Installation Instructions NeoSwitch Dual Technology Single Relay Occupancy Sensing Wall Switch

advertisement
Installation Instructions
P/N 9850-000314-01
NeoSwitch Dual Technology Single Relay
Occupancy Sensing Wall Switch
(Ground Required)
General Information
• Readallinstructionsonbothsidesofthis
sheetfirst
Coverage
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
Specifications
,
• WiretheONW-D-1001-347asdescribedinthewiringsection
• MounttheONW-D-1001-347inthejunctionbox
Minor Motion, IR
Major Motion, IR
,
8
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
,
10
,
8
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
15
Description
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
,
20
,
TheONW-D-1001-347OccupancySensingWallSwitchisaPassiveInfrared(PIR)andUltrasonic(US)motion
sensinglightingcontrolandconventionalwallswitchall-in-one,usedforenergysavingsandconvenience.
ThesensorcombinesPIRandUStechnologiestomonitoraroomforoccupancy.
Location
PIR Technology
Thesensor’ssegmentedlensdividesthefield-of-viewintosensorzones,anddetectsthechangesintemperature
thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
WheninstallingtheONW-D-1001-347inanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclear
line-of-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheONW-D-1001-347directlyintothe
hallwaywhereitmaydetectpassers-by.
US Technology
Thesensorproducesalowintensity,inaudiblesound.Itdetectsoccupancyfromchangesintheacousticwaves
causedbymotion,suchasreachingforatelephone,turningapageinabook,walkingintoaroom,turningina
swivelchair,etc.Thesensordoesnotrespondtoaudiblesound.
DualTechnologysensorsensurethegreatestsensitivityandcoveragefortoughapplicationsthussavingadditional
energy.PIRisusedtoturnthelightsONandtheneitherorbothtechnologiesareusedtokeepthelightsON.
TheONW-D-1001-347allowsthecontrolofoneloadwithoneoccupancysensorswitch.
ThesensorcanbeconfiguredtoenhanceenergysavingsbysettingtheunitforManualONoperation.
InAutomaticONMode,thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,the
lightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,thelightsstayON
aslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyaftera
presettimedelayinterval.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime
delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy
savingsthatareavailableintheparticularapplication.
TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
TheWalk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.
ThesensorwillswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinueto
detectmotion20secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minutetimedelay.
TheON/OFFButtonDisableOption–WhenselectedthisoptiondisablestheON/OFFbutton(s)andsensor
becomesautomaticonlycontrol.
ONW-D-1001-347-W
ONW-D-1001-347-V
ONW-D-1001-347-LA
ONW-D-1001-347-G
ONW-D-1001-347-B
TheONW-D-1001-347canbeinstalledinanystandardsinglegangbox.Itmay
beinstalledinthesamemannerasanordinarywallswitch.
,
20
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%non-condensing
Housing:Durable,injectionmoldedhousing.
PolycarbonateresincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.35"Hx1.732"W(110.49mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752"
Wx1.9"D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;
GreenLEDindicatesUltrasonicdetection.
#
#
#
#
#
Installation
TheONW-D-1001-347isdesignedforofficesupto300squarefeet.
36
Technology:PassiveInfrared(PIR)andUltrasonic(US)
Electrical Ratings:
347VAC:
• Incandescent/Tungsten–
Max.load:4.3amps,1500W,50/60Hz
• Fluorescent/Ballast–
Max.load:4.3amps,1500W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Model
Model
Model
Model
Model
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used
as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All
installations should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1.MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.
3.Mountunittowallbox.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.Installwallswitchplate.
Wiring Diagram 1:
347 VAC single level
single circuit wiring diagram
BLUE
BLACK
347 VAC
GREEN
LOAD
GROUND
NEUTRAL
Wiring Diagram 2:
347 VAC single level switch
dual level wiring using a toggle
switch wiring diagram
BLACK
347 VAC
GREEN
BLUE
LOAD 1
LOAD 2
GROUND
NEUTRAL
A/B SWITCHING USING TOGGLE
SWITCH TO TURN OFF SECOND LOAD
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Installer Adjustments
Wiring Diagram 3: 347 VAC single level single circuit three-way wiring diagram
TRAVELLER
WIRES
347 VAC
Sensitivity Adjustments
BLUE
BLUE
BLACK
GREEN
BLACK
GREEN
LOAD 1
GROUND
GROUND
Issue
Ultrasonic Sensitivity(GreenLED)–Usingasmallflatheadscrewdriverturnthe
greenpotentiometersothatthearrowpointsUP.
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthe
greenpotentiometerclockwiseinsmallincrements.RepeatStep1.
3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnot
turnON.
4. IfGreenLEDturnsONwithoutmotionorisconstantlyONdecreasethe
US sensitivitybyturninggreenpotentiometercounter-clockwiseinsmall
decrements.RepeatStep3.
Lights
Will Not
Turn ON
automatically
Possible Causes
Suggestions
SensorisinManualONmode
Presspushbutton.IfAutoModeis
desiredchangeActivationModetoAuto.
SensorwasturnedOFFmanually.Ifthe
SensorwasturnedOFFmanuallybefore
thetimedelayexpired,lightswillremain
OFFfortheremainderofthetimedelay
PressthepushbuttontoturnthelightsbackON
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer
Powerinterruption
Checkincomingvoltageand/orwiring
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer
Powerinterruption
Checkincomingvoltageand/orwiring
ON/OFFButtonDisabled
MoveDIPSwitch7down
Note:DoNotadjustsensitivityhigherthannecessary.
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit
per relay. Both circuits must be fed from the same phase.
DIP Switch Settings
DIP Switch Legend
Time Delay
Activation
Relay 1
DIP Switch
1
2
15 Sec Test/Auto*
Auto
Manual
5 Minutes
15 Minutes
30 Minutes
*Self-Adjusts to
10 min. user
mode
Troubleshooting
PIR Sensitivity Walk-Through Mode
ON/OFF Button
Override
Not Used
Maintain Lights On
Not Used
Not Used
3
4
6
5
Full
50%
Disable
Enable
7
Enable
Disable
8
Disable
Enable
9
10
Either
Both
11
12
Default =
1
2
3
4
5
6
7
8
9
10 11 12
Checkout and Adjustment
AdjustmentsshouldbemadewiththeHVACsystemONsothattheinstallerwillbeabletodetecttheeffectofairflowonthe
operationoftheONW-D-1001-347.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopower-upandstabilize.
Self-Adjust
Sensorisshippedinself-adjustmode.Thisappliestotime
delay,USandPIRsensitivity.InpreparationfortheInstaller
Test,thetimedelayissetto15seconds,afterthesensoris
Red (PIR) & Green (US)
installed,poweredONandhasstabilized,theunitwilltimeDetection LEDs
out15secondsafterthelastmotiondetected.Coverageand
PIR Lens
sensitivitycanbeconfirmedbywatchingtheGreen(US)and
Ultrasonic Detection
Daylight
Red(PIR)indicatorLEDsonthefrontofthesensor,while
Sensor Level
Ultrasonic
movingaroundtheroom.
Adjustment
Sensitivity
Adjustment
1. WalkaroundtheroomandmonitorLEDs.
2. Standindifferentpartsoftheroomandwaveyour
DIP Switches
hands.LEDsshouldonlyturnONforonesecondwith
eachmotion.(IfLEDsdonotturnON,gotoInstaller
Adjustments–SensitivityAdjustmentSection)
3. Standstillthreetofourfeetawayfromsensorfor
fiveseconds.LEDsshouldnotturnON.(IfanyLED
ON/OFF Button
turnsON,noteLEDandgotoInstallerAdjustments–
SensitivityAdjustmentssection)
4. Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
5. Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection)
6. Atthispointyoucanexittheroomandletthesensortime-out.Whenthesensortimes-outandisOFFwithpowerONforfive
minutes,theunitwillgotoa10minuteTimeDelayusermodesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch12outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
PIR Sensitivity
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheRedLEDdoesnotturnON,checkforanyobstructions.
3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnot
turnON.
4. IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPswitch5up.
2. Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
3. AdjustUltrasonicSensitivity.
ON/OFF Disabled Feature
1. ON/OFFButtonDisableOption–Whenselected
thisoptiondisablestheON/OFFbuttonandsensor
becomesautomaticonlycontrolregardlessofthe
settingforautomaticormanualactivation.Thisfeature
willnotallowsomeonetoturnlight(s)OFFviathe
pushbuttonwhilepeopleareincommonareassuchas
restroom,breakroomandcopyroomareas.
1
2
3
4
5
6
7
8
9
Lights
Will Not
Turn ON
manually
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
10 11 12
Daylight Adjustments
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis
enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom,the
sensorwillallowthelightstoturnONwhenoccupied.ThesensorwillnotallowtheDaylightingfeaturetoturntheloadOFFuntilthe
spaceisvacantorthelightlevelrisesabovethesetpointandthetimedelayexpires.WhileinManualActivationMode,ifsomeone
attemptstoturntheloadONandthereissufficientdaylightavailabletheDaylightingfeaturewillholdthelightsOFF.
1. Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Ifthisfeatureisnotneeded,leavethe
lightlevelatmaximum(fullyCW).
2. Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPswitch8outofitscurrentposition,wait
3secondsandthenbackintoitsoriginalposition.
3. Setthelightleveltominimum(fullyCCW).
4. Letthesensortime-outsolightsareOFF.Enterthe
spaceandlightsshouldremainOFF.
5. Makesurenottoblockthesensorfromthedaylight
sourceandadjustthelightlevelpotentiometerCWin
smallincrements.(Pause5secondsbetween
1 2 3 4 5 6 7 8 9 10 11 12
1 and 2
eachadjustment)
6. LightswillnotturnONuponoccupancyactivation,
whentheambientlightlevelexceedsthedaylight
thresholdsetting.
Lights
Will Not
Turn OFF
automatically
Lights
Will Not
Turn OFF
manually
Override
MakesuresensorisnotinOverrideMode
Self-Adjust
IfsensorisinSelf-AdjustMode,itmaybe
possiblefortheunittohaveincreasedthetime
delaytoa30minutedelay.Ifthelightsdonot
turnOFFafter30minutesfollownextstep.
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep
UltrasonicSensitivitysetHigh
Lowersensitivitybyturninggreen
potentiometerCCWinsmalldecrements
PIRactivatedbyheatsource
otherthanoccupant
MoveDIPSwitch5up
CallTechnicalServices
ON/OFFButtonDisabled
MoveDIPSwitch7down
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10minutes.As
longastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,by
alternatelymakingslightadjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbenoneedfor
manualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPswitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPswitches1and2down.(IfDIPswitches1and2arealreadydown,
toggleDIPswitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1. MoveDIPswitch12up.
2. ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF.