Installation Instructions Ultrasonic Ceiling Mounted Line Voltage Occupancy Sensor Model # OAC-U-2000-MV Model # OAC-U-2000-DMV Ultrasonic Activated P/N 9850-000183-02 General Information • Readallinstructionsonbothsidesofthis sheetfirst • InstallinaccordancewithALLlocalcodes • Forindooruseonly Specifications Power Requirements: 120to347VAC,50/60Hz-NeutralRequired 120VAC: • Incandescent/Tungsten-0to800W,50/60Hz • Fluorescent/Ballast-0to1200W,50/60Hz MotorLoad:¼HP@125VAC 230VAC: • Fluorescent/Ballast-0to1200W,50/60Hz 277VAC: • Fluorescent/Ballast-0to2700W,50/60Hz 347VAC: • Fluorescent/Ballast-0to1500W,50/60Hz Operating Environment: • Temperature:32°F–104°F(0°C–40°C) • RelativeHumidity:upto90%non-condensing Location Wiring Themaximumcoverageareamayvarysomewhataccordingtoroomshapeandthepresenceofobstacles.Decrease totalcoverageareaby15%for“soft”rooms(forexample,heavydraperiesorheavycarpeting).Thesensormusthavea clearviewoftheareatobecontrolled.Thesensorwillnot“see”throughglass.Mountingheightshouldnotexceed12 feet.Optimummountingheightis8to10feet.Mountthesensorsothegrillesfacetheopenportionoftheroomand arenotfacinganearbywall,door,windoworotherobstructingobject.Avoidpointingintohallways.Mountingatfixture heightismosteffective.*Topreventfalseactivation,thesensorshouldbemountedawayfromtheairsupplyducta minimumof4to6feet. CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. 30 ft 9.14 m 30 ft 9.14 m Description TheOAC-UCeilingMountLineVoltageOccupancySensorisanUltrasonic(US)motionsensinglightingcontrol, usedforenergysavingsandconvenience.Thesensorproducesalowintensity,inaudiblesoundtodetectoccupancy inaroom.Changesinthesensor’sacousticwavecausedbymotion,suchaswalkingintheroom,reachingfora telephoneorswivelinginachair,willcausethelightstoturnON.Thesensordoesnotrespondtoaudiblesound. 1.MakesurepoweristurnedOFFatthebranchcircuitbreaker. 2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsfor allconnections)CAPALLUNUSEDWIRELEADS. 3.Mountunittoceiling,junctionboxorroundfixturewithraceway. 4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize. 5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection) One Sensor, One Switchpack OAC-U-2000 120-347 VAC Line Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand timedelayinreal-time. Coverage Load 1 Black Blue White Installation TheOAC-Usensorcanbemountedtoastandard2.125"deepx4"octagonor2.125"deepx4"foursquareelectrical box(foursquareboxrequiresatwo-gangmudring). 20 ft (6.096m) 16 ft (4.87 m) Neutral 12 ft (3.65 m) Manual or Automatic-On Control of Two Standard Switchpacks 0 120-347 VAC Line Neutral 12 ft (3.65 m) 16 ft (4.87 m) 20 ft (6.096m) 32 ft (9.75 m) 23 ft 15 ft (7.01 m) (4.57 m) 10 ft (3 m) Minor Motion, Ultrasonic Major Motion, Ultrasonic 5 ft (1.52 m) 0 5 ft (1.52 m) 10 ft (3 m) 23 ft 15 ft (4.57 m) (7.01 m) Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. 32 ft (9.75 m) Black White Blue Red Red Load 1 Load 2 Red leads are non-polorarity sensitive. OAC-U-2000 Coverage Diagram Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com DIP Switch Settings Installer Adjustments Not Used 3 LEDs Not Used Override Not Used Daylighting Bathroom Mode Relay Swap 4 Relay 2 Relay 1 & 2 (DMV model only) (DMV model only) (DMV model only) Daylight Sensor Adjustment Ultrasonic Sensitivity Adjustment Troubleshooting Sensitivity Adjustments Ultrasonic Sensitivity (GreenLED)-Usingasmallflatheadscrewdriverturnthegreenpotentiometersothatthe arrowpointsup. 1.Standindifferentareasoftheroomandwaveyourhands. 2.IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthegreenpotentiometerclockwisein smallincrements.RepeatStep1. 3.Standstillsixtoeightfeetawayfromsensorforfiveseconds.LEDshouldnotturnON. 4.IfGreenLEDturnsONwithoutmotionorisconstantlyONdecreasetheUSsensitivitybyturningtheGreen potentiometercounter-clock-wiseinsmalldecrements.RepeatStep3. Issue Possible Causes Suggestions Lights Will Not Turn ON automatically DaylightingFeatureEnabled IfalllightsarerequiredtoturnON adjustdaylightpotentiometer Powerinterruption Checkincomingvoltageand/orwiring If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879 Field-of-view outside the space AdjustUltrasonicsensitivity. Daylight Adjustments (0 to 300 foot-candles) Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyclockwise). TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.If thereisenoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlight intheroom,thesensorwillallowthelightstoturnONwhenoccupied.HoweverthelightswillnotturnOFFifthelight levelgoesabovethepresetvalueaspertheDaylightpotentiometer. ON 1 2 3 4 5 6 7 8 9 10 11 12 Checkout and Adjustment LED Indicators Functionality During Installer/Test Mode While in User Mode LED Flashing Speed LEDswillflashonceper¼second LEDswillflashoncepersecond Duration 10minutes 10to30minutes AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments. Self-Adjust SensorisshippedintheSelf-AdjustMode.ThisappliestotimedelayandUSsensitivity.Inpreparationforthe InstallerTest,thetimedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,the unitwilltime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconfirmedbywatching theGreen(US)indicatorLEDsonthefrontofthesensor,whilemovingaroundtheroom. 1.WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONfor¼secondwitheachmotion.(IfLEDs donotturnON,gotoInstallerAdjustments-SensitivityAdjustmentssection) 2.Standstillsixtoeightfeetawayfromthesensorforfiveseconds.LEDsshouldnotturnON.(IfanyLEDturns ON,noteLEDandgotoInstallerAdjustments–SensitivityAdjustmentsection) 3.Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller Adjustmentssection) 4.Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingsection) 5.TheunitwillremaininTestModefor10minutesthenautomaticallyexitTestModeandgointothe10minute TimeDelayUserModesetting. Note:ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.To forceinto10min.UserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofits currentposition,wait3seconds,andthenbacktoitsoriginalposition)WhileinTestMode,theLEDswillflashonceper1/4second. Note:Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded. 1.WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrent position,wait3secondsandthenbackintoitsoriginalposition. 2.SetDIPSwitch10toRelayTwoonlyorRelayOneandTwo. 3.Setthelightleveltominimum(fullyCCW). 4.Leavetheroomandletthesensortime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF. 5.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall incrementsuntilthelightsareON.(Pause5secondsbetweeneachadjustment) 6.OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethe currentillumination. Time Delay Adjustments Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10 minutes.AslongasAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween, byalternatelymakingslightadjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbe noneedformanualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend. ResetsensortimedelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2are alreadydown,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition) Lights Will Not Turn OFF automatically Override MakesuresensorisnotinOverrideMode(DIPSwitch8up) Sensorinstalledclosetoanairvent Sensorsshouldbeinstalledminimum4-6feetaway fromanyairventandoutofpathofheavyairflow Sensorinstalledclosetoindirectlighting Sensorsshouldbemountedawayfromindirectlighting Self-adjust Itmaybepossiblefortheunittohaveself-adjusted thetimedelaytoa30minutedelay.Ifthelightsdo notturnOFFafter30minutesfollownextstep 30MinuteDelay Maximumtimedelayis30Minutes.CheckDIP SwitchestoverifyDIPSwitchsettings.Iflightsdo notturnOFFatthesettimedelay,checknextstep UltrasonicSensitivitysetHigh Lowersensitivitybyturninggreen potentiometerCCWinsmalldecrements If lights will still not turn OFF, call Technical Services at 1-800-553-3879 Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. Automatic Mode InAutomaticONMode,thelightsturnONwhenapersonenterstheroom.Ifoptionalmomentarylowvoltage switchesareusedalongwithAutomaticONMode,activatingtheswitch(es)whiletheloadisONturnstheloadOFF. WhentheloadisturnedOFFmanually,aslongasthesensorcontinuestodetectoccupancy,theloadsstayOFF.After thetimedelayexpires,thelightsstayOFFandthesensorgoesbacktoAutomaticONMode.Forwiringinformationfor theoptionalmomentarylowvoltageswitch(es),pleaseseethewiringsectionoftheinstallationinstructions. Bathroom Mode (OAC-U-200-DMV Model Only) Whenselected,BathroomModekeepsthesecondrelayONforanadditional10minutesafterthefirstrelayhasbeen turnedOFF. Relay Swap (OAC-U-200-DMV Model Only) Acommonprobleminelectricwiringiswiringthewrongwiretothewrongload.Thiscanmakecontrolofloads confusingtoanenduser.TheRelaySwapoptionsolvestheproblembyswappingtherelaysaftertheunitiswired andinstalled. Override TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure. 1.MoveDIPSwitch8up. Printed in Malaysia Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com