COOPER LIGHTING - SURE-LITES ® DESCRIPTION The P4C Series is a decorative, mini-system that features solid-state electronics and a long-life, maintenance-free battery. The low-profile design combined with its remote capabilities provides a flexible, low cost electronic system. The P4C is designed for surface mounting but may be semi-recessed or fully recessed by using a field-installed recessing kit. The diffused tungsten halogen light source and reliable electronics make the P4C Series ideal for illuminating corridors, stairways, doorways, and offices. Type Catalog # Project Date Comments Prepared by S P E C I F I C AT I O N F E AT U R E S E l e c t ro n i c H o u s i n g C o n s t ru c t i o n H e a d / L a m p Da t a - Dual Voltage Input 120/277 VAC, 60 Hz - Line-latching - Solid-state Voltage Limited Charger - Solid-state Switching - Low-Voltage Disconnect - Brownout Circuit - Overload/Short Circuit Protection - Test Switch/Power Indicator Light - Black Thermoplastic - Conduit Knockouts, 1/2" - Universal J-Box Mounting Pattern - Surface Mount, Recessed, SemiRecessed - Wall or Ceiling Mounting - Tungsten Halogen Standard - Glare-Free Lens - Remote Capability - High Impact Acrylic Lens - Optional Impact-Resistant Polycarbonate Lens - Test Switch Behind Flexible Lens - White Thermoplastic Collar with Reflector Code Compliance - UL 924 Listed - Life Safety NFPA 101 - NEC/OSHA - Most State and Local Codes B a tte r y - Sealed Nickel Cadmium - Maintenance-Free, Long-Life - Full Recharge Time, 24 hrs. (max.) - Color Coded Leadwires Wa rra n t y - Unit: 1-year - Battery: 15-year pro-rata P4C SERIES T H E R M O P L AST I C D E C O R AT I V E S QU A R E SEALED NICKEL C A D M I U M B AT T E RY 8 7/8" [225mm] E M E R G E N CY L I G H T I N G 2 1/4" [57mm] 5" [127mm] 8 7/8" [225mm] E L E C T R I C A L R AT I N G S R a t e d W a t t a ge to 87 1/2% of Rated D.C. Voltage Model P4C6 P4C7 P4C72 3 DC Voltage 1 1/2 Hours 6 6 6 15 24 24 2 Hours 12 18 18 3 Hours 8 12 12 Lamp Information 4 Hours 6 10 10 Type Wattage Number Bi-Pin Halogen Bi-Pin Halogen Bi-Pin Halogen 10 10 10 29-40 29-40 29-40 ORDERING INFORMATION E N E R G Y D ATA Series Accessories P4C6 Protective Housing Input Current (Max.): P4C7 WG7=Wire Guard 120V= .06A VS1=Polycarbonate Vandal Shield 277V= .03A P4C72 1 2 P4C6 VS1WP=Polycarbonate Vandal Shield - Weatherproof Rough-In Kit P4C7, P4C72 USF1=Rough-In Kit for Semi-Recessed Installation 8-1/4''L x 8-1/4''W x 2-7/8''D (210mm X 210mm X 73mm) Input Current (Max.): FRK1=Rough-In Kit for Fully Recessed Installation 9-1/8''L x 9-1/8''W x 5-1/8''D (232mm X 232mm X 130mm) 120V= .07A VK1=Voltmeter Notes: 277V= .04A 1 Twin Lamps. 2 Order separately. Specifications and dimensions subject to change without notice. Consult your representative for additional options and finishes. ADX041162 pc 2010-07-15 11:03:14 P4C SERIES P H OTO M E T R I C S Emergency Photometrics Emergency Photometrics Mounting Height 5' 6' 7' 8' 9' Initial Horizontal Footcandles at Nadir 1.60 1.12 0.84 0.66 0.53 Mounting Height Dia. of Circle with 0.5 Footcandle Illumination 5' 6' 7' 8' 9' 10' 9'9" 9'7" 8'2" 12'9" 13'2" Initial Horizontal Footcandles at Nadir Dia. of Circle with 0.5 Footcandle Illumination 3.76 2.63 1.95 1.51 1.21 1.00 11'9" 12'0" 12'9" 13'0" 13'1" 12'10" Twin Lamp Model Lamp No. 29-40 Initial Lumens – 29-40 @ 201 each Single Lamp Model Lamp No. 29-40 Initial Lumens – 29-40 @ 201 T E C H N I C A L DATA Optics High output tungsten halogen lamps are optimally located in polished metal reflector assembly. High strength acrylic diffuser is matched to the optical system to maximize light output. E n c l o s u re Attractively styled thermoplastic housing is impact resistant. White collar with regress blend nicely with interior decors. Semi-recessed installation in walls and ceilings is facilitated with the USF-1 accessory kit. FRK-1 accessory rough-in kit allows the P4C unit to be fully recessed in ceiling installations. FRK-1 is supplied with white finishing trim. L i n e - L a t ch e d Sure-Lites’ line-latched electronic circuitry makes installation easy and economical. A labor efficient AC-activated load switch prevents the lamps from turning on during installation to a non-energized AC circuit. Line-latching eliminates the need for a contractor’s return to a job site to connect the batteries when the building’s main power is permanently turned on. S o l i d - S t a te C h a rge r Supplied with a 120/277 VAC, voltage regulated solid-state charger. Immediately upon restoration of AC current after a power failure, the charger provides a high charge rate. The charge circuit reacts to the condition of the battery and alters the rate of charge in order to maintain peak battery capacity and maximize battery life. Solid-state construction recharges the battery following a power failure in accordance with UL 924. O ve rl o a d a n d S h o rt C i rc u i t P ro te c t i o n Te s t Sw i t ch / Powe r I n d i c a to r L i g h t The solid-state overload monitoring device in the DC circuit disconnects the lamp load from the battery should excessive wattage demands be made and automatically resets when the overload or short circuit is removed. This overload current protective feature eliminates the need for fuses or circuit breakers for the DC load. Conveniently located Test Switch allows for manual verification of proper operation of the transfer circuit and emergency lamps. The Power Indicator Light provides visual assurance that the AC power is on. B row n o u t C i rc u i t The brownout circuit in Sure- Lites’ units monitors the flow of AC current to the unit and activates the emergency lighting system when a predetermined reduction of AC power occurs. This dip in voltage will cause most ballasted fixtures to extinguish causing loss of normal lighting even though a total power failure has not occurred. S e a l e d L e a d C a l c i u m B a tte r y The fully sealed, long-life, maintenance-free lead calcium battery is ideal for emergency lighting applications. These recombinant cycle batteries typically provide eight to ten years of life and may be operated in any position. Wa rra n t y All Sure-Lites’ units are backed by a firm oneyear warranty against defect in material and workmanship (excluding lamps). Maintenancefree, long-life, sealed lead calcium batteries carry a five-year pro-rata warranty. S o l i d - S t a te Tra n s fe r The unit incorporates a solid-state switching transistor which eliminates corroded and pitted contacts or mechanical failures associated with relays. The switching circuit is designed to detect a loss of AC voltage and automatically energizes the lamp(s). Upon restoration of the AC power, the emergency lamp(s) will switch off and the charger will automatically recharge the battery. L ow- Vo l t a ge D i s c o n n e c t When the battery’s terminal voltage falls below 80% of the rated voltage, the low-voltage circuitry disconnects the lighting load. The disconnect remains in effect until normal utility power is restored, preventing deep battery discharge. Specifications and dimensions subject to change without notice. Sure-Lites • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801 ADX041162 pc 2010-07-15 11:03:14 2010-08-11 10:08:31