Safety Services Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 CENTRAL HOUSE University College London 14 Upper Woburn Place, London WC1H 0NN INTRODUCTION NOTES This document will provide you with the information that you need to know in order to use your building safely whilst complying with UCL policy and fire safety legislation. Each UCL building has been given a risk rating, and this dictates how often fire safety reviews take place, as well as how often departmental staff and fire evacuation marshals should receive full fire safety training. UCL Departments must ensure that: • all staff are adequately trained on induction; • this training is refreshed periodically (depending on the fire risk rating); • fire evacuation marshals (FEM) are appointed for each floor the building; • fire evacuation marshals are suitably trained, including refresher trained periodically (depending on the fire risk rating); • departmental areas and the risks contained therein are managed safely; • appropriate arrangements are in place to ensure the safe evacuation of disabled people; Fire Safety Reviews - UCL Fire Safety Staff will periodically carry out fire risk assessments and fire safety reviews. The period in which these reviews will take place will be dictated by the determined risk of the building. Every October - a fire drill will be carried out in most UCL buildings and following the drill, fire FEMs will receive a Toolbox Talk of relevant information to report back to their colleagues. A report will be published on line, and this process will act as an annual training supplement to ensure that UCL people remain aware of the significant findings of our fire risk management process. _______________________________________________________________________________________________________________ Date Last Amended: Aug 14 EP: 1 of 8. Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / fire@ucl.ac.uk / Tel: 020 7679 1240 Premises Fire Safety Handbook Bldg Name: Central House (388) _______________________________________________________________________________________________________ Part 1 - Instruction to Building Occupants: Building Fire Risk Rating: Fire Risk Assessment: Category 2 Risk Fire Risk Assessment in this building will be undertaken every 3 years (subject to building changes or alterations) Fire Risk Assessment Review: Interim A (Annually) - Fire Safety Staff Department Fire Risk Review (iaw TN077): Department - review annually & keep completed copies locally for fire brigade inspection Staff Training (TN086): New Staff Induction - immediate on arrival carry out full walk of building, escape routes & Staff member to complete ‘Basic Fire Safety’ eLearning on Moodle Refresher - full training as per induction to be completed by all staff on periods determined in risk rating time line above. (Additional refresher training will be delivered by means of Toolbox Talks. These will be given following fire risk assessments, reviews and fire evacuation drills, at least annually to FEMs. This information will then be cascaded to all staff by FEMs). FEM Training (TN099): Minimum number of trained FEMs per floor in this building is: FIVE (5) New / initial FEM training - completed through eLearning on Moodle. Refresher - the FEM refresher period is determined in risk rating time line above. (Additional refresher training will be delivered by means of Toolbox Talks. These will be given following fire risk assessments, reviews and fire evacuation drills, at least annually, to FEMs). Relevant Information Fire Drill: Scheduled annually for start of term (October) Persons with Disabilities: Department to provide PEEPs arrangements (see details below) and specific Floor By-Pass Facilities - occupying Departments must ensure that access to either stair is available at all times and that intermediate doors are not locked or if there is a need that these locks have suitable emergency escape door furniture or release mechanisms are fitted. Escape From Ground Level - Reception Unavailable Other Information: Main Entrance Fire Curtain - the main entrance fire curtain is designed to drop and protect the principal escape route (Stair A) from a fire incident in Reception Area. In the unlikely event that the shutter drops, the escape route via the main entrance becomes unavailable & occupants are redirected to escape via the corridor around the main stair (Stair A) discharging at final exit onto Upper Woburn Place - this corridor also provides protected access to Stair A if required by the Fire Brigade. Fire curtain will only drop if the local detector has activated indicating, that there is fire in the immediate Reception Area preventing escape through the main entrance. _______________________________________________________________________________________________________________ Date Last Amended: Aug 14 EP: 2 of 7. Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / fire@ucl.ac.uk / Tel: 020 7679 1240 Premises Fire Safety Handbook Bldg Name: Central House (388) _______________________________________________________________________________________________________ Part 2 - Specific Evacuation Instructions: Local fire information: Fire Action Notices (and in some premises, additional supplementary instructions) located throughout the premises at fire points and within residential sleeping accommodation rooms, are the local fire Emergency Plan and you should be aware of its contents. Action on discovering a fire: On discovery or being made aware of a fire, immediately raise the alarm to give warning throughout the building by operating the nearest fire alarm call point. On hearing the fire alarm: On hearing the fire alarm, leave the building immediately by the nearest available fire exit (this may not necessarily be the way you entered the building). The fire alarm system: (1). This building is equipped with a single stage addressable fire alarm system. Which when activated, emits a continuous warning throughout the building. (2). Automatic Fire Detection (AFD) – smoke & heat detecting devices are provided for early warning of fire to aid faster escape. (3). Manual Call Points (MCPs) - means for raising the fire alarm in addition to fire detection is by operating MCPs that may be found on routes leading from the building (including corridors, landings, staircases & final exits). Calling the fire brigade: Dial Ext: 222 on a UCL Internal Extension and report the fire (use the Building Reference number to assist in identifying the premises or the address shown on the UCL Fire Action Notices). This building’s fire alarm system is monitored on a 24-hour basis who will summon the Fire Brigade. However, you should always make an Emergency Telephone call (Ext: ‘222’) to raise the alarm Evacuation procedure and using lifts during fire: On hearing the alarm or being directed by a Fire Evacuation Marshal (FEM), occupants are to evacuate the building by the nearest available escape stair, corridor or exit route to the Final Exit from the building. If your escape route is blocked / obstructed by fire or smoke, you should turn your back on the fire and follow the alternative route from the building by following the green fire escape directional signage provided. Lifts should not be used in the event of the fire alarm sounding. Fire Assembly Point: On leaving the building you should proceed to the Fire Assembly Point; the location of the Fire Assembly Point(s) is indicated on the local Fire Action Notices provided, which may also be supplemented with additional information such as local escape route plans etc. Do not obstruct the building entrances as this may hinder access to the fire brigade crews & appliances. Beware of the road traffic and your and others safety during the evacuation! Electronic security door release mechanisms see TN002 and TN004: Where fitted doors forming part of the Means of Escape (MoE) may be provided with Electromagnetic Security Locks (Gallagher): (1). Generally, locks release on activation of the fire alarm system (but there are some specialist exceptions to this requirement); (2). Each door is provided with an independent ‘break glass’ emergency release device (green box) in the direction of escape that may be activated to release the door in an emergency. _______________________________________________________________________________________________________________ Date Last Amended: Aug 14 EP: 3 of 7. Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / fire@ucl.ac.uk / Tel: 020 7679 1240 Premises Fire Safety Handbook Bldg Name: Central House (388) _______________________________________________________________________________________________________ Part 3 - Emergency Disabled Evacuation Provisions: Mobility Impaired Persons (MIP) or Persons with Disabilities: Department’s local management arrangements and fire evacuation strategy for MIP and disabled persons should not rely solely on the Fire & Rescue Service, rescuing people waiting in refuges but for the Department to have satisfactory arrangements in place to assist person from the building. Personal Emergency Evacuation Plan (PEEP) Managers should review & use the ‘Disable Information Emergency Egress Assessment & personal Emergency Evacuation Plan (PEEP)’ available from www.ucl.ac.uk/fire/documents under ‘Disabled’ Disabled Facilities: Where refuges are provided, they will be located in fireresisting structure, which creates a protected area so the refuge can be used as a safe resting place as well as a place to wait in a phased evacuation while the go-ahead for a full escape is established. Where provided, the refuge will be equipped with a suitable means of communications. Refuges (Generally, only provided on individual Risk Assessment or as part of a PEEP initiated by the Department): People should never be left in a refuge point to wait for the Fire and Rescue Service. Refuges should only be used in conjunction with effective management rescue arrangements. People should never be left in a refuge point to wait for the Fire and Rescue Service. Refuges should only be used in conjunction with effective management rescue arrangements. Relevant Information Disabled Refuge Communications Facilities: (1). Local coms by phone or talk box with local instructions and numbers to call; (2). Mobile Users should call the UCL Security Control Room (available 24/7) who can arrange help and assistance on: (Communication facilities for disabled refuges have BT big button telephone or system complying BS5839-9): 020 7679 3333 (Ext: 33333) Disabled Evacuation Lift: East stair (Stair B) is provided with an evacuation lift activation and training roved when required by a local PEEP. Deaf Persons Fire Alarm Alerting Facilities: Deaf Messaging System (DMS) provide and connected to the fire alarm system: General Emergency Evacuation Plan (GEEP): Alternative Number (24/7) - 020 7387 5256 UCL Security Ops (24/7) - 020 7679 2108 (Ext: 32108) • Not provided The building is provided with fire safe lobbies to each stair - which will provide time for arrangements to be made for others to assist. The person you are visiting will take you to the refuge, which is within the evacuation stairway at each level of the building. If you are able, make you own way down the stairs in your own time, once all other occupants have passed you. Designated Refuges are located on each landing in Stair B Other Information: Specific arrangments will be provided via a PEEP Assessment _______________________________________________________________________________________________________________ Date Last Amended: Aug 14 EP: 4 of 7. Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / fire@ucl.ac.uk / Tel: 020 7679 1240 Premises Fire Safety Handbook Bldg Name: Central House (388) _______________________________________________________________________________________________________ Part 3 - Centrally Timetabled Space Disability Provisions (Cont.): Centrally Timetabled Lecture Theatres & Seminar Rooms - Disable (Wheelchair) Emergency Egress Facilities / Arrangements Lecture Theatre / Seminar Room Locations Accessible / Egress Bartlett School Library Accessible1 Access via main entrance and library located at ground level Seminar Room G01 Accessible Access via main entrance and seminar room located at ground level. N/A Limited2 N/A N/A None3 N/A 1 Evacuation Arrangements Accessible - Access and Egress available without general assistance as generally facility where practical to self-escape; Limited - Emergency egress requires management & other assistance, should be planned & written up on PEEP; 3 None - No Disabled Access or Egress available; _______________________________________________________________________________________________________________ Date Last Amended: Aug 14 EP: 5 of 7. Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / fire@ucl.ac.uk / Tel: 020 7679 1240 2 Premises Fire Safety Handbook Bldg Name: Central House (388) _______________________________________________________________________________________________________ Part 4 - Background Information & Arrangements: Fire Fighting Equipment Fire fighting equipment is strategically placed throughout the building in accordance with the hazards identified. Only use fire-fighting equipment if you have been specifically trained and it is safe for you to do so; and you are confident that you are using the most appropriate fire extinguisher on the correct type fire. Emergency & Escape Lighting Emergency escape lighting is provided in large &/or specific rooms, all corridors and stair enclosures to illuminate safely the escape routes from the premises in the event of a ‘Local Lighting Circuit’ failure (they do not illuminate on the fire alarm sounding). In addition, illuminated directional escape signage may also be provided. Emergency stop of machines / processes / high risk areas: Designate Staff or FEMs should ensure that where hazardous processes are being used, they are shut down safely and quickly before leaving the area. If this is not possible, a responsible person must inform the Senior FEM or a Fire Brigade Officer of the hazard and possible affect if left unattended etc immediately on leaving the building! Meeting the Fire Brigade & Hazard Information: Normal Working Hours - the fire brigade will be met by the Senior Fire Marshal on behalf of Departments / Institutes with local security or maintenance staff in attendance. Out of Hours - generally UCL or local Security will meet and assist the Fire Brigade with maintenance staff attending if required. Fire Brigade Emergency Building Plans: Fire Plans are provided for each building to assist in the management of fire safety in the premises and are updated as part of the fire risk assessment process. These plans show the fire escape stairs, routes emergency door furniture, final exits and other relevant information for use by Fire Brigade & others - Departments may obtain copies through the UCL Fire Safety Manager. Premises Information Boxes (PIB): Fire Brigade Contingency Plans & Hazard Information - fire brigade building plans and general / hazard information is provided in a Red A4 Folder placed in the fire brigade Premises Information Box which is generally located close to main entrance and the master fire alarm panel. Protected Main Stairs Protected Stair Enclosures - stairs are to remain free of any combustible materials, storage, fixtures or fittings with all wall and floors having a surface flame spread of ‘Class 0’ to ensure the maintenance of the means of escape. See UCL Fire Safety Technical Note TN069 www.ucl.ac.uk/fire/. Location and Provision of Lockers (Circulation Areas) - stairs and some corridors are to remain free of any storage including lockers for further and specific information see UCL Fire Safety Technical Note TN070 www.ucl.ac.uk/fire/. Other Information: 10 Duke Road (including basement, ground floor and staff flat) forms part of Central House _______________________________________________________________________________________________________________ Date Last Amended: Aug 14 EP: 6 of 7. Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / fire@ucl.ac.uk / Tel: 020 7679 1240 Premises Fire Safety Handbook Bldg Name: Central House (388) _______________________________________________________________________________________________________ Part 5 - Staff Training & Fire Evacuation Marshal Arrangements: Senior Fire Evacuation Marshal (SFEM) The Senior FEM meets the fire brigade & assists them with building information and notifying them of hazards within building The Head of Department / Institutes must appoint a suitable member(s) of staff in each building that the Department occupies, to become a Senior Fire Evacuation Marshal (SFEM) to: (1). Liaise with other SFEMs (if a multi-occupied building) and fire brigade, local security and maintenance staff during normal working hours etc.; (2). Co-ordinate the Departmental FEMs with others (such as the Landlord’s agents) and with other occupiers, as necessary; (3). Provide local information to the fire brigade on any specific hazards related to the premises areas occupied; particularly, where there are laboratories or hazardous substances or processes used etc.; Fire Evacuation Marshals (FEMS): Due to the size and complexity of UCL, it is neither practical nor feasible to maintain a meaningful register of building occupants to account for those persons using premises during normal working hours. It is UCL policy that all Heads of Departments shall designate sufficient staff to act as Fire Evacuation Marshals (FEMs), who in the event of a fire or incident will check their areas of responsibility. FEMs will request politely but firmly that all staff, students and visitors evacuate the building immediately by the nearest available fire exit route, they may assist Persons with Disabilities and liaise with the fire brigade, as necessary. Staff Working Outside of Normal Hours: Heads of Departments must have arrangements in place to insure that staff or students are employed out of normal working ours that there is suitable ‘Lone Working’ policy and arrangements in place to ensure that all occupants can be accounted for in case of fire and evacuation by the fire brigade. UCL FEMs Fire Evacuation Drills: Fire Drills - annual fire drills are carried out at beginning of the Autumn Term (October) of each year by the UCL Fire Safety Manager or the Landlord if your are Tenants in a non-owned UCL or managed premises. Note: Unwanted alarm activations are treated as supplementary fire drills throughout the year. Staff & Student Training Induction Familiarisation (Staff, Visitors & Contractors): The Heads of Departments must have arrangements in place so that all Temporary & Permanent Staff, Postgraduate Research Students and others working for more than 3 days in the Department, receive Local Fire Safety Induction familiarisation and an approved training record raised and kept. Training (Students): The Heads of Departments shall provide at the start of each academic session, fire safety information for all undergraduates / postgraduates studying in their Department. Periodical (Staff) Familiarisation: The Regulatory Reform (Fire Safety) Order requires that all temporary and permanent staff receive local fire safety familiarisation of the building(s) that staff, work or visit periodically or when there has been a change of work activities or working environment for employees, postgraduate students or visitors; and that a record is kept. Based on the building layout, evacuation procedures and risk based approach the frequency for under taking staff fire evacuation familiarisation in this building _______________________________________________________________________________________________________________ Date Last Amended: Aug 14 EP: 7 of 7. Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / fire@ucl.ac.uk / Tel: 020 7679 1240 Fire Action Central House 14 Upper Woburn Place On discovering a fire - operate the nearest fire alarm call point. Dial Ext 222 or (9)999 & call the Fire Brigade - your address is: Central House 14 Upper Woburn Place, London WC1H 0NN Only attempt to fight the fire, if it is safe and practical to do so - using the most appropriate fire extinguisher for the type of fire you intend to tackle. Do not use WATER on ELECTRICAL or FLAMMABLE LIQUID fires. On hearing the fire alarm - leave the building by the nearest AVAILABLE FIRE EXIT. CLOSE - all doors and windows as you leave. Do NOT - stop to collect belongings. Do NOT - use the lift. Do NOT - re enter the building until instructed to do so by the Senior Fire Officer present. When clear of the building - proceed to your designated FIRE ASSEMBLY POINT at: Tavistock Square (Outside NatWest Bank on pavement - please ensure that pavement remains unobstructed for pedestrians) Issued by: Fire Safety Manager, UCL Estates, Gower Street, London, WC1E 6BT. NOTES Fire Escape By-pass Route to Alternative Escape Stair Must Be Maintained on All Floors Occupants Emergence Fastening (EF) - doors used for escape to be provided if necessary with a simple locking device which operated from the outside by a key and from the inside by a knob or lever (i.e. night latch, thumb turn, push pads) etc. (as per UCL fire plans iaw BS1635); GENERAL LAYOUT UPPER FLOORS 30 minute Fire Curtain drops on actuation of local smoke detectors Master Fire Alarm Control Panel OPEN PLAN OFFICE UPPER WOBURN PLACE Free From Fastenings (FFF) - doors used for escape to be free from any locking devices (as per UCL fire plans iaw BS1635); DO NOT SCALE OFF THIS DRAWING. ALL DIMENSIONS MUST BE CHECKED ON SITE PRIOR TO ANY WORK BEING PUT IN HAND. ANY DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF THE PROJECT MANAGER IMMEDIATELY UPON DISCOVERY. SHOWER MALE WC WC LOBBY FEMALE WC A Note - Escape Route from Main Stair if Fire Roller Shutter Activated to Main Entrance LIFT CORE LIFT B Disabled Evacuation Lift FIRE EXIT Stair B G01 EXHIBITION / SEMINAR G01B Fire Panel Cpd G01A STORE LIGHT WELL LIGHT WELL G07A SHORT LOANS G06 LIBRARY OFFICE Sub Master FAP G08 MEETING ROOM G09 GROUP STUDY AREA You Are here G94A LIFTS MAIN ENTRANCE G16 LIBRARY COLLECTION G96 G97 G96A G94 A G12 STORE G13 MALE WC UCL ESTATES G15 DISABLED WC G14 FEMALE WC G10 TEA POINT GOWER STREET, LONDON WC1E 6BT G10A PRINT ROOM G13A Slave Fire Alarm Control Panel LIGHT WELL G02 RECEPTION Fire Escape Route G97A G92 LIGHT WELL G14A G04 G03 TEA POINT DISABLED WC G05 MEETING ROOM Fire Escape Route G91 G11 QUIET STUDY ROOM Drawn: Date: Scale: File: G89 Fire Escape Route Fire Escape Route G93 Fire Escape Route G93 Alternative escape route from Stair A on a fire in the Reception area actuating the fire shutter to prevent escape via main entrance S.H. August 2014 N.T.S. UCL Estates/388/Fire Rev. S.H. Oct. 2014 G98 FIRE EXIT G11A G99A LIFT G87 G90 G86 G99 B Disabled Evacuation Lift GENERAL LAYOUT GROUND FLOOR G88 AREA C G85 D Stair B FIRE EXIT G84 Stair C Stair D G21 STORE GROUND FLOOR 10 DUKE ROAD DUKE R OAD UPPER WOBURN PLACE G07 RECEPTION G95 Central House 14 Woburn Place London WC1H 0NN GENERAL ARRANGEMENT Fire Safety & Fire Brigade Contingency Plans DWG. NO. 388-04-GA rev