> PRE-PUNCHED CENTER WEB > 6" NOMINAL SIDE RAIL HEIGHT,

advertisement
> PRE-PUNCHED CENTER WEB
> 6" NOMINAL SIDE RAIL HEIGHT,
5" CABLE FILL
> REMOVABLE / MOVABLE RUNGS
> 6063-T6 COPPER FREE ALUMINUM ALLOY
> SPLICES & HARDWARE INCLUDED
> CABLE TRAY WILL SUPPORT 200 lb.
CONCENTRATED LOAD
> UL CLASSIFIED
> EACH RUNG WILL SUPPORT A 200 lb.
CONCENTRATED LOAD (24" WIDTH AND UNDER)
> LOAD TEST IN ACCORDANCE WITH
NEMA VE1/CSA C22.2 NO 126
RUNG
SPACING
> RUNGS ATTACHED WITH 1/4 - 20,
CHROMIUM ZINC HARDWARE
1.71
43.50
1.57
39.903
CABLE
FILL
5.51
140.00
WIDTH
WIDTH+1.568
LENGTH
RSI06A050KO06SL-18-144
SERIES
RSI
MATERIAL
RUNG SPACING
NOMINAL SIDE
06 = 6"(150)
RAIL HEIGHT A = ALUMINUM
KNOCKOUT TYPE 09 = 9"(225)
12 = 12"(300)
06 = 6" (5" CABLE
BLANK = NONE
FILL)
050KO = .50
075KO = .75
TYPE
100KO = 1.00
125KO = 1.25
STRAIGHT LADDER
150KO = 1.50
WIDTH
06 = 6"(150)
09 = 9"(225)
12 = 12"(300)
LENGTH
18 = 18"(450)
24 = 24"(600)
30 = 30"(750) 120 = 120"(3000)
36 = 36"(900) 144 = 144"(3600)
FOR VENTILATED BOTTOM TRAY,
REPLACE RUNG SPACING WITH VB. EX: RSI06AVBSL-18-144
B-LINE
SERIES
NEMA, CSA & UL
CLASSIFICATIONS
RSI06
NEMA: 12B
CSA: 121 kg/m 3.7 m
UL CROSS-SECTIONAL
AREA = .60 in^2
SPAN LOAD DEFLECTION DESIGN FACTOR
SPAN
LOAD DEFLECTION DESIGN FACTOR
(ft) (LBS/ft) MULTIPLIER FOR TWO RAILS (METERS) (Kg/m) MULTIPLIER FOR TWO RAILS
6
8
10
12
224
184
118
82
0.0005
0.0017
0.0041
0.0085
AREA=1.18 in^2
Sx=1.98 in^3
Ix=5.51 in^4
1.8
2.4
3.0
3.7
333
273
175
121
0.009
0.029
0.070
0.144
AREA=7.59 cm^2
Sx=32.5 cm^3
Ix=230 cm^4
WHEN CABLE TRAYS ARE USED IN CONTINUOUS SPANS, THE DEFLECTION OF THE CABLE TRAY IS REDUCED BY AS
MUCH AS 50%.
DESIGN FACTORS: Ix = MOMENT OF INERTIA, Sx = SECTION MODULUS.
NOTE: VALUES ARE BASED ON SIMPLE BEAM TESTS PER NEMA VE-1 ON 36" WIDE CABLE TRAY WITH RUNGS SPACE ON 12"
CENTERS. THE PUBLISHED LOAD SAFETY FACTOR IS 1.5. TO CONVERT 1.5 SAFETY FACTOR TO 2.0, MULTIPLY THE PUBLISHED
LOAD BY 0.75. TO OBTAIN MID-SPAN DEFLECTION, MULTIPLY A LOAD BY THE DEFLECTION MULTIPLIER. CABLE TRAY MUST BE
SUPPORTED ON SPANS SHORTER THAN OR EQUAL TO THE LENGTH OF THE TRAY.
THIS DRAWING AND/OR THE TECHNICAL INFORMATION CONTAINED HEREON IS THE PROPERTY OF COOPER B-LINE, INC. ("B-LINE"), AND IS ISSUED IN CONFIDENCE FOR B-LINE ENGINEERING PURPOSES ONLY AND MAY NOT BE REPRODUCED OR USED FOR ANY PURPOSE WHATSOEVER
WITHOUT THE EXPRESS WRITTEN PERMISSION OF B-LINE TO THE USER. THIS DRAWING AND/OR TECHNICAL INFORMATION IS THE PROPERTY OF B-LINE AND IS LOANED FOR MUTUAL ASSISTANCE, TO BE RETURNED WHEN ITS' INTENDED PURPOSE HAS BEEN SERVED.
TITLE:
509 W. Monroe Street
Highland, IL 62249
Phone (618) 654-2184
FAX (618) 654-5499
www.cooperbline.com
SUBMITTAL DRAWING
SUBMITTAL NO:
REFERENCE DWG(S):
00019081
S00019081C
6" REDI - RAIL CABLE TRAY
STRAIGHT SECTION
DRAWN BY:
LT PSR
DATE:
MODEL SOURCE FILE:
EQUIPMENT FURNISHED HAS BEEN FABRICATED IN ACCORDANCE WITH THIS DRAWING.
00019081
REV:
00
SHEET:
REV.
A
03/17/12
1 OF 1