HALO Commercial

advertisement
HALO Commercial
d esc r iption
Catalog #
Recessed 8 inch aperture open wall wash for one horizontal 26W
double twin tube or 26/32/42W triple twin tube compact fluorescent
lamp. Fixture is suitable for commercial construction. Insulation
must be kept 3" from top and sides of housing. Universal input
electronic ballast with dimming and emergency options.
Type
Project
Comments
Date
Prepared by
S P E C I F I C A T I O N feat u r es
M ec h anica l
Frame
Boat shaped galvanized steel
frame with 1/2" plaster lip
accommodates ceilings up to
2" thick. May be used for new
construction or remodeling
installations. Provided with (2)
remodel clips to secure frame
when installed from below the
ceiling.
Trim Retention
Reflector assembly is retained
with two torsion springs and
held tightly to the finished ceiling
surface. Orientation markings on
housing and trim facilitate proper
alignment.
E l ect r ica l
Junction Box
(6) 1/2" and (2) 3/4" trade size pry
outs positioned to allow straight
conduit runs. Listed for (12)
#12 AWG (six in, six out) 90°C
conductors and feed thru branch
wiring.
Mounting Brackets
Bar hanger receivers adjusts 2"
vertically from above the ceiling
or thru the aperture. Use with
No Fuss™ bar hangers or with
Lamp Socket
1/2" EMT. Removable to facilitate
4-pin G24q base accepts (1) 26W
installation from below the ceiling.
DTT or 26/32/42W TTT lamp.
No Fuss™ Bar Hangers
Socket Housing
Pre-installed and centered bar
Galvanized steel socket housing
hanger locks to tee grid with a
attached securely to reflector
screwdriver or pliers. Centering
with captive thumbscrew. Vents
marks on the bar hanger
provide effective lamp thermal
mechanism allows consistent
management.
positioning of fixtures.
Control Gear
O ptica l
Universal 120V - 277V UNV or
Reflector
347V input electronic ballast for
Highly efficient one piece
26/32/42W compact fluorescent
aluminum reflector combined with
lamp.
spun aluminum gradient kicker
Emergency Battery Pack
reflector provides for vertical
REM – Remote emergency
illumination with a downlight
component. Equal cutoff on room test switch. Housing includes
120V/277V, 60Hz dual-tap battery
side and uniform illumination
pack provides 90 minutes of
of the wall plane for a visually
emergency illumination. Long life
comfortable optic. Self flanged
maintenance free sealed nickel
standard.
cadmium batteries recharge fully
-Specular Reflectors - Polished in 24 hours. REM configuration
flange standard with white includes prewired and attached
painted flange option.
remote test switch plate and
-Baffles and White Reflector - indicator light. REM option
White painted flange is the standard emergency
standard.
configuration, and is compatible
with all standard reflector options,
ordered separately.
Emergency Battery Pack - Average
Lamp Lumen Ratings
REM option: 26W 425lm, 32W
600lm, 42W 750lm
(Note: average lamp lumens are
based upon REM manufacturer
ratings. Delivered lumens
depend upon trim; refer to trim
photometry to factor delivered
lumens).
Code Compliance
- Thermally protected and cULus listed for damp locations.
-IP20 rated for open trims
- NFPA Life Safety (Emergency Battery Pack).
- EMI/RFI per FCC Title 47 CFR, Part 18, non consumer limits.
-Peel down wattage label
from 42W to 32W and 26W.
Allows de-rating to set max.
relamp wattage per project
specifications (multi-wattage housings only).
-DR - De-rated label housings are
wattage specific for 26/32W or 26W.
PD8H142
82HWW
(1) 26W DTT
26/32/42W TTT
Compact Fluorescent
8-Inch Aperture
Open Wall Wash
New Construction or
Remodel
Non-IC
- High efficacy luminaire may be used to meet IECC, ASHRAE, and Title 24 commercial standards.
ADV111712
January 10, 2013 9:15 AM
HALO Commercial
PD8H142
82HWW
E N E R G Y D ATA
PD8H142E, PD8CPH142E
PD8H1423E
Min. Starting Temp -5°F / -20°C Sound Rating Class A
EMI/RFI Emissions FCC 47CFR Part 18 Non-Consumer Limits
Input Frequency 50/60 Hz
Power Factor > 0.98
THD < 10%
Input Voltage 120V - 277V ±10%
Crest factor < 1.7
UL Listed Class P, Type 1 Outdoor, CSA or C/UL Certified
Operating Frequency > 40kHz
Input Power 28W
CFQ26W/G24Q
Input Current 0.50A @ 120V
Crest factor < 1.6
Input Power 31W
CFTR26W/GX24Q
Input Current 0.50A @ 120V
Ballast factor 1.02
Crest factor < 1.6
Ballast factor 1.00
Input Power 36W
CFTR32W/GX24Q
Input Current 0.50A @ 120V
Input Current 0.11A @ 347V
Ballast factor 0.98
Input Current 0.22A @ 277V
Crest factor < 1.5
Ballast factor .98
Input Power 50W
CFTR42W/GX24Q
Input Current 0.50A @ 120V
Input Current 0.22A @ 277V
Input Current 0.15A @ 347V
Ballast factor 1.00
Crest factor < 1.5
Ballast factor .96
DIMENSIONS
5.850"
[148.59 mm]
8.375" I.D.
[212.73mm]
9.250"
[234.95mm]
9.750" O.D
[247.65mm]
26.400"
[670.56mm]
9.472"
[240.59mm]
16.181"
[410.99mm]
www.cooperlighting.com
Input Current 0.09A @ 347V
Input Current 0.22A @ 277V
Input Power 45W
CFTR42W/GX24Q
Ballast factor 1.02
Ballast factor 1.00
Input Power 35W
CFTR32W/GX24Q
Input Current 0.09A @ 347V
CFQ26W/G24Q
Input Current 0.22A @ 277V
Input Power 28W
CFTR26W/GX24Q
Min. Starting Temp 0°F / -18°C
Sound Rating Class A
EMI/RFI Emissions FCC 47CFR Part 18 Non-Consumer Limits
Input Frequency 60 Hz
Power Factor > 0.98
THD < 10%
Input Voltage 347VAC ±10%
cULus Listed Class P, Type 1 Outdoor, Type CC
Operating Frequency 50-60 kHz
Input Power 31W
HALO Commercial
PD8H142
82HWW
O r d e r ing info r mation
SAMPLE NUMBER: : PD8H142E 82HWWC
O r d e r h o u s i n g , r e fl e c t o r a n d l a m p s e p a r a t e l y f o r a c o m p l e t e l u m i n a i r e .
Finish Option
C=Specular Clear
G=Specular Gold
H=Semi Specular Clear
W=White (White Flange)
Reflector
82HWW = 8” horizontal
open wall wash
Housing
Multi-Wattage
PD8H142 = 8 Inch horizontal (1) 26/32/42W DTT/TTT CFL
PD8CPH142 = 8 Inch horizontal (1) 26/32/42W DTT/TTT CFL,
CCEA listed (Chicago Plenum)
Flange Option
Blank=Polished Flange
(C, G, H)
Blank=White flange
(W)
WF=White Flange
(C, G, H Reflectors)
De-Rated Label
PD8H132 = 8 Inch horizontal (1) 26/32W DTT/TTT CFL
PD8CPH132 = 8 Inch horizontal (1) 26/32W DTT/TTT CFL,
CCEA listed (Chicago Plenum)
PD8H126 = 8 Inch horizontal (1) 26W DTT/TTT CFL
PD8CPH126 = 8 Inch horizontal (1) 26W DTT/TTT CFL,
CCEA listed (Chicago Plenum)
Accessories
HB128APK = L channel hanger bar,
26”, ‘No-Fuss’,
pair (replacement)
RMB22 = 22” long wood joist
mounting bars
Ballast Option
E = 120V – 277V 50/60Hz UNV
REM = 120V/277V 60Hz dual-tap emergency battery ballast with remote test switch plate
3E = 347V, 50/60Hz
1DMARKX = 5% two-wire (26/32/42W) dimming, 120V
2DMARKX = 5% two-wire (26/32/42W) dimming, 277V
EDMARK7 = 5% 0-10V discrete two-wire (26/32/42W) dimming, 120-277V
1DMARKXREM = 5% two-wire (26/32/42W) dimming, 120V; with REM emergency option
2DMARKXREM = 5% two-wire (26/32/42W) dimming, 277V; with REM emergency option
EDMARK7REM = 5% 0-10V discrete two-wire (26/32/42W) dimming, 120-277V; with REM emergency option
P H OTO M E T RY
PD8H142E-82HWWC_32TTT
Candela Distribution
Spacing Criteria = 1.50
Lumens per Watt = 51 LpW
Test No. P31434
Test Model: PD8H142E-82HWWC_32TTT
Candlepower Distribution Curve
90°
80°
70°
60°
50°
40°
10°
Zone
Degree
Candela
0*
548
5
532
45
13903
15
550
55
10676
25
559
65
5872
35
558
75
2903
45
425
85
308
55
282
65
126
75
46
85
3
90
0
Avg. 0°
Luminance
Lumens
% Lamp
% Fixture
0-30
640.02
26.70
38.00
0-40
1067.21
44.50
63.40
0-60
1598.97
66.60
95.00
0-90
1682.45
70.10
100.00
*CBCP
30°
0°
Zonal Lumen Summary
Luminance
(Average Candela/M2)
Degrees
Vertical
20°
Single Unit Footcandles
Multiple Unit Footcandles
2.5' from wall
Multiple Unit Footcandles
2.5' from wall
(distance from fixture along wall)
2.5' from wall
(spacing between fixtures)
(spacing between fixtures)
3
4
1
4.3
3.5
1.4
0.5
1
12.3
10.7
12.3
1
14.5
16.2
14.5
2
21.7
15.9
6.7
2.0
2
30.0
31.0
30.0
2
36.6
40.8
36.6
3
24.0
19.7
12.3
5.7
3
27.5
30.2
27.5
3
33.0
35.3
33.0
4
17.3
15.0
11.5
6.6
4
20.4
23.0
20.4
4
23.9
24.9
23.9
5
10.7
10.2
8.8
6.3
5
13.9
16.2
13.9
5
15.7
16.5
15.7
10.1
6
6.2
6.6
6.4
5.1
6
9.3
10.8
9.3
6
10.1
10.4
7
3.8
4.1
4.4
4.0
7
6.5
7.1
6.5
7
6.7
6.8
6.7
8
2.6
2.9
3.0
3.0
8
4.8
5.0
4.8
8
4.7
4.9
4.7
9
1.9
2.1
2.2
2.2
9
3.5
3.7
3.5
9
3.5
3.6
3.5
10
1.5
1.6
1.6
1.6
10
2.7
2.8
2.7
10
2.7
2.0
2.7
Beam diameter is to 50% of maximum footcandles, rounded to the nearest half-foot.
Footcandle values are initial, apply appropriate light loss factors where necessary.
Note: Specifications and Dimensions subject to change without notice.
Visit our web site at www.cooperlighting.com
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770 486.4801
www.cooperlighting.com
Cooper Lighting 5925 McLaughlin Rd. Mississauga, Ontario, Canada L5R 1B8 905.507.4000 FAX 905.568.7049
Download