GENERAL INFORMATION

advertisement
OSP10DA-EN (REV. D)
ENGLISH
Title 24
Compliant
IN U.S.A.: Cooper Wiring Devices, 203 Cooper Circle, Peachtree City, GA 30269 • 866-853-4293
NEXION PASSIVE INFRARED TECHNOLOGY (PIR) DUAL RELAY OCCUPANCY SENSING WALL SWITCH — OSP10D
PASSIVE
INFRARED
A
GENERAL INFORMATION
• For Indoor use only
• Technology: Passive Infrared (PIR)
36’
20’
RATINGS:
Major Motion, IR
8’
15’
120VAC
• Incandescent/Tungsten – Max load: 6.7 Amps, 800W, 50/60 Hz
• Fluorescent Ballast – Max. load: 10 Amps, 1200W, 50/60 Hz
• Motor Load: ¼ HP
277VAC
• Fluorescent Ballast – Max. load: 9.8 Amps, 2700W, 50/60 Hz
Minor Motion, IR
RoHS
INSTINCT™
TECHNOLOGY
• Ensure that DIP SW 11 & 12 are in the up position ().
• Place the device in Test Mode (refer below to TEST Mode).
• Rotate the Blue dial fully counterclockwise to Min.
• Immediately leave the area and observe that the lights turn OFF after
15 seconds.
• Return to the room. The lights should NOT automatically turn ON the lights.
• Rotate the blue dial clockwise in small increments, and pause for 5 seconds
after each adjustment, until the light turns ON. Take care to not block the
sensor from natural daylight while adjusting the blue dial. When the light
turns ON, the adjustment is complete.
• The sensor will now prevent the lights from turning ON automatically for
any light level brighter than the calibrated light level.
SPECIFICATIONS:
• Compatible with Magnetic ballast or Electronic ballast
• The life of some fluorescent lamps may be shortened by frequent switching.
Compatibility should be verified with the fluorescent ballast manufacturer.
• No Minimum Load Requirements
• Coverage: Major Motion – 1,000 ft2
Minor Motion – 300 ft2
• Time Delay: Self Adjusting or Selectable 5,15,30 minutes
• Light Level Sensing: 0 to 200 foot-candles
• Operating Temperature: 32 F to 104 F
• Operating Relative Humidity: 20% to 90 % non-condensing
• Mounting Strap Dimension: 4.20 inch x 1.73 inch
• Product Housing Dimension: 2.62 inch Long x 1.75 Wide x 1.90 Deep
• PIR Detection: Red LED
DESCRIPTION:
The OSP10D Occupancy Sensor is a Dual Output Passive Infrared (PIR) motion
sensing lighting control and conventional wall switch all in one. The dual output
allows separate control of two different loads.
INSTALLATION:
• When replacing a switch, choose a location that has clear line-of-sight
between the sensor and the area being controlled.
• Before installing or servicing the sensor, the power MUST be turned OFF at
the circuit breaker.
• The sensor should be installed according to National Electric Code and all
applicable local codes.
• The sensor should be wired according to the applicable wiring diagram
shown, using the wire connectors provided.
• Mount the device to the wallbox using the mounting screws provided, and
proceed with the setup process.
• After completing the set-up process install the wallplate.
Time Delay Adjustment (DIP SW 1 - SW 2)
SET-UP PROCESS
Auto Adjust () - This is the normal factory setting. In this mode the time
delay and sensitivity will automatically adjust based on the occupant usage,
starting with a time delay of 10 minutes.
5 Min / 15 Min / 30 Min – There are three choices for fixed time delay. Refer to
Table 1 for DIP Switch positions.
• Tools Required:
Small flat head screwdriver
Field of View Adjustment
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
General Explanation
After applying power to the device, wait 2 minutes for the sensor to power up
and stabilize before proceeding with the setup. All adjustment features and
mode selection switches are located under the main button. The button is
removed by releasing latches on either side of the button. DIP Switches are
located under the DIP Switch label.
Adjustments should be made with the HVAC system ON in order that the effects
of airflow on the sensor will be accounted for.
If the sensor is mounted in a position that causes the sensor to view undesired
areas such as a hallway, the unwanted triggering of the sensor can be reduced
by placing the provided non-reflective strips onto the sensor lens.
WIRING DIAGRAM 1: DUAL LEVEL SINGLE CIRCUIT
PIR Sensitivity Adjustment (DIP SW 5)
This adjustment is typically used to improve Major motion performance.
The Red LED will blink momentarily when the PIR sensor detects motion.
Default setting for DIP SW 5 is down. If the Red LED is constantly ON the sensitivity can be reduced by 50% by moving DIP SW 5 up ().
HOT
BLACK
BLUE
RED
RED
Daylight Adjustment (Blue Dial)
• This feature prevents the lights from automatically turning ON when there is
sufficient natural lighting, regardless of whether the room is occupied.
• If this feature is not required the blue dial should be rotated fully clockwise.
This feature is also disabled by the Daylighting Mode (Refer below to Daylight
Mode)
• This adjustment must be done when the natural light level is at the level when
the lights should turn ON automatically.
GREEN
LOAD 2
GROUND
NEUTRAL
LOAD 1
Table 1: Dip Switch Settings
WIRING DIAGRAM 2: DUAL LEVEL DUAL CIRCUIT
Time Delay
CIRCUIT 2
HOT
RED
3
4
Override
Not Used
Not Used
Not Used
Daylighting
Relay 1
Relay 2
DIP Switch
1
2
Auto*
q
q
Auto
q
Auto
q
Full
q
Disable
q
Disable
q
Disable
q
Disable
q
5 Minutes
p
Manual
p
Manual
p
50%
p
Enable
p
Enable
p
Enable
p
Enable
p
15 Minutes
30 Minutes
p
p
q
p
BLUE
BLACK
PIR Sensitivity Walk-Through Mode
Relay 2 (Red)
p
CIRCUIT 1
HOT
Activation Mode
Relay 1 (Blue)
RED
5
6
8
7
9
12
11
10
Troubleshooting
*Self-Adjusts to
GREEN
10 min. user=
Default
LOAD 1
LOAD 2
CIRCUIT 1
GROUND
Issue
Possible Causes
Suggestions
Sensor is in Manual ON mode
Press pushbutton, if Auto Mode
is desired change Activation Mode to Auto.
mode
Override Mode (DIP SW 8)
NEUTRAL (CIRCUIT 2)
NEUTRAL (CIRCUIT 1)
CAUTION: IF A ROOM IS WIRED FOR TWO CIRCUITS USING TWO SEPARATE HOT LEADS, IT IS VERY IMPORTANT TO CONNECT
ONLY ONE CIRCUIT PER RELAY.
*BOTH CIRCUITS MUST BE FED FROM THE SAME PHASE.
This feature allows the sensor to operate as a service switch in the
unlikely event of a failure. The device will not time out when in this mode.
The Factory default is DISABLE ().
To enable Override, select ENABLE ().
Sensor was turned OFF manually. If the SenIf LED is ON this is an indication that the lights were
sor was turned OFF manually before the time
Lights
turned OFF manually.
delay expired, lights will remain OFF for the
Will Not
Press the pushbutton to turn the lights back ON.
remainder
of
the
time
delay.
Turn ON
automatically
If all lights are required to turn ON adjust
Daylight Feature Enabled
DIP Switches 11 and 12 and/or daylight potentiometer.
Power interruption
Check incoming voltage and/or wiring.
Daylighting Mode (DIP SW 11 and DIP SW 12)
MODE SELECTIONS
Activation Mode (DIP SW 3 and DIP SW 4)
This setting allows the sensor to be set to either Auto Mode (Occupancy) or
Manual Mode (Vacancy). Each output has its own individual control for
Activation Mode.
Auto Mode () Lights will turn ON automatically when a person enters the
room, and will turn OFF automatically after the sensor times out.
Manual Mode () Lights must be turned ON manually and will turn OFF
automatically after the sensor times out.
This feature allows you to select individually if you want to allow the control of
the outputs to be affected by the amount of natural light.
The factory default is for this feature to be disabled for both output 1 and 2
( ).
To enable the daylight control feature select ENABLE () for either output.
When enabled the light level set by the Blue dial will determine the light level
below which the lights will be allowed to turn ON when motion is detected.
Refer to “Daylight Adjustment” section.
Test Mode - Factory Setting (DIP SW 12)
Walkthrough Mode (DIP SW 6)
This feature allows for additional energy savings by turning the lights OFF
after only 2 minutes regardless of the time delay setting. This occurs when a
person is only detected for a short initial period of time (less than 20 seconds).
The Factory default is DISABLE ().
To enable the Walkthrough feature select ENABLE ().
When the sensor is initially powered up it will enter the Test Mode. In the Test
mode the time delay is reduced to 15 seconds to allow easy setup.
The sensor will automatically exit the test mode 5 minutes after the sensor
turns OFF.
In order to return the sensor to the Test Mode, toggle DIP SW 12 from its
current position, wait 3 seconds, and then return back to its original position.
WIRING DIAGRAM 3: DUAL LEVEL SINGLE CIRCUIT 3-WAY
TRAVELER
WIRES
Lights
Will Not
Turn ON
manually
Power interruption
Check incoming voltage and/or wiring.
Power interruption
Check incoming voltage and/or wiring.
Power interruption
Check incoming voltage and/or wiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-866-853-4293
Override
Make sure sensor is not in Override Mode
(DIP Switch 8 down).
Self-Adjust
If sensor is in Self-Adjust Mode, it may be possible for
the unit to have increased the time delay to a 30 minute
delay. If the lights do not turn OFF after 30 minutes
follow next step.
30 Minute Delay
Maximum time delay is 30 Minutes. Check DIP
Switches to verify DIP Switch settings. If lights do not
turn OFF at the set time delay, check next step.
PIR activated by heat source other than
occupant
Move DIP Switch 5 up.
Wiring error
Check wiring.
Lights
Will Not
Turn OFF
automatically
Lights
Will Not
Turn OFF
manually
If lights will still not turn OFF, call Technical Services at 1-866-853-4293
HOT
PIR LENS
COOPER WIRING DEVICES LIMITED 5 YEAR WARRANTY
RED (PIR)
DETECTION LED
BLACK
BLUE
RED
RED
BLUE
RED
GREEN
DAYLIGHT SENSOR
LIGHT LEVEL
ADJUSTMENT
RED
Min
Max
DAYLIGHTING
Time Delay
Auto
5 Min
15 Min
30 Min
1
Enable / Manual
3 Act Relay 1
4 Act Relay 2
5 See Instruction Sheet
6 Walk Through
2
Min
Max
ULTRASONIC SENSITIVITY
Disable / Auto
7, 9, 10 Not Used
8 Override
11 Daylight Relay 1
12 Daylight Relay 2
DIP SWITCHES
(located under label)
GREEN
LOAD 2
GROUND
BLACK
LOAD 1
REMOVABLE FASCIA
FOR COLOR CHANGE
GROUND
NEUTRAL
3-WAY WIRING DIAGRAM: LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT
ON/OFF BUTTON
Cooper Wiring Devices (CWD) warrants this device to be free of defects in materials and workmanship in normal
use and service for a period of five years from date of original purchase. THIS 5 YEAR LIMITED WARRANTY IS IN
LIEU OF ALL OTHER WARRANTIES, OBLIGATIONS, OR LIABILITIES, EXPRESSED OR IMPLIED (INCLUDING ANY
IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE THAT IS IN DURATION IN
EXCESS OF 5 YEARS FROM THE DATE OF ORIGINAL CONSUMER PURCHASE). NO AGENT, REPRESENTATIVE, OR
EMPLOYEE OF CWD HAS AUTHORITY TO INCREASE OR ALTER THE OBLIGATIONS OF CWD UNDER THIS
WARRANTY.
To obtain warranty service for any properly installed CWD device that proves defective in normal use send the
defective Sensor prepaid and insured to Quality Control Dept., Cooper Wiring Devices, 203 Cooper Circle, Peachtree
City, GA 30269; in Canada: Cooper Wiring Devices, 5925 McLaughlin Road, Mississauga, Ontario L5R 1B8.
CWD will repair or replace the defective unit, at its option. CWD will not be responsible under this warranty if
examination shows that the defective condition of the unit was caused by misuse, abuse, improper installation,
alteration, improper maintenance or repair of damage in shipment to CWD.
CWD SHALL HAVE NO RESPONSIBILITY FOR INSTALLATION OF THE SENSOR, OR FOR ANY PERSONAL INJURY,
PROPERTY DAMAGE, OR ANY SPECIAL, INCIDENTAL, CONTINGENT, OR CONSEQUENTIAL DAMAGES OF ANY KIND,
RESULTING FROM DEFECTS IN THE SENSOR OR FOR BREACH OF ANY EXPRESS OR IMPLIED
WARRANTY ON THIS PRODUCT.
Download