Installation Instructions Ultrasonic Ceiling Mounted Line Voltage Occupancy Sensor General Information

advertisement
Installation Instructions
Ultrasonic Ceiling Mounted Line
Voltage Occupancy Sensor
Model # OAC-U-2000-MV
Model # OAC-U-2000-DMV
Ultrasonic
Activated
P/N 9850-000183-02
General Information
• Readallinstructionsonbothsidesofthis
sheetfirst
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
Specifications
Power Requirements:
120to347VAC,50/60Hz-NeutralRequired
120VAC:
• Incandescent/Tungsten-0to800W,50/60Hz
• Fluorescent/Ballast-0to1200W,50/60Hz
MotorLoad:¼HP@125VAC
230VAC:
• Fluorescent/Ballast-0to1200W,50/60Hz
277VAC:
• Fluorescent/Ballast-0to2700W,50/60Hz
347VAC:
• Fluorescent/Ballast-0to1500W,50/60Hz
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:upto90%non-condensing
Location
Wiring
Themaximumcoverageareamayvarysomewhataccordingtoroomshapeandthepresenceofobstacles.Decrease
totalcoverageareaby15%for“soft”rooms(forexample,heavydraperiesorheavycarpeting).Thesensormusthavea
clearviewoftheareatobecontrolled.Thesensorwillnot“see”throughglass.Mountingheightshouldnotexceed12
feet.Optimummountingheightis8to10feet.Mountthesensorsothegrillesfacetheopenportionoftheroomand
arenotfacinganearbywall,door,windoworotherobstructingobject.Avoidpointingintohallways.Mountingatfixture
heightismosteffective.*Topreventfalseactivation,thesensorshouldbemountedawayfromtheairsupplyducta
minimumof4to6feet.
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be
turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker
is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked
“SWD”. All installations should be in compliance with the National Electric Code and all state and
local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
30 ft
9.14 m
30 ft
9.14 m
Description
TheOAC-UCeilingMountLineVoltageOccupancySensorisanUltrasonic(US)motionsensinglightingcontrol,
usedforenergysavingsandconvenience.Thesensorproducesalowintensity,inaudiblesoundtodetectoccupancy
inaroom.Changesinthesensor’sacousticwavecausedbymotion,suchaswalkingintheroom,reachingfora
telephoneorswivelinginachair,willcausethelightstoturnON.Thesensordoesnotrespondtoaudiblesound.
1.MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsfor
allconnections)CAPALLUNUSEDWIRELEADS.
3.Mountunittoceiling,junctionboxorroundfixturewithraceway.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
One Sensor, One Switchpack
OAC-U-2000
120-347 VAC
Line
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand
timedelayinreal-time.
Coverage
Load 1
Black
Blue
White
Installation
TheOAC-Usensorcanbemountedtoastandard2.125"deepx4"octagonor2.125"deepx4"foursquareelectrical
box(foursquareboxrequiresatwo-gangmudring).
20 ft
(6.096m)
16 ft
(4.87 m)
Neutral
12 ft
(3.65 m)
Manual or Automatic-On Control of Two Standard Switchpacks
0
120-347 VAC
Line
Neutral
12 ft
(3.65 m)
16 ft
(4.87 m)
20 ft
(6.096m)
32 ft
(9.75 m)
23 ft
15 ft
(7.01 m) (4.57 m)
10 ft
(3 m)
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
5 ft
(1.52 m)
0
5 ft
(1.52 m)
10 ft
(3 m)
23 ft
15 ft
(4.57 m) (7.01 m)
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
32 ft
(9.75 m)
Black
White
Blue
Red
Red
Load 1
Load 2
Red leads are non-polorarity sensitive.
OAC-U-2000 Coverage Diagram
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
DIP Switch Settings
Installer Adjustments
Not Used
3
LEDs
Not Used
Override
Not Used
Daylighting
Bathroom Mode
Relay Swap
4
Relay 2
Relay 1 & 2
(DMV model only) (DMV model only) (DMV model only)
Daylight Sensor Adjustment
Ultrasonic Sensitivity Adjustment
Troubleshooting
Sensitivity Adjustments
Ultrasonic Sensitivity (GreenLED)-Usingasmallflatheadscrewdriverturnthegreenpotentiometersothatthe
arrowpointsup.
1.Standindifferentareasoftheroomandwaveyourhands.
2.IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthegreenpotentiometerclockwisein
smallincrements.RepeatStep1.
3.Standstillsixtoeightfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4.IfGreenLEDturnsONwithoutmotionorisconstantlyONdecreasetheUSsensitivitybyturningtheGreen
potentiometercounter-clock-wiseinsmalldecrements.RepeatStep3.
Issue
Possible Causes
Suggestions
Lights
Will Not
Turn ON
automatically
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer
Powerinterruption
Checkincomingvoltageand/orwiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Field-of-view outside the space
AdjustUltrasonicsensitivity.
Daylight Adjustments (0 to 300 foot-candles)
Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyclockwise).
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.If
thereisenoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlight
intheroom,thesensorwillallowthelightstoturnONwhenoccupied.HoweverthelightswillnotturnOFFifthelight
levelgoesabovethepresetvalueaspertheDaylightpotentiometer.
ON
1 2 3 4 5 6
7 8 9 10 11 12
Checkout and Adjustment
LED Indicators Functionality
During Installer/Test Mode
While in User Mode
LED Flashing Speed
LEDswillflashonceper¼second
LEDswillflashoncepersecond
Duration
10minutes
10to30minutes
AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments.
Self-Adjust
SensorisshippedintheSelf-AdjustMode.ThisappliestotimedelayandUSsensitivity.Inpreparationforthe
InstallerTest,thetimedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,the
unitwilltime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconfirmedbywatching
theGreen(US)indicatorLEDsonthefrontofthesensor,whilemovingaroundtheroom.
1.WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONfor¼secondwitheachmotion.(IfLEDs
donotturnON,gotoInstallerAdjustments-SensitivityAdjustmentssection)
2.Standstillsixtoeightfeetawayfromthesensorforfiveseconds.LEDsshouldnotturnON.(IfanyLEDturns
ON,noteLEDandgotoInstallerAdjustments–SensitivityAdjustmentsection)
3.Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
Adjustmentssection)
4.Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingsection)
5.TheunitwillremaininTestModefor10minutesthenautomaticallyexitTestModeandgointothe10minute
TimeDelayUserModesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.To
forceinto10min.UserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofits
currentposition,wait3seconds,andthenbacktoitsoriginalposition)WhileinTestMode,theLEDswillflashonceper1/4second.
Note:Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.
1.WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrent
position,wait3secondsandthenbackintoitsoriginalposition.
2.SetDIPSwitch10toRelayTwoonlyorRelayOneandTwo.
3.Setthelightleveltominimum(fullyCCW).
4.Leavetheroomandletthesensortime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF.
5.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
incrementsuntilthelightsareON.(Pause5secondsbetweeneachadjustment)
6.OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethe
currentillumination.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10
minutes.AslongasAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,
byalternatelymakingslightadjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbe
noneedformanualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2are
alreadydown,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Lights
Will Not
Turn OFF
automatically
Override
MakesuresensorisnotinOverrideMode(DIPSwitch8up)
Sensorinstalledclosetoanairvent
Sensorsshouldbeinstalledminimum4-6feetaway
fromanyairventandoutofpathofheavyairflow
Sensorinstalledclosetoindirectlighting
Sensorsshouldbemountedawayfromindirectlighting
Self-adjust
Itmaybepossiblefortheunittohaveself-adjusted
thetimedelaytoa30minutedelay.Ifthelightsdo
notturnOFFafter30minutesfollownextstep
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep
UltrasonicSensitivitysetHigh
Lowersensitivitybyturninggreen
potentiometerCCWinsmalldecrements
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Automatic Mode
InAutomaticONMode,thelightsturnONwhenapersonenterstheroom.Ifoptionalmomentarylowvoltage
switchesareusedalongwithAutomaticONMode,activatingtheswitch(es)whiletheloadisONturnstheloadOFF.
WhentheloadisturnedOFFmanually,aslongasthesensorcontinuestodetectoccupancy,theloadsstayOFF.After
thetimedelayexpires,thelightsstayOFFandthesensorgoesbacktoAutomaticONMode.Forwiringinformationfor
theoptionalmomentarylowvoltageswitch(es),pleaseseethewiringsectionoftheinstallationinstructions.
Bathroom Mode (OAC-U-200-DMV Model Only)
Whenselected,BathroomModekeepsthesecondrelayONforanadditional10minutesafterthefirstrelayhasbeen
turnedOFF.
Relay Swap (OAC-U-200-DMV Model Only)
Acommonprobleminelectricwiringiswiringthewrongwiretothewrongload.Thiscanmakecontrolofloads
confusingtoanenduser.TheRelaySwapoptionsolvestheproblembyswappingtherelaysaftertheunitiswired
andinstalled.
Override
TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure.
1.MoveDIPSwitch8up.
Printed in Malaysia