Installation Instructions NeoSwitch Dual Technology Dual Relay Vacancy Sensing Wall Switch (Ground Required) P/N 9850-000278-02 General Information • Readallinstructionsonbothsidesofthis sheetfirst. Model # VNW-D-1001-DMV-W Model # VNW-D-1001-DMV-V Model # VNW-D-1001-DMV-G Coverage • InstallinaccordancewithALLlocalcodes. • Forindooruseonly. 1.MakesurepoweristurnedOFFatthebranchcircuitbreaker. 2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements. 3.Mountunittowallbox. 4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize. 5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection) 6.Installwallswitchplate. TheVNW-D-1001-DMVisdesignedforofficesupto300squarefeet. 36 , , 20 Specifications Technology:PassiveInfrared(PIR)andUltrasonic(US) Electrical Ratings: 120VAC: • Incandescent/Tungsten–Max.load:6.7amps, 800W,50/60Hz • Fluorescent/Ballast–Max.load:10amps,1200W, 50/60Hz MotorLoad:¼HP@125VAC 277VAC: • Fluorescent/Ballast–Max.load:9.8amps, 2700W,50/60Hz Ballast Compatibility:Compatiblewithmagneticand electronicballasts No Minimum Load Requirement Time Delays:Self-Adjusting,15seconds/test(10min Auto),Selectable5,15,30minutes Coverage:Majormotion–1000sq.ft. Minormotion–300sq.ft. Light Level Sensing:0to200foot-candles Operating Environment: • Temperature:32°F–104°F(0°C–40°C) • RelativeHumidity:20%to90%non-condensing Housing:Durable,injectionmoldedhousing. PolycarbonateresincomplieswithUL94VO. Size: • MountingPlate/StrapDimensions: 4.195"Hx1.732"W(106.553mmx44mm) • ProductHousingDimensions:2.618"Hx1.752" Wx1.9"D(66.5mmx44.5mmx48.26mm) LED Indicators:RedLEDindicatesPIRdetection;Green LEDindicatesUltrasonicdetection. Minor Motion, IR Major Motion, IR , 8 Minor Motion, Ultrasonic 120/277 VAC , 10 , BLACK BLUE RED RED GREEN 8 15 The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. , 20 , TheVNW-D-1001-DMVVacancySensingWallSwitchisaPassiveInfrared(PIR)andUltrasonic(US)motion sensinglightingcontrolandconventionalwallswitchall-in-one,usedforenergysavingsandconvenience. ThesensorcombinesPIRandUStechnologiestomonitoraroomforoccupancy. WheninstallingVNW-D-1001-DMVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearline-ofsightbetweenthesensorandtheareatobecovered.AvoidpointingtheVNW-D-1001-DMVdirectlyintothehallway whereitmaydetectpassers-by. • WiretheVNW-D-1001-DMVasdescribedinthewiringsection. • MounttheVNW-D-1001-DMVinthejunctionbox. LOAD 2 LOAD 1 Wiring Diagram 2: 120/277 VAC dual level dual circuit wiring diagram CIRCUIT 1 120/277 VAC BLACK BLUE CIRCUIT 2 120/277 VAC RED RED GREEN GROUND NEUTRAL Wiring Diagram 3: 120/277 VAC dual level single circuit three-way wiring diagram TRAVELER WIRES 120/277 VAC BLACK BLUE RED RED GREEN Wiring CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. LOAD 1 NEUTRAL Installation TheVNW-D-1001-DMVcanbeinstalledinanystandardsinglegangbox.Itmaybe installedinthesamemannerasanordinarywallswitch. LOAD 2 GROUND Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. Location US Technology Thesensorproducesalowintensity,inaudiblesound.Itdetectsoccupancyfromchangesintheacousticwaves causedbymotion,suchasreachingforatelephone,turningapageinabook,walkingintoaroom,turningina swivelchair,etc.Thesensordoesnotrespondtoaudiblesound. TheVNW-D-1001-DMVallowsthecontroloftwoseparateloadswithoneoccupancysensorswitch. ThelightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.ThelightsstayONaslong asthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyafterapreset timedelayinterval. Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy savingsthatareavailableintheparticularapplication. TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight. BathroomMode–Whenselected,bathroommodekeepsthesecondrelayONforanadditional8minutes,after thefirstrelayhasbeenturnedOFF.Combinethiswithchangingthepushbuttontothelight/fangraphicandyounow havetheuniversallyrecognizedandeasytousebathroomsolution. RelaySwapOption–Acommonprobleminelectricwiringiswiringthewrongswitchtothewrongload.Thiscan makecontrolofloadsconfusingtoanenduser.TheRelaySwapoptionsolvestheproblembyallowingtheswitch buttonsonthefaceoftheunittobeswapped,aftertheunitiswiredandinstalled. 120/277 VAC dual level single circuit wiring diagram Major Motion, Ultrasonic Description PIR Technology Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperature thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone. Wiring Diagram 1: GROUND BLUE RED LOAD 2 LOAD 1 BLACK RED GREEN GROUND NEUTRAL THREE-WAY WIRING DIAGRAM: LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT. CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per relay. Both circuits must be fed from the same phase. Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com DIP Switch Settings DIP Switch Legend Time Delay DIP Switch Not Used PIR Sensitivity Maintain Lights On Not Used Override Bathroom Relay Swap Daylighting Relay 1 1 2 3 4 5 6 7 8 9 10 Relay 2 11 12 Full Either Disable Disable Normal Disable Disable 5 Minutes 50% Both Enable Enable Swap Enable Enable 15 Minutes 30 Minutes Auto* *Self-Adjusts to 10 min. user mode PIR Sensitivity 1.Standindifferentareasoftheroomandwaveyourhands. 2.IftheRedLEDdoesnotturnON,checkforanyobstructions. 3.Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON. 4.IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up. Field-of-view outside the space 1. AdjustPIRsensitivityto50%bymovingDIPSwitch5up. 2. Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace. 3. AdjustUltrasonicSensitivity. Default = 1 2 3 4 5 6 7 8 9 10 11 12 Checkout and Adjustment AdjustmentsshouldbemadewiththeHVACsystemonsothattheinstallerwillbeabletodetecttheeffectof airflowontheoperationoftheVNW-D-1001-DMV.Useonlyinsulatedtoolstomakeadjustments. Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopowerup andstabilize. Self-Adjust SensorisshippedinSelf-AdjustMode.ThisappliestoTime Red (PIR) & Green (US) Detection LEDs Delay,USandPIRsensitivity.InpreparationfortheInstallerTest, PIR Lens thetimedelayissetto15seconds,afterthesensorisinstalled, Ultrasonic Detection Daylight poweredONandhasstabilized,theunitwilltime-out15seconds Sensor Level Ultrasonic Adjustment Sensitivity afterthelastmotiondetected.Coverageandsensitivitycanbe Adjustment confirmedbywatchingtheGreen(US)andRed(PIR)indicatorLEDs DIP Switches onthefrontofthesensor,whilemovingaroundtheroom. 1.WalkaroundtheroomandmonitorLEDs. 2.Standindifferentpartsoftheroomandwaveyourhands. LEDsshouldonlyturnONforonesecondwitheachmotion. (IfLEDdoesnotturnON,gotoInstallerAdjustmentSection) ON/OFF Buttons 1&2 3.Standstillthreetofourfeetawayfromsensorforfive seconds.LEDsshouldnotturnON.(IfLEDdoesturnON,go toInstallerAdjustmentSection) 4.Walkoutsidetheroomandwait15secondsforthelightsto turnOFF.(IflightsdonotturnOFFgotoInstallerAdjustmentsSection) 5.Re-entertheroomandmanuallyactivatethesensor.(IflightsdonotturnONgotoTroubleshootingSection) 6.Atthispointyoucanexittheroomandletthesensortime-out.Whenthesensortimes-outandisOFFforfive minutes,theunitwillgotoa10minuteTimeDelayusermodesetting. Note:ToplaceintoTestMode,toggleDIPSwitch12outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition. Installer Adjustments Sensitivity Adjustments UltrasonicSensitivity(GreenLED)–Usingasmallflatheadscrew driverturnthegreenpotentiometersothatthearrowpointsUP. 1.Standindifferentareasoftheroomandwaveyourhands. 2.IftheGreenLEDdoesnotturnON,increasetheUSsensitivityby turningthegreenpotentiometerclockwiseinsmallincrements. RepeatStep1. 3.Standstillthreetofourfeetawayfromsensorforfiveseconds. LEDshouldnotturnON. 4.IfGreenLEDturnsONwithoutmotionorisconstantlyON decreasetheUSsensitivitybyturninggreenpotentiometer counter-clockwiseinsmalldecrements.RepeatStep3. Daylight Adjustments TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthere isenoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom, thesensorwillallowthelightstoturnON.TheDaylightingfeatureallowstheselectionofwhichrelaytocontrolviaDaylighting (dualloadmodelsonly).ThesensorwillnotallowtheDaylightingfeaturetoturntheloadOFFuntilthespaceisvacantifthe lightlevelrisesabovethesetpointandthetimedelayexpires.IfsomeoneattemptstoturntheloadONandthereissufficient daylightavailabletheDaylightingfeaturewillholdthelightsOFF. 1.Setthelightlevelwhentheambientlightisatthelevel wherenoartificiallightisneeded.Ifthisfeatureisnot needed,leavethelightlevelatmaximum(fullyCW). 2.SetDIPSwitches11(Relay1)and/or12(Relay2)for 11 12 11 and 12 daylightcontrol. 3.Withtheload(s)ON,putthesensorintoTestMode.To placeintoTestMode,toggleDIPSwitch12outofits currentposition,wait3secondsandthenbackintoits originalposition. 4.SettheLightleveltominimum(fullyCCW). 5.Letthesensortime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF. 6.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall increments.(Pause5secondsbetweeneachadjustment) 7.LightswillnotturnONuponmanualactivation,whentheambientlightlevelexceedsthedaylightthresholdsetting. 1 2 3 4 5 6 7 8 9 10 Time Delay Adjustments Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10 minutes.Aslongastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairoffalseoffswithnonormal offinbetween,byalternatelymakingslightadjustmentsto eithertimedelay(by2minuteincrements)orsensitivity,so thereshouldbenoneedformanualadjustment.Ifmanual adjustmentisdesired,refertoTimeDelaysettingsinDIP Switchlegend. 1 2 1 and 2 ResetsensorTimeDelaytofactorysettingsbymoving DIPSwitches1and2down.(IfDIPSwitches1and2 arealreadydown,toggleDIPSwitch1outofitscurrent position,wait3seconds,andthenbacktoitsoriginalposition) 3 4 5 6 7 8 Troubleshooting Issue Lights Will Not Turn ON manually Possible Causes Suggestions DaylightFeatureEnabled IfalllightsarerequiredadjustDIPSwitches 11and12and/ordaylightpotentiometer. Powerinterruption Checkincomingvoltageand/orwiring. If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879 Lights Will Not Turn OFF automatically Override MakesuresensorisnotinOverrideMode(DIPSwitch8up). Self-Adjust IfsensorisinSelf-AdjustMode,itmaybepossibleforthe unittohaveincreasedtheTimeDelaytoa30minutedelay. IfthelightsdonotturnOFFafter30minutesfollownextstep. 30MinuteDelay MaximumTimeDelayis30Minutes.CheckDIPSwitches toverifyDIPSwitchsettings.IflightsdonotturnOFFatthe setTimeDelay,checknextstep. UltrasonicSensitivitysetHigh Lowersensitivitybyturninggreen potentiometerCCWinsmalldecrements. PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5up. Lights Will Not Turn OFF manually CallTechnicalServices If lights will still not turn OFF, call Technical Services at 1-800-553-3879 Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. 9 10 11 12 Override TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure. 1.MoveDIPSwitch8up. 2.ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF. Note:DoNotadjustsensitivityhigherthannecessary. Printed in Malaysia Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com