COOPER LIGHTING - METALUX

advertisement
COOPER LIGHTING - METALUX
DESCRIPTION
The HBL series is ideal for high mounting height industrial or retail
applications. Advanced optical designs provide maximum performance
from either T5 or T8 lamps. Optional uplight component produces
excellent ceiling uniformity. HBL's high lumen package allows the
benefits of fluorescent to be applied at high mounting heights that were
traditionally exclusive to HID. Benefits include exceptional color
rendering, high system efficacy, 95% lumen maintenance, long lamp life,
instant on/instant re-strike, economical dimming, and uniform brightness
control. Typical HBL applications include retail, shopping malls, light
industrial and recreational environments.
®
Type
Catalog #
Project
Date
Comments
Prepared by
S P E C I F I C AT I O N F E AT U R E S
C o n s t ru c t i o n
Channel and end plates are
constructed of die-formed steel.
The channel provides strength,
numerous KOs for easy
installation, and excellent thermal
dissipation without any special or
proprietary components. Stiffening
brackets add additional strength
and rigidity to channel and
reflectors.
E l e c t ri c a l
The HBL comes with a standard
Class "P" electronic ballast and
twist-lock lampholders. UL/cUL
listed for high ambient
environments up to 55°C (131°F)
for all lamp and ballast
combinations listed. Suitable for
damp locations.
Finish
Electrostatically applied baked
white enamel finish is preceded by
a multistage cleaning cycle, iron
phosphate coating with rust
inhibitor.
Optics
Die-formed, segmented optical
design optimizes performance
across three distributions. Optical
choices include a narrow
distribution for aisles, medium
distribution for assembly and
loading areas, or wide distribution
for general, open area lighting. An
uplight option is offered to permit
ceiling uniformity and allow for
ample lamp and luminaire heat
dissipation.
Mounting
The HBL series is ideally suited for
suspension mounting with optional
wire hook and chain set, or cable
mounting. Single monopoint
mounting is also available with
SPM tong hanger. Includes V
Hangers for rapid installation.
Wa rra n t y
When operated in high ambient
conditions, the HBL is supported
by a 5 yr/55°C and 3 yr/65°C ballast
warranty for T5 and T8 (277V)
options when used w/high
temperature ballast in open,
uplight configurations. To maximize
your warranty, the HBL should be
ordered with a high-temperature
ballast in ambient environments
that typically exceed 40°C (102°F).
HBL
SERIES
U LT R A 4 7
4 , 6 , 8 , O R 10 T 5 L A M P S
High-Bay Industrial Open
Luminaire
2-15/32
[63mm]
19-17/32" [496mm]
L A M P C O N F I G U R AT I O N S
4 LAMP
D I M E N S I O N TO P V I E W
4/6 LAMP
48-7/16" [1230mm]
2-15/32" [63mm]
19-17/32" [496mm]
E N E R G Y D ATA
19-17/32"
[496mm]
10 LAMP
2-15/32" [63mm]
Input Watts:
EHT Ballast
647=311
25-1/4" [641mm]
2-15/32"
[63mm]
L A M P C O N F I G U R AT I O N S
Luminaire Efficacy Rating
LER = 83
Catalog Number: HBL-647T5-UPL
D I M E N S I O N TO P V I E W
8/10 LAMP
8 LAMP
48-7/16" [1230mm]
2-15/32" [63mm]
20-11/32" [517mm]
24-19/32" [625mm]
Yearly Cost of 1000 lumens,
3000 hrs at .08 KWH = $2.89
25-1/4" [641mm]
*Reference the lamp/ballast data in the
Technical Section for specific lamp/ballast
requirements.
6 LAMP
**Consult Pre Sales Technical Support.
2-15/32" [63mm]
19-17/32" [496mm]
25-1/4"
[641mm]
LAMPS CONTAIN MERCURY. DISPOSE ACCORDING
TO LOCAL, STATE OR FEDERAL LAWS
Safe and convenient means of
disconnecting power.
X
X=2-15/32"
[63mm]
Specifications and dimensions subject to change without notice.
Consult your representative for additional options and finishes.
ADF110941 pc
2011-05-17 13:24:26
HBL T5
P H OTO M E T R I C S
HBL-447T5-UNV-UPL C a n d e l a
(1) Electronic Ballast
(4) F54T5-47W lamps Angle Along II
0
10037
4285 lumens
5
9943
10
9777
Spacing criterion:
15
9525
(II) 1.2 x mounting
20
9182
height, (⊥) 0.7 x
25
8765
mounting height
30
8274
35
7713
Efficiency 99.3%
40
7074
Test Report:
45
6389
HBL447.IES
50
5633
55
4852
LER=83
60
4038
Yearly Cost of 1000 65
3183
2312
lumens, 3000 hrs at 70
75
1471
.08 KWH = $2.89
80
85
90
734
169
4
Across ⊥
10037
9918
9166
7664
5887
4392
3681
3333
2993
2738
2485
2226
2144
1882
1286
645
106
0
5
45°
10037
9932
9528
8737
7506
6096
4733
3690
3149
2771
2401
2105
1820
1544
1389
901
347
2
2
Effective floor cavity reflectance
80%
70%
70 50 30 10
70 50 30 10
118
109
100
92
85
79
73
69
64
60
57
118
105
93
83
74
67
61
56
52
48
45
118
101
87
75
66
59
53
48
44
40
37
118
98
82
69
60
53
47
42
38
35
32
115
107
98
90
83
77
72
67
63
59
56
115
103
91
81
73
66
60
55
51
47
44
115
99
85
74
65
58
52
48
43
40
37
115
96
81
69
60
52
47
42
38
35
32
20%
50%
50 30 10
30%
50 30 10
10%
50 30 10
0%
0
110
99
88
78
71
64
58
54
50
46
43
106
95
84
76
68
62
57
52
49
45
42
101
91
82
73
66
60
55
51
47
44
41
99
86
73
63
55
49
44
39
36
33
30
110
96
83
72
64
57
52
47
43
39
37
110
93
79
68
59
52
46
42
38
35
32
106
93
81
71
63
56
51
46
42
39
36
Zonal Lumen Summary
Luminance Data
Zone
0-30
0-40
0-60
0-90
0-180
Angle
in Deg
45
55
65
75
85
Lumens
6299
9233
14204
17022
17022
%Lamp
36.7
53.9
82.9
99.3
99.3
Candela
Angle
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
Across ⊥
10884
10658
9795
8645
7522
6483
5883
5653
5208
4666
4322
3911
3492
3023
2632
2037
1431
599
39
Along II
45°
10884
10884
10787
10710
10619
10181
10352
9367
9987
8378
9548
7412
9020
6452
8422
5591
7746
5046
7008
4716
6218
4186
5369
3594
4493
3175
3565
2683
2615
2204
1693
1788
854
1224
235
596
3
37
C o e f fi c i e n t s o f U t i l i z a t i o n
C o e f fi c i e n t s o f U t i l i z a t i o n
rc
rw
RCR
0
1
2
3
4
5
6
7
8
9
10
HBL-647T5-UNV-UPL
(2) Electronic Ballasts
(6) F54T5-47W lamps
4285 lumens
Spacing criterion:
(II) 1.2 x mounting
height, (⊥) 0.8 x
mounting height
Efficiency 99.5%
Test Report: HBL647UPL.IES
LER=83
Yearly Cost of 1000
lumens, 3000 hrs at
.08 KWH = $2.89
%Fixture
37.0
54.2
83.4
100.0
100.0
Average
0-Deg
cd/sm
19774
18513
16483
12438
4244
106
90
77
66
58
51
46
41
38
35
32
101
90
78
69
61
55
50
45
42
39
36
101
88
75
65
57
51
46
41
38
34
32
Average
45-Deg
cd/sm
8576
8032
7995
7619
50
Average
90-Deg
cd/sm
8474
8493
9746
5454
50
rc
rw
RCR
0
1
2
3
4
5
6
7
8
9
10
Effective floor cavity reflectance
80%
70%
70 50 30 10
70 50 30 10
117
107
97
89
81
75
69
64
60
56
53
117
102
89
78
70
62
56
51
47
43
40
117
97
82
70
61
54
48
43
39
35
32
117
94
76
64
54
47
41
37
33
30
27
113
103
94
86
78
72
67
62
58
54
51
113
99
86
76
68
61
55
50
46
42
39
113
95
80
69
60
53
47
42
38
35
32
113
91
75
63
54
47
41
36
33
30
27
20%
50%
50 30 10
30%
50 30 10
50
107
93
82
72
64
58
53
48
44
41
38
101
88
77
69
61
55
50
46
42
39
36
95
84
74
65
58
53
48
44
41
38
35
107
90
77
66
58
51
45
41
37
34
31
107
87
72
61
52
45
40
36
32
29
27
101
86
73
63
55
49
44
40
36
33
30
Zonal Lumen Summary
Luminance Data
Zone
0-30
0-40
0-60
0-90
0-180
Angle
in Deg
45
55
65
75
85
Lumens
7212
11157
18599
23829
25586
%Lamp
28.0
43.4
72.3
92.7
99.5
%Fixture
28.2
43.6
72.7
93.1
100.0
Average
0-Deg
cd/sm
21690
20485
18461
14315
5901
101
83
70
59
51
44
39
35
31
29
26
10%
30 10
95
82
70
61
53
47
43
39
35
32
30
Average
45-Deg
cd/sm
14596
13713
13894
15119
14966
0%
0
95
80
67
57
49
43
38
34
31
28
26
93
77
65
55
47
41
36
32
29
26
24
Average
90-Deg
cd/sm
14441
14922
15654
17224
15041
Modular F-Bay Power Supply Option
Cooper Lighting’s F-Bay Modular Power Supply option is available for use with all F-Bay products. The modular power supply
allows external fixture access for safe and easy servicing. There is no need to remove lamps or reflectors to disconnect fixture
power with F-Bay Modular Power Supply. Access to the individual fixture’s power supply allows servicing without turning off
all the fixtures, disrupting occupants. F-Bay Modular Power Supply is a time-saver in installation – simply plug & power.
Code Compliance
• UL/cUL Certified for Make/Break
under load (UL2549)
• Meets NEC requirements for
ballast disconnect (NEC 410.73G)
1
• Allows for addition of Occupancy
Sensor without hard connections
2
1. Modular Power Supply Receptacle supplied
mounted into fixture Access Plate
2. Modular Power Cord & Plugs in 120, 277, 347,
& 480V configurations for easy plug & power
into existing supply
No internal fixture
access required for
installation or
disconnecting power
Modular Motion Sensor Option
supplied with Mounting Box and
Modular Power Supply Receptacle
• Receptacles complete with
insulating/dust cap
Specifications and dimensions subject to change without notice.
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770 468.4801
ADF110941 pc
2011-05-17 13:24:26
HBL T5
O R D E R I N G I N F O R M AT I O N
SAMPLE NUMBER: HBL-647T5-N-UNV-EHT-UPL-U
Series
HBL=Linear High Bay
No. of Lamps
4=4 Lamps
6=6 Lamps
8=8 Lamps
10 =10 Lamps
Lamp Type
47T5=47W T5HO Lamp (48" Long)
Distribution
N=Narrow Beam (Standard)
M=Medium Beam
W=Wide Beam
Voltage (1)
UNV=Universal 120/277 Voltage
120V=120 Volt
277V=277 Volt
Lamps Installed 5
Ballast Type
T5 Systems
EHT =T5HO Linear Electronic Program
Rapid Start High Ambient. 4
Total Harmonic Distortion < 10%
No. of Ballast
1, 2 or 3
L5841=T5HO Lamp, 85CRI 4100K
L5850=T5HO Lamp, 85CRI 5000K
GL=Single Element Fuse
GM=Double Element Fuse
EL=Emergency Installed 1
NOTES:
1 Voltage must be specified when ordered with plugs or emergency ballasts.
2 When ordering MS option, specify as UNV (for 120 or 277V).
3 Requires use of MC or MPC cord accessories, specify voltage for plugs.
4 EHT/HT5/HCT5 ballast systems suitable for ambient environments not to exceed 149°F (65°C)
in open uplight configurations and less lens option.
5 Must specify lamps when ordering.
6 Cannot be combined with Modular Power Receptacle (MP).
For MWS with MP, choose MP in fixture logic and then choose MWS.
7 Two required.
8 For MWS with MP, choose MP in the fixture logic and then choose MWS accessory such as MDS6.
Packaging
Options
UPL=Uplight Apertures on Reflector U=Unit Pack
MP=Modular Power Receptacle
PALC=Job Pack
(Used for all Cord or Cord and
In Carton
Plug options) 3
PAL =Job pack
MWS=Modular Wiring System 6
Out of Carton
MS=360° or 180° Motion Sensor installed
2
(120V through 347V or 480V )
Accessories (order separately)
HB-SPM =Single Monopoint Hanger w/Hub
RH-1=Retrofit Hanger
FH-1=Fixture Hook
FL-1=Fixture Loop
Y- TOGGLE=Y Mounting Toggle, #2 Cable
(Specify 10' or 30' - Requires 2 per fixture) 7
HBAYC-CHAIN/SET/U=(2) V-Hook Hangers, 36"
ChainSets w/S-Hooks
MC3=3' Modular Power Cord
MPC3=3' Modular Power Cord & Plug
(Specify Voltage)
MC6=6' Modular Power Cord
MPC6=6' Modular Power Cord & Plug
(Specify Voltage)
MMS=360° or 180° Aisle Motion Sensor with Modular
Power Receptacle (120-277V) 1
MDS6=6' Modular Power Cord with MWS
27DS18/2G06MP Connector 8
WG/HBL6-4FT-B=4/6 Lamp w/Lamp Wireguard w/Clips
WG/HBL8-4FT-B=8 Lamp w/Lamp Wireguard w/Clips
S H I P P I N G DATA
Catalog No.
HBL-647T5-UNV-UPL
Specifications and dimensions subject to change without notice.
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770 468.4801
Wt.
16 lbs.
ADF110941 pc
2011-05-17 13:24:26
Download