Installation Instructions P/N 9850-000323-01 NeoSwitch Dual Technology Single Relay Occupancy Sensing Wall Switch (Ground Required) General Information • Readallinstructionsonbothsidesofthis sheetfirst Coverage • InstallinaccordancewithALLlocalcodes • Forindooruseonly 36 , • WiretheONW-D-1001-MVasdescribedinthewiringsection • MounttheONW-D-1001-MVinthejunctionbox Minor Motion, IR Major Motion, IR PIR Technology Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperature thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone. US Technology Thesensorproducesalowintensity,inaudiblesound.Itdetectsoccupancyfromchangesintheacousticwaves causedbymotion,suchasreachingforatelephone,turningapageinabook,walkingintoaroom,turningina swivelchair,etc.Thesensordoesnotrespondtoaudiblesound. DualTechnologysensorsensurethegreatestsensitivityandcoveragefortoughapplicationsthussavingadditional energy.PIRisusedtoturnthelightsONandtheneitherorbothtechnologiesareusedtokeepthelightsON. TheONW-D-1001-MVallowsthecontrolofoneloadwithoneoccupancysensorswitch. ThesensorcanbeconfiguredtoenhanceenergysavingsbysettingtheunitforManualONoperation. InAutomaticONMode,thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,the lightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,thelightsstayON aslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyaftera presettimedelayinterval. Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy savingsthatareavailableintheparticularapplication. TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight. Walk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.The sensorwillswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetect motion20secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minutetimedelay. ON/OFFButtonDisableOption–WhenselectedthisoptiondisablestheON/OFFbutton(s)andsensorbecomes automaticonlycontrol. Wiring , 8 Minor Motion, Ultrasonic Major Motion, Ultrasonic , 10 , 8 Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. 15 Description TheONW-D-1001-MVOccupancySensingWallSwitchisaPassiveInfrared(PIR)andUltrasonic(US)motion sensinglightingcontrolandconventionalwallswitchall-in-one,usedforenergysavingsandconvenience. ThesensorcombinesPIRandUStechnologiestomonitoraroomforoccupancy. ONW-D-1001-MV-W ONW-D-1001-MV-V ONW-D-1001-MV-LA ONW-D-1001-MV-G ONW-D-1001-MV-B TheONW-D-1001-MVcanbeinstalledinanystandardsinglegangbox.Itmaybe installedinthesamemannerasanordinarywallswitch. , 20 Coverage:Majormotion–1000sq.ft. Minormotion–300sq.ft. Light Level Sensing:0to200foot-candles Operating Environment: • Temperature:32°F–104°F(0°C–40°C) • RelativeHumidity:20%to90%non-condensing Housing:Durable,injectionmoldedhousing.ABSresin complieswithUL94VO. Size: • MountingPlate/StrapDimensions: 4.195"Hx1.732"W(106.553mmx44mm) • ProductHousingDimensions:2.618"Hx1.752" Wx1.9"D(66.5mmx44.5mmx48.26mm) LED Indicators:RedLEDindicatesPIRdetection; GreenLEDindicatesUltrasonicdetection. # # # # # Installation TheONW-D-1001-MVisdesignedforofficesupto300squarefeet. Specifications Technology:PassiveInfrared(PIR)andUltrasonic(US) Electrical Ratings: 120VAC: • Incandescent/Tungsten– Max.load:6.7amps,800W,50/60Hz • Fluorescent/Ballast– Max.load:10amps,1200W,50/60Hz MotorLoad:¼HP@125VAC 277VAC: • Fluorescent/Ballast– Max.load:9.8amps,2700W,50/60Hz Ballast Compatibility:Compatiblewithmagneticand electronicballasts No Minimum Load Requirement Time Delays:Self-Adjusting,15seconds/test(10min Auto),Selectable5,15,30minutes Model Model Model Model Model The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. , 20 , CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. 1.MakesurepoweristurnedOFFatthebranchcircuitbreaker. 2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsfor allconnections.) 3.Mountunittowallbox. 4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize. 5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection) 6.Installwallswitchplate. Location Wiring Diagram 1: WheninstallingtheONW-D-1001-MVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearlineof-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheONW-D-1001-MVdirectlyintothehallway whereitmaydetectpassers-by. 120/277 VAC single level single circuit wiring diagram 120/277 VAC BLUE BLACK GREEN LOAD GROUND NEUTRAL Wiring Diagram 2: 120/277 VAC BLACK BLUE 120/277 VAC single level switch dual level wiring using a toggle switch wiring diagram GREEN LOAD 1 LOAD 2 GROUND NEUTRAL A/B SWITCHING USING TOGGLE SWITCH TO TURN OFF SECOND LOAD Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com Installer Adjustments Wiring Diagram 3: 120/277 VAC single level single circuit three-way wiring diagram TRAVELLER WIRES 120/277 VAC BLUE BLUE BLACK GREEN BLACK GREEN LOAD 1 GROUND GROUND THREE-WAY WIRING DIAGRAM: LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT. CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per relay. Both circuits must be fed from the same phase. DIP Switch Settings DIP Switch Legend Time Delay Activation Relay 1 1 2 PIR Sensitivity Walk-Through Mode ON/OFF Button Override Not Used Maintain Lights On 4 6 5 7 8 9 10 Auto Full Disable Enable Disable Either 5 Minutes Manual 50% Enable Disable Enable Both 30 Minutes *Self-Adjusts to 10 min. user mode Not Used Not Used 3 15 Minutes 15 Sec Test/Auto* Sensitivity Adjustments Ultrasonic Sensitivity(GreenLED)–Usingasmallflatheadscrewdriverturnthe greenpotentiometersothatthearrowpointsUP. 1. Standindifferentareasoftheroomandwaveyourhands. 2. IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthe greenpotentiometerclockwiseinsmallincrements.RepeatStep1. 3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshould notturnON. 4. IfGreenLEDturnsONwithoutmotionorisconstantlyON,decreasethe USsensitivitybyturninggreenpotentiometercounter-clockwiseinsmall decrements.RepeatStep3. Issue Lights Will Not Turn ON automatically Possible Causes Suggestions SensorisinManualONmode Presspushbutton.IfAutoMode isdesiredchangeActivationModetoAuto. SensorwasturnedOFFmanually.Ifthe SensorwasturnedOFFmanuallybefore thetimedelayexpired,lightswillremain OFFfortheremainderofthetimedelay. PressthepushbuttontoturnthelightsbackON. DaylightingFeatureEnabled IfalllightsarerequiredtoturnON adjustdaylightpotentiometer. Powerinterruption Checkincomingvoltageand/orwiring DaylightingFeatureEnabled IfalllightsarerequiredtoturnON adjustdaylightpotentiometer. Powerinterruption Checkincomingvoltageand/orwiring ON/OFFButtonDisabled MoveDIPSwitch7down Note:DoNotadjustsensitivityhigherthannecessary. NEUTRAL DIP Switch Troubleshooting 11 12 Default = 1 2 3 4 5 6 7 8 9 10 11 12 Checkout and Adjustment AdjustmentsshouldbemadewiththeHVACsystemONsothattheinstallerwillbeabletodetecttheeffectofairflowonthe operationoftheONW-D-1001-MV.Useonlyinsulatedtoolstomakeadjustments. Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopower-upandstabilize. Self-Adjust Sensorisshippedinself-adjustmode.Thisappliestotime delay,USandPIRsensitivity.InpreparationfortheInstaller Test,thetimedelayissetto15seconds,afterthesensoris Red (PIR) & Green (US) installed,poweredONandhasstabilized,theunitwilltimeDetection LEDs PIR Lens out15secondsafterthelastmotiondetected.Coverageand sensitivitycanbeconfirmedbywatchingtheGreen(US)and Ultrasonic Detection Daylight Red(PIR)indicatorLEDsonthefrontofthesensor,while Sensor Level Ultrasonic Adjustment Sensitivity movingaroundtheroom. Adjustment 1. WalkaroundtheroomandmonitorLEDs. 2. Standindifferentpartsoftheroomandwaveyour DIP Switches hands.LEDsshouldonlyturnONforonesecondwith eachmotion.(IfLEDsdonotturnON,gotoInstaller Adjustments–SensitivityAdjustmentSection) 3. Standstillthreetofourfeetawayfromsensorforfive ON/OFF Button seconds.LEDsshouldnotturnON.(IfanyLEDturnsON, noteLEDandgotoInstallerAdjustments–Sensitivity Adjustmentssection) 4. Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller AdjustmentsSection) 5. Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection) 6. Atthispointyoucanexittheroomandletthesensortime-out.Whenthesensortimes-outandisOFFwithpowerONforfive minutes,theunitwillgotoa10minuteTimeDelayusermodesetting. Note:ToplaceintoTestMode,toggleDIPSwitch12outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition. PIR Sensitivity 1. Standindifferentareasoftheroomandwaveyourhands. 2. IftheRedLEDdoesnotturnON,checkforanyobstructions. 3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON. 4. IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up. Field-of-view outside the space 1. AdjustPIRsensitivityto50%bymovingDIPSwitch5up. 2. Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace. 3. AdjustUltrasonicSensitivity. ON/OFF Disabled Feature 1. ON/OFFButtonDisableOption–Whenselectedthis optiondisablestheON/OFFbuttonandsensorbecomes automaticonlycontrolregardlessofthesettingfor automaticormanualactivation.Thisfeaturewillnot allowsomeonetoturnlight(s)OFFviathepushbutton whilepeopleareincommonareassuchasrestroom, breakroom,andcopyroomareas. 1 2 3 4 5 6 7 8 9 Lights Will Not Turn ON manually If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879 10 11 12 Daylight Adjustments TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom,the sensorwillallowthelightstoturnONwhenoccupied.ThesensorwillnotallowtheDaylightingfeaturetoturntheloadOFFuntilthe spaceisvacantorthelightlevelrisesabovethesetpointandthetimedelayexpires.WhileinManualActivationMode,ifsomeone attemptstoturntheloadONandthereissufficientdaylightavailabletheDaylightingfeaturewillholdthelightsOFF. 1. Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Ifthisfeatureisnotneeded,leavethe lightlevelatmaximum(fullyCW). 2. Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait 3secondsandthenbackintoitsoriginalposition. 3. SettheLightleveltominimum(fullyCCW). 4. LetthesensorTime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF. 5. MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmallincrements. (Pause5secondsbetweeneachadjustment) 6. LightswillnotturnONuponoccupancyactivation,whentheambientlightlevelexceedsthedaylightthresholdsetting. Time Delay Adjustments Peoplewhoremainverystillforlongperiodsoftime mayneedalongertimedelaythanthedefaultsettingof10 minutes.Aslongastheself-adjustingfeatureisenabled,the switchwillrespondtoeachpairoffalse-OFFswithnonormal OFFinbetween,byalternatelymakingslightadjustmentsto eithertimedelay(by2minuteincrements)orsensitivity,so 1 2 3 4 5 6 7 8 9 10 11 12 1 and 2 thereshouldbenoneedformanualadjustment.Ifmanual adjustmentisdesired,refertoTimeDelaysettingsinDIP Switchlegend. ResetsensortimedelaytofactorysettingsbymovingDIP Switches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrentposition,wait3seconds, andthenbacktoitsoriginalposition) Lights Will Not Turn OFF automatically Lights Will Not Turn OFF manually Override MakesuresensorisnotinOverrideMode.(DIPSwitch8up) Self-Adjust IfsensorisinSelf-AdjustMode,itmaybepossibleforthe unittohaveincreasedthetimedelaytoa30minutedelay. IfthelightsdonotturnOFFafter30minutesfollownextstep. 30MinuteDelay Maximumtimedelayis30Minutes.CheckDIP SwitchestoverifyDIPSwitchsettings.Iflightsdo notturnOFFatthesetTimeDelay,checknextstep. UltrasonicSensitivitysetHigh Lowersensitivitybyturninggreen potentiometerCCWinsmalldecrements. PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5up. CallTechnicalServices ON/OFFButtonDisabled MoveDIPSwitch7down If lights will still not turn OFF, call Technical Services at 1-800-553-3879 Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. Override TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure. 1. MoveDIPSwitch12up. 2. ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF. Printed in Malaysia Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com