Installation Instructions NeoSwitch Passive Infrared (PIR) Technology RR7

advertisement
Installation Instructions
EcoMeter Operation
• ForusewithRR7/9typerelays
• DonotrunanyGreengateLowVoltagewiringinthe
sameconduitaspowerconductors
Load 1
EcoMeter LED
OFF
ON
ON
OFF
Specifications
Technology:PassiveInfrared(PIR)
Electrical Ratings:
Input:
• 24VAC±10%Maximumcurrentneededis25mA
persensor.
• 1VAmaxforeachsensor
• 7VAmaxforeachGERR7/9relay
• 8.5VAmaxforeachSierra1070-Brelay
Output:
• Half-waverectified24VACfor300mspulsefor
drivingupto4GERR7/9typerelaysorupto2
Sierra1070-Btyperelays.
• IsolatedFormCRelay
• IsolatedFormCRelayRatings:1A30VDC/VAC.
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%Non-condensing
Housing:Durable,injectionmoldedhousing.
PolycarbonateresincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.195"Hx1.732"W(106.553mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752"
Wx1.9"D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;Green
LEDactsasEcoMeterornightlightlocator.
Description
TheONW-P-1001-RR7OccupancySensingWallSwitchisaPassiveInfrared(PIR)motionsensinglightingcontrol
andconventionalWallSwitchall-in-one,usedforenergysavingsandconvenience.
Action
EcoMeter
Apersonentersthespaceand
theloadisactivated
Benefit
OFF
Theareaisvacatedandthe
lightsturnOFFautomatically
ON
Increasedawarenessofenergysavings;
Actsasanightlightlocator
ApersonturnsthelightsOFF
manuallyuponexitinganarea
ON
Increasedawarenessofenergysavingsand
remindsindividualstotakecontroloftheir
lightingforadditionalsavings;Actsasanight
lightlocator
Thedaylightfeatureprevents
thelightsfromautomatically
turningONwhenaperson
entersanarea
ON
Increasedawarenessofenergysavingsand
letsindividualknowthatthedaylighting
featureisworking
ONW-P-1001-RR7-W
ONW-P-1001-RR7-V
ONW-P-1001-RR7-LA
ONW-P-1001-RR7-G
ONW-P-1001-RR7-B
Installation
TheONW-P-1001-RR7canbeinstalledinanystandardsinglegang
box.ItmaybeinstalledinthesamemannerasanordinaryWallSwitch.
• WiretheONW-P-1001-RR7asdescribedinthewiringsection.
• MounttheONW-P-1001-RR7inthejunctionbox.
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF
at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main
switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be
in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
Coverage
1.MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.
3.MountunittoWallBox.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.InstallWallSwitchplate.
TheONW-P-1001-RR7isdesignedforofficesupto300squarefeet.
36
,
,
20
Minor Motion, IR
PIR Technology
Major Motion, IR
Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperature
thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
,
TheONW-P-1001-RR7allowsthecontroloffourGERR7/9relaysortwoSierra1070-Brelays.
8
Thesensormaybeinterfacedtoanenergymanagementsystemthatacceptseitheranormallyopenornormally
closeddrycontactviathesensor’sFormCrelay.
ThesensorcanbeconfiguredtoenhanceenergysavingsbysettingtheunitformanualONoperation.
InAutomaticONMode,thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,the
lightsareturnedONbypressingtheuniversallyrecognizedlighticonPushbutton.Ineithermode,thelightsstayON
aslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyafter
apresetTimeDelayinterval.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand
Maximum coverage area may
TimeDelayinReal-time.ByadjustingsensitivityandTimeDelayautomatically,thesensorismaximizingthepotential
vary somewhat according to room
energysavingsthatareavailableintheparticularapplication.
shape and the presence of obstacles.
TheEcoMeterprovidesavisualindicatorofenergyusage,increasingenduserawarenessandreminding
individualstotakecontroloftheirlightingtomaximizeenergysavings.
TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
Walk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.The
sensorwillswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetect Location
motion20secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minuteTimeDelay.
WheninstallingtheONW-P-1001-RR7inanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
TrackingModeallowstheloadconnectedtotheFormCrelaytofollowthestateofthesensor’sbluelead.
coverageoftheoccupiedarea.WhenreplacinganexistingWallSwitch,bearinmindthattheremustbeaclearLineHVACModeallowstheloadconnectedtotheFormCrelaytoremainONwhenthelightsareturnedOFFmanually. of-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheONW-P-1001-RR7directlyintothehallway
ApplicationsmayincludekeepingtheroomatadesiredtemperaturewhilegivingapresentationandthelightsareOFF.
whereitmaydetectpassers-by.
Wiring Diagram 1
NEUTRAL
LOAD
HOT
RELAY
24 VAC
BLACK
• Readallinstructionsonbothsidesofthissheetfirst
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
#
#
#
#
#
RED
General Information
Model
Model
Model
Model
Model
BLUE
P/N 9850-000347-01
NeoSwitch Passive Infrared (PIR) Technology RR7
Compatible Occupancy Sensing Wall Switch
TO
ADDITIONAL
RELAYS
NOTE- USE ONLY APPROVED RELAYS:
GE RR7 TYPE MAXIMUM OF FOUR OR
SIERRA 1070-B TYPE MAXIMUM OF TWO.
ORANGE (N.O.)
WHITE
GRAY (COMMON)
RED
PURPLE (N.C.)
BLACK
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect
only one circuit per relay. Both circuits must be fed from the same phase.
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
DIP Switch Settings
DIP Switch Legend
Time Delay
DIP Switch
Activation
Isolated Relay
PIR Sensitivity Walk-Through Mode
Override
EcoMeter
Relay 1
1
2
Auto*
5 Minutes
Auto
Tracking
Full
Disable
Enable
Disable
Manual
HVAC
50%
Enable
Disable
Enable
15 Minutes
30 Minutes
*Self-Adjusts to
10 min. user mode
3
4
6
5
7
8
Default =
1
2
3
4
5
6
7
8
Checkout and Adjustment
AdjustmentsshouldbemadewiththeHVACsystemonsothattheinstallerwillbeabletodetecttheeffectof
airflowontheoperationoftheONW-P-1001-RR7.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopowerup
andstabilize.
Self-Adjust
Sensorisshippedinself-adjustmode.This
appliestoTimeDelayandPIRsensitivity.In
Red (PIR)
preparationfortheInstallerTest,theTime
Detection LEDs
PIR Lens
Delayissetto15seconds,afterthesensoris
installed,poweredONandhasstabilized,the
Daylight
unitwillTime-out15secondsafterthelast
Sensor Level
motiondetected.Coverageandsensitivity
Adjustment
canbeconfirmedbywatchingtheRed(PIR)
indicatorLEDonthefrontofthesensor,while
DIP Switches
movingaroundtheroom.
1.WalkaroundtheroomandmonitorLEDs.
2.Standindifferentpartsoftheroomand
waveyourhands.LEDshouldonlyturn
ONforonesecondwitheachmotion.
ON/OFF Button
(IfLEDdoesnotturnON,gotoInstaller
Adjustments–SensitivityAdjustment
Section)
3.Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.(IfLEDturnsON,goto
InstallerAdjustments–SensitivityAdjustmentssection)
4.Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
5.Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection)
6.AtthispointyoucanexittheroomandletthesensorTime-out.Whenthesensortimes-outandisOFFforfive
minutes,theunitwillgotoa10minuteTimeDelayusermodesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
Daylight Adjustments
ThedaylightingfeaturepreventsthelightsfromturningONwhenthe
roomisadequatelyilluminatedbynaturallight.Ifthereisenoughlightinthe
roomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthere
isnotenoughlightintheroom,thesensorwillallowthelightstoturnON
whenoccupied.Thesensorwillnotallowthedaylightingfeaturetoturnthe
loadOFFuntilthespaceisvacantorthelightlevelrisesabovethesetpoint
andtheTimeDelayexpires.WhileinManualActivationMode,ifsomeone
attemptstoturntheloadONandthereissufficientdaylightavailablethe
DaylightingfeaturewillholdthelightsOFF.
1.Setthelightlevelwhentheambientlightisatthelevelwhereno
artificiallightisneeded.Ifthisfeatureisnotneeded,leavethelight
levelatmaximum(fullyCW).
2.Withtheload(s)ON,putthesensorintoTestMode.Toplaceintotest
mode,toggleDIPSwitch8outofitscurrentposition,wait3seconds
andthenbackintoitsoriginalposition.
3.SettheLightleveltominimum(fullyCCW).
4.LetthesensorTime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF.
5.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
increments.(Pause5secondsbetweeneachadjustment)
6. LightswillnotturnONuponoccupancyactivation,whentheambientlightlevelexceedsthedaylightthresholdsetting.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemay
needalongerTimeDelaythanthedefaultsettingof10minutes.
Aslongastheself-adjustingfeatureisenabled,theswitch
willrespondtoeachpairofFalse-offswithnonormalOFFin
between,byalternatelymakingslightadjustmentstoeitherTime
Delay(by2minuteincrements)orsensitivity,sothereshouldbe
noneedformanualadjustment.Ifmanualadjustmentisdesired,
refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensorTimeDelaytofactorysettingsbymovingDIP
Switches1and2down.(IfDIPSwitches1and2arealready
down,toggleDIPSwitch1outofitscurrentposition,wait3
seconds,andthenbacktoitsoriginalposition).
Troubleshooting
Issue
Possible Causes
Suggestions
SensorisinManualONmode
PressPushbutton.IfAutoMode
isdesiredchangeActivationModetoAuto.
SensorwasturnedOFFmanually.IftheSensor
Lights
wasturnedOFFmanuallybeforetheTimeDelay
Will Not
expired,lightswillremainOFFfortheremainder
Turn ON
oftheTimeDelay.
automatically
Lights
Will Not
Turn ON
manually
CheckEcoMeterLED.IfLEDisONthisis
anindicationthatthelightswereturnedOFFmanually.
PressthePushbuttontoturnthelightsbackON.
DaylightFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer.
Powerinterruption
Checkincomingvoltageand/orwiring.
DaylightFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer.
Powerinterruption
Checkincomingvoltageand/orwiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
DIP Switches
1&2
1
2
3
4
5
6
7
8
Tracking/HVAC
WhentheoccupancysensorturnsthelightsONorOFFeitherbydetectionoramanualpress,thelightscanbeturned
OFFmanuallybypressingthePushbutton.ThelightswillremainOFFaslongasthereismotionintheroom,oncethe
occupancysensornolongerdetectsmotionandtheTimeDelayexpires,thesensorwillrevertbacktoits
normaloperation.
TrackingMode–Isolatedrelaywillfollowoperationofsensorinallmodes.Relaystatewillchangewhenoccupancy
sensorisactivatedand/orturnedONorOFFmanually.
HVACMode–IsolatedrelaywillonlychangestateinAuto/ManualONandAutoOFFmodes.Thestatewillnot
change,iftheoccupancysensoristurnedOFFmanually.TherelaywillchangestateoncetheTimeDelayexpires.
Override
Theoverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1.MoveDIPSwitch8up.
2.ThePushbuttoncanbeusedtomanuallyturnlightsONorOFF.
Override
MakesuresensorisnotinOverrideMode(DIPSwitch8up).
Self-Adjust
IfsensorisinSelf-AdjustMode,itmaybepossibleforthe
unittohaveincreasedtheTimeDelaytoa30minutedelay.
IfthelightsdonotturnOFFafter30minutesfollownextstep.
30MinuteDelay
MaximumTimeDelayis30Minutes.CheckDIPSwitches
toverifyDIPSwitchsettings.IflightsdonotturnOFFatthe
setTimeDelay,checknextstep.
PIRactivatedbyheatsourceotherthanoccupant
MoveDIPSwitch5up.
Lights
Will Not
Turn OFF
automatically
Lights
Will Not
Turn OFF
manually
CallTechnicalServices
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Installer Adjustments
PIR Sensitivity
1.Standindifferentareasoftheroomandwaveyourhands.
2.IftheRedLEDdoesnotturnON,checkforanyobstructions.
3.Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4.IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1.AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
2.Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
Printed in Malaysia
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Download