Quadcast LED Occupancy Sensor and Bird Guard TM INSTALLATION INSTRUCTIONS Sheet 1 of 3 IMPORTANT: READ BEFORE INSTALLING FIXTURE. RETAIN FOR FUTURE REFERENCE. SAFETY: This fixture must be wired in accordance with the National Electrical Code and applicable local codes and ordinances. Proper grounding is required to insure personal safety. Carefully observe grounding procedure under installation section. WARNING: Make certain power is OFF before starting installation or attempting any maintenance. Risk of fire/electric shock. If not qualified, consult an electrician. 7/27/2012 IMI-776 • RISK OF ELECTRIC SHOCK—Disconnect power at fuse or circuit breaker before installing or servicing. • RISK OF BURN—Disconnect power and allow fixture to cool before servicing. • RISK OF PERSONAL INJURY—Fixture may become damaged and/or unstable if not installed properly. Tighten all fixture components to their recommended torque values. WARNING: Make certain power is OFF before starting installation or attempting any maintenance. TOOLS REQUIRED: Electrical wiring tools, Phillips screwdriver, 1-1/8" metal drill bit or sheet metal punch, wire stripper. Occupancy sensor installation (FIG. 4). Occupancy Sensor Location Mark 1. U nscrew door mounting screws with Phillips screwdriver. CAUTION: DOOR WILL HINGE DOWN UPON REMOVAL OF SCREWS. SUPPORT DOOR WHILE REMOVING SCREWS. (2) Door Hinge Screws (2) Door Mounting Screws 2. Unscrew ground wire nut and disconnect grounding conductor from door. 3. U nscrew door hinge screws and remove door. For Steps 4-9 place door on a soft surface. CAUTION: ENSURE THE PAINT FINISH IS NOT SCRATCHED OR CHIPPED. 4. U sing a 1-1/8" metal hole saw or equivalent sheet metal punch, drill/punch a 1-1/8" diameter hole in the door at the indented occupancy sensor location mark on the door (FIG. 1). 5. R emove lens and tightening ring from occupancy sensor. 6. Insert the threaded sensor collar through the hole from inside the fixture. Sensor gasket should be inside of fixture (FIG. 2). 7. S ecure sensor to housing using tightening ring. Tighten to snug fit (FIG. 3). 8. R emove sticker on sensor face and screw lens to sensor with snug fit. Do not over tighten lens as threads will strip. 9. R eattach door by screwing in the two door hinge screws, tighten to 15 inch-pounds. 10. R econnect the green grounding conductor and tighten nut to 10 inch-pounds. Refer to FIG. 4 page 3 for occupancy sensor wiring diagram • Locate the line (Black) and neutral (White) conductors on the input side of the driver. Cut the white and black conductor 3" from the driver. Strip insulation on exposed ends 3/8" in length. • Connect the sensor load conductor (RED) to the driver input black conductor using the lever-lock connector supplied with occupancy sensor. • Connect the sensor neutral conductor (white) to the driver input neutral and AC input neutral conductors using the lever-lock connector supplied with occupancy sensor. • Connect the sensor line conductor (Black) to the AC input black conductor using the lever-lock connector supplied with occupancy sensor. 11. L ift door to closing position and secure with two door mounting screws. Tighten screws to 15 inch-pounds to seal fixture. ALL WIRING AND ELECTRICAL CONNECTIONS MUST REMAIN INSIDE ENCLOSURE. ENSURE WIRING IS SECURED WITHIN ENCLOSURE WHILE CLOSING DOOR. FIG. 1 Bottom of Fixture FIG. 2 Occupancy Sensor Lens Sensor Gasket Occupancy Sensor Tightening Ring FIG. 3 Door Occupancy Sensor Align sensor as shown on inside of door Inside of Door —continued These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every possible contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for user’s purpose, please contact your nearest representative. NOTE: Specifications and dimensions subject to change without notice. Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 P: 770.486.4800 F: 770.486.4801 www.cooperlighting.com ADH121391 Quadcast LED Occupancy Sensor and Bird Guard TM INSTALLATION INSTRUCTIONS Sheet 2 of 3 IMPORTANT: READ BEFORE INSTALLING FIXTURE. RETAIN FOR FUTURE REFERENCE. 7/27/2012 IMI-776 WARNING: Make certain power is OFF before starting installation or attempting any maintenance. DESCRIPTION AND OPERATION The occupancy sensor has an integral photocontrol that turns lighting ON and OFF based on occupancy and ambient light levels. 2. M ove out of the sensor’s view. Lights turn OFF after 30 seconds. 3. M ove into the controlled area. The red LED in the sensor lens should illuminate and the lights should turn ON. The sensors use passive infrared (PIR) sensing technology that reacts to changes in infrared energy (moving body heat) within the coverage area. Once the space is vacant and the time delay elapses (adjustable from 30 seconds to 30 minutes), lights will turn OFF. TEST AND ADJUST LIGHT LEVEL PHOTOCONTROL SENSOR AND TIME DELAY 1. R emove the lens assembly and adjust the light level and the time delay to minimum. Put the lens assembly back onto the sensor. Leave the controlled area and let the sensor time out so lights are OFF. 2. E nter the controlled area and lights should remain OFF. 3. M ake sure your body does not cast a shadow on the sensor. Turn the light level trimpot clockwise in small increments. After each adjustment, put the lens back on the sensor then move about the controlled area. Wait 5-10 seconds to see if the lights turn ON. 4. C ontinue this procedure until the lights turn ON. At this setting the lights will not turn ON with occupancy if the light level is above the current level. 5. S et the time delay to the desired 20 min. 15 min. setting. The time delay can be set from 25 min. 30 seconds (fully counterclockwise) to 10 min. 30 minutes (fully clockwise). IMPORTANT, THERE IS AN INITIAL WARM-UP PERIOD: It may take up to a minute before the lights turn ON due to a sensor warm-up period required during initial power-up. This occurs during installation or after a lengthy power failure only. WARNING DO NOT OVERTURN TRIMPOT WHEN ADJUSTING THE SENSOR. DO NOT TOUCH THE SQUARE INFRARED DETECTOR UNDER THE LENS ASSEMBLY. LIGHT LEVEL FEATURE The Light Level photocontrol feature holds OFF and turns OFF lights when the space is occupied and adequate ambient light exists. When the light level drops below the set level it will turn the lights ON when the space is occupied. The factory setting is for maximum, meaning that even bright ambient light will not cause the sensor to hold the lights OFF if it detects occupancy in the controlled area. 5 min. TROUBLESHOOTING Factory Settings Light Level Maximum (light level should not affect load operation*) 30 min. 30 sec. Time Delay 15 minutes SENSOR ADJUSTMENT The Light Level and Time Delay adjustment trimpots are located under the lens assembly. The trimpots are accessed easily after the sensor is mounted in the fixture. Gently unscrew the lens assembly. Do not remove the thumbscrew collar; it holds the sensor in place on the fixture. Identify each trimpot. Set the light level when the controlled light would normally be turned OFF due to the presence of sufficient daylight or other electric light. [If this feature is not needed, leave the light level at maximum (fully clockwise)]. * A t the maximum setting, the light level entering the photosensor must exceed 120 Fc, which only happens in rare applications or when the lens is removed. TEST OCCUPANCY SENSOR (OPTIONAL) 1. S et Light Level to maximum (fully clockwise, factory setting) and Time Delay to minimum (fully counterclockwise). Put the lens assembly back onto the sensor. LIGHTS WILL NOT TURN ON: • LED does not flash: - Check all wire connections and verify the ground wire is tightly secured. • LED does flash: - Check all wire connections and verify the load wire is tightly secured. - Check light level photocontrol setting. Cover the sensor lens to simulate darkness in the room. If the lights come ON, the light level needs to be adjusted. If set for minimum, more than 10 Fc of ambient light will cause the lights to be held OFF. See Sensor Adjustment section for instructions. LIGHTS WILL NOT TURN OFF: The time delay can be set from a minimum of 30 seconds (fully counter-clockwise) to a maximum of 30 minutes (fully clockwise). Ensure that the time delay is set to the desired delay and that there is no movement within the sensor’s view for that time period. • To quickly test the unit for proper operation, turn the time delay to minimum and move out of the sensor’s view. Lights should turn OFF after 30 seconds. OPERATION DURING POWER-UP During the sensor warm-up period, which can last up to a minute after initial power-up (or after a lengthy power outage), the load can be either ON or OFF, depending on the status of the relay before the sensor was powered down. After warm-up, the sensor will open or close the relay to correspond to the occupancy status of the room. —continued These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every possible contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for user’s purpose, please contact your nearest representative. NOTE: Specifications and dimensions subject to change without notice. Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 P: 770.486.4800 F: 770.486.4801 www.cooperlighting.com ADH121391 Quadcast LED Occupancy Sensor and Bird Guard TM INSTALLATION INSTRUCTIONS Sheet 3 of 3 IMPORTANT: READ BEFORE INSTALLING FIXTURE. RETAIN FOR FUTURE REFERENCE. 7/27/2012 IMI-776 WARNING: Make certain power is OFF before starting installation or attempting any maintenance. BIRD GUARD INSTALLATION (FIG 5): Conduit NOTE: Bird Guard requires minimum 7" length of pendant pipe (Supplied by others). Bird guard is suitable for use with 1-gang, 2-gang, and 4" round UL wet location listed junction boxes. Install bird guard after fixture installation. FIG. 5 1. Remove the bird guard screw. 2. Gently open bird guard and slide around conduit. 3. Align and insert metal tabs on bird guard with slots in housing. 4. Reinstall the bird guard screw to snug fit. 5. Bend tabs on bird guard to secure to housing. Screw Housing Slots Bird Guard Tabs WIRING DIAGRAM FIG. 4 Factory Wired AC Input to Driver Line (Black) LED Driver DC OUTPUT Neutral (White) AC INPUT Quadcast without Occupancy Sensor Red Black Factory Wired Driver to LEDs Factory Wired AC Input to Driver Neutral (White) Neutral (White) Line (Black) Occupancy Sensor Line (Black) AC INPUT Line (Black) Neutral (White) LED Driver DC OUTPUT Neutral (White) Quadcast with Occupancy Sensor Red Black Factory Wired Driver to LEDs Line (Black) Load (Red) Load (Red) These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every possible contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for user’s purpose, please contact your nearest representative. NOTE: Specifications and dimensions subject to change without notice. Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 P: 770.486.4800 F: 770.486.4801 www.cooperlighting.com ADH121391