OSD10NA-EN (REV. D) ENGLISH Title 24 Compliant IN U.S.A.: Cooper Wiring Devices, 203 Cooper Circle, Peachtree City, GA 30269 • 866-853-4293 NEXION DUAL TECHNOLOGY SINGLE RELAY OCCUPANCY SENSING WALL SWITCH — OSD10N GENERAL INFORMATION Daylight Adjustment (Blue Dial) • For Indoor use only • Technology: Passive Infrared (PIR) and Ultrasonic (U/S) 36’ 20’ RATINGS: Minor Motion, IR Major Motion, IR 8’ 15’ 120VAC • Incandescent/Tungsten – Max load: 6.7 Amps, 800W, 50/60 Hz • Fluorescent Ballast – Max. load: 10 Amps, 1200W, 50/60 Hz • Motor Load: ¼ HP 277VAC • Fluorescent Ballast – Max. load: 9.8 Amps, 2700W, 50/60 Hz DESCRIPTION: The OSD10N Occupancy Sensor is a Passive Infrared (PIR) and Ultrasonic (U/S) motion sensing lighting control and conventional wall switch all in one. The sensor combines PIR and U/S technologies to monitor a room for occupancy. The combination of these two technologies enables the sensor to detect both Minor Motion, such as hand movements, and Major Motion, such as a person walking into a room. INSTALLATION: • When replacing a switch, choose a location that has clear line-of-sight between the sensor and the area being controlled. • Before installing or servicing the sensor, the power MUST be turned OFF at the circuit breaker. • The sensor should be installed according to National Electric Code and all applicable local codes. • The sensor should be wired according to the applicable wiring diagram shown, using the wire connectors provided. • Mount the device to the wallbox using the mounting screws provided, and proceed with the setup process. • After completing the set-up process install the wallplate. 8’ SPECIFICATIONS: • Compatible with Magnetic ballast or Electronic ballast • The life of some fluorescent lamps may be shortened by frequent switching. Compatibility should be verified with the fluorescent ballast manufacturer. • Requires Neutral connection • No Minimum Load Requirements • Coverage: Major Motion – 1,000 ft2 Minor Motion – 300 ft2 • Time Delay: Self Adjusting or Selectable 5,15,30 minutes • Light Level Sensing: 0 to 200 foot-candles • Operating Temperature: 32 F to 104 F • Operating Relative Humidity: 20% to 90 % non-condensing • Mounting Strap Dimension: 4.20 inch x 1.73 inch • Product Housing Dimension: 2.62 inch Long x 1.75 Wide x 1.90 Deep • PIR Detection: Red LED • Ultrasonic Detection: Green LED INSTINCT™ TECHNOLOGY PASSIVE INFRARED A ULTRASONIC ACTIVATED RoHS • This feature prevents the lights from automatically turning ON when there is sufficient natural lighting, regardless of whether the room is occupied. • If this feature is not required the blue dial should be rotated fully clockwise. • This adjustment must be done when the natural light level is at the level when the lights should turn ON automatically. • Ensure that DIP SW 11 & 12 are in the down position (). • Place the device in Test Mode (refer below to TEST Mode). • Rotate the Blue dial fully counterclockwise to Min. • Immediately leave the area and observe that the lights turn OFF after 15 seconds. • Return to the room. The lights should NOT automatically turn ON the lights. • Rotate the blue dial clockwise in small increments, and pause for 5 seconds after each adjustment, until the light turns ON. Take care to not block the sensor from WIRING DIAGRAM 1: SINGLE LEVEL WIRING DIAGRAM Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. BLUE BLACK HOT SET-UP PROCESS • Tools Required: Small flat head screwdriver GREEN WHITE General Explanation After applying power to the device, wait 2 minutes for the sensor to power up and stabilize before proceeding with the setup. All adjustment features and mode selection switches are located under the main button. The button is removed by releasing latches on either side of the button. DIP Switches are located under the DIP Switch label. Adjustments should be made with the HVAC system ON in order that the effects of airflow on the sensor will be accounted for. PIR Sensitivity Adjustment (DIP SW 5) This adjustment is typically used to improve Major motion performance. The Red LED will blink momentarily when the PIR sensor detects motion. Default setting for DIP SW 5 is down. If the Red LED is constantly ON the sensitivity can be reduced by 50% by moving DIP SW 5 up (). LOAD GROUND NEUTRAL WIRING DIAGRAM 2: DUAL LEVEL WIRING USING A TOGGLE SWITCH WIRING DIAGRAM BLACK HOT BLUE UltraSonic Sensitivity Adjustment (Green Dial) This adjustment is typically used to improve Minor Motion performance. The Green LED will blink momentarily when the U/S sensor detects motion. Ultrasonic sensitivity is adjusted by rotating the green dial. When standing in front of the sensor and waving your hands, if the Green LED does not turn ON, then increase sensitivity by rotating the Green dial by clockwise towards Max in small increments. If the green LED remains ON when there is no motion, then reduce sensitivity by rotating the Green dial counterclockwise towards Min in small increments. GREEN WHITE GROUND NEUTRAL LOAD 1 LOAD 2 Troubleshooting Table 1: Dip Switch Settings Issue Time Delay Activation Mode Not Used PIR Sensitivity Walk-Through Mode Not Used Override Mode Not Used Trigger Mode 9 10 Not Used Relay 1 (Blue) DIP Switch 1 2 Auto Adjustment q q Auto q Full q Disable q Disable q Either q 5 Minutes p p Manual p 50% p Enable p Enable p Both p 15 Minutes 30 Minutes p p q p 3 4 6 5 7 8 11 12 2 minutes regardless of the time delay setting. This occurs when a person is only detected for a short initial period of time (less than 20 seconds). The Factory default is DISABLE (). To enable the Walkthrough feature select ENABLE (). TRAVELER WIRES HOT BLACK BLUE BLUE GREEN Override Mode (DIP SW 8) BLACK This feature allows the sensor to operate as a service switch in the unlikely event of a failure. The device will not time out when in this mode. The Factory default is DISABLE (). To enable Override, select ENABLE (). GREEN WHITE GROUND LOAD WHITE Suggestions Sensor is in Manual ON mode Press pushbutton, if Auto Mode is desired change Activation Mode to Auto Sensor was turned OFF manually. If the Sensor was turned OFF manually before the Lights time delay expired, lights will remain off for Will Not the remainder of the time delay. Turn ON automatically Daylight Feature Enabled Default = WIRING DIAGRAM 3: SINGLE LEVEL THREE-WAY WIRING DIAGRAM Possible Causes See Test Mode Lights Will Not Turn ON manually Check incoming voltage and/or wiring Daylight Feature Enabled If all lights are required to turn ON adjust daylight potentiometer. Power interruption Power interruption Check incoming voltage and/or wiring. Check incoming voltage and/or wiring ON/OFF Button Disabled Move DIP Switch 7 down If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-866-853-4293 Trigger Mode (DIP SW 10) NEUTRAL natural daylight while adjusting the blue dial. When the Light turns ON, the adjustment is complete. • The sensor will now prevent the lights from turning ON automatically for any light level brighter than the calibrated light level. Time Delay Adjustment (DIP SW 1 - SW 2) Auto Adjust () - This is the normal factory setting. In this mode the time delay and sensitivity will automatically adjust based on the occupant usage, starting with a time delay of 10 minutes. 5 Min / 15 Min / 30 Min – There are three choices for fixed time delay. Refer to Table 1 for DIP Switch positions. This feature is used for installations that are prone to false triggering due to air flow. The Factory default is EITHER (). To reduce unwanted false triggering, select BOTH (). Override Make sure sensor is not in Overide Mode (DIP Switch 8 up). Self-Adjust If sensor is in Self-Adjust Mode, it may be possible for the unit to have increased the time delay to a 30 minute delay. If the lights do not turn OFF after 30 minutes follow next step. 30 Minute Delay Maximum time delay is 30 Minutes. Check DIP Switches to verify DIP Switch settings. If lights do not turn OFF at the set time delay, check next step. Ultrasonic Sensitivity set High Lower sensitivity by turning green potentiometer counter-clockwise in small decrements. PIR activated by heat source other than occupant Move DIP Switch 5 up. MODE SELECTIONS Activation Mode (DIP SW 3) This setting allows the sensor to be set to either Auto Mode (Occupancy) or Manual Mode (Vacancy). Auto Mode () Lights will turn ON automatically when a person enters the room, and will turn OFF automatically after the sensor times out. Manual Mode () Lights must be turned ON manually and will turn OFF automatically after the sensor times out. RED (PIR) AND GREEN (U/S) DETECTION LEDs Wiring error. Wiring error. Check wiring. Check wiring. DAYLIGHT SENSOR LIGHT LEVEL ADJUSTMENT PIR LENS ULTRASONIC DETECTION TIME DELAY 1 Min Max DAYLIGHTING 3 5 4 6 2 Auto 5 Min 15 Min 30 Min Act Relay 1 Manual PIR Sensitivity 50% Enable/Both Maintain Lights ON Walk Through Min Max ULTRASONIC Auto Full Disable/Either 7 See Instruction 8 Override Walkthrough Mode (DIP SW 6) This feature allows for additional energy savings by turning the lights OFF after only Lights Will Not Turn OFF manually If lights will still not turn OFF, call Technical Services at 1-866-853-4293 Field of View Adjustment If the sensor is mounted in a position that causes the sensor to view undesired areas such as a hallway, the unwanted triggering of the sensor can be reduced by placing the provided non-reflective strips onto the sensor lens. Lights Will Not Turn OFF automatically Test Mode - Factory Setting (DIP SW 12) When the sensor is initially powered up it will enter the Test Mode. In the Test mode the time delay is reduced to 15 seconds to allow easy setup. The sensor will automatically exit the test mode 5 minutes after the sensor turns OFF. In order to return the sensor to the Test Mode, toggle DIP SW 12 from its current position, wait 3 seconds, and then return back to its original position. If all lights are required to turn ON adjust daylight potentiometer. Power interruption GROUND THREE-WAY WIRING DIAGRAM: LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT. Press the pushbutton to turn the lights back ON. ON/OFF BUTTON Sheet ULTRASONIC SENSITIVITY ADJUSTMENT DIP SWITCHES (located under label) COOPER WIRING DEVICES LIMITED 5 YEAR WARRANTY Cooper Wiring Devices (CWD) warrants this device to be free of defects in materials and workmanship in normal use and service for a period of five years from date of original purchase. THIS 5 YEAR LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, OBLIGATIONS, OR LIABILITIES, EXPRESSED OR IMPLIED (INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE THAT IS IN DURATION IN EXCESS OF 5 YEARS FROM THE DATE OF ORIGINAL CONSUMER PURCHASE). NO AGENT, REPRESENTATIVE, OR EMPLOYEE OF CWD HAS AUTHORITY TO INCREASE OR ALTER THE OBLIGATIONS OF CWD UNDER THIS WARRANTY. To obtain warranty service for any properly installed CWD device that proves defective in normal use send the defective Sensor prepaid and insured to Quality Control Dept., Cooper Wiring Devices, 203 Cooper Circle, Peachtree City, GA 30269; in Canada: Cooper Wiring Devices, 5925 McLaughlin Road, Mississauga, Ontario L5R 1B8. CWD will repair or replace the defective unit, at its option. CWD will not be responsible under this warranty if examination shows that the defective condition of the unit was caused by misuse, abuse, improper installation, alteration, improper maintenance or repair of damage in shipment to CWD. CWD SHALL HAVE NO RESPONSIBILITY FOR INSTALLATION OF THE SENSOR, OR FOR ANY PERSONAL INJURY, PROPERTY DAMAGE, OR ANY SPECIAL, INCIDENTAL, CONTINGENT, OR CONSEQUENTIAL DAMAGES OF ANY KIND, RESULTING FROM DEFECTS IN THE SENSOR OR FOR BREACH OF ANY EXPRESS OR IMPLIED WARRANTY ON THIS PRODUCT.