Installation Instructions NeoSwitch Dual Technology Single Relay Occupancy Sensing Wall Switch

advertisement
Installation Instructions
P/N 9850-000323-01
NeoSwitch Dual Technology Single Relay
Occupancy Sensing Wall Switch
(Ground Required)
General Information
• Readallinstructionsonbothsidesofthis
sheetfirst
Coverage
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
36
,
• WiretheONW-D-1001-MVasdescribedinthewiringsection
• MounttheONW-D-1001-MVinthejunctionbox
Minor Motion, IR
Major Motion, IR
PIR Technology
Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperature
thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
US Technology
Thesensorproducesalowintensity,inaudiblesound.Itdetectsoccupancyfromchangesintheacousticwaves
causedbymotion,suchasreachingforatelephone,turningapageinabook,walkingintoaroom,turningina
swivelchair,etc.Thesensordoesnotrespondtoaudiblesound.
DualTechnologysensorsensurethegreatestsensitivityandcoveragefortoughapplicationsthussavingadditional
energy.PIRisusedtoturnthelightsONandtheneitherorbothtechnologiesareusedtokeepthelightsON.
TheONW-D-1001-MVallowsthecontrolofoneloadwithoneoccupancysensorswitch.
ThesensorcanbeconfiguredtoenhanceenergysavingsbysettingtheunitforManualONoperation.
InAutomaticONMode,thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,the
lightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,thelightsstayON
aslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyaftera
presettimedelayinterval.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime
delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy
savingsthatareavailableintheparticularapplication.
TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
Walk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.The
sensorwillswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetect
motion20secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minutetimedelay.
ON/OFFButtonDisableOption–WhenselectedthisoptiondisablestheON/OFFbutton(s)andsensorbecomes
automaticonlycontrol.
Wiring
,
8
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
,
10
,
8
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
15
Description
TheONW-D-1001-MVOccupancySensingWallSwitchisaPassiveInfrared(PIR)andUltrasonic(US)motion
sensinglightingcontrolandconventionalwallswitchall-in-one,usedforenergysavingsandconvenience.
ThesensorcombinesPIRandUStechnologiestomonitoraroomforoccupancy.
ONW-D-1001-MV-W
ONW-D-1001-MV-V
ONW-D-1001-MV-LA
ONW-D-1001-MV-G
ONW-D-1001-MV-B
TheONW-D-1001-MVcanbeinstalledinanystandardsinglegangbox.Itmaybe
installedinthesamemannerasanordinarywallswitch.
,
20
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%non-condensing
Housing:Durable,injectionmoldedhousing.ABSresin
complieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.195"Hx1.732"W(106.553mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752"
Wx1.9"D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;
GreenLEDindicatesUltrasonicdetection.
#
#
#
#
#
Installation
TheONW-D-1001-MVisdesignedforofficesupto300squarefeet.
Specifications
Technology:PassiveInfrared(PIR)andUltrasonic(US)
Electrical Ratings:
120VAC:
• Incandescent/Tungsten–
Max.load:6.7amps,800W,50/60Hz
• Fluorescent/Ballast–
Max.load:10amps,1200W,50/60Hz
MotorLoad:¼HP@125VAC
277VAC:
• Fluorescent/Ballast–
Max.load:9.8amps,2700W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Model
Model
Model
Model
Model
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
,
20
,
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the
main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations
should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1.MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsfor
allconnections.)
3.Mountunittowallbox.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.Installwallswitchplate.
Location
Wiring Diagram 1:
WheninstallingtheONW-D-1001-MVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearlineof-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheONW-D-1001-MVdirectlyintothehallway
whereitmaydetectpassers-by.
120/277 VAC single level
single circuit wiring diagram
120/277 VAC
BLUE
BLACK
GREEN
LOAD
GROUND
NEUTRAL
Wiring Diagram 2:
120/277 VAC
BLACK
BLUE
120/277 VAC single level
switch dual level wiring using a
toggle switch wiring diagram
GREEN
LOAD 1
LOAD 2
GROUND
NEUTRAL
A/B SWITCHING USING TOGGLE
SWITCH TO TURN OFF SECOND LOAD
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Installer Adjustments
Wiring Diagram 3: 120/277 VAC single level single circuit three-way wiring diagram
TRAVELLER
WIRES
120/277 VAC
BLUE
BLUE
BLACK
GREEN
BLACK
GREEN
LOAD 1
GROUND
GROUND
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit
per relay. Both circuits must be fed from the same phase.
DIP Switch Settings
DIP Switch Legend
Time Delay
Activation
Relay 1
1
2
PIR Sensitivity Walk-Through Mode
ON/OFF Button
Override
Not Used
Maintain Lights On
4
6
5
7
8
9
10
Auto
Full
Disable
Enable
Disable
Either
5 Minutes
Manual
50%
Enable
Disable
Enable
Both
30 Minutes
*Self-Adjusts to
10 min. user
mode
Not Used
Not Used
3
15 Minutes
15 Sec Test/Auto*
Sensitivity Adjustments
Ultrasonic Sensitivity(GreenLED)–Usingasmallflatheadscrewdriverturnthe
greenpotentiometersothatthearrowpointsUP.
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthe
greenpotentiometerclockwiseinsmallincrements.RepeatStep1.
3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshould
notturnON.
4. IfGreenLEDturnsONwithoutmotionorisconstantlyON,decreasethe
USsensitivitybyturninggreenpotentiometercounter-clockwiseinsmall
decrements.RepeatStep3.
Issue
Lights
Will Not
Turn ON
automatically
Possible Causes
Suggestions
SensorisinManualONmode
Presspushbutton.IfAutoMode
isdesiredchangeActivationModetoAuto.
SensorwasturnedOFFmanually.Ifthe
SensorwasturnedOFFmanuallybefore
thetimedelayexpired,lightswillremain
OFFfortheremainderofthetimedelay.
PressthepushbuttontoturnthelightsbackON.
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer.
Powerinterruption
Checkincomingvoltageand/orwiring
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer.
Powerinterruption
Checkincomingvoltageand/orwiring
ON/OFFButtonDisabled
MoveDIPSwitch7down
Note:DoNotadjustsensitivityhigherthannecessary.
NEUTRAL
DIP Switch
Troubleshooting
11
12
Default =
1
2
3
4
5
6
7
8
9
10 11 12
Checkout and Adjustment
AdjustmentsshouldbemadewiththeHVACsystemONsothattheinstallerwillbeabletodetecttheeffectofairflowonthe
operationoftheONW-D-1001-MV.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopower-upandstabilize.
Self-Adjust
Sensorisshippedinself-adjustmode.Thisappliestotime
delay,USandPIRsensitivity.InpreparationfortheInstaller
Test,thetimedelayissetto15seconds,afterthesensoris
Red (PIR) & Green (US)
installed,poweredONandhasstabilized,theunitwilltimeDetection LEDs
PIR Lens
out15secondsafterthelastmotiondetected.Coverageand
sensitivitycanbeconfirmedbywatchingtheGreen(US)and
Ultrasonic Detection
Daylight
Red(PIR)indicatorLEDsonthefrontofthesensor,while
Sensor Level
Ultrasonic
Adjustment
Sensitivity
movingaroundtheroom.
Adjustment
1. WalkaroundtheroomandmonitorLEDs.
2. Standindifferentpartsoftheroomandwaveyour
DIP Switches
hands.LEDsshouldonlyturnONforonesecondwith
eachmotion.(IfLEDsdonotturnON,gotoInstaller
Adjustments–SensitivityAdjustmentSection)
3. Standstillthreetofourfeetawayfromsensorforfive
ON/OFF Button
seconds.LEDsshouldnotturnON.(IfanyLEDturnsON,
noteLEDandgotoInstallerAdjustments–Sensitivity
Adjustmentssection)
4. Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
5. Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection)
6. Atthispointyoucanexittheroomandletthesensortime-out.Whenthesensortimes-outandisOFFwithpowerONforfive
minutes,theunitwillgotoa10minuteTimeDelayusermodesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch12outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
PIR Sensitivity
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheRedLEDdoesnotturnON,checkforanyobstructions.
3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4. IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
2. Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
3. AdjustUltrasonicSensitivity.
ON/OFF Disabled Feature
1. ON/OFFButtonDisableOption–Whenselectedthis
optiondisablestheON/OFFbuttonandsensorbecomes
automaticonlycontrolregardlessofthesettingfor
automaticormanualactivation.Thisfeaturewillnot
allowsomeonetoturnlight(s)OFFviathepushbutton
whilepeopleareincommonareassuchasrestroom,
breakroom,andcopyroomareas.
1
2
3
4
5
6
7
8
9
Lights
Will Not
Turn ON
manually
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
10 11 12
Daylight Adjustments
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis
enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom,the
sensorwillallowthelightstoturnONwhenoccupied.ThesensorwillnotallowtheDaylightingfeaturetoturntheloadOFFuntilthe
spaceisvacantorthelightlevelrisesabovethesetpointandthetimedelayexpires.WhileinManualActivationMode,ifsomeone
attemptstoturntheloadONandthereissufficientdaylightavailabletheDaylightingfeaturewillholdthelightsOFF.
1. Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Ifthisfeatureisnotneeded,leavethe
lightlevelatmaximum(fullyCW).
2. Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait
3secondsandthenbackintoitsoriginalposition.
3. SettheLightleveltominimum(fullyCCW).
4. LetthesensorTime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF.
5. MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmallincrements.
(Pause5secondsbetweeneachadjustment)
6. LightswillnotturnONuponoccupancyactivation,whentheambientlightlevelexceedsthedaylightthresholdsetting.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftime
mayneedalongertimedelaythanthedefaultsettingof10
minutes.Aslongastheself-adjustingfeatureisenabled,the
switchwillrespondtoeachpairoffalse-OFFswithnonormal
OFFinbetween,byalternatelymakingslightadjustmentsto
eithertimedelay(by2minuteincrements)orsensitivity,so
1 2 3 4 5 6 7 8 9 10 11 12
1 and 2
thereshouldbenoneedformanualadjustment.Ifmanual
adjustmentisdesired,refertoTimeDelaysettingsinDIP
Switchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIP
Switches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrentposition,wait3seconds,
andthenbacktoitsoriginalposition)
Lights
Will Not
Turn OFF
automatically
Lights
Will Not
Turn OFF
manually
Override
MakesuresensorisnotinOverrideMode.(DIPSwitch8up)
Self-Adjust
IfsensorisinSelf-AdjustMode,itmaybepossibleforthe
unittohaveincreasedthetimedelaytoa30minutedelay.
IfthelightsdonotturnOFFafter30minutesfollownextstep.
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesetTimeDelay,checknextstep.
UltrasonicSensitivitysetHigh
Lowersensitivitybyturninggreen
potentiometerCCWinsmalldecrements.
PIRactivatedbyheatsourceotherthanoccupant
MoveDIPSwitch5up.
CallTechnicalServices
ON/OFFButtonDisabled
MoveDIPSwitch7down
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1. MoveDIPSwitch12up.
2. ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF.
Printed in Malaysia