Kyle Shrubline VFI P a d m o u n t e d Va c u u m F a u l t I n t e r r u p t e r Overcurrent Protection For Underground Residential Distribution Systems Resettable Fault Protection through 25kV Deadfront Construction for Safety • • • • • No Fuses To Replace No Special To o l s Fast Service Restoration Resettable Breaker Operation Breaker Doubles As An Open/Close Load-Break Switch • Familiar Low Profile Design Kyle Shrubline VFI Safe - Efficient - Easy to Use 51.0 Dimensions (inches) 36.3 34.0 6.0 8.75 16.0 T1 S1 20.0 69.2 35.0 10.5 30.7 1.5 1.5 29.7 34.0 1.5 1.5 13.5 Pentahead Bolt with Padlockable Hasp Nameplate Operation One-Line Diagram One Piece Door Construction, for Ease of Operation Oil Fill Plug Pressure Relief Valve Oil Level Indicator Parking Stands 200A Bushing Wells Standard Floating Lock Pocket for Easy Engagement Note: Elbows and bushing well inserts are not supplied. 2 VFI Tri-Phase Control VFI Operating Handle Oil Drain Plug Ground Provisions Vacuum Fa ul t Inte rrupter Overcurrent Protection with Circuit Breaker Ease and Speed Shrubline VFI Padmount Switchgear Shrubline VFI, a Breaker “and” a Switch The Shrubline VFI (Vacuum Fault Interrupter) represents the latest technology in low profile URD Padmount Switchgear. Overcurrent protection is accomplished with Kyle ® vacuum interrupters instead of fuses. The resettable breaker mechanism allows immediate service restoration, eliminating the added downtime and expenses associated with changing out conventional fuses. The Shrubline VFI breaker also serves as a vacuum load-break switch. Tap switching has traditionally been accomplished by pulling load-break elbows, or by loadbusting fuses. With the Shrubline VFI, the tap can be switched with a simple push-pull of the operation handle. Tri-Phase Control The Shrubline VFI meets the switching duty cycle requirements of ANSI C37.72 and the stringent interrupter duty cycle requirements of ANSI C37.60. Shrubline VFI also meets the enclosure integrity and coating performance requirements of ANSI C57.12.28. The Tri-Phase electronic breaker control sets a new standard for ease of Time-Current-Curve (TCC) coordination. Just like Kyle’s time-proven recloser controls, the Tri-Phase control offers over 100 minimum trip settings and an assortment of time-current-curves. With standard instantaneous trip and optional minimum response curves, the Tri-Phase control will satisfy all of your coordination needs. Low Maintenance The internal mechanisms and bus work are insulated with mineral oil, which provides electrical insulation only. Both load and fault interruption take place in sealed vacuum interrupters. ANSI Padmount Switchgear Standards Low Profile Sealed Construction Shrubline VFI utilizes the same familiar time proven tank and enclosure currently used by RTE Distribution Transformers. The low profile design features a safe “no sharp edges’” enclosure, making it safe for residential applications. The low profile design is unobtrusive and aesthetically acceptable. The sealed tank construction, like all Kyle padmount switchgear, is immune to airborne contaminants and moisture which contaminate and degrade the insulation on livefront and air-insulated switchgear. Since there are no expulsion fuses or switching by-products to contaminate the insulation medium, maintenance intervals are greatly increased. Oil Level Indicators Oil level indicators are provided on the tank, inside the cable compartment, to provide clear indication of proper oil level within the switchgear. For more details on the Tri-Phase Control, refer to VFI Bulletin 91041 3 Kyle Shrubline VFI Applications Introduction The Kyle Shrubline VFI is specially designed for use in Underground Residential Distribution (URD). From riser pole to the end of a URD loop, the Shrubline VFI offers practical and affordable advantages. Shrubline VFI replaces riser pole fuses, provides intermediate “in-line” fault protection, tap or “branch line” protection, protection for isolated loads, and protection for normally open points in loop-fed URD systems. Examples Refer to Figure 1 for examples of various Shrubline VFI applications. 1 . 200A Riser Pole Protection Installed at the base of the riser pole, a Shrubline VFI replaces the riser pole fuse. Riser pole protection for singlephase tap lines is typically accomplished with fused cutouts. Fuse selection can result in improper coordination with upline protective devices; or in some cases, fuses can be selected which are not sized properly to handle the dynamics of the tap line load. In extreme situations, the only traditional solution may be to install a sectionalizing switch on the riser pole and leave these taps virtually unfused. In the cases where fuse size and type are limited by the sensitivity of upline devices, a Shrubline VFI with the flexibility of the Tri-Phase control may be an acceptable alternative. It is sometimes necessary to provide service to isolated loads utilizing dedicated, long extension “cross-country” taps. Unprotected, the additional exposure reduces the service reliability to all interconnected distribution lines. The Shrubline VFI is an economical, reliable, and maintenance-free means of individually protecting isolated loads. 3 . T- Taps and Three Point Junctions 5 . Terminal Point Protection (Retrofit) Multiple tap lines from main 200A URD single-phase circuits using 3-point splices have been virtually eliminated in URD systems. This is due primarily to the inability to sectionalize these lines during fault-chasing scenarios. Reductions in overall reliability and increased outage durations are typical operational hazards of permanent “hard-wired” taps. While above- ground separable connectors allow manual sectionalizing during fault-chasing, the Shrubline VFI additionally provides overcurrent protection and “localizes” the fault to assist in minimizing the outage area and the outage duration. Switching and load transfers are often required during routine operation of loopfed URD systems. As a result of these transfers, both protective device loading and protective device exposure are increased. In mature URD developments, these zones of protection can be maintained by installing Shrubline VFI at locations where “permanent” normally open points have been established. ALTERNATE OVERHEAD FEED OVERHEAD FEED 2 . Intermediate Fault Protection 1 “In-line” fault protection is now available for long single-phase radial URD taps. Radial URD single-phase taplines 3 2/ 5 4 LOAD Figure 1 URD One-line 4 4 . Individual Protection for Isolated Loads often do not have fault protective devices applied at mid-point or at other strategic intermediate points on the line. Primary faults must be cleared by the riser fuse and result in widespread outages. Service restoration accomplished using manual “fault-chasing” techniques can be cumbersome and time consuming. Properly coordinated and suitably located, the Shrubline VFI can effectively minimize both outage area and outage duration. 1 Vacuum Fa ul t Inte rrupter Simple, Money-Saving Substitute For Costly Fuse Systems Coordination The EF curve is provided as a standard and is suitable for most applications. Four optional curves (KF, TF, H, and F) are also available to meet your coordination requirements. When standard curves miscoordinate, the instantaneous trip feature, or one of the 5 minimum response accessories, can be applied to modify or “shape” the TCC to fit the requirements of the application. TCCs with definite response times at high fault currents, like the H and F curves shown in Figure 2, can be used to coordinate Shrubline VFI with upline relay type devices as well as with downline Shrubline VFI. In Figure 2, an upline device with an F-Curve at 130A H Curve at 100A minimum trip. These settings could be applied to Shrublines 1 and 3 or 1 and 4 in Figure 1. Coordination and application of the TriPhase control is identical to fuse application, but with the benefit of a greatly expanded offering of trip ratings and timing curves. In Figure 3, the EF TCC provides ideal coordination when protecting single-phase 1000 EF-TCC 100A Min. Trip 100 Composite: 50A ELSP & 15A Bayonet T 10 I M E 1 Single-phase URD transformer protection. 400A GND 1200A Phase 0.10 1000 Shrubline VFI with H & F TCCs C09-400A GND 0.010 100 1 CO9 1200A PHASE T 10 I M E 1 VFI-100A H-TCC VFI-130A F-TCC 0.010 10 100 1000 10 100 1000 10000 100000 10000 100000 CURRENT Figure 2 Shrubline VFI with H and F TCCs minimum trip works with both the upline substation breaker or recloser and the downline Shrubline VFI with an 1000 TF-TCC 130A Min. Trip CURRENT Figure 3 Single-phase URD transformer protection 0.10 1 Shrubline VFI can sense and clear 12kA fault currents in two cycles. This works well with upline substation breakers or reclosers which typically operate in 3-5 cycles, and downline expulsion fuses which can operate in 0.5 to 1.0 cycle. For optimum coordination with upline fuses and downline VFI, TCCs must be matched for each application to prevent simultaneous operation of the fuse and the VFI. In Figure 4, midline and downline Shrublines coordinate with each other through 12kA. However, the midline Shrubline only coordinates with the upline 100A T-link fuse at the riser pole up through 2300A; while the downline Shrubline coordinates with that same 100A T-link fuse up through 3885A. These settings are applicable for VFIs beyond fused riser poles like Shrublines 1, 3, and 4 of Figure 1 (substitute fuses for switches in Figure 1). distribution transformer loop schemes. The cable and transformer can be protected to rated load with ample margin between the EF and the upline recloser. The Shrubline VFI, used with the control features and accessories, provides an economical solution to virtually any problem which arises when planning the application of protective devices for URD systems. TF-TCC 100A Min.Trip 100 Shrubline VFI to Fuse Coordination 100A T-Link Fuse T 10 I M E 1 0.10 0.010 1 10 100 1000 10000 100000 CURRENT Figure 4 Shrubline VFI in Fuse Coordination 5 Kyle Shrubline VFI Options and Accessories The TCCs in Figure 6 shows coordination between three devices with TF TCCs. Note that minimum trip settings are chosen to simulate 50A, 65A, and 80A rated devices. Miscoordination Tri-Phase Control Accessories Minimum Response Time The minimum response time accessory is used to achieve coordination between inline protective interrupting devices, located where fault-current levels would normally cause simultaneous tripping. 1000 3 Shrubline VFI w/standard TCC Minimum Response Time Accessory 100 TF-TCC 130A Min. Trip Typical Response Curve 10 100 10 100 1000 10000 100000 CURRENT 1000 10000 100000 CURRENT Figure 5 M i n i m u m R e s p o n s e T i m e A c c e ssory The accessory inhibits tripping until a predetermined (user selectable) minimum time has elapsed; available minimum response times are 0.050, 0.100, 0.145, 0.205, 0.260, 0.335, 0.405, 0.495, or 0.580 seconds; time selection is made with a convenient slide switch. The example shown in Figure 5 demonstrates a response curve modified by Minimum Response. 6 100 1000 10000 100000 Figure 7 Shrubline VFI with Minimum Response Figure 6 Shrubline VFI with Standard TCC 1 10 CURRENT 1 0.010 TF-TCC 160A Min. Trip 0.58s Min. Response TF-TCC 100A Min. Trip 1 0.010 0.10 T 10 I M E 1 0.010 TF-TCC 100A Min. Trip TF-TCC 160A Min. Trip Minimum Response Time 100 0.10 0.10 T 10 I M E 1 Shrubline VFI w/Min. Response TF-TCC 130A Min. Trip 0.205s Min. Response 100 T 10 I M E 1 1000 1000 occurs at times below 0.07 seconds. This miscoordination can be corrected by applying the minimum response accessory to each device as shown in Figure 7. Minimum response selections of 0.58 seconds for the 160A minimum trip and 0.205 seconds for the 130A minimum trip can be applied. Vacuum Fault Interrupter Ordering Information • Single-Phase • 14.4 and 24.9kV Nominal • 200 Amp Max Continuous • 12000 Amp Interrupting Rating KSHRUB1 - Basic letters for a 15/25kV Kyle Shrubline VFI with 200A bushings. 1 Insulating Medium 1 - oil (standard) 2 - R-Temp* 1 Tank and Cabinet Construction 1 - Mild Steel (standard) 2 - Stainless Steel* How To Order To order a Kyle Shrubline VFI: 1. Use the chart at right to construct a catalog number that describes the required basic construction. 2. From Tables 1 and 2, specify the catalog numbers for the time-current curves and bushing inserts. 3 Standard unit includes 200A wells only. KSHRUB1 *Non-standard items require longer leadtimes. TABLE 3 Accessories (One TCC per control required) KPA-TCC-EF (standard) KPA-TCC-F* * KPA-TCC-H* * KPA-TCC-KF* * KPA-TCC-TF* * Minimum Response TCCs KPA-MINR-EF* * KPA-MINR-F* * KPA-MINR-H* * KPA-MINR-KF* * *Default settings: EF Timing Card, 80A Min. Trip; Instantaneous Trip OFF. **Ordered in place of standard TCC card. TABLE 2 Bushing Inserts* Catalog Number Description Catalog Number Ground Rod KPA-1037-2 Operations Counter KPA-113-7 ExamVoltage (kV) One-Line Diagram Item 1 200A 200A S T 2 KSHRUB111 15 200A 200A S T KSHRUB111 25 200A and KSHRUB111 15kV 200A S T 15 200A Single inserts source and tap Single inserts source, feedthru insert tap Feedthru insert source and tap Feedthru insert source, single insert tap and KPA-1036-1* Description Single inserts source and tap Single inserts source, feedthru insert tap Feedthru insert source and tap Feedthru insert source, single insert tap Catalog Number KPA-1035-1* 3 15kV KPA-1035-1 KPA-1035-2 KPA-1035-3 KPA-1035-4 25kV KPA-1036-1 KPA-1036-2 KPA-1036-3 KPA-1036-4 1 KSHRUB111 is the catalog number for the basic Kyle Shrubline VFI. TABLE 1 Time-Current Curve Cards* Fixed TCCs 1 200A 4 S 200A and KPA-1035-4* 25kV KSHRUB111 200A T 25 200A and KPA-1036-3* *Bushings and feedthru inserts are optional. For additional product and application information, contact your local Cooper Power Systems representative. *Standard unit is supplied with 200 Amp bushing wells only 7 K y le Shrubline VFI Features & Benefits: Resettable Breaker-Type Operation • No fusing expense • No spare fuses to keep on trucks or in stock • Eliminates installation of wrong replacement fuses • Can be used to de-energize tap prior to elbow removal, thus extending elbow life Adjustable Minimum Trip Ratings and Time-Current Curves • Current ratings can be changed to accommodate load changes • Minimize inventory of components • Shorter downtime for service restoration • Trip settings can be adjusted without de-energizing customers • Visual indication of faulted tap • Increased system protection for larger loads • Breaker doubles as an open/close switch • Large selection of TCCs for precise coordination Sealed Deadfront Construction Compact Size • Meets padmount switchgear standard ANSI C37.72, which requires deadfront construction for safety • Sealed oil insulated design allows compact construction through 25 kV • Meets ANSI C37.60 for fault interrupter duty • Low profile familiar design for residential applications • Meets ANSI C57.12.28 enclosure integrity and coating performance requirements • Non-vented design allows for application in high contaminant environments • Sealed tank eliminates catastrophic failure due to flood immersion The Quality System at Cooper Power Systems, Kyle Distribution Switchgear is ISO9001 Certified © 1999 Cooper Power Systems, Inc. ® Kyle is a Registered Trademark of Cooper Industries, Inc. Bulletin 94001 • July 1999 • Supersedes March 1994 File: Catalog 285-15 P.O. Box 1640 Waukesha, WI 53187 www.cooperpower.com KTM 7/99