Installation Instructions Ultrasonic Ceiling Mounted Low Voltage Vacancy Sensor Model # VAC-U-0501-R Model # VAC-U-1000-R Model # VAC-U-2000-R Ultrasonic Activated P/N 9850-000198-01 Wiring CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. 12 ft (3.65 m) 0 1.Makesurepoweristurnedoffatthebranchcircuitbreaker. 2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsfor allconnections)CAPALLUNUSEDWIRELEADS. 3.Mountunittoceiling,junctionbox,orroundfixturewithraceway. 4.Turnpowerbackonatthebranchcircuitbreakerandwait2minutesfortheunittostabilize. 5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection) 12 ft (3.65 m) 16 ft (4.87 m) 20 ft (6.096m) 32 ft (9.75 m) 23 ft 15 ft (7.01 m) (4.57 m) 10 ft (3 m) Minor Motion, Ultrasonic Description Major Motion, Ultrasonic 5 ft (1.52 m) 0 5 ft (1.52 m) 10 ft (3 m) 23 ft 15 ft (4.57 m) (7.01 m) 32 ft (9.75 m) Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. One Sensor, One Switchpack The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. TheVAC-UCeilingMountLowVoltageVacancySensorisanUltrasonic(US)motionsensinglightingcontrol,used forenergysavingsandconvenience.Thesensorproducesalowintensity,inaudiblesoundtodetectoccupancy VAC-U-2000-R Coverage Diagram inaroom.Changesinthesensor’sacousticwavecausedbymotion,suchaswalkingintheroom,reachingfora telephoneorswivelinginachair,willmaintainthelightsON.Thesensordoesnotrespondtoaudiblesound.Whena Location manualswitchisused,thebluewireiselectronicallyconnectedtotheredwire,energizingtherelayintheswitchpack Themaximumcoverageareamayvarysomewhataccordingtoroomshapeandthepresenceofobstacles.Decrease toturnontheload.Ifvacancyisdetected,thebluewireisdisconnectedfromthered,causingtherelaytoopen totalcoverageareaby15%for“soft”rooms(forexample,heavydraperiesorheavycarpeting).Thesensormusthavea turningOFFtheload.Theredleadis10-30VDCsupply,theblackleadiscommonandtheblueistherelaycontrol. Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime clearviewoftheareatobecontrolled.Thesensorwillnot“see”throughglass.Mountingheightshouldnotexceed12 feet.Optimummountingheightis8to10feet.Mountthesensorsothegrillesfacetheopenportionoftheroomandare delayinreal-time. notfacinganearbywall,door,windoworotherobstructingobject.Avoidpointingintohallways.Mountingatfixtureheight ismosteffective.*Topreventfalseactivation,thesensorshouldbemountedawayfromtheairsupplyductaminimumof 4to6feet. Coverage Hot Red Blue Black Brown Yellow Purple Gray Orange White/Brown Line Neutral **Use black lead for 120 VAC Use orange lead for 277 VAC Cap unused lead. Manual ON Control of Two Standard Switchpacks 20 ft (6.096m) 12 ft (3.65 m) 30 ft 9.14 m 9 ft (2.74 m) Hot Line Neutral **Use black lead for 120 VAC Use orange lead for 277 VAC Cap unused lead. Red (15 VDC) Blue (Control) Black (Common) 0 0 20 ft (6.096m) Minor Motion, Ultrasonic Major Motion, Ultrasonic Installation TheVAC-Usensorcanbemountedtotheceiling,junctionbox,orroundfixturewithraceway. 20 ft (6.096m) 5 ft (1.52 m) 10 ft (3.05 m) 15 ft (4.57 m) 23 ft (7.01 m) Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. VAC-U-0501-R Coverage Diagram 23 ft (7.01 m) 15 ft 17 ft 10 ft (5.18 m) (4.57 m) (3 m) Minor Motion, Ultrasonic Major Motion, Ultrasonic 5 ft (1.5 m) 0 5 ft (1.5 m) 10 ft 15 ft 17 ft (3 m) (4.57 m) (5.18 m) Manual Mode Operation: Switches are required to turn corresponding loads ON. Lights turn OFF when sensor times out or with the switch. 23 ft (7.01 m) Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. OAC-STEM Threaded Rod (sold separately) VAC-U-1000-R Coverage Diagram Hot Red Blue Black Brown Yellow Purple Gray Orange White/Brown If daylight sensor is enabled and light level is above setpoint, switchpack connected to yellow lead will not turn ON. Recommended Wire: 18-3 AWG Stranded Wire non/shielded. Line Neutral **Use black lead for 120 VAC Use orange lead for 277 VAC Cap unused lead. Red (15 VDC) Blue (Control) Black (Common) SWITCHPACK Blue VAC-U-0501 White 12 ft (3.65 m) Blue **Hot 9 ft (2.74 m) 12 ft (3.65 m) SWITCHPACK Load 1 DT1k VAC-U-1000 & OAC-U-2000 9 ft (2.74 m) Blue Black (Common) Red (10-30 VDC) Blue (Control - Occupancy) Yellow (Control - Occupancy and Daylight) Brown (Switch-Blue Lead Control) Brown/White (Switch-Yellow Lead Control) Sensor's Isolated Relay Orange (Normally Open) Gray (Common) Purple (Normally Closed) Model GMDS - Load 1 (Normally Open Momentary Switch) 12 ft (3.65 m) 15 ft 4.57 m Load 1 SENSOR WIRE LEAD LEGEND If daylight sensor is enabled and light level is above setpoint, switchpack connected to yellow lead will not turn ON. Recommended Wire: 18-3 AWG Stranded Wire non/shielded. 15 ft 4.57 m 30 ft 9.14 m 20 ft (6.096m) 9 ft (2.74 m) SWITCHPACK Red (15 VDC) Blue (Control) Black (Common) Manual Mode Operation: Switches are required to turn corresponding loads ON. Lights turn OFF when sensor times out or with the switch. Blue • BASwithIsolatedFormCRelay(-Rmodel) • IsolatedFormCRelayRatings:1A30VDC/VAC Operating Environment: • Temperature:32°F–104°F(0°C–40°C) • RelativeHumidity:upto90%non-condensing White Power Requirements: Input: • 0-30VDCfromGreengateSwitchpackor Greengatesystem.Maximumcurrentneededis 25mApersensor Output: • Opencollectoroutputtoswitchuptoten GreengateSwitchpacks **Hot Specifications Blue • ForUsewithGreengateSwitchpacks& SystemsOnly • DonotrunanyGreengateLowVoltageWiringin thesameconduitaspowerconductors White • Readallinstructionsonbothsidesofthis sheetfirst • InstallinaccordancewithALLlocalcodes • Forindooruseonly 20 ft (6.096m) 16 ft (4.87 m) **Hot General Information Load 2 Blue Model GMDS - Load 2 (Normally Open Momentary Switch) Model GMDS - Load 1 (Normally Open Momentary Switch) Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com DIP Switch Settings Not Used Not Used Not Used LEDs Override Sweep Full/Half Logic HVAC/Tracking (-R model only) Daylight Sensor Adjustment Zero Time Delay (-R model only) Ultrasonic Sensitivity Adjustment Daylight Adjustments (-R Model Only 0 to 300 foot-candles) Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyclockwise). TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom,thesensor willallowthelightstoturnONwhenoccupied. Full and Half Logic Modes (SeeDIPSwitchlegend): InbothFullandHalfLogicmodes,lightsconnectedtotheyellowcontrolleadwillnotturnONuponoccupancyactivation,should theambientlightlevelexceedthepresetfoot-candlelevel. After activation: FullLogicMode–shouldtheambientlightlevelexceedthepresetfoot-candlelevel,thelightsconnectedtotheyellowcontrol leadwillturnOFF.ThelightswillremainOFF,untiltheambientlightlevelfallsbelowthesetpoint. HalfLogicMode–theoutputstateoftheyellowcontrolleadwillnotchangewithambientlightchanges,afteroccupancy activation.Iftheamountofnaturallightavailablerisesabovethesetpoint,thedaylightsensorwillnotturnthelightsOFFwhile occupancyisbeingdetected. ON 1 2 3 4 5 6 7 8 9 10 11 12 Checkout and Adjustment LED Indicators Functionality During Installer/Test Mode While in User Mode LED Flashing Speed LEDswillflashonceper¼second LEDswillflashoncepersecond Duration 10minutes 10to30minutes AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments. Self-Adjust SensorisshippedintheSelf-AdjustMode.ThisappliestotimedelayandUSsensitivity.InpreparationfortheInstallerTest,the timedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,theunitwilltime-out15secondsafter thelastmotiondetected.CoverageandsensitivitycanbeconfirmedbywatchingtheGreen(US)indicatorLEDsonthefrontofthe sensor,whilemovingaroundtheroom. 1. WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONfor¼secondwitheachmotion.(IfLEDsdonotturnON, gotoInstallerAdjustments–SensitivityAdjustmentsSection) 2. Standstillsixtoeightfeetawayfromthesensorforfiveseconds.LEDsshouldnotturnON.(IfanyLEDturnsON,noteLED andgotoInstallerAdjustments–SensitivityAdjustmentsection) 3. Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller AdjustmentsSection) 4. Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection) 5. TheunitwillremaininTestModefor10minutesthenautomaticallyexitTestModeandgofor10min.TimeDelayUser Modesetting. Note: ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.Toforce into10minUserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrentposition, wait3seconds,andthenbacktoitsoriginalposition)WhileinTestMode,theLEDswillflashonceper1/4second. Installer Adjustments Sensitivity Adjustments Ultrasonic Sensitivity (GreenLED)–Usingasmallflatheadscrewdriverturnthegreenpotentiometersothatthearrowpointsup. 1. Standindifferentareasoftheroomandwaveyourhands. 2. IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthegreenpotentiometerclockwiseinsmall increments.RepeatStep1. 3. Standstillsixtoeightfeetawayfromsensorforfiveseconds.LEDshouldnotturnON. 4. IfGreenLEDturnsONwithoutmotionorisconstantlyONdecreasetheUSsensitivitybyturningthegreenpotentiometer counter-clock-wiseinsmalldecrements.RepeatStep3. Field-of-view outside the space 1. AdjustUltrasonicsensitivity. Note: Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Inorderforthisfeaturetofunction, theyellowcontrolleadmustbewired. 1. WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3 secondsandthenbackintoitsoriginalposition. 2. SetDIPSwitch10toFullorHalfLogicMode. 3. Setthelightleveltominimum(fullyCCW). 4. Leavetheroomandletthesensortime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF. 5. MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmallincrementsuntil thelightsareON.(Pause5secondsbetweeneachadjustment) 6. OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethecurrentillumination. Time Delay Adjustments Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10minutes.Aslong asAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,byalternatelymakingslight adjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbenoneedformanualadjustment.Ifmanual adjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend. ResetsensortimedelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggle DIPSwitch10outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition) Manual Mode (-R Model Only) InManualONMode,themomentarylowvoltageswitch(es)isrequiredtoturntheload(s)ON.Onceactivatedthesensorwillmaintain thelightsONuntilmotionceasesandthetimedelayexpires.WhiletheroomisoccupiedtheBASrelayremainsactive.Afterthetime delayexpires,theload(s)willautomaticallybeturnedOFFandtheswitch(es)mustbeusedtoturntheload(s)ONunlessthereismotion detectedwithinthe10secondre-triggerperiod. Troubleshooting Issue Possible Causes Suggestions Lights Will Not Turn ON manually DaylightingFeatureEnabled IfalllightsarerequiredadjustDIPSwitch10 and/ordaylightpotentiometer Powerinterruption Checkincomingvoltageand/orwiring If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879 Lights Will Not Turn OFF automatically Lights Will Not Turn OFF manually Override MakesuresensorisnotinOverrideMode (DIPSwitch8up) Sensorinstalledclosetoanairvent Sensorsshouldbeinstalledminimum4-6feetaway fromanyairventandoutofpathofheavyairflow Sensorinstalledclosetoindirectlighting Sensorsshouldbemountedawayfromindirectlighting Self-adjust Itmaybepossiblefortheunittohaveself-adjusted thetimedelaytoa30minutedelay.Ifthelightsdo notturnOFFafter30minutesfollownextstep. 30MinuteDelay Maximumtimedelayis30Minutes.CheckDIP SwitchestoverifyDIPSwitchsettings.Iflightsdo notturnOFFatthesettimedelay,checknextstep. Bypass Checkwiringtomakesuresensor orswitchpackarenotbypassed Override MakesuresensorisnotinOverrideMode (DIPSwitch8up) If lights will still not turn OFF, call Technical Services at 1-800-553-3879 Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. Lighting Sweep Option Ifselected,thisDIPSwitchoptionforcesaninitial60seconddelayupon“power-up”topreventfalseactivationinbuildingswith computercontrolsystems. 1. MoveDIPSwitch9up.Ifnotselected(DipSwitch9down),uponinitial“power-up”orrestorationofpowerthesensorwillforcethe lightsONnomatterthestateofoccupancy. HVAC/Tracking Mode (-R model only) Ifselected,TrackingModeallowstheloadconnectiontotheFormCrelaytofollowthestateofthesensor’sbluelead.HVACMode allowstheloadconnectedtotheFormCrelaytoremainONwhenthelightsareturnedOFFmanually.Applicationsmayincludekeeping theroomatadesiredtemperaturewhilegivingapresentationandthelightsareOFF. Zero Time Delay Mode InZeroTimeDelayMode,theoutputisactuatedforonesecondtosignalanotherdevicethatthespacebeingmonitoredisoccupied. Applicationsmayincludetheuseofalightingcontrolsystemtomanagethedelayofthelightingdeactivation.Pleaseseethewiring diagramsectionforwiringdetails. WheninZeroTimeDelayModeandTrackingModetheloadconnectedtotheFormCrelayshallfollowthestateofthesensor’sblue lead(zeroTimeDelayfortheformCrelay). WheninZeroTimeDelayModeandHVACMode,theloadconnectedtotheFormCrelayremainsONforthestandardTimeDelay. Override TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure. 1. MoveDIPSwitch8up. WhileinOverrideMode,theoptionallowvoltagemomentaryswitch(es)willtogglethelightingload(s). Printed in Malaysia Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com