Technical Data Effective September 30, 2014 CEPC – Emergency Power Control Catalog# Prepared by Project Date Comments Type CEPC-1 CEPC-D-F-S-120 Overview The Eaton's Cooper Controls Emergency Power Control (CEPC) device allows the control of emergency lighting in iLumin architectural dimming systems. Technical Data CEPC – Emergency Power Control September 2014 Specifications General Electrical Data Mechanical: Mounting: Environment: Interfacing: Eliminates energy waste by allowing emergency lighting to be switched and dimmed Fail safe operation Visible emergency power LED Visible regular power LED Integral test switch Senses local circuit power loss UL 924 listed, meets NEC, OSHA and NFPA safety codes Connections: Normal Power Sensing/Control: 120V or 277V Emergency Power: 120V or 277V Load Ratings: 20A Ballast Load Rating 1800W Incandescent Load Rating at 120V 1500W Incandescent Load Rating at 277V (CEPC-1 only) Size: CEPC-1 Body Size: 2-7/8” x 1-3/4” x 1-3/4” Flushmount size: 4-3/4”x2-3/4”x 1/4” CEPC-D-F-S-* Surface mount size: 6”x6”x2-1/4” CEPC-1 mounts to a 4-11/16” Junction box with single gang plater ring UL94-5VA Rated Plastic Color: CEPC-1 = White, CEPC-D-F-S-* = Black Weight: CEPC-1 = 8oz, CEPC-D-F-S-* = 16oz Ambient Temp Rating: 32°F - 140°F (0°C - 60°C) Compatibility: CEPC-1: iLumin SC-RP, SC-RPB and Greengate Occupancy Sensors CEPC-D-F-S-*: iLumin SC-UN, SC-UN-FT Standards 2 www.coopercontrol.com Operation The CEPC senses a local single normal power circuit. As long as normal power is present the CEPC permits normal and emergency switching and dimming of the lighting load from the iLumin architectural dimming system. If normal power is lost for any reason, the CEPC will force the connected emergency fixtures to full ON. The CEPC can be wired as either a control device along with a relay panel and occupancy sensor, or as a shunt to bypass line voltage switching devices when normal power fails. The CEPC-D-F-S is a universally compatible device that allows control of 2, 3, and 4-wire emergency dimming loads. When normal power is lost the CEPC-D-F-S will force the emergency fixtures to the full bright condition. Both CEPC models include a test switch feature for verifying proper functionality. In addition the CEPC-1 model also provides an automatic test feature. Under normal operation, when the controlled load is turned OFF, the emergency lighting will remain on an additional 2.5 seconds, providing safety and convenience while leaving the area and eliminating the need of special equipment to test the emergency control of the device. Installation The CEPC can be installed down line of the iLumin panels. The CEPC should be located next to the emergency fixture it is controlling. Technical Data CEPC – Emergency Power Control September 2014 Wiring Diagram Wiring Diagram for 3-Wire Dimming Loads CEPC-1-D Emergency Power 3 4 20A Test Emergency Panel 5 6 7 8 9 10 Test 7 EM Neutral 20A Emergency Lighting Load Test Emergency Panel Emergency Lighting Load 6 EM Load RED Test (Violet 0-10V) Utility Power Blue X1 X2 (Violet 0-10V) 1 2 3 Utility Power Emergency Power 5 EM Hot 1 or 2 4 CEPC-D-F-S Regular Neutral 0-10V Gray wire Regular Line Hot (Sensing Circuit) iLumin SC-UN Power Card Load Hot Switched Hot Dimmed Hot Line CK4A or Room Controller Relay Neutral 3-Wire Dimming CEPC-D-F-S CEPC-D-F-S Wire## Wire 3 - Wire Dimming VIOGRY 1 1 Description Description iLumin Connection Connection iLumin 4-Wire Dimming CEPC-1-D Wire # Color Description iLumin Connection 1 Black Regular Hot (120V) Constant Hot and Relay Line 2 Orange Regular Hot (277V) Constant Hot and Relay Line iLumin Power Card (D) 3 Red Switched Hot Relay Load iLumin Power Card (N) 4 White Regular Neutral 5 blue Emergency Hot 6 Yellow Emergency Load Hot 7 White/Blue Emergency Neutral Do Not Do Not CutCut Blue Dimmer Violet (0-10V +) Do Not Cut Red To Load Violet (0-10V +) Black Cap Off 1 1 Regular HotHot Regular iLumin Power CardCard (L) iLumin Power (L) 2 2 Regular Neutral Regular Neutral iLumin Power CardCard (N) iLumin Power (N) 3 3 Emergency HotHot Emergency 4 4 Emergency Neutral 5 Switched Hot iLumin Power Card (S) 6 Dimmed Hot 7 Regular Neutral 5 6 7 8 9 Emergency Neutral Switched Hot iLumin Power Card (D) Regular Neutral iLumin Power Card (N) To Load Hot 9 Load Hot Hot ToTo Load Dimmed 10 Load Dimmed Hot ToTo Load Neutral 10 X1 X1 iLumin Power Card (S) Dimmed Hot 8 ToNot Load Do CutNeutral X2 X2 CK4A or Room Controller 0-10V outputs Panel Dimmer Output Violet Wiring Diagram for 2-Wire Dimming Loads CEPC-D-F-S Emergency Panel 5 6 7 Test Emergency Lighting Load X1 X2 Test Emergency Panel Yellow Test Red iLumin SC-UN Power Card Switchleg Regular Line Hot (iLumin SC-RP transformer power) (or other constant hot circuit) Load 20A Neutral CEPC-D-F-S CEPC-D-F-S # Wire Wire # Regular Neutral (iLumin SC-RP Neutral wire) iLumin SC-RP Relay Card Hot Switched Hot Dimmed Hot 2-Wire Dimming 2 - Wire Dimming Emergency Lighting Load Blue/ White Utility Power 1 2 Utility Power CEPC Emergency Power Blue Blue/ White 20A White Test 8 9 10 Black/ Orange 20A Wiring Diagram for 2-Wire Non Dimmed Loads Emergency Power 3 4 Line Normal Panel Description iLumin Connection Description iLumin Connection 2 - Wire Non Dimmed 2-Wire Non Dimmed 1 1 2 2 Regular Hot Regular Hot iLuminCard Power iLumin Power (L) Card (L) CEPCCEPC Wire # Description Regular Regular Neutral Neutral iLuminCard Power iLumin Power (N) Card (N) Blue Emergency Hot 3 3 Emergency Hot Emergency Hot Yellow Emergency Switchleg 4 4 Emergency Emergency Neutral Neutral Blue/White Emergency Neutral 5 5 Dimming Hot Dimming Hot 6 6 Not Used Not Used Black/Orange Hot(Sensing) (Sensing) Regular Hot Black/Orange Regular Transformer Power (or Transformer Power other constant hot circuit 7 7 Regular Regular Neutral Neutral Red Switchleg Relay Load Terminal Block 8 8 9 Regular Neutral Regular Neutral Transformer Neutral Wire Transformer Neutral wire Not Used 9 To LoadTo Hot Load Hot 10 To Load Neutral Do Not Cut X2 Do Not Cut X1 X2 Blue Yellow iLuminCard Power iLumin Power (D) Card (D) iLumin Power (N) Card (N) iLuminCard Power Blue/White Red White White Description iLumin Connection iLumin Connection Emergency Hot Emergency Switchleg Emergency Neutral Switchleg (or other constant hot circuit) Relay Load Terminal Block Not Used X1 10 Wire # To Load Neutral Do Not Cut Do Not Cut www.coopercontrol.com 3 Technical Data CEPC – Emergency Power Control September 2014 Ordering Catalog # Descriptoin Rating CEPC-1 CEPC-D-F-S-120 CEPC-D-F-S-277 Emergency Power Control 120V/277V Emergency Power Control 120V Emergency Power Control 277V 120V or 277V (Switching) 120V (2-wire, 3-wire, 4-wire dimming loads) 277V (2-wire, 3-wire, 4-wire dimming loads) CEPC-1-D Emergency Power Control 120V/277V 0-10V 120V or 277V (0-10 dimming loads) CEPC-1-CUL Emergency Power Control for Canada 120V/277V 120V or 277V (Switching) CEPC-D-F-S-120V-CUL Emergency Power Control for Canada 120V 120V (2-wire, 3-wire, 4-wire dimming loads) CEPC-D-F-S-277V-CUL Emergency Power Control for Canada 277V 277V (2-wire, 3-wire, 4-wire dimming loads) CEPC-1-D-CUL Emergency Power Control for Canada 120V/277V 0-10V 120V or 277V (0-10 dimming loads) Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, GA 30269 coopercontrol.com © 2014 Eaton All Rights Reserved Printed in USA Publication No. ACC140950 September 30, 2014 Eaton is a registered trademark. All other trademarks are property of their respective owners.