Installation Instructions Wiring General Information Model # VAC-U-0501-R

advertisement
Installation Instructions
Ultrasonic Ceiling Mounted Low
Voltage Vacancy Sensor
Model # VAC-U-0501-R
Model # VAC-U-1000-R
Model # VAC-U-2000-R
Ultrasonic
Activated
P/N 9850-000198-01
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the
main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations
should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
12 ft
(3.65 m)
0
1.Makesurepoweristurnedoffatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsfor
allconnections)CAPALLUNUSEDWIRELEADS.
3.Mountunittoceiling,junctionbox,orroundfixturewithraceway.
4.Turnpowerbackonatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
12 ft
(3.65 m)
16 ft
(4.87 m)
20 ft
(6.096m)
32 ft
(9.75 m)
23 ft
15 ft
(7.01 m) (4.57 m)
10 ft
(3 m)
Minor Motion, Ultrasonic
Description
Major Motion, Ultrasonic
5 ft
(1.52 m)
0
5 ft
(1.52 m)
10 ft
(3 m)
23 ft
15 ft
(4.57 m) (7.01 m)
32 ft
(9.75 m)
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
One Sensor, One Switchpack
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
TheVAC-UCeilingMountLowVoltageVacancySensorisanUltrasonic(US)motionsensinglightingcontrol,used
forenergysavingsandconvenience.Thesensorproducesalowintensity,inaudiblesoundtodetectoccupancy
VAC-U-2000-R Coverage Diagram
inaroom.Changesinthesensor’sacousticwavecausedbymotion,suchaswalkingintheroom,reachingfora
telephoneorswivelinginachair,willmaintainthelightsON.Thesensordoesnotrespondtoaudiblesound.Whena Location
manualswitchisused,thebluewireiselectronicallyconnectedtotheredwire,energizingtherelayintheswitchpack
Themaximumcoverageareamayvarysomewhataccordingtoroomshapeandthepresenceofobstacles.Decrease
toturnontheload.Ifvacancyisdetected,thebluewireisdisconnectedfromthered,causingtherelaytoopen
totalcoverageareaby15%for“soft”rooms(forexample,heavydraperiesorheavycarpeting).Thesensormusthavea
turningOFFtheload.Theredleadis10-30VDCsupply,theblackleadiscommonandtheblueistherelaycontrol.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime clearviewoftheareatobecontrolled.Thesensorwillnot“see”throughglass.Mountingheightshouldnotexceed12
feet.Optimummountingheightis8to10feet.Mountthesensorsothegrillesfacetheopenportionoftheroomandare
delayinreal-time.
notfacinganearbywall,door,windoworotherobstructingobject.Avoidpointingintohallways.Mountingatfixtureheight
ismosteffective.*Topreventfalseactivation,thesensorshouldbemountedawayfromtheairsupplyductaminimumof
4to6feet.
Coverage
Hot
Red
Blue
Black
Brown
Yellow
Purple
Gray
Orange
White/Brown
Line
Neutral
**Use black lead for 120 VAC
Use orange lead for 277 VAC
Cap unused lead.
Manual ON Control of
Two Standard Switchpacks
20 ft
(6.096m)
12 ft
(3.65 m)
30 ft
9.14 m
9 ft
(2.74 m)
Hot
Line
Neutral
**Use black lead for 120 VAC
Use orange lead for 277 VAC
Cap unused lead.
Red (15 VDC)
Blue (Control)
Black (Common)
0
0
20 ft
(6.096m)
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
Installation
TheVAC-Usensorcanbemountedtotheceiling,junctionbox,orroundfixturewithraceway.
20 ft
(6.096m)
5 ft
(1.52 m)
10 ft
(3.05 m)
15 ft
(4.57 m)
23 ft
(7.01 m)
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
VAC-U-0501-R Coverage Diagram
23 ft
(7.01 m)
15 ft
17 ft
10 ft
(5.18 m) (4.57 m) (3 m)
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
5 ft
(1.5 m)
0
5 ft
(1.5 m)
10 ft 15 ft
17 ft
(3 m) (4.57 m) (5.18 m)
Manual Mode Operation:
Switches are required to
turn corresponding loads ON.
Lights turn OFF when sensor
times out or with the
switch.
23 ft
(7.01 m)
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
OAC-STEM Threaded Rod
(sold separately)
VAC-U-1000-R Coverage Diagram
Hot
Red
Blue
Black
Brown
Yellow
Purple
Gray
Orange
White/Brown
If daylight sensor is
enabled and light level is
above setpoint, switchpack
connected to yellow lead
will not turn ON.
Recommended Wire:
18-3 AWG Stranded Wire
non/shielded.
Line
Neutral
**Use black lead for 120 VAC
Use orange lead for 277 VAC
Cap unused lead.
Red (15 VDC)
Blue (Control)
Black (Common)
SWITCHPACK
Blue
VAC-U-0501
White
12 ft
(3.65 m)
Blue
**Hot
9 ft
(2.74 m)
12 ft
(3.65 m)
SWITCHPACK
Load 1
DT1k
VAC-U-1000 & OAC-U-2000
9 ft
(2.74 m)
Blue
Black
(Common)
Red
(10-30 VDC)
Blue
(Control - Occupancy)
Yellow
(Control - Occupancy and Daylight)
Brown
(Switch-Blue Lead Control)
Brown/White (Switch-Yellow Lead Control)
Sensor's Isolated Relay
Orange (Normally Open)
Gray
(Common)
Purple
(Normally Closed)
Model GMDS - Load 1
(Normally Open
Momentary Switch)
12 ft
(3.65 m)
15 ft
4.57 m
Load 1
SENSOR WIRE LEAD LEGEND
If daylight sensor is
enabled and light level is
above setpoint, switchpack
connected to yellow lead
will not turn ON.
Recommended Wire:
18-3 AWG Stranded Wire
non/shielded.
15 ft
4.57 m
30 ft
9.14 m
20 ft
(6.096m)
9 ft
(2.74 m)
SWITCHPACK
Red (15 VDC)
Blue (Control)
Black (Common)
Manual Mode Operation:
Switches are required to
turn corresponding loads ON.
Lights turn OFF when sensor
times out or with the
switch.
Blue
• BASwithIsolatedFormCRelay(-Rmodel)
• IsolatedFormCRelayRatings:1A30VDC/VAC
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:upto90%non-condensing
White
Power Requirements:
Input:
• 0-30VDCfromGreengateSwitchpackor
Greengatesystem.Maximumcurrentneededis
25mApersensor
Output:
• Opencollectoroutputtoswitchuptoten
GreengateSwitchpacks
**Hot
Specifications
Blue
• ForUsewithGreengateSwitchpacks&
SystemsOnly
• DonotrunanyGreengateLowVoltageWiringin
thesameconduitaspowerconductors
White
• Readallinstructionsonbothsidesofthis
sheetfirst
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
20 ft
(6.096m)
16 ft
(4.87 m)
**Hot
General Information
Load 2
Blue
Model GMDS - Load 2
(Normally Open
Momentary Switch)
Model GMDS - Load 1
(Normally Open
Momentary Switch)
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
DIP Switch Settings
Not Used
Not Used
Not Used
LEDs
Override
Sweep
Full/Half Logic HVAC/Tracking
(-R model only)
Daylight Sensor Adjustment
Zero Time Delay
(-R model only)
Ultrasonic Sensitivity Adjustment
Daylight Adjustments (-R Model Only 0 to 300 foot-candles)
Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyclockwise).
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis
enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom,thesensor
willallowthelightstoturnONwhenoccupied.
Full and Half Logic Modes (SeeDIPSwitchlegend):
InbothFullandHalfLogicmodes,lightsconnectedtotheyellowcontrolleadwillnotturnONuponoccupancyactivation,should
theambientlightlevelexceedthepresetfoot-candlelevel.
After activation:
FullLogicMode–shouldtheambientlightlevelexceedthepresetfoot-candlelevel,thelightsconnectedtotheyellowcontrol
leadwillturnOFF.ThelightswillremainOFF,untiltheambientlightlevelfallsbelowthesetpoint.
HalfLogicMode–theoutputstateoftheyellowcontrolleadwillnotchangewithambientlightchanges,afteroccupancy
activation.Iftheamountofnaturallightavailablerisesabovethesetpoint,thedaylightsensorwillnotturnthelightsOFFwhile
occupancyisbeingdetected.
ON
1 2 3 4 5 6
7 8 9 10 11 12
Checkout and Adjustment
LED Indicators Functionality
During Installer/Test Mode
While in User Mode
LED Flashing Speed
LEDswillflashonceper¼second
LEDswillflashoncepersecond
Duration
10minutes
10to30minutes
AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments.
Self-Adjust
SensorisshippedintheSelf-AdjustMode.ThisappliestotimedelayandUSsensitivity.InpreparationfortheInstallerTest,the
timedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,theunitwilltime-out15secondsafter
thelastmotiondetected.CoverageandsensitivitycanbeconfirmedbywatchingtheGreen(US)indicatorLEDsonthefrontofthe
sensor,whilemovingaroundtheroom.
1. WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONfor¼secondwitheachmotion.(IfLEDsdonotturnON,
gotoInstallerAdjustments–SensitivityAdjustmentsSection)
2. Standstillsixtoeightfeetawayfromthesensorforfiveseconds.LEDsshouldnotturnON.(IfanyLEDturnsON,noteLED
andgotoInstallerAdjustments–SensitivityAdjustmentsection)
3. Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
4. Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection)
5. TheunitwillremaininTestModefor10minutesthenautomaticallyexitTestModeandgofor10min.TimeDelayUser
Modesetting.
Note: ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.Toforce
into10minUserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrentposition,
wait3seconds,andthenbacktoitsoriginalposition)WhileinTestMode,theLEDswillflashonceper1/4second.
Installer Adjustments
Sensitivity Adjustments
Ultrasonic Sensitivity (GreenLED)–Usingasmallflatheadscrewdriverturnthegreenpotentiometersothatthearrowpointsup.
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthegreenpotentiometerclockwiseinsmall
increments.RepeatStep1.
3. Standstillsixtoeightfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4. IfGreenLEDturnsONwithoutmotionorisconstantlyONdecreasetheUSsensitivitybyturningthegreenpotentiometer
counter-clock-wiseinsmalldecrements.RepeatStep3.
Field-of-view outside the space
1. AdjustUltrasonicsensitivity.
Note: Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Inorderforthisfeaturetofunction,
theyellowcontrolleadmustbewired.
1. WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3
secondsandthenbackintoitsoriginalposition.
2. SetDIPSwitch10toFullorHalfLogicMode.
3. Setthelightleveltominimum(fullyCCW).
4. Leavetheroomandletthesensortime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF.
5. MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmallincrementsuntil
thelightsareON.(Pause5secondsbetweeneachadjustment)
6. OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethecurrentillumination.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10minutes.Aslong
asAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,byalternatelymakingslight
adjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbenoneedformanualadjustment.Ifmanual
adjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggle
DIPSwitch10outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Manual Mode (-R Model Only)
InManualONMode,themomentarylowvoltageswitch(es)isrequiredtoturntheload(s)ON.Onceactivatedthesensorwillmaintain
thelightsONuntilmotionceasesandthetimedelayexpires.WhiletheroomisoccupiedtheBASrelayremainsactive.Afterthetime
delayexpires,theload(s)willautomaticallybeturnedOFFandtheswitch(es)mustbeusedtoturntheload(s)ONunlessthereismotion
detectedwithinthe10secondre-triggerperiod.
Troubleshooting
Issue
Possible Causes
Suggestions
Lights
Will Not
Turn ON
manually
DaylightingFeatureEnabled
IfalllightsarerequiredadjustDIPSwitch10
and/ordaylightpotentiometer
Powerinterruption
Checkincomingvoltageand/orwiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Lights Will Not
Turn OFF
manually
Override
MakesuresensorisnotinOverrideMode
(DIPSwitch8up)
Sensorinstalledclosetoanairvent
Sensorsshouldbeinstalledminimum4-6feetaway
fromanyairventandoutofpathofheavyairflow
Sensorinstalledclosetoindirectlighting
Sensorsshouldbemountedawayfromindirectlighting
Self-adjust
Itmaybepossiblefortheunittohaveself-adjusted
thetimedelaytoa30minutedelay.Ifthelightsdo
notturnOFFafter30minutesfollownextstep.
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep.
Bypass
Checkwiringtomakesuresensor
orswitchpackarenotbypassed
Override
MakesuresensorisnotinOverrideMode
(DIPSwitch8up)
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Lighting Sweep Option
Ifselected,thisDIPSwitchoptionforcesaninitial60seconddelayupon“power-up”topreventfalseactivationinbuildingswith
computercontrolsystems.
1. MoveDIPSwitch9up.Ifnotselected(DipSwitch9down),uponinitial“power-up”orrestorationofpowerthesensorwillforcethe
lightsONnomatterthestateofoccupancy.
HVAC/Tracking Mode (-R model only)
Ifselected,TrackingModeallowstheloadconnectiontotheFormCrelaytofollowthestateofthesensor’sbluelead.HVACMode
allowstheloadconnectedtotheFormCrelaytoremainONwhenthelightsareturnedOFFmanually.Applicationsmayincludekeeping
theroomatadesiredtemperaturewhilegivingapresentationandthelightsareOFF.
Zero Time Delay Mode
InZeroTimeDelayMode,theoutputisactuatedforonesecondtosignalanotherdevicethatthespacebeingmonitoredisoccupied.
Applicationsmayincludetheuseofalightingcontrolsystemtomanagethedelayofthelightingdeactivation.Pleaseseethewiring
diagramsectionforwiringdetails.
WheninZeroTimeDelayModeandTrackingModetheloadconnectedtotheFormCrelayshallfollowthestateofthesensor’sblue
lead(zeroTimeDelayfortheformCrelay).
WheninZeroTimeDelayModeandHVACMode,theloadconnectedtotheFormCrelayremainsONforthestandardTimeDelay.
Override
TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure.
1. MoveDIPSwitch8up.
WhileinOverrideMode,theoptionallowvoltagemomentaryswitch(es)willtogglethelightingload(s).
Printed in Malaysia
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com