Installation Instructions P/N 9850-000314-01 NeoSwitch Dual Technology Single Relay Occupancy Sensing Wall Switch (Ground Required) General Information • Readallinstructionsonbothsidesofthis sheetfirst Coverage • InstallinaccordancewithALLlocalcodes • Forindooruseonly Specifications , • WiretheONW-D-1001-347asdescribedinthewiringsection • MounttheONW-D-1001-347inthejunctionbox Minor Motion, IR Major Motion, IR , 8 Minor Motion, Ultrasonic Major Motion, Ultrasonic , 10 , 8 Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. 15 Description The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. , 20 , TheONW-D-1001-347OccupancySensingWallSwitchisaPassiveInfrared(PIR)andUltrasonic(US)motion sensinglightingcontrolandconventionalwallswitchall-in-one,usedforenergysavingsandconvenience. ThesensorcombinesPIRandUStechnologiestomonitoraroomforoccupancy. Location PIR Technology Thesensor’ssegmentedlensdividesthefield-of-viewintosensorzones,anddetectsthechangesintemperature thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone. WheninstallingtheONW-D-1001-347inanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclear line-of-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheONW-D-1001-347directlyintothe hallwaywhereitmaydetectpassers-by. US Technology Thesensorproducesalowintensity,inaudiblesound.Itdetectsoccupancyfromchangesintheacousticwaves causedbymotion,suchasreachingforatelephone,turningapageinabook,walkingintoaroom,turningina swivelchair,etc.Thesensordoesnotrespondtoaudiblesound. DualTechnologysensorsensurethegreatestsensitivityandcoveragefortoughapplicationsthussavingadditional energy.PIRisusedtoturnthelightsONandtheneitherorbothtechnologiesareusedtokeepthelightsON. TheONW-D-1001-347allowsthecontrolofoneloadwithoneoccupancysensorswitch. ThesensorcanbeconfiguredtoenhanceenergysavingsbysettingtheunitforManualONoperation. InAutomaticONMode,thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,the lightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,thelightsstayON aslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyaftera presettimedelayinterval. Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy savingsthatareavailableintheparticularapplication. TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight. TheWalk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy. ThesensorwillswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinueto detectmotion20secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minutetimedelay. TheON/OFFButtonDisableOption–WhenselectedthisoptiondisablestheON/OFFbutton(s)andsensor becomesautomaticonlycontrol. ONW-D-1001-347-W ONW-D-1001-347-V ONW-D-1001-347-LA ONW-D-1001-347-G ONW-D-1001-347-B TheONW-D-1001-347canbeinstalledinanystandardsinglegangbox.Itmay beinstalledinthesamemannerasanordinarywallswitch. , 20 Light Level Sensing:0to200foot-candles Operating Environment: • Temperature:32°F–104°F(0°C–40°C) • RelativeHumidity:20%to90%non-condensing Housing:Durable,injectionmoldedhousing. PolycarbonateresincomplieswithUL94VO. Size: • MountingPlate/StrapDimensions: 4.35"Hx1.732"W(110.49mmx44mm) • ProductHousingDimensions:2.618"Hx1.752" Wx1.9"D(66.5mmx44.5mmx48.26mm) LED Indicators:RedLEDindicatesPIRdetection; GreenLEDindicatesUltrasonicdetection. # # # # # Installation TheONW-D-1001-347isdesignedforofficesupto300squarefeet. 36 Technology:PassiveInfrared(PIR)andUltrasonic(US) Electrical Ratings: 347VAC: • Incandescent/Tungsten– Max.load:4.3amps,1500W,50/60Hz • Fluorescent/Ballast– Max.load:4.3amps,1500W,50/60Hz Ballast Compatibility:Compatiblewithmagneticand electronicballasts No Minimum Load Requirement Time Delays:Self-Adjusting,15seconds/test(10min Auto),Selectable5,15,30minutes Coverage:Majormotion–1000sq.ft. Minormotion–300sq.ft. Model Model Model Model Model Wiring CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. 1.MakesurepoweristurnedOFFatthebranchcircuitbreaker. 2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements. 3.Mountunittowallbox. 4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize. 5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection) 6.Installwallswitchplate. Wiring Diagram 1: 347 VAC single level single circuit wiring diagram BLUE BLACK 347 VAC GREEN LOAD GROUND NEUTRAL Wiring Diagram 2: 347 VAC single level switch dual level wiring using a toggle switch wiring diagram BLACK 347 VAC GREEN BLUE LOAD 1 LOAD 2 GROUND NEUTRAL A/B SWITCHING USING TOGGLE SWITCH TO TURN OFF SECOND LOAD Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com Installer Adjustments Wiring Diagram 3: 347 VAC single level single circuit three-way wiring diagram TRAVELLER WIRES 347 VAC Sensitivity Adjustments BLUE BLUE BLACK GREEN BLACK GREEN LOAD 1 GROUND GROUND Issue Ultrasonic Sensitivity(GreenLED)–Usingasmallflatheadscrewdriverturnthe greenpotentiometersothatthearrowpointsUP. 1. Standindifferentareasoftheroomandwaveyourhands. 2. IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthe greenpotentiometerclockwiseinsmallincrements.RepeatStep1. 3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnot turnON. 4. IfGreenLEDturnsONwithoutmotionorisconstantlyONdecreasethe US sensitivitybyturninggreenpotentiometercounter-clockwiseinsmall decrements.RepeatStep3. Lights Will Not Turn ON automatically Possible Causes Suggestions SensorisinManualONmode Presspushbutton.IfAutoModeis desiredchangeActivationModetoAuto. SensorwasturnedOFFmanually.Ifthe SensorwasturnedOFFmanuallybefore thetimedelayexpired,lightswillremain OFFfortheremainderofthetimedelay PressthepushbuttontoturnthelightsbackON DaylightingFeatureEnabled IfalllightsarerequiredtoturnON adjustdaylightpotentiometer Powerinterruption Checkincomingvoltageand/orwiring DaylightingFeatureEnabled IfalllightsarerequiredtoturnON adjustdaylightpotentiometer Powerinterruption Checkincomingvoltageand/orwiring ON/OFFButtonDisabled MoveDIPSwitch7down Note:DoNotadjustsensitivityhigherthannecessary. NEUTRAL THREE-WAY WIRING DIAGRAM: LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT. CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per relay. Both circuits must be fed from the same phase. DIP Switch Settings DIP Switch Legend Time Delay Activation Relay 1 DIP Switch 1 2 15 Sec Test/Auto* Auto Manual 5 Minutes 15 Minutes 30 Minutes *Self-Adjusts to 10 min. user mode Troubleshooting PIR Sensitivity Walk-Through Mode ON/OFF Button Override Not Used Maintain Lights On Not Used Not Used 3 4 6 5 Full 50% Disable Enable 7 Enable Disable 8 Disable Enable 9 10 Either Both 11 12 Default = 1 2 3 4 5 6 7 8 9 10 11 12 Checkout and Adjustment AdjustmentsshouldbemadewiththeHVACsystemONsothattheinstallerwillbeabletodetecttheeffectofairflowonthe operationoftheONW-D-1001-347.Useonlyinsulatedtoolstomakeadjustments. Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopower-upandstabilize. Self-Adjust Sensorisshippedinself-adjustmode.Thisappliestotime delay,USandPIRsensitivity.InpreparationfortheInstaller Test,thetimedelayissetto15seconds,afterthesensoris Red (PIR) & Green (US) installed,poweredONandhasstabilized,theunitwilltimeDetection LEDs out15secondsafterthelastmotiondetected.Coverageand PIR Lens sensitivitycanbeconfirmedbywatchingtheGreen(US)and Ultrasonic Detection Daylight Red(PIR)indicatorLEDsonthefrontofthesensor,while Sensor Level Ultrasonic movingaroundtheroom. Adjustment Sensitivity Adjustment 1. WalkaroundtheroomandmonitorLEDs. 2. Standindifferentpartsoftheroomandwaveyour DIP Switches hands.LEDsshouldonlyturnONforonesecondwith eachmotion.(IfLEDsdonotturnON,gotoInstaller Adjustments–SensitivityAdjustmentSection) 3. Standstillthreetofourfeetawayfromsensorfor fiveseconds.LEDsshouldnotturnON.(IfanyLED ON/OFF Button turnsON,noteLEDandgotoInstallerAdjustments– SensitivityAdjustmentssection) 4. Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller AdjustmentsSection) 5. Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection) 6. Atthispointyoucanexittheroomandletthesensortime-out.Whenthesensortimes-outandisOFFwithpowerONforfive minutes,theunitwillgotoa10minuteTimeDelayusermodesetting. Note:ToplaceintoTestMode,toggleDIPSwitch12outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition. PIR Sensitivity 1. Standindifferentareasoftheroomandwaveyourhands. 2. IftheRedLEDdoesnotturnON,checkforanyobstructions. 3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnot turnON. 4. IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up. Field-of-view outside the space 1. AdjustPIRsensitivityto50%bymovingDIPswitch5up. 2. Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace. 3. AdjustUltrasonicSensitivity. ON/OFF Disabled Feature 1. ON/OFFButtonDisableOption–Whenselected thisoptiondisablestheON/OFFbuttonandsensor becomesautomaticonlycontrolregardlessofthe settingforautomaticormanualactivation.Thisfeature willnotallowsomeonetoturnlight(s)OFFviathe pushbuttonwhilepeopleareincommonareassuchas restroom,breakroomandcopyroomareas. 1 2 3 4 5 6 7 8 9 Lights Will Not Turn ON manually If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879 10 11 12 Daylight Adjustments TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom,the sensorwillallowthelightstoturnONwhenoccupied.ThesensorwillnotallowtheDaylightingfeaturetoturntheloadOFFuntilthe spaceisvacantorthelightlevelrisesabovethesetpointandthetimedelayexpires.WhileinManualActivationMode,ifsomeone attemptstoturntheloadONandthereissufficientdaylightavailabletheDaylightingfeaturewillholdthelightsOFF. 1. Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Ifthisfeatureisnotneeded,leavethe lightlevelatmaximum(fullyCW). 2. Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPswitch8outofitscurrentposition,wait 3secondsandthenbackintoitsoriginalposition. 3. Setthelightleveltominimum(fullyCCW). 4. Letthesensortime-outsolightsareOFF.Enterthe spaceandlightsshouldremainOFF. 5. Makesurenottoblockthesensorfromthedaylight sourceandadjustthelightlevelpotentiometerCWin smallincrements.(Pause5secondsbetween 1 2 3 4 5 6 7 8 9 10 11 12 1 and 2 eachadjustment) 6. LightswillnotturnONuponoccupancyactivation, whentheambientlightlevelexceedsthedaylight thresholdsetting. Lights Will Not Turn OFF automatically Lights Will Not Turn OFF manually Override MakesuresensorisnotinOverrideMode Self-Adjust IfsensorisinSelf-AdjustMode,itmaybe possiblefortheunittohaveincreasedthetime delaytoa30minutedelay.Ifthelightsdonot turnOFFafter30minutesfollownextstep. 30MinuteDelay Maximumtimedelayis30Minutes.CheckDIP SwitchestoverifyDIPSwitchsettings.Iflightsdo notturnOFFatthesettimedelay,checknextstep UltrasonicSensitivitysetHigh Lowersensitivitybyturninggreen potentiometerCCWinsmalldecrements PIRactivatedbyheatsource otherthanoccupant MoveDIPSwitch5up CallTechnicalServices ON/OFFButtonDisabled MoveDIPSwitch7down If lights will still not turn OFF, call Technical Services at 1-800-553-3879 Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. Time Delay Adjustments Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10minutes.As longastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,by alternatelymakingslightadjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbenoneedfor manualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPswitchlegend. ResetsensortimedelaytofactorysettingsbymovingDIPswitches1and2down.(IfDIPswitches1and2arealreadydown, toggleDIPswitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition) Override TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure. 1. MoveDIPswitch12up. 2. ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF. Printed in Malaysia Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com