Installation Instructions NeoSwitch Dual Technology Dual Relay Vacancy Sensing Wall Switch (Ground Required)

advertisement
Installation Instructions
NeoSwitch Dual Technology Dual Relay
Vacancy Sensing Wall Switch
(Ground Required)
P/N 9850-000278-02
General Information
• Readallinstructionsonbothsidesofthis
sheetfirst.
Model # VNW-D-1001-DMV-W
Model # VNW-D-1001-DMV-V
Model # VNW-D-1001-DMV-G
Coverage
• InstallinaccordancewithALLlocalcodes.
• Forindooruseonly.
1.MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.
3.Mountunittowallbox.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.Installwallswitchplate.
TheVNW-D-1001-DMVisdesignedforofficesupto300squarefeet.
36
,
,
20
Specifications
Technology:PassiveInfrared(PIR)andUltrasonic(US)
Electrical Ratings:
120VAC:
• Incandescent/Tungsten–Max.load:6.7amps,
800W,50/60Hz
• Fluorescent/Ballast–Max.load:10amps,1200W,
50/60Hz
MotorLoad:¼HP@125VAC
277VAC:
• Fluorescent/Ballast–Max.load:9.8amps,
2700W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%non-condensing
Housing:Durable,injectionmoldedhousing.
PolycarbonateresincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.195"Hx1.732"W(106.553mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752"
Wx1.9"D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;Green
LEDindicatesUltrasonicdetection.
Minor Motion, IR
Major Motion, IR
,
8
Minor Motion, Ultrasonic
120/277 VAC
,
10
,
BLACK
BLUE
RED
RED
GREEN
8
15
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
,
20
,
TheVNW-D-1001-DMVVacancySensingWallSwitchisaPassiveInfrared(PIR)andUltrasonic(US)motion
sensinglightingcontrolandconventionalwallswitchall-in-one,usedforenergysavingsandconvenience.
ThesensorcombinesPIRandUStechnologiestomonitoraroomforoccupancy.
WheninstallingVNW-D-1001-DMVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearline-ofsightbetweenthesensorandtheareatobecovered.AvoidpointingtheVNW-D-1001-DMVdirectlyintothehallway
whereitmaydetectpassers-by.
• WiretheVNW-D-1001-DMVasdescribedinthewiringsection.
• MounttheVNW-D-1001-DMVinthejunctionbox.
LOAD 2
LOAD 1
Wiring Diagram 2:
120/277 VAC dual level
dual circuit wiring diagram
CIRCUIT 1
120/277 VAC
BLACK
BLUE
CIRCUIT 2
120/277 VAC
RED
RED
GREEN
GROUND
NEUTRAL
Wiring Diagram 3: 120/277 VAC dual level single circuit three-way wiring diagram
TRAVELER
WIRES
120/277 VAC
BLACK
BLUE
RED
RED
GREEN
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF
at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main
switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be
in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects
of cycling.
LOAD 1
NEUTRAL
Installation
TheVNW-D-1001-DMVcanbeinstalledinanystandardsinglegangbox.Itmaybe
installedinthesamemannerasanordinarywallswitch.
LOAD 2
GROUND
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
Location
US Technology
Thesensorproducesalowintensity,inaudiblesound.Itdetectsoccupancyfromchangesintheacousticwaves
causedbymotion,suchasreachingforatelephone,turningapageinabook,walkingintoaroom,turningina
swivelchair,etc.Thesensordoesnotrespondtoaudiblesound.
TheVNW-D-1001-DMVallowsthecontroloftwoseparateloadswithoneoccupancysensorswitch.
ThelightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.ThelightsstayONaslong
asthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyafterapreset
timedelayinterval.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime
delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy
savingsthatareavailableintheparticularapplication.
TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
BathroomMode–Whenselected,bathroommodekeepsthesecondrelayONforanadditional8minutes,after
thefirstrelayhasbeenturnedOFF.Combinethiswithchangingthepushbuttontothelight/fangraphicandyounow
havetheuniversallyrecognizedandeasytousebathroomsolution.
RelaySwapOption–Acommonprobleminelectricwiringiswiringthewrongswitchtothewrongload.Thiscan
makecontrolofloadsconfusingtoanenduser.TheRelaySwapoptionsolvestheproblembyallowingtheswitch
buttonsonthefaceoftheunittobeswapped,aftertheunitiswiredandinstalled.
120/277 VAC dual level
single circuit wiring diagram
Major Motion, Ultrasonic
Description
PIR Technology
Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperature
thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
Wiring Diagram 1:
GROUND
BLUE
RED
LOAD 2
LOAD 1
BLACK
RED
GREEN
GROUND
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED
ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect
only one circuit per relay. Both circuits must be fed from the same phase.
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
DIP Switch Settings
DIP Switch Legend
Time Delay
DIP Switch
Not Used
PIR Sensitivity
Maintain Lights On
Not Used
Override
Bathroom
Relay Swap
Daylighting
Relay 1
1
2
3
4
5
6
7
8
9
10
Relay 2
11
12
Full
Either
Disable
Disable
Normal
Disable
Disable
5 Minutes
50%
Both
Enable
Enable
Swap
Enable
Enable
15 Minutes
30 Minutes
Auto*
*Self-Adjusts to
10 min. user
mode
PIR Sensitivity
1.Standindifferentareasoftheroomandwaveyourhands.
2.IftheRedLEDdoesnotturnON,checkforanyobstructions.
3.Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4.IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
2. Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
3. AdjustUltrasonicSensitivity.
Default =
1
2
3
4
5
6
7
8
9
10 11 12
Checkout and Adjustment
AdjustmentsshouldbemadewiththeHVACsystemonsothattheinstallerwillbeabletodetecttheeffectof
airflowontheoperationoftheVNW-D-1001-DMV.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopowerup
andstabilize.
Self-Adjust
SensorisshippedinSelf-AdjustMode.ThisappliestoTime
Red (PIR) & Green (US)
Detection LEDs
Delay,USandPIRsensitivity.InpreparationfortheInstallerTest,
PIR Lens
thetimedelayissetto15seconds,afterthesensorisinstalled,
Ultrasonic Detection
Daylight
poweredONandhasstabilized,theunitwilltime-out15seconds
Sensor Level
Ultrasonic
Adjustment
Sensitivity
afterthelastmotiondetected.Coverageandsensitivitycanbe
Adjustment
confirmedbywatchingtheGreen(US)andRed(PIR)indicatorLEDs
DIP Switches
onthefrontofthesensor,whilemovingaroundtheroom.
1.WalkaroundtheroomandmonitorLEDs.
2.Standindifferentpartsoftheroomandwaveyourhands.
LEDsshouldonlyturnONforonesecondwitheachmotion.
(IfLEDdoesnotturnON,gotoInstallerAdjustmentSection)
ON/OFF Buttons
1&2
3.Standstillthreetofourfeetawayfromsensorforfive
seconds.LEDsshouldnotturnON.(IfLEDdoesturnON,go
toInstallerAdjustmentSection)
4.Walkoutsidetheroomandwait15secondsforthelightsto
turnOFF.(IflightsdonotturnOFFgotoInstallerAdjustmentsSection)
5.Re-entertheroomandmanuallyactivatethesensor.(IflightsdonotturnONgotoTroubleshootingSection)
6.Atthispointyoucanexittheroomandletthesensortime-out.Whenthesensortimes-outandisOFFforfive
minutes,theunitwillgotoa10minuteTimeDelayusermodesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch12outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
Installer Adjustments
Sensitivity Adjustments
UltrasonicSensitivity(GreenLED)–Usingasmallflatheadscrew
driverturnthegreenpotentiometersothatthearrowpointsUP.
1.Standindifferentareasoftheroomandwaveyourhands.
2.IftheGreenLEDdoesnotturnON,increasetheUSsensitivityby
turningthegreenpotentiometerclockwiseinsmallincrements.
RepeatStep1.
3.Standstillthreetofourfeetawayfromsensorforfiveseconds.
LEDshouldnotturnON.
4.IfGreenLEDturnsONwithoutmotionorisconstantlyON
decreasetheUSsensitivitybyturninggreenpotentiometer
counter-clockwiseinsmalldecrements.RepeatStep3.
Daylight Adjustments
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthere
isenoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom,
thesensorwillallowthelightstoturnON.TheDaylightingfeatureallowstheselectionofwhichrelaytocontrolviaDaylighting
(dualloadmodelsonly).ThesensorwillnotallowtheDaylightingfeaturetoturntheloadOFFuntilthespaceisvacantifthe
lightlevelrisesabovethesetpointandthetimedelayexpires.IfsomeoneattemptstoturntheloadONandthereissufficient
daylightavailabletheDaylightingfeaturewillholdthelightsOFF.
1.Setthelightlevelwhentheambientlightisatthelevel
wherenoartificiallightisneeded.Ifthisfeatureisnot
needed,leavethelightlevelatmaximum(fullyCW).
2.SetDIPSwitches11(Relay1)and/or12(Relay2)for
11 12
11 and 12
daylightcontrol.
3.Withtheload(s)ON,putthesensorintoTestMode.To
placeintoTestMode,toggleDIPSwitch12outofits
currentposition,wait3secondsandthenbackintoits
originalposition.
4.SettheLightleveltominimum(fullyCCW).
5.Letthesensortime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF.
6.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
increments.(Pause5secondsbetweeneachadjustment)
7.LightswillnotturnONuponmanualactivation,whentheambientlightlevelexceedsthedaylightthresholdsetting.
1
2
3
4
5
6
7
8
9
10
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10
minutes.Aslongastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairoffalseoffswithnonormal
offinbetween,byalternatelymakingslightadjustmentsto
eithertimedelay(by2minuteincrements)orsensitivity,so
thereshouldbenoneedformanualadjustment.Ifmanual
adjustmentisdesired,refertoTimeDelaysettingsinDIP
Switchlegend.
1 2
1 and 2
ResetsensorTimeDelaytofactorysettingsbymoving
DIPSwitches1and2down.(IfDIPSwitches1and2
arealreadydown,toggleDIPSwitch1outofitscurrent
position,wait3seconds,andthenbacktoitsoriginalposition)
3
4
5
6
7
8
Troubleshooting
Issue
Lights
Will Not
Turn ON
manually
Possible Causes
Suggestions
DaylightFeatureEnabled
IfalllightsarerequiredadjustDIPSwitches
11and12and/ordaylightpotentiometer.
Powerinterruption
Checkincomingvoltageand/orwiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override
MakesuresensorisnotinOverrideMode(DIPSwitch8up).
Self-Adjust
IfsensorisinSelf-AdjustMode,itmaybepossibleforthe
unittohaveincreasedtheTimeDelaytoa30minutedelay.
IfthelightsdonotturnOFFafter30minutesfollownextstep.
30MinuteDelay
MaximumTimeDelayis30Minutes.CheckDIPSwitches
toverifyDIPSwitchsettings.IflightsdonotturnOFFatthe
setTimeDelay,checknextstep.
UltrasonicSensitivitysetHigh
Lowersensitivitybyturninggreen
potentiometerCCWinsmalldecrements.
PIRactivatedbyheatsourceotherthanoccupant
MoveDIPSwitch5up.
Lights
Will Not
Turn OFF
manually
CallTechnicalServices
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
9 10 11 12
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1.MoveDIPSwitch8up.
2.ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF.
Note:DoNotadjustsensitivityhigherthannecessary.
Printed in Malaysia