters are installed in all univents.
If false, list locations and create work orders to initiate corrective action.
ii. High efficiency filters are installed in the air handling units.
If false, list locations and create work orders to initiate correction action.
iii. Filters are being changed every six months and the installed date is written on the outer filter casing.
If filter is older than 6 months, list locations and create work orders to initiate corrective action.
c. Insects, bird nests, or droppings are not evident near outdoor air intakes.
If false, indicate locations here:
d. Trash dumpsters are located away from doors, windows, and outdoor air intakes.
e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial
plants, exhaust from nearby buildings)
f. Trucks and buses are not allowed to keep their engines idling near the building.
Page 1 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
IAQ Check List
Building: Sarah Adams Elementary School
Date: February 1, 2012
Building Inspection Performed by: Lyle Erstad/Deny Armashov
Report Compiled by: Lyle Erstad
Check List
True False
g. No evidence of drainage problems exist. Water drains away from the building including roof
downspouts.
We have been monitoring doors, 6, 7 and 8 as a result of the work that was done this past summer.
It seems that water is being diverted and no longer coming into the building under these doors.
h. Sprinklers do not spray directly toward the building or into outdoor air intakes.
i.
Grass clippings from mowers are directed away from the building air intakes.
j.
Clean walk-off mats are present at exterior entrances.
N/A
3. Roof (Inspections conducted weather permitting)
a. Roofing consultant has not found any issues requiring immediate repair.
Most recent roofing inspection date/company: 5-year roofing plan completed 5/25/2010 with C. E.
Crowley & Associates.
b. There is no evidence of water ponding on the roof.
c. Intake ventilation units are operating properly and free of debris.
d. All exhaust fans are operating properly and free of debris.
e. Air intake dampers are set to allow air flow even at minimum setting.
f. Insects, birds, animal nests or droppings are not evident near outdoor air intakes.
g. Plumbing stacks and exhaust vents are located away from air intakes.
4. Attic
a. There is no evidence of roof or plumbing leaks.
No Attic
Page 2 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
Building: Sarah Adams Elementary School
Date: February 1, 2012
IAQ Check List
Building Inspection Performed by: Lyle Erstad/Deny Armashov
Report Compiled by: Lyle Erstad
Check List
True False
N/A
b. There is no evidence in attic of insects, birds, animals, or nests.
No Attic
5. General Considerations
a. Classrooms, offices and/or common areas appear recently cleaned.
If examples of poor housekeeping are found, record locations below:
b. Only vacuums with HEPA filters are being used.
c. All supply and exhaust ventilation units are working properly.
d. Occupied space temperatures and relative humidity levels are within the standards listed below.
i. Temperature range:
Winter temperatures 70-73 degrees.
Summer temperatures 74-80 in air-conditioned spaces and 74-85 in non-air-conditioned
spaces.
Outdoor air temperature: 55; 37.9 degrees.
Highest temperature – Location: 2 B; 2A; Reading of 75.3; 70.6 degrees.
Lowest temperature – Location: 110; 22; Reading of 69.9; 69.2 degrees.
ii. Relative humidity range is 30% to 60%.
Non-air-conditioned spaces may be higher on rainy or humid summer humid days.
All spaces may be less than 30% when the out-door air temperature is less than 32 degrees.
Outdoor relative humidity: 54.4; 59.6%
Highest relative humidity – Location: 110; 22; Reading of 40.2; 33.3%
Lowest relative humidity – Location: Principal's Office; 2A;Reading of 28.3; 29.3%
Page 3 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
IAQ Check List
Building: Sarah Adams Elementary School
Date: February 1, 2012
Building Inspection Performed by: Lyle Erstad/Deny Armashov
Report Compiled by: Lyle Erstad
Check List
True False
Readings not within acceptable standards will result in the creation of a work order, requesting
maintenance to address. (Readings are noted on the attached test data sheet)
N/A
e. Occupied space readings of carbon monoxide (CO) levels are less than 9.0 PPM.
Outdoor Air CO Reading: .1; .1
Highest CO Location: 110; 22 Reading: .6; .7
Lowest CO Location: Several rooms; 21, 2A
Reading: 0.0; .1
If the CO level is greater than 9.0 PPM in any space as measured with a handheld device or “leave-in”
monitor, the space must be cleared of all occupants and steps taken to correct the problem. The issue
will be immediately addressed by maintenance and the Fire Department. (Readings are noted on the
attached test data sheet)
f. CO2 levels in any occupied space are below threshold limits.
i. Perform CO2 check with Gray Wolf or other portable device. Measure four times yearly or more
often if needed. Measure only in fully occupied rooms. Reading should be less than 700 PPM plus
outside air CO2 PPM.
700 PPM + 358; 350 PPM = 1058; 1050 PPM
Assume outside CO2 is 350 if temperature is below 41 degrees and air is not stagnant with no- wind.
Record all occupied space CO2 levels on forms provided. Provide the outdoor CO2 level as well as
the high and low CO2 extremes below:
Outdoor reading: 358; 353 PPM
Highest CO2 reading – Location: 25; 21; Reading of 1026; 771 PPM
Lowest CO2 reading – Location: 15; 2A; Reading of 467; 641 PPM
ii. If reading is above threshold, check univent and air handling dampers to ensure a value is set to
provide at least 15 cfm of fresh air intake per student based on average space occupancies. If
Page 4 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
IAQ Check List
Building: Sarah Adams Elementary School
Date: February 1, 2012
Building Inspection Performed by: Lyle Erstad/Deny Armashov
Report Compiled by: Lyle Erstad
Check List
True False
reading is consistently elevated, then use data logging to monitor CO2 concentrations over time and
look for other sources of problems.
N/A
iii. CO2 levels were checked three months ago.
g.
h.
i.
j.
iv. CO2 levels on “leave-in” devices, where present, where checked.
No leave-in devices
Offensive odors are not apparent.
If false, list problem areas:
Water damage is not evident.
Check for roof leaks, pipe leaks, spills, stained ceiling tiles, etc, visually and with moisture meter. Look
for the source of any water leaks and schedule repairs. Discard porous items such as ceiling tiles if wet
for more than 24 hours. For carpeting, if less than 9 square feet of wet area, shampoo with germicide
and fan dry. For areas greater than 9 square feet, replace carpet with tile in reasonable timeframe. If
carpet is over ACM tile, replace during next unoccupied break time (winter break, spring break,
summer).
If false, record findings and locations here: Stained ceiling tile were found in the Library near a unit
ventilator. Work orders were written to check the unit and address the stained ceiling tile. Though
it was dry, it was diagnosed as a condensate leak from earlier last year. No insulation was
disturbed.
Mold or mildew growth is not evident.
If false, record findings and locations here:
All pest management issues are being handled by Integrated Pest Management.
k. No other unresolved concerns or complaints by building personnel are known.
If false, list any pending issues not previously mentioned in this report here: We are trying to resolve
a mouse problem in some locations. We handle our pest and rodent control using Orkin but
we are now in process of trying to make sure that all possible means for a mouse to enter the
building are corrected.
Page 5 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
IAQ Check List
Building: Sarah Adams Elementary School
Date: February 1, 2012
Building Inspection Performed by: Lyle Erstad/Deny Armashov
Report Compiled by: Lyle Erstad
Check List
True False
l. There are no incomplete HVAC preventative maintenance (PM) work requests.
If false, list any incomplete HVAC work request here:
6. Bathrooms and General Plumbing
a. All locker or restroom exhaust fans are working.
Inoperable or malfunctioning fans are listed as follows:
Location:
Problem:
N/A
b. All of the following drain-trap maintenance procedures are being conducted according to the frequency
indicated.
If false, indicate all deviations and locations: The Custodial staff is reminded regularly on these
procedures.
i. Water is poured into floor drains once per week (approximately 1 quart of water) or water and a
teaspoon of cooking oil poured into the drain once a month.
ii. Water is poured into sinks at least once per week (about 2 cups of water).
iii. Toilets are flushed at least once per week.
7. Lab Chemicals & Maintenance Supplies
a. Lab chemicals are used with exhaust fans turned on.
b. Lab chemical storage areas have been inspected yearly by ROE and Fire Department.
Record last inspection dates below:
ROE: 11/2011
LZFD: 11/2011
c. Flammables are not stored with igniters.
Page 6 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
IAQ Check List
Building: Sarah Adams Elementary School
Date: February 1, 2012
Building Inspection Performed by: Lyle Erstad/Deny Armashov
Report Compiled by: Lyle Erstad
Check List
True False
d. All chemicals that may react or produce toxic or explosive by-products are separated and maintained in
approved containers stored in approved storage. (e.g. lockable, with appropriate ventilation).
N/A
e. Chemical disposal records for all lab chemicals are available for review.
f. All cleaning products used in building contain no/low VOC.
List any exceptions:
g. Increased ventilation is considered when installing new carpets, cleaning upholstered furniture,
shampooing carpets, etc.
h. Exhaust ventilation systems in chemical and trash storage areas are turned on and functioning properly.
i.
Portable fuel containers are properly closed.
j.
Power equipment, like snow blowers and lawn mowers, have been serviced and maintained according to
manufacturers’ guidelines.
k. Oil based paints are stored in approved storage cabinets.
No oil based paint allowed in District.
l. Green Cleaning products and processes are used in this building.
8.
Combustion Appliances
a. Combustion analysis is performed at the start of the heating season on all boilers. Adjustments are
made to the burners to correct any abnormalities and improve efficiency.
b. In rooms that contain combustion appliances, there is no evidence of combustion gas or fuel odors.
If false, record locations here:
Page 7 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
Building: Sarah Adams Elementary School
Date: February 1, 2012
IAQ Check List
Building Inspection Performed by: Lyle Erstad/Deny Armashov
Report Compiled by: Lyle Erstad
Check List
True False
c. No leaks, disconnections, and/or deterioration were found on exhaust hoods.
N/A
d. Flue components are clean and free of soot.
e. All combustion appliances have flues or exhaust hoods and vent NO2.
i. If false, inspect cooking hoods, chemical hoods. Assure that cooking stoves and appliances are
correctly installed, used, and maintained according to manufacturers’ specifications.
ii. If not vented, ensure that “leave-in” CO monitors are placed in room. Record locations here: NONE
iii. CO levels in rooms with combustion appliances are measured and recorded with an IAQ monitor. CO
readings outside of normal CO range will result in an immediate response by maintenance to reduce
CO level or vacating the room/building, if necessary.
Record locations here:
9. Other
a. Paint
No peeling and/or flaking paint found.
If planned building renovation will damage paint or if peeling paint is discovered, lead testing may be
necessary. If peeling paint is found, send email to the building Principal and the Facilities Director
alerting them of the problem. Staff and teachers need to pick up any flakes of paint to prevent
children from being exposed. The Facilities Director will advise the Facilities Coordinator (a Certified
Lead Paint Renovator) to test the paint for lead. Lead paint was discontinued in 1978. Buildings built
after 1978 are exempt from lead paint testing.
If lead is present, required repairs should be done immediately using lead-safe methods and, if
necessary, a licensed lead contractor.
Location(s) of known peeling paint in building:
b. The following preventive measures are being taken to reduce lead exposure.
i. Play areas and toys are cleaned nightly.
Page 8 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
Building: Sarah Adams Elementary School
Date: February 1, 2012
ii.
IAQ Check List
Building Inspection Performed by: Lyle Erstad/Deny Armashov
Report Compiled by: Lyle Erstad
Check List
True False
N/A
Floors are mopped nightly.
iii. Dust at least weekly.
c. Radon testing is recommended by IEMA every 5 years. Last testing date listed below:
Date: 12/16 - 19/ 2011; Reading of (Highest) 2.8 pCi/L was recorded in Room 31.
National concern level is 4.0 pCi/L or higher.
d. The IAQ testing equipment used for this inspection was calibrated and is in good working order.
Equipment Used: Gray Wolf
Last date of calibration: 1/20/2012
Page 9 of 9
Revised 3/7/2011 AMJ
Created 11/2010
555 Old Mill Grove Road. Indoor Air Quality Testing Readings Winter 2012
Site
Location
Date/Time
Temperature °F
Relative Humidity
%RH
Carbon
Monoxide ppm
Carbon
Dioxide ppm
Sarah Adam Elementary
Outdoor Air
31-Jan-12 11:17:34 AM
55.0
54.4
0.1
358
Sarah Adam Elementary
110
31-Jan-12 11:23:17 AM
69.9
40.2
0.6
558
7
Sarah Adam Elementary
12
31-Jan-12 12:19:01 PM
73.3
38.0
0.1
903
26
Sarah Adam Elementary
13
31-Jan-12 11:38:52 AM
71.8
34.4
0.2
678
5
Sarah Adam Elementary
14
31-Jan-12 12:23:12 PM
72.7
36.4
0.2
1017
20
Sarah Adam Elementary
15
31-Jan-12 12:30:12 PM
70.2
34.1
0.0
467
4
Sarah Adam Elementary
16
31-Jan-12 12:21:49 PM
72.4
36.2
0.4
747
25
Sarah Adam Elementary
17
31-Jan-12 12:51:05 PM
74.6
34.0
0.0
568
7
Sarah Adam Elementary
18
31-Jan-12 11:41:22 AM
71.6
36.4
0.1
650
17
Sarah Adam Elementary
19
31-Jan-12 11:42:32 AM
72.5
35.7
0.1
725
11
Sarah Adam Elementary
1A
31-Jan-12 11:28:31 AM
71.8
36.7
0.4
691
3
Sarah Adam Elementary
1B
31-Jan-12 11:29:24 AM
71.5
35.8
0.3
682
3
Sarah Adam Elementary
20
31-Jan-12 11:43:34 AM
72.0
36.7
0.0
745
16
Sarah Adam Elementary
23
31-Jan-12 11:45:12 AM
73.5
35.0
0.0
729
7
Sarah Adam Elementary
24
31-Jan-12 11:46:17 AM
73.1
37.1
0.2
775
21
Sarah Adam Elementary
25
31-Jan-12 11:47:30 AM
74.0
36.4
0.1
1026
20
Sarah Adam Elementary
25 A
31-Jan-12 12:45:12 PM
73.8
33.3
0.3
981
1
Sarah Adam Elementary
26
31-Jan-12 11:49:20 AM
73.2
35.4
0.3
814
10
Sarah Adam Elementary
27
31-Jan-12 11:57:29 AM
73.9
38.1
0.3
1011
28
Sarah Adam Elementary
28
31-Jan-12 11:52:22 AM
72.1
36.1
0.4
694
20
Sarah Adam Elementary
29
31-Jan-12 11:50:38 AM
73.4
36.2
0.0
786
11
Sarah Adam Elementary
2B
31-Jan-12 12:09:03 PM
75.3
32.1
0.1
735
2
Sarah Adam Elementary
2C
31-Jan-12 12:10:18 PM
75.1
31.5
0.2
666
2
Sarah Adam Elementary
3
31-Jan-12 12:11:45 PM
74.6
34.9
0.3
872
23
Sarah Adam Elementary
4
31-Jan-12 11:31:38 AM
72.4
36.5
0.0
620
8
Sarah Adam Elementary
5
31-Jan-12 12:13:10 PM
74.0
32.7
0.3
595
16
Sarah Adam Elementary
6
31-Jan-12 01:08:58 PM
73.0
32.9
0.3
521
15
Sarah Adam Elementary
7
31-Jan-12 12:15:00 PM
73.4
33.3
0.0
648
21
Sarah Adam Elementary
8
31-Jan-12 12:16:39 PM
72.8
34.5
0.2
842
25
Sarah Adam Elementary
Cafeteria
31-Jan-12 11:35:02 AM
72.8
35.7
0.3
634
75
Sarah Adam Elementary
Conference rooms
31-Jan-12 12:36:36 PM
72.1
28.5
0.2
644
2
Sarah Adam Elementary
Gymnasium
31-Jan-12 12:33:46 PM
70.8
35.5
0.3
485
24
Sarah Adam Elementary
Main office
31-Jan-12 12:01:57 PM
74.2
30.1
0.1
685
3
Sarah Adam Elementary
Nurse office
31-Jan-12 12:04:46 PM
74.1
29.0
0.2
646
2
Sarah Adam Elementary
10
31-Jan-12 11:36:46 AM
72.7
37.3
0.2
1023
28
Sarah Adam Elementary
Principal office
31-Jan-12 12:38:24 PM
72.2
28.3
0.3
637
1
Sarah Adam Elementary
Staff lounge
31-Jan-12 12:03:11 PM
73.9
30.4
0.2
696
9
CO2 Formula 358 + 700 = 1058
Occupants
Taken by
Taken With
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Open
Window
Yes
Yes
Site
Location
Date/Time
Temperature °F
Relative Humidity
%RH
Carbon
Monoxide ppm
Carbon
Dioxide ppm
Sarah Adam Elementary
Outdoor Air
02-Feb-12 10:31:08 AM
37.9
59.6
0.1
353
Sarah Adam Elementary
22
02-Feb-12 10:44:24 AM
69.2
33.3
0.7
664
Sarah Adam Elementary
2A
02-Feb-12 10:52:13 AM
70.6
29.3
0.1
641
2
Sarah Adam Elementary
21
02-Feb-12 10:48:31 AM
70.3
31.5
0.1
771
24
CO2 Formula 350 + 700 = 1053
Occupants
2
Taken by
Taken With
Denys
Denys
Denys
Denys
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Open
Window
Download