Recloser Advantages at Breaker Rating Levels

advertisement
Recloser Advantages
at Breaker Rating Levels
• Superior Control Systems.
• Recloser Application
Versatility.
• Performance Proven
Design, Construction.
• Easily Tested, Quickly
Commissioned.
• Low Maintenance,
Long Operating Life.
Kyle® Vacuum Reclosers
Type VSA20 and VSA20A
800 and 1200 Amps Continuous
20000 Amps Sym Interrupting
The powerful Form 6 Recloser Control
offers the coordination flexibility and
dependable performance needed in
complex feeder protection schemes. A
standardized, yet customizable system,
the Form 6 integrates protection,
metering, and automation functions.
Form 6
Recloser Control
Low-Maintenance Reclosers
RATINGS
Voltage Ratings
Maximum Design Voltage (kV)
Nominal Operating Voltage (kV)
Basic Insulation Level (BIL) (kV)
60 Hertz Withstand Voltage (kV)
Dry, one minute
Wet, ten seconds
Max RIV at 1.0 MHz/9.41 kV(µV)
VSA20
VSA20A
15.5
2.4–14.4
110
15.5
2.4–14.4
110
50
45
100
50
45
100
Kyle VSA20 and VSA20A air-insulated vacuum reclosers
operate dependably over a long life and require
practically no service other than periodic inspection.
Operating components are designed for long-term
dependability and to withstand the rugged recloser duty.
Inspection is simplified by easy access to the mechanism
and interrupter cabinets; no special tools or procedures
are required.
The recloser operating mechanism employs a 240-Vac
motor to charge the closing spring that in turn provides
the force to close the vacuum interrupters and charge the
opening springs. When tripping and closing operations
are required, springs are released by solenoids actuated
with 24-volt signals from the recloser's electronic control.
Current Ratings
VSA20 VSA20A
Continuous Current (A)
Symmetric Interrupting Current (A)
Magnetizing Interrupting Current (A)
3-Second Current,Symmetric (A)
Momentary Current,RMS Asym (A)
Capacitive Switching,General Purpose,
Isolated Bank (A)
800
20000
28
20000
32000
1200
20000
42
20000
32000
250
250
Duty Cycle
Percent of
Interrupting Rating
X/R Ratio
15-20
45-55
90-100
Number of Unit
Operations
4
8
16
88
112
32
Total 232
Electrical Specifications
Trip Solenoid:
Operating voltage (Vdc)............................................... 24
Peak current (A) ........................................................ 12.2
Current duration (cycles) .............................................1.25
Close Solenoid:
Operating voltage (Vdc)............................................... 24
Peak current (A) ........................................................ 15.5
Current duration (cycles) ...............................................1.5
Spring Charging Motor:
Operating Voltage (Vac)
Voltage Range (Vac)
Maximum Current, RMS (A)
Steady State Current (A)
Running Time (cycles (sec))
STANDARD
240
160-257
14
4.1
40 (0.67)
ACCESSORY
120
90-127
18
9
40 (0.67)
Arc interruption takes place within the sealed vacuum
interrupters; consequently, no arcing by-products
contaminate the recloser structure. The interrupters are
mounted independently of the recloser bushings. This
permits quicker bushing replacement and requires no
interrupter adjustment.
Multiple Operations Stored Should the motor supply
be lost while the closing spring is charged, an open-closeopen operating sequence remains stored in the mechanism.
If the recloser trips under these conditions, the stored
closing operation allows an immediate reclosing if
required; after such closing, one further trip operation
then remains stored. Once closed, the recloser always
contains energy for at least one trip operation.
Manual Operations Totally manual operations are
easily achieved while motor power is lost. A hand crank
can be used to charge the closing spring; its release
charges the tripping springs. Closing and subsequent
tripping operations can then be manually actuated at the
operator cabinet or from the recloser control.
Mechanical Life
Open-Close, no load operations ......................... 2500
Reclosing Interval The first reclosing interval may be
configured to operate in less than 24 cycles, followed by a
reclosing interval of 2 seconds.
Quality Vacuum Interrupters
High-quality Kyle vacuum interrupters provide fast, lowenergy arc interruption and exhibit long contact and
interrupter life. Because of their short contact stroke,
operation of the vacuum interrupters causes less stress
and wear on the recloser mechanism, which allows a
longer operating life requiring less service.
Kyle vacuum interrupters employ a metal and ceramic
housing for maximum strength and long-term vacuum
integrity. The high-alumina ceramic is more than five
times as strong as glass, permits a higher processing
temperature to develop maximum purity of envelope
interior, and is impervious to helium penetration to
sustain the vacuum level. Metal components are of highpurity alloys to minimize contamination.
Because the smallest amount of internal contamination
can significantly shorten the interrupter's life, a cleanroom facility is used for interrupter production. Special
care is taken to avoid even minute contamination
whether it be from dust particles, machining oils, or
human body salts.
Superior Control
The Form 6: a powerful, yet flexible recloser control with
all your operating needs met in the front panel design.
One-touch function keys and analysis keys, intuitive
graphical interfaces, and LED indicators with day or
night visibility all simplify training and operation.
ProViewTM software, which operates in a Microsoft
Windows environment, integrates protection, metering,
and automation functions for quick configuration of the
Form 6 recloser control. Innovative control features that
provide new tools for protection, metering, and analysis
include Oscillography, Recloser Replay, directional
functionality, TCC Editor II, and the graphical Idea
WorkbenchTM.
®
®
Form 6 Control
with front panel
programmability
and interrogation.
ORDERING INFORMATION
To completely specify a Type VSA20 or VSA20A recloser,
the order must include description and catalog number of:
1. The basic recloser.
2. Recloser accessories.
3. Recloser mounting equipment.
4. Recloser control and accessories.
5. Control cable.
Description
Basic Recloser
Type VSA20
Type VSA20A
Description
Recloser Accessories
17-in creepage-distance bushings,
set of six, factory installed on a
VSA20 recloser
Catalog Number
KVS-15-20-800
KVS-15-20-1200
Catalog
Number
KA59VS
Three-stage auxiliary switch with
six independent contacts
KA55VSM3
120-Vac spring charging motor
KA60VSM2
External contact position indicator
KA61VSM2
External spring charging handle
KA59VSM2
Mounting Equipment
VSA20
Substation frame extension
Single pole-mounting hanger
Control mounting bracket
Single-size cabinet
Double-size cabinet
VSA20
Substation frame extension
Single pole-mounting hanger
Control mounting bracket
Single-size cabinet
Double-size cabinet
KA55VS1
KA56VS
KA55VS2
KA55VS4
KA55VS8
KA52VSM
KA55VS2
KA55VS9
622
(24.5)
1130 (44.5)
260
(10.25)
305
(12)
286
(11.25)
330 (13)
Dimensions
These figures show a VSA20 (upper) and a
VSA20A recloser (lower) installed on the
substation-mounting frame extension
accessory. Dimensions shown are only for
general information; for critical construction
dimensions, refer to factory.
305
(12)
OPEN
Operating
Cabinet
SPRINGS
DISCHARGED
TYPE VSA20
2107 (83)
at
minimum
height
Manual Trip
Pullring
All dimensions are given as mm (in).
Adjustable
2440 (96)
to
2897 (114)
in 76 (3)
increments
Bushing Specifications
Creepage Distance
VSA20, standard bushing ............305 (12)
VSA20, accessory bushing ...........432 (17)
VSA20A, standard bushing ..........432 (17)
Minimum Strike Distance
VSA20 recloser
Terminal to ground ..................191 (7.5)
Across phase ..........................244 (9.75)
Phase to phase.......................244 (9.75)
VSA20A recloser
Terminal to ground ................197 (7.75)
Across phase .............................279 (11)
Phase to phase..........................279 (11)
Grounding Connector
2/0-250 MCM
1080 (42.5)
572
(22.5)
1143 (45)
622
(24.5)
826
(32.5)
1308 (51.5)
298
(11.75)
356
(14)
356
(14)
286
(11.25)
330 (13)
OPEN
Operating
Cabinet
Equipment Mass (Weight) kg (lb.)
VSA20 recloser only...................238 (525)
VSA20 with pole-top frame ........272 (600)
VSA20 with substation frame .....306 (675)
SPRINGS
DISCHARGED
TYPE VSA20A
2156 (85)
at
minimum
height
Manual Trip
Pullring
VSA20A recloser only.................336 (740)
VSA20A with pole-top frame......381 (840)
VSA20A with substation frame ...404 (890)
Adjustable
2486 (98)
to
2943 (116)
in 76 (3)
increments
Grounding Connector
2/0-250 MCM
1257 (49.5)
775 (30.5)
1321 (52)
838 (33)
©2001 Cooper Industries, Inc.
Kyle® is a registered trademarks of Cooper Industries, Inc.
ProView™, Idea™, and Idea Workbench™ are trademarks of Cooper Industries, Inc.
Microsoft® and Windows® are either registered trademarks or trademarks of
Microsoft Corporation in the United States and/or other countries.
Bulletin 91048 • June 2001 • Supersedes 12/91