Installation Instructions Passive Infrared Ceiling Mounted Low Voltage Vacancy Sensor Model # VAC-P-0500-R Model # VAC-P-1500-R P/N 9850-000195-01 General Information Wiring 18 ft (5.49 m) • ForUsewithGreengateSwitchpacks& SystemsOnly • DonotrunanyGreengateLowVoltageWiringin thesameconduitaspowerconductors • Readallinstructionsonbothsidesofthis sheetfirst • InstallinaccordancewithALLlocalcodes • Forindooruseonly Specifications 12 ft (3.66 m) 0 Power Requirements: Input: • 10-30VDCfromGreengateSwitchpackor Greengatesystem.Maximumcurrentneededis 25mApersensor Output: • Opencollectoroutputtoswitchuptoten GreengateSwitchpacks. Minor Motion, IR The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. Major Motion, IR • BASwithIsolatedFormCRelay(-Rmodel) • IsolatedFormCRelayRatings:1A30VDC/VAC Operating Environment: • Temperature:32°F–104°F(0°C–40°C) • RelativeHumidity:upto90%non-condensing Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. 12 ft (3.66 m) 18 ft (5.49 m) CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. 1.MakesurepoweristurnedOFFatthebranchcircuitbreaker. 2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsfor allconnectionsCAPALLUNUSEDWIRELEADS. 3.Mountunittoceiling,junctionbox,orroundfixturewithraceway. 4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize. 5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection) 8.5 ft (2.59 m) One Sensor, One Switchpack 3 ft (0.91) 0 30 ft 9.14 m 20 ft (6.096m) 15 ft 4.57 m Hot Line Neutral 15 ft 4.57 m 0 Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. VAC-P-1500 DT1k Major Motion, IR 5 ft (1.5 m) The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. Red (15 VDC) Blue (Control) Black (Common) VAC-P-0500 Installation 15 ft (4.57 m) Red Blue Black Brown Yellow Purple Gray Orange White/Brown Manual Mode Operation: Switches are required to turn corresponding loads ON. Lights turn OFF when sensor times out or with the switch. 20 ft (6.096m) 8.5 ft (2.59 m) 3 ft (0.91) 0 20 ft (6.096m) 15 ft (4.57 m) 10 ft (3 m) 5 ft (1.5 m) 0 5 ft (1.5 m) 10 ft (3 m) 15 ft (4.57 m) 20 ft (6.096m) VAC-P-1500-R Coverage Diagram SWITCHPACK Load 1 Blue Hot TheVAC-Psensorcanbemountedtotheceiling,junctionbox,orroundfixturewithraceway. 10 ft (3 m) **Use black lead for 120 VAC Use orange lead for 277 VAC Cap unused lead. OAC-STEM Threaded Rod (sold separately) If daylight sensor is enabled and light level is above setpoint, switchpack connected to yellow lead will not turn ON. Recommended Wire: 18-3 AWG Stranded Wire non/shielded. Line Neutral **Use black lead for 120 VAC Use orange lead for 277 VAC Cap unused lead. Red (15 VDC) Blue (Control) Black (Common) SWITCHPACK Blue Minor Motion, IR Black (Common) Red (10-30 VDC) Blue (Control - Occupancy) Yellow (Control - Occupancy and Daylight) Brown (Switch-Blue Lead Control) Brown/White (Switch-Yellow Lead Control) Sensor's Isolated Relay Orange (Normally Open) Gray (Common) Purple (Normally Closed) Model GMDS - Load 1 (Normally Open Momentary Switch) Manual ON Control of Two Standard Switchpacks Blue SENSOR WIRE LEAD LEGEND If daylight sensor is enabled and light level is above setpoint, switchpack connected to yellow lead will not turn ON. Recommended Wire: 18-3 AWG Stranded Wire non/shielded. 30 ft 9.14 m 10 ft (3 m) 5 ft (1.5 m) SWITCHPACK Red (15 VDC) Blue (Control) Black (Common) Manual Mode Operation: Switches are required to turn corresponding loads ON. Lights turn OFF when sensor times out or with the switch. Load 1 White 15 ft (4.57 m) Neutral **Use black lead for 120 VAC Use orange lead for 277 VAC Cap unused lead. **Hot Coverage Line Blue VAC-P-0500-R Coverage Diagram TheVAC-PCeilingMountLowVoltageVacancySensorisaPassiveInfrared(PIR)motionsensinglighting control,usedforenergysavingsandconvenience.ThesensorproducesaPassiveInfrared(PIR)motionsensing lightingcontrol,usedforenergysavingsandconvenience.WhenmanuallyturnedON,thebluewireiselectronically Location connectedtotheredwire,energizingtherelayintheswitchpacktoturnONtheload.Ifvacancyisdetected,theblue Themaximumcoverageareamayvarysomewhataccordingtoroomshapeandthepresenceofobstacles.Follow wireisdisconnectedfromthered,causingtherelaytoopenturningOFFtheload.Theredleadis10-30VDCsupply, thecoveragediagramconcerningmajorandminormotioncoverage.Thesensormusthaveaclearviewoftheareato theblackleadiscommon,andtheblueistherelaycontrol. becontrolled.Thesensorwillnot“see”throughglass.Mountingheightshouldnotexceed12feet.Optimummounting Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime heightis8to10feet.Avoidpointingintohallways.Mountingatfixtureheightismosteffective.*Topreventfalse delayinreal-time. activation,thesensorshouldbemountedawayfromtheairsupplyductaminimumof4to6feet. Red Blue Black Brown Yellow Purple Gray Orange White/Brown White 18 ft (5.49 m) **Hot 12 ft (3.66 m) Blue 0 White 12 ft (3.66 m) **Hot Description Hot 18 ft (5.49 m) Load 2 Blue Model GMDS - Load 2 (Normally Open Momentary Switch) Model GMDS - Load 1 (Normally Open Momentary Switch) Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com DIP Switch Settings LEDs Override Sweep Full/Half Logic HVAC/Tracking (-R model only) Zero Time Delay (-R model only) Daylight Sensor Adjustment Daylight Adjustments (-R Model Only 0 to 300 foot-candles) Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyclockwise). TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom,the sensorwillallowthelightstoturnONwhenoccupied. Full and Half Logic Modes(SeeDIPSwitchlegend): InbothFullandHalfLogicmodes,lightsconnectedtotheyellowcontrolleadwillnotturnONuponoccupancyactivation,should theambientlightlevelexceedthepresetfoot-candlelevel. After activation: FullLogicMode–shouldtheambientlightlevelexceedthepresetfoot-candlelevel,thelightsconnectedtotheyellowcontrol leadwillturnOFF.ThelightswillremainOFF,untiltheambientlightlevelfallsbelowthesetpoint. HalfLogicMode–theoutputstateoftheyellowcontrolleadwillnotchangewithambientlightchanges,afteroccupancy activation.Iftheamountofnaturallightavailablerisesabovethesetpoint,thedaylightsensorwillnotturnthelightsOFFwhile occupancyisbeingdetected. PIR Detector ON 1 2 3 4 5 6 7 8 9 10 11 12 Checkout and Adjustment LED Indicators Functionality During Installer/Test Mode While in User Mode LED Flashing Speed LEDswillflashonceper¼second LEDswillflashoncepersecond Duration 10minutes 10to30minutes AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments. Self-Adjust SensorisshippedintheSelf-AdjustMode.ThisappliestotimedelayandPIRsensitivity.InpreparationfortheInstallerTest, thetimedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,theunitwilltime-out15seconds afterthelastmotiondetected.CoverageandsensitivitycanbeconfirmedbywatchingthePassiveInfrared(PIR)indicatorLEDson thefrontofthesensor,whilemovingaroundtheroom. 1. WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONfor¼secondwitheachmotion.(IfLEDsdonotturn ON,gotoInstallerAdjustments–SensitivityAdjustmentsSection) 2. Standstillsixtoeightfeetawayfromthesensorforfiveseconds.LEDsshouldnotturnON.(IfanyLEDturnsON,noteLED andgotoInstallerAdjustments–SensitivityAdjustmentsection) 3. Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller AdjustmentsSection) 4. Re-entertheroomandmanuallyturnthelightsON.(IflightsdonotturnONgotoTroubleshootingSection) 5. TheunitwillremaininTestModefor10minutesthenautomaticallyexitTestModeandgofor10min.TimeDelayUser Modesetting. Note: ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.To forceinto10minUserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrent position,wait3seconds,andthenbacktoitsoriginalposition)WhileinTestMode,theLEDswillflashonceper1/4second. Installer Adjustments Sensitivity Adjustments PIR Sensitivity 1. Standindifferentareasoftheroomandwaveyourhands. 2. IftheRedLEDdoesnotturnON,checkforanyobstructions. 3. Standstillsixtoeightfeetawayfromsensorforfiveseconds.LEDshouldnotturnON. 4. IfRedLEDturnsONwithoutmotionorisconstantlyonadjustPIRsensitivityto50%bymovingDIPSwitch5up. Field-of-view outside the space 1. AdjustPIRsensitivityto50%bymovingDIPSwitch5up. Note:Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Inorderforthisfeauretofunction, theyellowcontrolleadmustbewired. 1. WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait 3secondsandthenbackintoitsoriginalposition. 2. SetDIPSwitch10toFullorHalfLogicMode. 3. Setthelightleveltominimum(fullyCCW). 4. Leavetheroomandletthesensortime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF. 5. MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmallincrementsuntil thelightsareON.(Pause5secondsbetweeneachadjustment) 6. OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethecurrentillumination. Time Delay Adjustments Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10minutes.Aslong asAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,byalternatelymakingslight adjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbenoneedformanualadjustment.Ifmanual adjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend. ResetsensortimedelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2arealreadydown, toggleDIPSwitch10outofitscurrentposition,wait3secondsandthenbacktoitsoriginalposition) Manual Mode InManualONMode,theoptionalmomentarylowvoltageswitch(es)isrequiredtoturntheload(s)ON.Onceactivatedthesensor willmaintainthelightsONuntilmotionceasesandthetimedelayexpires.WhiletheroomisoccupiedtheBASrelayremainsactive. Afterthetimedelayexpires,theload(s)willautomaticallybeturnedOFFandtheswitch(es)mustbeusedtoturntheload(s)ONunless thereismotiondetectedwithinthe10secondre-triggerperiod. Lighting Sweep Option Ifselected,thisDIPSwitchoptionforcesaninitial60seconddelayupon“power-up”topreventfalseactivationinbuildingswith computercontrolsystems. 1. MoveDIPSwitch9up.Ifnotselected(DipSwitch9down),uponinitial“power-up”orrestorationofpowerthesensorwillforce thelightsONnomatterthestateofoccupancy. Troubleshooting Issue Possible Causes Suggestions Lights Will Not Turn ON manually DaylightingFeatureEnabled IfalllightsarerequiredadjustDIPSwitch10 and/ordaylightpotentiometer Powerinterruption Checkincomingvoltageand/orwiring If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879 Lights Will Not Turn OFF automatically Lights Will Not Turn OFF manually Override MakesuresensorisnotinOverrideMode(DIPSwitch8up) Sensorinstalledclosetoanairvent Sensorsshouldbeinstalledminimum4-6feetaway fromanyairventandoutofpathofheavyairflow. Sensorinstalledclosetoindirectlighting Sensorsshouldbemountedawayfromindirectlighting. Self-adjust Itmaybepossiblefortheunittohaveself-adjusted thetimedelaytoa30minutedelay.Ifthelightsdo notturnOFFafter30minutesfollownextstep 30MinuteDelay Maximumtimedelayis30Minutes.CheckDIP SwitchestoverifyDIPSwitchsettings.Iflightsdo notturnOFFatthesettimedelay,checknextstep PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5up Bypass Checkwiringtomakesuresensoror switchpackarenotbypassed Override MakesuresensorisnotinOverrideMode (DIPSwitch8up) If lights will still not turn OFF, call Technical Services at 1-800-553-3879 Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. HVAC/Tracking Mode (-R model only) Ifselected,TrackingModeallowstheloadconnectiontotheFormCrelaytofollowthestateofthesensor’sbluelead.HVAC ModeallowstheloadconnectedtotheFormCrelaytoremainONwhenthelightsareturnedOFFmanually.Applicationsmayinclude keepingtheroomatadesiredtemperaturewhilegivingapresentationandthelightsareOFF. Zero Time Delay Mode InZeroTimeDelayMode,theoutputisactuatedforonesecondtosignalanotherdevicethatthespacebeingmonitoredis occupied.Applicationsmayincludetheuseofalightingcontrolsystemtomanagethedelayofthelightingdeactivation.Pleaseseethe wiringdiagramsectionforwiringdetails. WheninZeroTimeDelayModeandTrackingModetheloadconnectedtotheFormCrelayshallfollowthestateofthesensor’s bluelead(zeroTimeDelayfortheformCrelay). WheninZeroTimeDelayModeandHVACMode,theloadconnectedtotheFormCrelayremainsONforthestandardtimedelay. Override TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure. 1. MoveDIPSwitch8up. WhileinOverrideMode,theoptionallowvoltagemomentaryswitch(es)willtogglethelightingload(s). Printed in Malaysia Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com