EMERGENCY PLAN ROCKEFELLER & MEDICAL SCHOOL BUILDINGS UNIVERSITY COLLEGE LONDON

advertisement
Bldg Name: Rockefeller & Medical School (201 & 374)
UCL ESTATES
Fire Safety
UNIVERSITY COLLEGE LONDON
EMERGENCY PLAN
Regulatory Reform (Fire Safety) Order 2005
Name & Address of
Building:
Occupying
Department(s) /
School(s) / Institute(s):
ROCKEFELLER & MEDICAL
SCHOOL BUILDINGS
University College London
21 University Street, London WC1E 6DE
74 Huntley Street, London WC1E 6AU
Faculties of Life Sciences & Biomedicine
PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:
LOCAL FIRE
INFORMATION
Local fire information is provided by UCL Fire Action
Notices (and in some buildings, by supplementary
instructions) that are provided throughout the premises
at Fire Alarm Manual Call Points & Fire Equipment
Points.
RELEVANT
INFORMATION
The Rockefeller & Medical School Buildings forms part of three
interconnecting 6-storey buildings that all sit over a substantial
Basement Boiler House. The Rockefeller and Medical School
buildings date from 1907 where they formed the UCL Hospital
Nurses Home, Matron’s House and the Medical School complex.
All three premises have basement; ground, first to sixth floors with
various roof plant facilities, as well as interlinking tunnels to
adjoining premises - they are treated as a single premise for fire
alarm purposes. The Rockefeller Boiler House is situated below
all three buildings and is separate for fire alarm purposes, but with
specific arrangements for fire evacuation and warning to the
buildings above. The Rockefeller Building has a complex layout
over various levels with numerous internal stairs and convoluted
escape routes with access to the adjoining Medical School,
Rockefeller Boiler House and Cruciform & Medical Sciences
Buildings (via under road tunnels). The Medical School Building
has a simpler layout with access to the adjoining Paul O’Gorman
and Cruciform Buildings (via under road tunnels).
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 1 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
Bldg Name: Rockefeller & Medical School (201 & 374)
PART TWO - SITE OR BUILDING SPECIFIC EVACUATION INSTRUCTIONS:
ITEMS
ROCKEFELLER - SPECIFIC INFORMATION OF INSTRUCTION
1.0. ROCKEFELLER ROOF AREAS - ALTERNATIVE ESCAPE
(a). Sixth Floor Postgraduate Write Up Areas & Roof Plant Rooms - escape
for 6th floor write up area is via internal stair (Stair D).
ROOF
(b). Alternative Escape - via walkway across the roof and access to the top of
the main stair (Stair A) is available down metal steps (Stair A1) to 5th floor.
2.0. ROCKEFELLER UPPER (FIRST TO FIFTH) FLOORS - ALTERNATIVE
ESCAPE
(a). Upper Floors - each floor has alternative escape via internal & external stair
enclosures (Stairs A, B & C), which descend directly to safety at ground level.
(b). Internal Stair South (Stair D) - 6th, 5th, 4th, 3rd & 2nd floors (South) have
alternative exit by using internal south stair (Stair D). The south stair discharges
at the second floor onto an external walkway & steps (Stair E1) that crosses a
light well to a further external walkway at first floor level on the north side, this
walkway leads into the goods lift lobby off the main stair (Stair A) - see Para 4.
UPPER
FLOORS
(c). Second Floor old Café Area & First Floor Path Lab off Main Stair (Stair
A) - have alternative route via internal stair (southwest Stair E) to external
walkway that leads into goods lift lobby off the main stair (Stair A) - see Para 4.
(d). First Floor Alternative Escape Goods lift Lobby (off Stair A) - if main stair
(Stair A) is unavailable for escape due to smoke or fire then escape from the 1st
Floor Goods Lift Lobby (for occupants using south & southwest stairs - Stairs D
& E/E1) is then via Clinical Skills Area (Note: access door releases on fire alarm
activation). On entering Clinical Skills corridor, follow signs to fire exit leading on
to External Stairs (Stair F), which discharges into the passageway between
Rockefeller & Gower Street Residences and follow the route into Chenies Mews.
3.0. ROCKEFELLER GROUND FLOOR - ALTERNATIVE ESCAPE
(a). Ground Floor Grant Museum (Thomas Lewis Rm) - has an alternative
exits discharging directly onto Gower Street; and, at the base of external
southeast stair (Stair C) to the rear passageway from Rockefeller Bldg leading to
Chenies Mews.
GROUND
FLOOR
(b). Ground Floor Secondary Stair (Stair B) - has exit on the half landing down
leading into the passageway between Rockefeller & Gower Street Residences;
follow the route into Chenies Mews.
(c). Ground Floor Main Entrance (Stair A) - the exit off the main stair leading
into rear light well and cycle park is not a designated fire escape although there
is access to Chenies Mews. The fire exit is via the Main Entrance discharging
onto University Street.
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 2 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
Bldg Name: Rockefeller & Medical School (201 & 374)
2.0.
Site or Building Specific Instructions or Other Relevant Information (Cont):
ROCKEFELLER - SPECIFIC INFORMATION OF INSTRUCTION
ITEMS
4.0. ROCKEFELLER BASEMENT - ALTERNATIVE ESCAPE
Note: With the exception of the tunnel under Gower Street, leading to the Anatomy Building there
is NO DESIGNATED ESCAPE via internal interlinking tunnels from Rockefeller / med school
basement level.
(a). Rooms B23, B24, B25, B26, B27 & B28A - short ‘Dead End’ corridor and
the link tunnel between medical school & Rockefeller bldg discharges into the
base of the main stair (Stair A) and up to ground floor main entrance.
Alternative escape through corridor secondary stair (Stair B) & up to half
landing & out to passageway to Chenies Mews.
(b). Lab B09 & B10 (Old Squash Courts) - escape from Laboratory (B09) via
main entrance into secondary stair (Stair B) and up to a half landing exit to
Chenies Mews, alternately east exit discharges into the link tunnel under Gower
Street and to Anatomy Bldg. In addition,
•
Lab B10 Area - alternative (limited) escape is available via link corridor
through into Stair B which discharges into rear passageway leading to
Chenies Mews
•
Office BM09A - alternative escape is available via Window Escape, which
discharges into a lightwell that leads into front lightwell of Gower Street
Residences stairs then take occupants up to Gower Street.
BASEMENT
(c). Secondary Stair (Stair B) - Fire escape from Rockefeller boiler house and
a number of other rooms off secondary stair (Stair B) have escape via half
landing into passageway leading into Chenies Mews.
(d). Anatomy Lab - has separate escape via lower corridor to Stair A or Stair
B and a rear fire exit via Stair J to Chenies Mews.
5.0.
FIRE ASSEMBLY POINTS
• Rockefeller Building - Corner of University Street &
Huntley Street,
• Medical School - University Street (In Front of
Rayne Institute),
ASSEMBLY
POINT
•
Paul O’Gorman Building - Corner of Shropshire
Place & Capper Street,
•
Rockefeller Boiler House - Chenies Mews,
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 3 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
Bldg Name: Rockefeller & Medical School (201 & 374)
2.0.
Site or Building Specific Instructions or Other Relevant Information (Cont):
ITEMS
MEDICAL SCHOOL - SPECIFIC INFORMATION OF INSTRUCTION
6.0. MED SCHOOL ROOF AREA
(a). Seventh Floor Roof Plant Room - single escape condition from 7th floor roof
area via protected internal stair (Stair Q).
ROOF
(b). Internal Stair (Stair Q) - provides access/egress between 5th, 6th and Roof
Access, at the 5th floor there is a choice routes available between medical school
main stair (Stair R) or along corridor to Rockefeller main stair (Stair A), both
stairs discharge at ground floor level main entrances.
7.0. MED SCHOOL SIXTH FLOORS - ESCAPE ROUTES
Note: 6th Floor is the ONLY floor in the Medical School Bldg that is provided with alternative
escape route into the Paul O’Gorman (POG) Building due to the top of the main stair lift shaft
discharging into 6th floor corridor. Therefore, all rooms have an alternative escape route via Internal
Stair (Stair Q) or POG main stair (Stair S).
(a). Sixth Floor (Room 633) - escape is via internal stair (Stair Q) down to 5th
floor where there is a choice of routes available between medical school main
stair (Stair R) or along corridor to Rockefeller main stair (Stair A), both stairs
discharge at ground floor level main entrances.
SIXTH
FLOOR
(b). Sixth Floor (Rooms 634 - 642) - access & egress is via internal stair (Stair
Q) down to 5th floor where there is a choice routes available between medical
school main stair (Stair R) or along corridor to Rockefeller main stair (Stair A),
both stairs discharge at Ground Floor Level Main Entrances. An alternative fire
escape route is available via corridor to Paul O’Gorman main stair (Stair S) that
discharges at ground floor level main entrance.
8.0. MED SCHOOL UPPER (FIRST TO FIFTH) FLOORS - ESCAPE ROUTES
Note: The medical school bldg fire strategy DOES NOT (except for the 6th Floor) provided for an
alternative escape route through into the Paul O’Gorman (POG) Building.
(a). First to Fifth Floors South Corridor Off Medical School Main Stair (Stair
R) - single escape condition from all floors via protected main stair (Stair R),
which discharges at ground floor level med school main entrance.
(b). 3rd to 5th Floors (Main) - access & egress is via med school main stair (Stair
R). Alternative escape routes available between main stair (Stair R) or along
corridor to Rockefeller main stair (Stair A), both stairs discharge at ground floor
level main entrances.
UPPER
FLOORS
(c). 3rd Floor (Main) - access & egress is via Rockefeller main stair (Stair A) with
an alternative escape route available via med school main stair (Stair R), both
stairs discharge at ground floor level main entrances.
(d). 3rd & 4th Floor (Main) - stub corridor (off main corridors) which is served by
internal accommodation stair (Stair N), has alternative escape routes from stub
corridors via Rockefeller main stair (Stair A) or med school main stair (Stair R),
both stairs discharge at ground floor level main entrances.
(e). 1st to 2nd Floors (Main) - access & egress is via med school main stair (Stair
R). Alternative escape route is via internal stair (Stair P) that descends to the
ground floor level, either via medical school main entrance or along corridor to
Rockefeller main entrance.
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 4 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
Bldg Name: Rockefeller & Medical School (201 & 374)
2.0.
Site or Building Specific Instructions or Other Relevant Information (Cont):
ITEMS
MEDICAL SCHOOL - SPECIFIC INFORMATION OF INSTRUCTION
9.0. MED SCHOOL GROUND FLOOR - ALTERNATIVE ESCAPE
Note: The medical school bldg fire strategy DOES NOT (except for the 6th Floor) provided for
an alternative escape route through into the Paul O’Gorman (POG) Building.
(a). South Corridor Off Medical School Main Stair (Stair R) - single escape
condition from ground floor via protected main staircase (Stair R), and the
directly out of med school main entrance to Huntley Street.
GROUND
FLOOR
(b). Ground Floor Corridors (Main) - access & egress is via either med school
or Rockefeller main entrances. Internal stair (Stair P) discharges from 1st, 2nd &
basement level at ground floor where escape is either via medical school main
entrance or along corridor to Rockefeller main entrance.
10.0. MED SCHOOL BASEMENT - ALTERNATIVE ESCAPE
Note 1: The Medical School Bldg Fire Strategy DOES NOT (except for the 6th Floor) provided
for an alternative escape route through into the Paul O’Gorman (POG) Building.
Note 2: There is NO ESCAPE via Internal Interlinking Tunnels from Med School Basement Level.
(a). South Corridor Off Medical School Main Stair (Stair R) - single escape
condition from basement via ascending main staircase (Stair R) to ground floor
level and leaving via med school main entrance to Huntley street.
BASEMENT
(b). Basement Corridor (Main) - single escape condition from basement via
ascending main staircase (Stair R) to ground floor level and leaving via med
school main entrance to Huntley Street.
(c). Basement Area (Base of Internal Stair (Stair P) - single escape condition
from basement rooms (B31 & 36 and B33, B34, B37 & B38) via ascending
internal staircase (Stair P) to ground floor level, where escape is either via the
medical school main entrance or along corridor to the Rockefeller main
entrance.
11.0. MED SCHOOL FIRE SAFETY MANAGEMENT INTERNAL STAIR Q
(a). Fifth, Sixth Floors & Roof Access (Stair Q) - internal stair (Stair Q) 5th, 6th
& 7th (roof) floor levels provides the only escape route for occupants of Room
633 and personnel having access to the roof. It is Mandatory under the
building’s fire strategy that this stair enclosure (Stair Q) particularly at the 5th
floor level remains free of any storage or combustible materials and
occupying departments manage this space particularly carefully.
MANDATORY
MANAGEMENT
OF STAIR
ENCLOSURES
(b). Main Entrance Office / Reception (Room G44) Ground Floor occupying department must manage this space particularly carefully due to
room opening onto main stair enclosure (Stair R). The door must be kept shut
when not occupied and that the fire loading is strictly controlled with minimum
storage & use of combustible materials.
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 5 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
Bldg Name: Rockefeller & Medical School (201 & 374)
PART THREE - DISABILITY PROVISIONS RELATING TO CENTRALLY TIMETABLED
SPACE:
Centrally Timetabled Lecture Theatres & Seminar Rooms - Disable
(Wheelchair) Emergency Egress Facilities / Arrangements
Lecture Theatre /
Seminar Room
Locations
Accessible
/ Egress
Rockefeller
Seminar Rm 333
(3rd Floor)
None1
Not Designated as Wheelchair Accessible
Rockefeller
Seminar Rm 335
(3rd Floor)
None
Not Designated as Wheelchair Accessible
Rockefeller
Seminar Rm 336
(3rd Floor)
None
Not Designated as Wheelchair Accessible
Rockefeller (David
Sacks) Seminar
Rm 337 (3rd Floor)
None
Not Designated as Wheelchair Accessible
Rockefeller
Seminar Rm 338
(3rd Floor)
None
Not Designated as Wheelchair Accessible
Rockefeller
Seminar Rm 339
(3rd Floor)
None
Not Designated as Wheelchair Accessible
Rockefeller
Seminar Rooms
B14 / B14 / B15 /
B16
Basement
1
Accessible2
Evacuation Arrangements
(See Attached Evacuation Plans for Individual Rooms)
Access via the Grant Museum entrance (nr corner of University &
Gower Street) along ground floor corridor to main entrance lift lobby,
take lift to basement turn right and rooms on the right along the
corridor - assistance may be required with some doors.
Emergency Egress - turn right into corridor, travel through stair
enclosure, and continue down ramp into tunnel under Gower Street
and into Medical Sciences building, where chair lift can take persons
into South Quadrangle. Assistance will be required with the doors.
None - No Disabled Access or Egress available,
Accessible - Access and Egress available without general assistance as generally facility where practical to self-escape,
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 6 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
2
Bldg Name: Rockefeller & Medical School (201 & 374)
Part Three - Disability Provisions Relating to Centrally Timetabled Space (Cont):
Centrally Timetabled Lecture Theatres & Seminar Rooms - Disable
(Wheelchair) Emergency Egress Facilities / Arrangements
Lecture Theatre /
Seminar Room
Locations
Accessible
/ Egress
Rockefeller
Seminar / Meeting
Rm G02
(Ground Floor )
None
Rockefeller
Seminar Room
G16
Accessible
Evacuation Arrangements
(See Attached Evacuation Plans for Individual Rooms)
Not Designated as Wheelchair Accessible
Access via the Grant Museum entrance (nr corner of University &
Gower Street) along ground floor corridor turn left into the Room 16 assistance may be required with some doors.
Ground Floor
Emergency Egress - turn right into corridor and travel to Grant
Museum exit onto University Street. Assistance will be required with
the doors.
Rockefeller
Computer Cluster
Room
Access via the Grant Museum entrance (nr corner of University &
Gower Street) along ground floor corridor turn right into the Room 11
- assistance may be required with some doors.
G11
Ground Floor
Accessible
Emergency Egress - turn left into corridor and travel to Grant
Museum exit onto University Street. Assistance will be required with
the doors.
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 7 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
Bldg Name: Rockefeller & Medical School (201 & 374)
PART FOUR - DISABILITY PROVISIONS RELATING TO EMERGENCY DISABLED
EVACUATION (CONT):
ITEMS
DISABLED PROVISION WITHIN THE BUILDING
DISABLED SIGNAGE:
Fire safety and directional signage
provided within the premises:
YES * Remarks:
Disabled Facilities provided
DISABLED EVACUATION LIFTS:
Complying with BS 5588 Part 8 are
provided in this building:
NO * Remarks:
No Disabled Facilities at present
DEAF PEOPLE FIRE ALARM
ALERTING FACILITIES:
Vibrating Pager equipment has been
provided and is connected to the fire
alarm system:
YES * Remarks:
Deaf Aid Transmitter is fitted Pagers available from Customer
Service Desk at rear (LGF) of 26
Gordon Sq
VISUAL SIGNALS - equipment,
tactile signage, colour coding or
other faculties have been provided
as part of the fire evacuation
strategy for this building:
YES * Remarks:
Some facilities provided
DISABLED REFUGE
COMMUNICATIONS FACILITIES:
Communication facilities for
Disabled Refuges / Safe Havens
have Telephone (BT Big Button /
Communications system complying
BS 5839 Part 9) in the premises:
YES * Remarks:
Rockefeller Main Stair (Stair A)
and in the Paul O’Gorman
building
DISABLED REFUGE FACILITIES:
Generally, only provided on
individual Risk Assessment or as
part of a PEEP initiated by the
Department
YES * Remarks:
Rockefeller Main Stair (Stair A)
and in the Paul O’Gorman
building
Location:
Where refuges are provided,
they should be enclosed in a fireresisting structure, which creates
a protected escape route leading
directly to a place of safety and
should only be used in
conjunction with effective
management rescue
arrangements.
Some Disabled Refuges provided in Rockefeller main stair
(Stair A) and in the Paul O’Gorman building but generally
horizontal evacuation provided on 1st to 6th floors between
Rockefeller / Medical School / Paul O’Gorman Buildings principal to move away from fire or hazard placing fire doors
between fire and yourself
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 8 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
Bldg Name: Rockefeller & Medical School (201 & 374)
PART FIVE - BACKGROUND INFORMATION & ARRANGEMENTS:
LOCAL FIRE
INFORMATION
Local fire information is provided by UCL Fire Action Notices (and in
some premises, by supplementary instructions) which are provided
throughout the premises at Fire Alarm Manual Call Points, Fire
Equipment Points and in sleeping accommodation rooms, as
appropriate.
ACTION ON
DISCOVERING
A FIRE
On discovery or being made aware of a fire, immediately raise the
alarm throughout the building by operating the nearest fire alarm
call point, or as per the premises fire action notices.
CALLING THE
FIRE BRIGADE
Dial Ext: 222 on a UCL Internal Extension and report the fire (if you
are unsure of your location use the Building Reference number to
assist in identifying the premises, which is shown on the UCL Fire
Action Notices).
This building’s fire alarm system is monitored on a 24-hour basis by
the UCL Security Control Room who will summon the Fire Brigade.
However, you should always make an Emergency Telephone call
(Ext: ‘222’) to raise the alarm.
ON HEARING
THE FIRE
ALARM
On hearing the fire alarm, immediately leave the building by the
nearest available fire exit (this may not necessarily be the way
you entered the building).
THE FIRE
ALARM
SYSTEM
(1). This building is equipped with a single stage addressable fire
alarm system. Which when activated, emits a continuous electronic
two-tone alarm throughout the building.
(2). Automatic Fire Detection (AFD) – smoke & heat detecting
devices are provided for early warning to Life 2 (L2) Standard.
(3). Fire alarm ‘Manual Call Points’ are found on routes leading from
the building (including corridors, landings, staircases & final exits).
EVACUATION
PROCEDURE
On hearing the alarm or being directed by a Fire Evacuation Marshal
(FEM), all occupants are to evacuate the building by the nearest
available escape stair, corridor or exit route to the Final Exit. If
your escape route is blocked or obstructed by fire or smoke, you
should turn your back on the fire and follow the alternative route from
the building by following the green safe condition fire safety
direction signage provided.
FIRE
ASSEMBLY
POINT
On leaving the building you should proceed to the Fire Assembly
Point; the location of the Fire Assembly Point(s) is indicated on the
local Fire Action Notices provided, which may also be supplemented
with additional information such as local escape route plans etc. Do
not obstruct the building entrances as this may hinder access to
the fire brigade crews & appliances. Beware of the road traffic and
your and others safety during the evacuation!
ELECTRONIC
SECURITY
DOOR
RELEASE
MECHANISMS
Where fitted doors forming part of the Means of Escape (MoE) may be
provided with Electromagnetic Security Locks (Cardex):
(1). Generally releasing on Activation of the Fire Alarm System, (but
there are some exceptions to this arrangement).
(2). Each door is provided with an independent ‘break glass’
emergency release device (green box) on the direction of escape
that should be broken to release the door in an emergency (or if the
fire alarm has not activate).
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 9 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
Bldg Name: Rockefeller & Medical School (201 & 374)
Part Five - Background Information & Arrangements (Continued):
PLAN OF THE
EMERGENCY
ROUTES
Fire safety drawings are provided with the Emergency Plan for the
building. These plans show the fire escape stairs, routes emergency
door furniture and final exits with copies available to the Fire Brigade
at the main entrance of the building (or through the UCL Fire Officer).
EMERGENCY &
ESCAPE
LIGHTING
Emergency escape lighting is provided in large &/or specific rooms,
all corridors and stair enclosures to illuminate safely the escape
routes from the premises in the event of a ‘Local Lighting Circuit’
failure (they do not illuminate on the fire alarm sounding). In
addition, illuminated directional escape signage may also be
provided.
FIRE FIGHTING
EQUIPMENT
Fire fighting equipment is strategically placed throughout the building
in accordance with the hazards identified. Only use fire-fighting
equipment if you have been specifically trained and it is safe for you
to do so; and you are confident that you are using the most
appropriate fire extinguisher on the correct type fire. Do not use
water on electrical or flammable liquid fires!
FIRE
EVACUATION
MARSHALS
(FEMS)
Due to the size and complexity of UCL, it is neither practical nor
feasible to maintain a meaningful register of building occupants to
account for those persons using premises during normal working
hours. It is UCL policy that all Heads of Departments shall
designate sufficient staff to act as Fire Evacuation Marshals
(FEMs), who in the event of a fire or incident will check their areas of
responsibility. FEMs will request politely but firmly that all staff,
students and visitors evacuate the building immediately by the
nearest available fire exit route, they may assist with Disabled
Persons and liaise with the Fire Brigade, as necessary.
SENIOR FIRE
EVACUATION
MARSHAL
(SFEM)
The Head of Department must appoint a suitable member of staff in
each building that the Department occupies, to become a Senior Fire
Evacuation Marshal (SFEM) to:
(1). liaise (if a multi-occupied building) with other SFEMs to ensure
assistance to the Fire Brigade, Duty Security and Estates staff during
normal working hours etc,
(2). co-ordinate the Departmental FEMs, or others such as the
Landlord’s agents and/or other occupiers as necessary,
(3). provide specialist information to the Fire Brigade and the Local
Authorities on any specific hazards related to the premises;
particularly, where there are laboratories or hazardous substances or
processes used etc,
(4). identify themselves to the Fire Brigade and other persons in
authority by wearing a Surcoat or by a coloured safety helmet (Red)
or some other distinguishing marker,
(5). be self-reliant when dealing with a fire incident at the premises.
Therefore, it is important that SFEMs meet the Fire Brigade on arrival
at the building entrance to ensure that they give all reasonable
assistance to the Senior Fire Brigade Officer in attendance.
HAZARDOUS
SUBSTANCES
Hazardous substances are used on the premises. Fire Brigade
Contingency Plans contain general information on the hazardous
materials that may be found on the premises.
UCL FEMs
SENIOR FEM
MEETING
THE FIRE
BRIGADE &
NOTIFYING
THEM OF
HAZARDS
WITHIN
BUILDING
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 10 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
Bldg Name: Rockefeller & Medical School (201 & 374)
Part Five - Background Information & Arrangements (Continued):
MEETING THE
FIRE BRIGADE &
HAZARD
INFORMATION
Normal Working Hours - the fire brigade will be met by the
Senior Fire Marshals / Department or local Security; Duty
Maintenance staff will generally attend.
Out of Hours - Security will meet and assist the Fire Brigade and
others, as required. Duty Maintenance staff will generally attend.
Fire Brigade Contingency Plans & Hazard Information - fire
brigade contingency plans & hazard information is provided in a
Red A4 Folder placed in the Fire Brigade Premises Box generally located close to the Master Fire Alarm Panel.
EMERGENCY
STOP OF
MACHINES /
PROCESSES /
HIGH RISK AREAS
Designate Staff or FEMs should ensure that where hazardous
processes are being used, they are shut down safely and quickly
before leaving the area. If this is not possible, a responsible
person must inform the Senior FEM or a Fire Brigade Officer
of the hazard and possible affect if left unattended etc
immediately on leaving the building!
FIRE EVACUATION
DRILLS
STAFF &
STUDENT
TRAINING
UCL Main Campus - an annual Fire Drill is carried out at
beginning of the Autumn Term (October) of each year by the UCL
Fire Officer.
Note: Unwanted alarm activations are treated as supplementary fire drills
throughout the year.
INDUCTION
FAMILIARISATION
(STAFF, VISITORS
& CONTRACTORS)
The Heads of Departments must have arrangements in place
so that all Temporary & Permanent Staff, Postgraduate Research
Students and others working for more than 3 days in the
Department,
receive
Local
Fire
Safety
Induction
familiarisation and an approved training record raised and
kept.
TRAINING
(STUDENTS)
The Heads of Departments shall provide at the start of each
academic session, fire safety information for all undergraduates
/ postgraduates studying in their Department.
PERIODICAL
(STAFF)
FAMILIARISATION
The Regulatory Reform (Fire Safety) Order requires that all
temporary and permanent staff receive local fire safety
familiarisation of the building(s) that staff, work or visit periodically
or when there has been a change of work activities or working
environment for employees, postgraduate students or visitors;
and that a record is kept.
PERIODICAL
STAFF
FAMILIARISATION
Based of the Building Layout, Evacuation Procedures and Risk
Based Approach the frequency for under taking Staff Fire
Evacuation familiarisation in this building is:
ANNUALLY
LOCAL DISABLED
EVACUATION
NOTES
(1). Your Department’s Local Management Arrangements &
Fire Evacuation Strategy for Disabled Persons should not rely
on the fire & rescue service, rescuing people waiting in a
refuge.
(2). Managers should review & use the Disable Information
Emergency Egress Assessment & personal Emergency
Evacuation
Plan
(PEEP)
available
from
www.ucl.ac.uk/fire/documents under ‘Disabled’ Heading.
End
_______________________________________________________________________________________________________________
Date Last Amended: Aug 11
EP: 11 of 11.
Issued by: Fire Officer, UCL Estates, Gower Street, London WC1E 6BT / fire.officer@ucl.ac.uk / Tel: 020 - 7679 - 1240
FIRE ESCAPE PLAN
Medical School
Room 333
Third Floor
Stair
A
Fire
Action
University Street
Room
333
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 374
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
You
are
here
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
Legend
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
University Street
In front of
Rayne Institute
Fire alarm call point
Huntley Street
Stair
R
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 37404005/110618
FIRE ESCAPE PLAN
Stair
A
You
are
here
Fire
Action
Medical School
Room 335
Third Floor
Room
335
University Street
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 374
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
Legend
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
University Street
In front of
Rayne Institute
Fire alarm call point
Huntley Street
Stair
R
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 37404005/110618
FIRE ESCAPE PLAN
Stair
A
Medical School
Room 336
Third Floor
You
are
here
Fire
Action
University Street
Room
336
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 374
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
Legend
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
University Street
In front of
Rayne Institute
Fire alarm call point
Huntley Street
Stair
R
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 37404005/110618
FIRE ESCAPE PLAN
Stair
A
Fire
Action
Medical School
Room 337
Third Floor
University Street
You
are
here
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 374
Room
337
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
Legend
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
University Street
In front of
Rayne Institute
Fire alarm call point
Huntley Street
Stair
R
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 37404005/110618
FIRE ESCAPE PLAN
Stair
A
Fire
Action
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 374
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
University Street
You
are
here
Room
338
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
Legend
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
University Street
In front of
Rayne Institute
Medical School
Room 338
Third Floor
Fire alarm call point
Huntley Street
Stair
R
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 37404005/110618
FIRE ESCAPE PLAN
Stair
A
Fire
Action
Medical School
Room 339
Third Floor
University Street
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 374
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
You
are
here
Room
339
Legend
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
University Street
In front of
Rayne Institute
Fire alarm call point
Huntley Street
Stair
R
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 37404005/110618
FIRE ESCAPE PLAN
Rockefeller Building
Room G11
Ground Floor
Stair
B
Fire
Action
Room
G11
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 201
You
are
here
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
Corner of University Street
and
Huntley Street
Stair
B
Legend
Fire alarm call point
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 20104002/110618
FIRE ESCAPE PLAN
Rockefeller Building
Room B16
Rockefeller Basement
Stair
A
Fire
Action
You
are
here
Room
B16
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 201
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
Stair
B
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
Corner of University Street
and
Huntley Street
Legend
Fire alarm call point
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 201-04001/110618
FIRE ESCAPE PLAN
Rockefeller Building
Room B15
Rockefeller Basement
Stair
A
Fire
Action
You
are
here
Room
B15
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 201
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
Stair
B
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
Corner of University Street
and
Huntley Street
Legend
Fire alarm call point
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 201-04001/110618
FIRE ESCAPE PLAN
Rockefeller Building
Room B14
Rockefeller Basement
Stair
A
Fire
Action
You
are
here
Room
B14
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 201
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
Stair
B
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
Corner of University Street
and
Huntley Street
Legend
Fire alarm call point
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 201-04001/110618
FIRE ESCAPE PLAN
Rockefeller Building
Room B14A
Rockefeller Basement
Stair
A
Fire
Action
You
are
here
Room
B14A
On discovering a fire - operate the nearest fire alarm call point.
Dial extension '222' on a UCL internal telephone giving the
building name and this FIRE ZONE Number – 201
Only attempt to fight the fire, if it is safe and practical to do so using the most appropriate fire extinguisher for the type of fire
you intend to tackle.
Stair
B
Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID
fires.
On hearing the fire alarm - leave the building by the nearest
AVAILABLE FIRE EXIT.
• CLOSE - all doors and windows as you leave.
• Do NOT - stop to collect belongings.
• Do NOT - use the lift.
• Do NOT - re enter the building until instructed to do so
by the Senior Fire Officer present.
When clear of the building - proceed to your designated FIRE
ASSEMBLY POINT at:
Corner of University Street
and
Huntley Street
Legend
Fire alarm call point
Safe refuge
Fire extinguisher
Emergency exit
Plan Ref: 201-04001/110618