UltraSIL polymer-housed VariSTAR station-class surge arresters

Surge Arresters
Catalog Data
CA235013EN
Effective December 2015
Supersedes August 2015
COOPER POWER
SERIES
UltraSIL® polymer-housed VariSTAR™
station-class surge arresters
General
Eaton has set a new standard of excellence for
polymer-housed station-class surge arresters with
its Cooper Power™ series UltraSIL® polymerhoused surge arresters. Enhancements in arrester
design allow Eaton to offer increased cantilever
strength and improved energy handling capability.
Eaton’s Cooper Power series VariSTAR® Type US,
UH, and UX station-class arresters incorporate
the industry recognized superior silicone rubber
housing with a unique high creep alternating shed
profile designed to withstand the most extreme
environments. The “standard” silicone rubber
housing is designed with a minimum specific
creepage distance of 31 mm/kV L-L, which meets
category IV (Very Heavy) pollution level according
to the IEC standard. This housing is applied over a
gapless MOV internal design.
Types US, UH, and UX arresters meet or exceed
the requirements of IEEE Std C62.11™-2005
standard including Short Circuit Tests performed
in accordance with IEEE Std C62.11a™-2008
standard.
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
1” STUD (UH, UX, and US outside of
exceptions below)
M12 STUD (US Cubicle Mount ≤ 60 kV
M20 STUD (US Base Mount ≤ 108 kV
UltraSIL SILICONE
RUBBER HOUSING
Table 1. UltraSIL (US, UH, and UX)
Station-Class Ratings and
Characteristics
ALUMINUM
ELECTRODE
Arrester Characteristic
Rating
Arrester Voltage Ratings (kV)
3-240
Cantilever Strength (in-Ibs)
US (3-108 kV)
UH (3-108 kV)
US (120-240 kV)
UX (3-108 kV)
UH (120-240 kV)
Rated Discharge Energy
(kJ/kV of MCOV)
US (3-108 kV)
UH (3-108 kV)
US (120-240 kV)
UX (3-108 kV)
UH (120-240 kV)
High Current
Withstand* (kA)
Impulse Classifying
Current (kA)
Pressure Relief Rating
(kA rms sym.)
System Frequency (Hz)
FIBERGLASS
REINFORCED EPOXY
COMPOSITE
MOV DISKS
ALUMINUM
ELECTRODE
ALUMINUM ALLOY
MOUNTING BASE
STAINLESS STEEL
NAMEPLATE
MDCLUltimate Static**
15,000
6,000
20,000
8,000
35,000
14,000
Single Impulse
Rating
3.9
6.2
10
100
10
63
50/60
* High current, short duration withstand (100 kA, 4/10 µs)
**Maximum design cantilever load–static or maximum working load is
40% of the ultimate.
Figure 1. Illustration of 10 kV UltraSIL Polymer-Housed VariSTAR Station-Class Arrester.
Construction
Features
The unique construction of UltraSIL polymer-housed Type US, UH,
and UX station-class arresters begins with world class Metal Oxide
Varistor (MOV) disks produced at our dedicated manufacturing
facility in Olean, NY. By manufacturing our own disks we maintain a
strict quality control over the entire pro­duction process, from initial
raw material inspection to final physical and electrical testing of
each disk. In addition, by controlling the manufacturing process of
both disks and arresters, we achieve the optimal combination. Eaton
produces MOV disks of unsurpassed quality through continuous
improvements in disk formulation and manufacturing technology.
The end result is a long history of in-service use with outstanding
durability and protective capability.
The UltraSIL silicone rubber housing was selected for its superior
insula­tion performance as compared to other polymeric housing
materials. Long term environmental testing has verified the lifetime
performance advantage that silicone rubber provides.
Arrester production begins by stacking glass-collared MOV disks in
series with aluminum end electrodes. Our proprietary process wraps
the assembly with a woven fiberglass-reinforced epoxy composite.
When cured, the arrester module is capable of withstanding heavy
electrical and cantilever load conditions.
The UltraSIL silicone rubber housing utilizes an inter­ference fit and
is bonded onto the internal module to form a solid, void-free, highdielectric strength insulation system. Once assembled, each arrester
must pass a strict series of electrical tests to insure the highest level
of in-service performance.
The silicone rubber housing results in lighter weight than similarly
rated porcelain-housed arresters. The silicone rubber housing is less
sensitive to physical damage than porcelain. Also, when compared
to other polymeric housing materials, silicone rubber generates
significantly lower external power losses under contaminated
conditions.
Independent laboratory tests have verified the superior water
repellent behavior of silicone rubber, which is responsible for the
lower external power losses, higher resistance to UV degradation
and surface tracking, superior performance in contaminated
environments, and other important insulating properties. Also,
UltraSIL silicone rubber has been proven to be non-flammable and
self-extinguishing per UL 94V0 standards.
The basic silicone rubber-housed arrester can be customized with
a variety of terminal and mounting options which allow users to
select the features that meet their application needs. Customers
who require longer creepage housings can easily select a different
housing option through the catalog numbering system. See pages
14-15 for a complete list of available options.
Operation
The operation of the UltraSIL polymer-housed Type US, UH, and UX
arrester is typical of gapless metal oxide arresters. During steadystate conditions, line-to-ground voltage is applied con­tinuously
between the line and ground terminals of the arrester. When surges
occur, the arrester immediately limits, or clamps, the overvoltage
condition by conducting the surge current to ground. After passage
of the surge, the arrester returns to its initial state, conducting
minimal leakage current. This minimal leakage current (which is
primarily capacitive, with a small resistive component) can be
withstood on a continuing basis.
The UltraSIL polymer-housed Type US, UH, and UX arresters easily
surpass the minimum fault current withstand requirements for
station-class arresters as defined in IEEE Std C62.11a™-2008
standard (40 kA). These arresters have been tested and shown to
withstand fault currents of 63 kA. During these tests, the silicone
2
www.eaton.com/cooperpowerseries
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
rubber housing ruptures without expelling internal parts.
UltraSIL polymer-housed Type US, UH, and UX arresters are ideal
for protection against repeated high energy switching surges and
provide reliable protection for substation equipment, capacitor banks,
multiple lines, and cable circuits. They are also ideal for applications
where lighter weight and shorter heights (when compared to
porcelain-housed arresters) are critical.
Design testing
The housing, internal components, and hardware of an arrester must
work together as a system. This system must stand up to years of
service while being subjected to a wide range of environmental and
electrical stresses. To ensure a superior level of performance, both
arrester components and finished arresters have been subjected
to a series of tests that accurately represents years of exposure to
actual field conditions. This testing far exceeds the requirements of
industry standards.
The UltraSIL polymer-housed arrester has also met or exceeded
all require­ments for station-class arresters as defined by IEEE
Std C62.11™-2005 standard. Reference CP1121 UltraSIL PolymerHoused VariSTAR Type US, UH and UX Station-Class Surge Arresters
Certified Test Report.
The Type US, UH, and UX arresters are USDA’s Rural Utilities Service
(RUS) Section ae approved, meeting or exceeding all RUS technical
specification and workmanship.
Production tests
Eaton has implemented a complete production test program to
ensure a quality product. Each MOV disk is subjected to a series of
electrical tests to maintain quality. We also perform additional tests
on every MOV disk batch. Listed below are the tests performed on
the MOV disks:
•
100% Physical Inspection
•
100% Discharge Voltage Test
•
100% Vref at Iref
•
100% Watt Loss Measured at 1.05 x MCOV
•
100% Transmission Line Discharge Energy Test
•
Batch High-Current, Short-Duration Test
•
Batch Thermal Stability Test
•
Batch Aging Test
Table 2. Recommended Arrester Applications for VariSTAR
Station-Class Arresters
System Voltage
(kV rms)
Recommended Arrester Rating (MCOV)
kV rms
Nominal
Maximum
Three-Wire or
Four-Wire Wye
Solidly Grounded
Neutral
2.4
4.16
4.8
6.9
2.52
4.37
5.04
7.25
3 (2.55)
3 (2.55)
—
6 (5.10)
8.32
8.74
6 (5.10)
12.0
12.6
12.47
13.1
13.2
13.9
13.8
14.5
20.78
21.8
22.86
24.0
24.9
26.2
34.5
36.2
46.0
48.3
69.0
72.5
115
121
138
145
161
169
9 (7.65)
10 (8.40)
9 (7.65)
10 (8.40)
10 (8.40)
12 (10.2)
10 (8.40)
12 (10.2)
15 (12.7)
21 (17.0)
18 (15.3)
21 (17.0)
18 (15.3)
21 (17.0)
27 (22.0)
30 (24.4)
36 (29.0)
39 (31.5)
54 (42.0)
60 (48.0)
90 (70.0)
96 (76.0)
108 (84.0)
120 (98.0)
120 (98.0)
132 (106)
144 (115)
3 (2.55)
6 (5.10)
6 (5.10)
9 (7.65)
9 (7.65)
10 (8.40)
12 (10.2)
15 (12.7)
15 (12.7)
18 (15.3)
15 (12.7)
—
15 (12.7)
18 (15.3)
24 (19.5)
27 (22.0)
24 (19.5)
27 (22.0)
24 (19.5)
27 (22.0)
36 (29.0)
39 (31.5)
48 (39.0)
—
72 (57.0)
—
108 (84.0)
—
132 (106)
144 (115)
144 (115)
168 (131)
—
230
242
172 (140)
180 (144)
192 (152)
228 (180)
240 (190)
—
1.600
1.500 1.486
Each fully assembled UltraSIL polymer-housed station-class arrester
must also pass the following production tests:
100% Physical Inspection
•
100% Vref Test
•
100% Watt Loss Test
•
100% Partial Discharge Inception Voltage Test
General application recommendations
The rating of an arrester is the maximum power-frequency lineto-ground voltage at which the arrester is designed to pass an
operating duty-cycle test (as defined in IEEE Std C62.11™-2005
standard). Table 2 provides a general application guide for the
selection of the proper arrester rating for a given system voltage
and grounding configurations as outlined in IEEE Std C62.22™2009 standard, which is the application guide for metal oxide surge
arresters.
1.427
1.417
1.400
1.358
Voltage (per unit COV)
•
Delta and
Ungrounded
Wye
1.300
No Prior Duty
1.348
1.289
1.279
1.220
1.200
1.210
Prior Duty
1.151
1.100
1.000
1.141
1.082
0.1
1
10
100
1000
10000
Time (sec)
Figure 2. Temporary overvoltage curve – 60° ambient
temperature.
Under fault conditions and other system anomalies, higher
than normal voltages can be imposed upon an arrester. With an
improper arrester selection, these abnormal system voltages can
cause an arrester to fail. To help ensure that the proper arrester
is selected, Eaton’s application engineers are available to make
recommendations.
www.eaton.com/cooperpowerseries
3
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
The following information is normally required:
Ordering information
1. Maximum system operating voltage.
Table 3 includes the shortened catalog numbers for UltraSIL
polymer-housed Type US, UH, and UX arresters. The arrester
represented by the shortened catalog number is configured with the
standard configurations shown in Table 10. The shortened catalog
numbers shown in Table 3 represent the same catalog numbers
shown in Table 9. For example, catalog number USAA060A from
Table 3 represents the same catalog number USAA060048A2845A11
from Table 9. Eaton offers other options that allow customers to
select specific features they desire. Options on housing sizes
(creepage length), hardware, and mounting options are available and
defined in Table 10. This table allows customers who prefer options
different from those in our standard Table 9 configuration to develop
a catalog number which provides the unique features they desire.
For additional assistance please contact your Eaton representative.
2. System grounding conditions;
A. For four-wire circuits, grounding conditions depend upon
whether the system is multi-grounded, whether it has
a neutral impedance and whether common primary and
secondary neutrals are used.
B. For three-wire circuits, grounding conditions depend upon
whether the system is solidly grounded at the source,
grounded through neutral impedance at the source transformers or ungrounded.
3. Available Fault Current.
4. Maximum line-to-ground voltage and overvoltage duration during
fault conditions.
Contact your Eaton representative to have your individual system
application needs reviewed.
Temporary overvoltage (TOV) withstand
ability
The UltraSIL polymer-housed Type US, UH, and UX arrester’s ability
to withstand 60 Hz overvoltage conditions (TOVs) is shown in Figure
2. The graph illustrates the time an arrester can survive a voltage,
and recover, without going into thermal runaway, for a given voltage
magnitude (expressed in Per Unit of arrester MCOV).
The graphs in Figure 2 illustrate TOV withstand ability, with and
without prior duty. The prior duty curve is based upon absorption of
rated energy (Refer to Table 1 — Single Impulse Rating) immediately
preceding application of the overvoltage.
Mounting information
The standard base of the UltraSIL polymer-housed Type US, UH, and
UX arresters is designed for mounting on 8.75” or 10” diameter bolt
circle patterns. The three slotted mounting holes are spaced 120°
from each other and are designed to handle 0.5” diameter bolts.
Mounting hardware (bolts, nuts, and washers) is not in­cluded with
the arrester. See Figure 3 for mounting base details. An inherently
strong design allows these arresters to be mounted in a variety of
ways. They can be mounted vertically, with attachment at the base,
or suspension (underhung) mounted. Eaton offers more flexibility
for customers to mount arresters in the field. Station-class arresters
can be configured in the underhung position (suspension mount) at
the plant or with a unique new option assembled in the field in the
underhung position*. UltraSIL polymer-housed station-class arresters
can also be horizontally mounted through 120 kV.
* Field base conversion for Types UH and UX only.
120° TYPICAL
(3) 0.56” x 1.18”
MOUNTING SLOTS
8.75” —
10.00”
DIA. BOLT
CIRCLE
THICKNESS OF
MOUNTING FEET
IS 1.25”
Figure 3. Mounting base details.
4
www.eaton.com/cooperpowerseries
Table 3. Shortened Catalog Numbers for Standard
Configuration Types US, UH, and UX Surge Arresters
Arrester
Rating
(kV rms)
MCOV
(kV rms)
Type US
Type UH
Type UX
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
120
132
138
144
162
168
172
180
192
198
204
216
228
240
2.55
5.1
7.65
8.4
10.2
12.7
15.3
17.0
19.5
22
24.4
27.5
29
31.5
34
36.5
39
42
48
53
57
62
68
72
76
84
98
106
111
115
130
131
140
144
152
160
165
174
180
190
USAA003A
USAA006A
USAA009A
USAA010A
USAA012A
USAA015A
USAA018A
USAA021A
USAA024A
USAA027A
USAA030A
USAA033A
USAA036A
USAA039A
USAA042A
USAA045A
USAA048A
USAA054A
USAA060A
USAA066A
USAA072A
USAA078A
USAA084A
USAA090A
USAA096A
USAA108A
USAA120A
USAA132A
USAA138A
USAA144A
USAA162A
USAA168A
USAA172A
USAA180A
USAA192A
USAA198A
USAA204A
USAA216A
USAA228A
USAA240A
UHAA003A
UHAA006A
UHAA009A
UHAA010A
UHAA012A
UHAA015A
UHAA018A
UHAA021A
UHAA024A
UHAA027A
UHAA030A
UHAA033A
UHAA036A
UHAA039A
UHAA042A
UHAA045A
UHAA048A
UHAA054A
UHAA060A
UHAA066A
UHAA072A
UHAA078A
UHAA084A
UHAA090A
UHAA096A
UHAA108A
UHAA120A
UHAA132A
UHAA138A
UHAA144A
UHAA162A
UHAA168A
UHAA172A
UHAA180A
UHAA192A
UHAA198A
UHAA204A
UHAA216A
UHAA228A
UHAA240A
UXAA003A
UXAA006A
UXAA009A
UXAA010A
UXAA012A
UXAA015A
UXAA018A
UXAA021A
UXAA024A
UXAA027A
UXAA030A
UXAA033A
UXAA036A
UXAA039A
UXAA042A
UXAA045A
UXAA048A
UXAA054A
UXAA060A
UXAA066A
UXAA072A
UXAA078A
UXAA084A
UXAA090A
UXAA096A
UXAA108A
-
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Protective characteristics
All UltraSIL polymer-housed Type US, UH, and UX arresters provide
excellent overvoltage protection for electrical equipment. The
specific protective characteristics for each arrester rating are shown
in Table 4 for US arresters, Table 5 for UH arresters and Table 6 for
UX arresters. Tables 5 and 6 are on pages 6 and 7, respectively.
Table 4. Protective Characteristics of the UltraSIL Polymer-Housed Station-Class Arrester-Type US
Arrester
Rating
(kV, rms)
Arrester
MCOV
(kV rms)
TOV*
1 Sec
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
120
132
138
144
162
168
172
180
192
198
204
216
228
240
2.55
5.1
7.65
8.4
10.2
12.7
15.3
17
19.5
22
24.4
27.5
29
31.5
34
36.5
39
42
48
53
57
62
68
72
76
84
98
106
111
115
130
131
140
144
152
160
165
174
180
190
3.5
6.9
10.4
11.4
13.9
17.2
20.8
23.1
26.5
29.9
33.1
37.3
39.4
42.8
46.2
49.6
53
57
65.2
72
77.4
84.2
92.3
97.8
103.2
114.1
133.1
143.9
150.7
156.2
176.5
177.9
190.1
195.6
206.4
217.3
224.1
236.3
244.4
258
Maximum Discharge Voltage (kV Crest)
8/20µs Current Wave
Switching Surge Protective Level***
(kV crest)
10
Sec
Front-of-wave
Protective
Level**
(kV Crest)
1.5 kA
3 kA
5 kA
10 kA
20 kA
40 kA
125 A
250 A
500 A
1000 A
3.3
6.6
9.9
10.8
13.1
16.4
19.7
21.9
25.1
28.4
31.5
35.4
37.4
40.6
43.8
47
50.3
54.1
61.9
68.3
73.5
79.9
87.7
92.8
98
108.3
126.3
136.6
143.1
148.2
167.6
168.9
180.5
185.6
195.9
206.2
212.7
224.3
232
244.9
8.8
17.5
26.2
28.8
34.9
43.5
52.4
58.2
66.7
75.3
83.5
94.1
99.2
108
117
125
134
144
165
182
195
213
233
247
260
288
314
339
355
368
416
419
448
461
486
512
528
556
576
608
6.8
13.6
20.4
22.4
27.2
33.8
40.8
45.3
51.9
58.6
65
73.2
77.2
83.9
90.5
97.2
104
112
128
142
152
165
181
192
203
224
250
270
283
293
331
334
357
367
387
408
420
443
459
484
7.2
14.4
21.6
23.7
28.8
35.8
43.1
47.9
55
62
68.8
77.5
81.7
88.8
95.8
103
110
119
136
150
161
175
192
203
215
237
263
285
298
309
349
352
376
387
408
430
443
467
483
510
7.6
15.2
22.7
24.9
30.3
37.7
45.4
50.4
57.8
65.2
72.3
81.5
86
93.4
101
109
116
125
143
158
169
184
202
214
226
249
275
298
312
323
365
368
393
404
427
449
463
488
505
533
8.3
16.6
24.9
27.3
33.1
41.3
49.7
55.2
63.3
71.4
79.2
89.3
94.2
103
111
119
127
137
156
172
185
202
221
234
247
273
298
323
338
350
396
399
426
438
463
487
502
529
548
578
9.1
18.2
27.3
29.9
36.3
45.2
54.5
60.5
69.4
78.3
86.8
97.9
104
113
121
130
139
150
171
189
203
221
242
257
271
299
323
349
366
379
429
432
461
475
501
527
544
573
593
626
10.4
20.7
31.1
34.1
41.4
51.5
62.1
69
79.1
89.2
98.9
112
118
128
138
148
159
171
195
215
232
252
276
292
309
341
361
390
408
423
478
482
515
530
559
589
607
640
662
699
5.9
11.8
17.7
19.4
23.5
29.3
35.3
39.2
44.9
50.7
56.2
63.3
66.8
72.5
78.3
84
89.8
96.7
111
122
132
143
157
166
175
194
219
237
248
257
291
293
313
322
340
358
369
389
402
424
6.1
12.1
18.1
19.9
24.1
30.1
36.2
40.2
46.1
52
57.7
65
68.6
74.5
80.4
86.3
92.2
99.3
114
126
135
147
161
171
180
199
225
243
255
264
298
300
321
330
348
367
378
399
413
435
6.3
12.5
18.8
20.6
25
31.1
37.5
41.6
47.8
53.9
59.8
67.3
71
77.1
83.2
89.4
95.5
103
118
130
140
152
167
177
186
206
232
251
263
272
308
310
331
341
360
378
390
412
426
449
6.6
13.1
19.6
21.5
26.1
32.5
39.1
43.5
49.8
56.2
62.4
70.3
74.1
80.5
86.9
93.3
99.6
108
123
136
146
159
174
184
195
215
241
261
273
283
319
322
344
354
373
393
405
427
442
467
* Temporary Overvoltage (TOV) with Prior Duty.
** Based on a 10 kA current impulse that results in a discharge voltage cresting in 0.5 µs.
*** 45-60 µs rise time for a 500 A peak current surge.
www.eaton.com/cooperpowerseries
5
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Table 5. Protective Characteristics of the UltraSIL Polymer-Housed Station-Class Arrester-Type UH
Arrester
Rating
(kV, rms)
Arrester
MCOV
(kV rms)
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
120
132
138
144
162
168
172
180
192
198
204
216
228
240
2.55
5.1
7.65
8.4
10.2
12.7
15.3
17
19.5
22
24.4
27.5
29
31.5
34
36.5
39
42
48
53
57
62
68
72
76
84
98
106
111
115
130
131
140
144
152
160
165
174
180
190
TOV*
1 Sec
10
Sec
Front-of-wave
Protective
Level**
(kV Crest)
3.5
6.9
10.4
11.4
13.9
17.2
20.8
23.1
26.5
29.9
33.1
37.3
39.4
42.8
46.2
49.6
53
57
65.2
72
77.4
84.2
92.3
97.8
103.2
114.1
133.1
143.9
150.7
156.2
176.5
177.9
190.1
195.6
206.4
217.3
224.1
236.3
244.4
258
3.3
6.6
9.9
10.8
13.1
16.4
19.7
21.9
25.1
28.4
31.5
35.4
37.4
40.6
43.8
47
50.3
54.1
61.9
68.3
73.5
79.9
87.7
92.8
98
108.3
126.3
136.6
143.1
148.2
167.6
168.9
180.5
185.6
195.9
206.2
212.7
224.3
232
244.9
8.2
16.3
24.5
26.9
32.6
40.6
48.9
54.4
62.4
70.3
78
87.9
92.7
101
109
117
125
135
154
170
183
199
218
231
243
269
297
321
336
348
394
397
424
436
460
485
500
527
545
575
1.5 kA
3 kA
5 kA
10 kA
20 kA
40 kA
125 A
250 A
500 A
1000 A
6.5
13
19.5
21.4
26
32.4
39
43.3
49.7
56
62.1
70
73.8
80.2
86.6
92.9
99.3
107
123
135
146
158
174
184
194
214
242
262
274
284
321
323
346
355
375
395
407
429
444
469
6.9
13.7
20.6
22.6
27.4
34.1
41.1
45.6
52.3
59
65.5
73.8
77.8
84.5
91.2
97.9
105
113
129
143
153
167
183
194
204
226
253
274
287
297
336
339
362
372
393
413
426
450
465
491
7.2
14.3
21.5
23.6
28.6
35.6
42.9
47.7
54.7
61.7
68.4
77.1
81.3
88.3
95.3
103
110
118
135
149
160
174
191
202
214
236
263
285
298
309
349
352
376
387
408
430
443
467
483
510
7.8
15.6
23.3
25.6
31.1
38.7
46.6
51.7
59.3
66.9
74.2
83.6
88.2
95.8
104
111
119
128
146
162
174
189
207
219
232
256
284
307
321
333
376
379
405
417
440
463
477
503
521
550
8.4
16.8
25.2
27.7
33.6
41.9
50.4
56
64.2
72.5
80.4
90.6
95.5
104
112
121
129
139
159
175
188
205
224
238
251
277
303
328
343
356
402
405
433
445
470
495
510
538
557
587
9.4
18.8
28.2
30.9
37.5
46.7
56.3
62.5
71.7
80.9
89.7
102
107
116
125
135
144
155
177
195
210
228
250
265
280
309
334
361
378
392
443
446
477
491
518
545
562
593
613
647
5.7
11.4
17.1
18.8
22.8
28.4
34.2
38
43.6
49.1
54.5
61.4
64.8
70.3
75.9
81.5
87.1
93.8
108
119
128
139
152
161
170
188
214
232
243
251
284
286
306
315
332
350
361
380
393
415
5.9
11.7
17.6
19.3
23.4
29.1
35.1
39
44.7
50.4
55.9
63
66.4
72.2
77.9
83.6
89.3
96.2
110
122
131
142
156
165
174
193
219
237
248
257
291
293
313
322
340
358
369
389
403
425
6.1
12.1
18.1
19.9
24.1
30
36.2
40.2
46.1
52
57.7
65
68.6
74.5
80.4
86.3
92.2
99.3
114
126
135
147
161
171
180
199
226
244
256
265
300
302
323
332
350
369
380
401
415
438
6.3
12.6
18.8
20.7
25.1
31.2
37.6
41.8
47.9
54
59.9
67.5
71.2
77.3
83.5
89.6
95.7
104
118
131
140
153
167
177
187
207
234
253
265
274
310
312
334
343
362
382
393
415
429
453
* Temporary Overvoltage (TOV) with Prior Duty.
** Based on a 10 kA current impulse that results in a discharge voltage cresting in 0.5 µs.
*** 45-60 µs rise time for a 500 A peak current surge.
6
www.eaton.com/cooperpowerseries
Switching Surge Protective
Level***
(kV crest)
Maximum Discharge Voltage (kV Crest)
8/20μs Current Wave
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Table 6. Protective Characteristics of the UltraSIL Polymer-Housed Station-Class Arrester-Type UX
Arrester
Rating
(kV, rms)
Arrester
MCOV
(kV rms)
TOV*
1 Sec
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
2.55
5.1
7.65
8.4
10.2
12.7
15.3
17
19.5
22
24.4
27.5
29
31.5
34
36.5
39
42
48
53
57
62
68
72
76
84
3.5
6.9
10.4
11.4
13.9
17.2
20.8
23.1
26.5
29.9
33.1
37.3
39.4
42.8
46.2
49.6
53
57
65.2
72
77.4
84.2
92.3
97.8
103.2
114.1
Maximum Discharge Voltage (kV Crest
8/20μs Current Wave
10 Sec
Front-of-wave
Protective
Level**
(kV Crest)
Switching Surge Protective Level***
(kV Crest)
1.5 kA
3 kA
5 kA
10 kA
20 kA
40 kA
125 A
250 A
500 A
1000 A
3.3
6.6
9.9
10.8
13.1
16.4
19.7
21.9
25.1
28.4
31.5
35.4
37.4
40.6
43.8
47
50.3
54.1
61.9
68.3
73.5
79.9
87.7
92.8
98
108.3
7.8
15.5
23.2
25.5
30.9
38.5
46.3
51.5
59.1
66.6
73.9
83.3
87.8
95.4
103
111
119
128
146
161
173
188
206
218
230
255
6.3
12.6
18.9
20.8
25.2
31.4
37.8
42
48.1
54.3
60.2
67.8
71.5
77.7
83.9
90
96.2
104
119
131
141
153
168
178
188
208
6.6
13.2
19.8
21.7
26.4
32.8
39.5
43.9
50.4
56.8
63
71
74.9
81.3
87.8
94.2
101
109
124
137
148
161
176
186
197
217
6.9
13.7
20.6
22.6
27.4
34.1
41.1
45.6
52.3
59.1
65.5
73.8
77.8
84.5
91.2
97.9
105
113
129
143
153
167
183
194
204
226
7.4
14.8
22.2
24.3
29.5
36.8
44.3
49.2
56.4
63.6
70.6
79.5
83.9
91.1
98.3
106
113
122
139
154
165
180
197
209
220
243
7.9
15.8
23.7
26
31.6
39.3
47.3
52.6
60.3
68
75.4
85
89.6
97.4
106
113
121
130
149
164
177
192
211
223
235
260
8.7
17.4
26.1
28.6
34.8
43.3
52.1
57.9
66.4
74.9
83.1
93.7
98.8
108
116
125
133
143
164
181
195
212
232
246
259
286
5.6
11.2
16.7
18.4
22.3
27.8
33.4
37.1
42.6
48.1
53.3
60.1
63.3
68.8
74.2
79.7
85.1
91.7
105
116
125
136
149
158
166
184
5.7
11.4
17.1
18.8
22.8
28.4
34.2
38
43.6
49.2
54.6
61.5
64.8
70.4
76
81.6
87.2
93.9
108
119
128
139
152
161
170
188
5.9
11.8
17.6
19.4
23.5
29.3
35.2
39.2
44.9
50.7
56.2
63.3
66.8
72.5
78.3
84
89.8
96.7
111
122
132
143
157
166
175
194
6.1
12.2
18.3
20.1
24.3
30.3
36.5
40.5
46.5
52.4
58.2
65.5
69.1
75.1
81
87
92.9
101
115
127
136
148
162
172
181
201
* Temporary Overvoltage (TOV) with Prior Duty.
** Based on a 10 kA current impulse that results in a discharge voltage cresting in 0.5 µs.
*** 45-60 µs rise time for a 500 A peak current surge.
www.eaton.com/cooperpowerseries
7
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Table 7. Creepage Distances and Insulation Withstand Voltages of UltraSIL Polymer-Housed Station-Class Arresters
Insulation Withstand Voltages
Creepage
Distance
(Inches)
Switching
Surge Impulse
(kV, Crest)
1.2/50 Impulse
(kV, Crest)
60 Hz, dry
60 Seconds
(kV, rms)
60 Hz, wet
10 Seconds
(kV, rms)
Arrester
Rating
(kV, rms)
Arrester
MCOV
(kV, rms)
US
UH
UX
US
UH
UX
US
UH
UX
US
UH
UX
US
UH
UX
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
120
132
138
144
162
168
172
180
192
198
204
216
228
240
2.55
5.1
7.65
8.4
10.2
12.7
15.3
17.0
19.5
22.0
24.4
27.5
29.0
31.5
34.0
36.5
39.0
42.0
48.0
53.0
57.0
62.0
68.0
72.0
76.0
84.0
98.0
106
111
115
130
131
140
144
152
160
165
174
180
190
30.7
38.4
38.4
38.4
46.1
46.1
53.7
53.7
61.4
61.4
69.1
69.1
69.1
84.4
84.4
92.1
99.8
99.8
107.5
138.2
138.2
153.5
168.9
176.6
184.3
199.6
215
230.3
245.7
245.7
307.1
314.8
322.4
330.1
337.8
353.2
360.8
406.9
422.2
429.9
30.7
38.4
38.4
38.4
46.1
46.1
53.7
53.7
61.4
61.4
69.1
69.1
69.1
84.4
84.4
92.1
99.8
99.8
107.5
115.2
122.8
153.5
168.9
176.6
184.3
199.6
215
230.3
245.7
245.7
307.1
314.8
322.4
330.1
337.8
353.2
360.8
406.9
422.2
429.9
30.7
38.4
38.4
38.4
46.1
46.1
53.7
53.7
61.4
61.4
69.1
69.1
69.1
84.4
84.4
92.1
99.8
99.8
107.5
115.2
122.8
153.5
168.9
176.6
184.3
199.6
-
115
134
134
134
155
155
176
176
201
201
217
217
217
252
252
275
294
294
316
434
434
469
504
527
550
588
638
591
631
631
830
851
872
893
914
955
973
1128
1170
1190
119
137
137
137
158
158
178
178
201
201
218
218
218
258
258
279
298
298
319
340
361
476
516
537
558
596
642
595
637
637
833
854
875
897
918
963
981
1133
1175
1198
126
138
138
138
159
159
179
179
206
206
220
220
220
262
262
281
300
300
321
342
364
482
524
543
562
600
-
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
972
994
1040
1062
1197
1247
1272
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1029
1052
1083
1106
1296
1320
1332
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
-
80
94
94
94
109
109
123
123
140
140
151
151
151
172
172
188
201
201
212
302
302
323
344
360
376
402
430
460
492
492
617
631
646
662
677
707
722
818
846
860
77
90
90
90
104
104
118
118
140
140
146
146
146
166
166
188
201
201
215
230
246
312
332
354
376
402
422
448
474
474
615
624
637
650
663
685
698
817
835
844
82
90
90
90
104
104
117
117
135
135
144
144
144
168
168
184
202
202
211
224
237
312
336
352
368
404
-
64
75
75
75
88
88
101
101
113
113
126
126
126
152
152
162
173
173
187
252
252
278
304
314
324
346
384
412
426
426
564
570
584
591
605
618
632
750
762
768
63
75
75
75
88
88
101
101
113
113
128
128
128
156
156
167
186
186
192
206
213
284
312
323
334
372
376
402
420
420
540
552
565
574
587
608
621
716
740
752
60
71
71
71
84
84
97
97
116
116
123
123
123
154
154
162
176
176
188
201
210
277
308
316
324
352
-
* Creepage distances are based on standard arrester build configurations.
8
www.eaton.com/cooperpowerseries
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Spacing requirements
D
C
D
C
Figure 4 illustrates a three-phase in-line mounting arrangement.
Dimen­sions C and D reference mini­mum phase-to-ground and
phase-to-phase distances respectively. These dimensions are listed
in Table 8.
C
Figure 4. Three-phase In-line mounting arrangement.
Table 8. Dimensions, Clearance Requirements, and Weights of UltraSIL Polymer-Housed Station-Class Arresters (Standard
Configuration)
Arrester
Rating
(kV, rms)
Arrester
MCOV
(kV, rms)
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
120
132
138
144
162
168
172
180
192
198
204
216
228
240
2.55
5.1
7.65
8.4
10.2
12.7
15.3
17.0
19.5
22.0
24.4
27.5
29.0
31.5
34.0
36.5
39.0
42.0
48.0
53.0
57.0
62.0
68.0
72.0
76.0
84.0
98.0
106
111
115
130
131
140
144
152
160
165
174
180
190
Figure 5
Dim. “A”
(Inches)
Figure 4
Dim. “C” Minimum
Phase-to-Ground
Clearances (inches)*
Figure 5
Dim. “B”
(inches)
Figure 4
Dim. “D” Minimum
Phase-to-Phase
Clearances (inches)*
Weight
(lbs.)
US
UH
UX
US
UH
UX
US
UH
UX
US
UH
UX
US
UH
UX
8.2
9.7
9.7
9.7
11.3
11.3
12.8
12.8
14.4
14.4
16
16
16
19.1
19.1
20.6
22.2
22.2
23.7
30
30
33.2
36.3
37.8
39.3
42.5
45.6
48.7
51.8
51.8
68.3
69.8
71.4
72.9
74.5
77.6
79.2
88.6
91.7
93.2
8.2
9.7
9.7
9.7
11.3
11.3
12.8
12.8
14.4
14.4
16
16
16
19.1
19.1
20.6
22.2
22.2
23.7
25.3
26.8
33.2
36.3
37.8
39.3
42.5
45.6
48.7
51.8
51.8
68.3
69.8
71.4
72.9
74.5
77.6
79.2
88.6
91.7
93.2
8.2
9.7
9.7
9.7
11.3
11.3
12.8
12.8
14.4
14.4
16
16
16
19.1
19.1
20.6
22.2
22.2
23.7
25.3
26.8
33.2
36.3
37.8
39.3
42.5
-
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.13
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.49
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
5.93
-
5.5
5.5
5.9
6.1
6.6
7.5
8.6
8.6
9.5
10.5
11.5
12.7
13.3
14.3
15.2
16.2
17.2
18.4
20.8
22.7
24.3
26.3
28.7
30.2
31.8
35
35.6
46.9
48.6
50
55.2
55.5
58.6
60
62.7
65.5
67.2
70.3
73.1
75.8
5.5
5.5
5.6
5.8
6.2
6.9
7.8
7.8
8.5
9.4
10.2
11.3
11.8
12.7
13.5
14.4
15.3
16.3
18.4
20.1
21.5
23.2
25.3
26.6
28
30.8
33.1
44.2
45.8
47.1
51.8
52.2
55
56.3
58.9
61.4
63
65.9
68.5
71
5.5
5.5
5.6
5.7
6
6.6
7.4
7.4
8
8.8
9.6
10.6
11.1
11.9
12.7
13.5
14.3
15.2
17.2
18.7
20
21.6
23.5
24.8
26.1
28.7
-
10
10
10.4
10.6
11.1
12
13.1
13.1
14
15
16
17.2
17.8
18.8
19.7
20.7
21.7
22.9
25.3
27.2
28.8
30.8
33.2
34.7
36.3
39.5
40.1
59.9
61.6
63
68.2
68.5
71.6
73
75.7
78.5
80.2
83.3
86.1
88.8
10
10
10.1
10.3
10.7
11.4
12.3
12.3
13
13.9
14.7
15.8
16.3
17.2
18
18.9
19.8
20.8
22.9
24.6
26
27.7
29.8
31.1
32.5
35.3
37.6
57.2
58.8
60.1
64.8
65.2
68
69.3
71.9
74.4
76
78.9
81.5
84
10
10
10.1
10.2
10.5
11.1
11.9
11.9
12.5
13.3
14.1
15.1
15.6
16.4
17.2
18
18.8
19.7
21.7
23.2
24.5
26.1
28
29.3
30.6
33.2
-
8.8
8.8
8.8
8.8
11.0
11.0
11.0
11.0
13.2
13.2
13.2
13.2
13.2
15.4
15.4
17.6
17.6
17.6
19.8
22.0
22.0
24.3
24.3
26.5
26.5
28.7
41.9
48.5
50.7
50.7
59.5
61.7
63.9
63.9
66.1
68.3
70.5
77.2
79.4
81.6
11.0
11.0
11.0
11.0
13.2
13.2
13.2
13.2
15.4
15.4
17.6
17.6
17.6
19.8
19.8
22.0
22.0
22.0
24.3
24.3
26.5
30.9
33.1
35.3
35.3
37.5
57.3
66.1
68.3
68.3
81.6
83.8
86.0
88.2
90.4
92.6
94.8
105.8
108.0
112.4
11.0
13.2
13.2
13.2
15.4
15.4
17.6
17.6
19.8
19.8
22.0
22.0
22.0
26.5
26.5
26.5
28.7
28.7
30.9
33.1
35.3
41.9
44.1
46.3
48.5
52.9
-
* Phase-to-Ground clearances are expressed as minimum arrester centerline-to-ground distances. Phase-to-Phase clearances are expressed as minimum arrester centerline-to-centerline distances.
www.eaton.com/cooperpowerseries
9
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
4.72”
4.72”
Stud Collar Height = 0.375”
11.44”
A
Ø26”
4.72”
A
A
ØB
ØB
1.92”
1.92”
1.25”
Arrester Rating:
1.25”
3 - 120 kV
132 - 240 kV
Figure 5. Outline drawing of standard UltraSIL Polymer-Housed Station-Class Arresters (for standard catalog numbers see Table 9).
Table 9 Catalog Numbers for Standard Configuration Type US,
UH, and UX Surge Arresters
Arrester
Rating
(kV, rms)
US
UH
UX
Arrester
Rating
(kV, rms)
US
UH
UX
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
USAA003002A0845A11
USAA006005A1045A11
USAA009007A1045A11
USAA010008A1045A11
USAA012010A1245A11
USAA015012A1245A11
USAA018015A1445A11
USAA021017A1445A11
USAA024019A1645A11
USAA027022A1645A11
USAA030024A1845A11
USAA033027A1845A11
USAA036029A1845A11
USAA039031A2245A11
USAA042034A2245A11
USAA045036A2445A11
USAA048039A2645A11
USAA054042A2645A11
USAA060048A2845A11
USAA066053A3645A11
UHAA003002A0845A11
UHAA006005A1045A11
UHAA009007A1045A11
UHAA010008A1045A11
UHAA012010A1245A11
UHAA015012A1245A11
UHAA018015A1445A11
UHAA021017A1445A11
UHAA024019A1645A11
UHAA027022A1645A11
UHAA030024A1845A11
UHAA033027A1845A11
UHAA036029A1845A11
UHAA039031A2245A11
UHAA042034A2245A11
UHAA045036A2445A11
UHAA048039A2645A11
UHAA054042A2645A11
UHAA060048A2845A11
UHAA066053A3045A11
UXAA003002A0845A11
UXAA006005A1045A11
UXAA009007A1045A11
UXAA010008A1045A11
UXAA012010A1245A11
UXAA015012A1245A11
UXAA018015A1445A11
UXAA021017A1445A11
UXAA024019A1645A11
UXAA027022A1645A11
UXAA030024A1845A11
UXAA033027A1845A11
UXAA036029A1845A11
UXAA039031A2245A11
UXAA042034A2245A11
UXAA045036A2445A11
UXAA048039A2645A11
UXAA054042A2645A11
UXAA060048A2845A11
UXAA066053A3045A11
72
78
84
90
96
108
120
132
138
144
162
168
172
180
192
198
204
216
228
240
USAA072057A3645A11
USAA078062A4045A11
USAA084068A4445A11
USAA090072A4645A11
USAA096076A4845A11
USAA108084A5245A11
USAA120098A5645A11
USAA132106A6045A11
USAA138111A6445A11
USAA144115A6445A11
USAA162130A8045A11
USAA168131A8245A11
USAA172140A8445A11
USAA180144A8645A11
USAA192152A8845A11
USAA198160A9245A11
USAA204165A9445A11
USAA216174AA645A11
USAA228180AB045A11
USAA240190AB245A11
UHAA072057A3245A11
UHAA078062A4045A11
UHAA084068A4445A11
UHAA090072A4645A11
UHAA096076A4845A11
UHAA108084A5245A11
UHAA120098A5645A11
UHAA132106A6045A11
UHAA138111A6445A11
UHAA144115A6445A11
UHAA162130A8045A11
UHAA168131A8245A11
UHAA172140A8445A11
UHAA180144A8645A11
UHAA192152A8845A11
UHAA198160A9245A11
UHAA204165A9445A11
UHAA216174AA645A11
UHAA228180AB045A11
UHAA240190AB245A11
UXAA072057A3245A11
UXAA078062A4045A11
UXAA084068A4445A11
UXAA090072A4645A11
UXAA096076A4845A11
UXAA108084A5245A11
10
www.eaton.com/cooperpowerseries
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Table 10. UltraQUIK Catalog Numbering System for UltraSIL Polymer-Housed Station-Class Arresters
1
U
2
3
A
4
A
5
6
7
8
9
10
11
A
12
13
14
15
16
17
18
Catalog Number Digits:
1 = “U” (UltraSIL Polymer-Housed Arrester)
S = Standard Energy Handling
2 = H = High Energy Handling
X = Xtra-High Energy Handling
3 = “A” Standard Electrical Build
4 = “A” Standard Cantilever Strength*
* Consult manufacturer for further information regarding additional cantilever strengths.
5 through 10 = Arrester Rating: Duty-cycle (MCOV)
003002 = 3 kV (2.55 kV)
042034 = 42 kV (34.0 kV)
138111 = 138 kV (111 kV)
006005 = 6 kV (5.1 kV)
045036 = 45 kV (36.5 kV)
144115 = 144 kV (115 kV)
009007 = 9 kV (7.65 kV)
048039 = 48 kV (39.0 kV)
162130 = 162 kV (130) kV
010008 = 10 kV (8.4 kV)
054042 = 54 kV (42.0 kV)
168131 = 168 kV (131 kV)
012010 = 12 kV (10.2 kV)
060048 = 60 kV (48.0 kV)
172140 = 172 kV (140 kV)
015012 = 15 kV (12.7 kV)
066053 = 66 kV (53.0 kV)
180144 = 180 kV (144 kV)
018015 = 18 kV (15.3 kV)
072057 = 72 kV (57.0 kV)
192152 = 192 kV (152 kV)
021017 = 21 kV (17.0 kV)
078062 = 78 kV (62.0 kV)
198160 = 198 kV (160 kV)
024019 = 24 kV (19.5 kV)
084068 = 84 kV (68.0 kV)
204165 = 204 kV (165 kV)
027022 = 27 kV (22.0 kV)
090072 = 90 kV (72.0 kV)
216174 = 216 kV (174 kV)
030024 = 30 kV (24.4 kV)
096076 = 96 kV (76.0 kV)
228180 = 228 kV (180 kV)
033027 = 33 kV (27.0 kV)
108084 = 108 kV (84.0 kV)
240190 = 240 kV (190 kV)
036029 = 36 kV (29.0 kV)
120098 = 120 kV (98.0 kV)
039031 = 39 kV (31.5 kV)
132106 = 132 kV (106 kV)
11 = “A” Standard High Creep UltraSIL Polymer-Housing
www.eaton.com/cooperpowerseries
11
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Table 10. UltraQUIK Catalog Numbering System for UltraSIL Polymer-Housed Station-Class Arresters (continued)
1
2
U
3
4
A
A
5
6
7
8
9
10
11
12
A
13
14
15
16
17
18
Catalog Number Digits:
12 and 13 = Housing Code (Select from Table below): * = Standard Housing (31 mm/kV), 0 = Optional Housing
Type US Housing Codes Digits
12 & 13
08
10
12
14
16
18
20
22
24
26
30.7
38.4
46.1
53.7
61.4
69.1
76.8
84.4
92.1
99.8
*
*
*
O
O
O
*
*
O
O
O
O
O
*
*
*
O
O
O
O
O
O
O
28
36
40
44
46
48
50
52
54
56
199.6 207.3
215
60
64
80
Leakage
Distance
(in.)
Arrester
Rating
(kV rms)
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
120
132
138
144
162
168
172
180
192
198
204
216
228
240
107.5 138.2 153.5 168.9 176.6 184.3
192
230.3 245.7 307.1
*
O
O
O
O
*
*
O
O
O
O
*
*
O
O
O
O
O
O
*
*
O
O
O
O
O
O
O
*
O
O
O
O
O
O
*
*
O
O
O
O
O
O
*
*
*
*
Leakage
Distance (in.)
Arrester
Rating
(kV rms)
Digits
12 & 13
O
*
O
O
*
O
O
O
*
O
O
O
O
O
O
O
O
*
O
O
O
O
O
O
O
O
*
*
O
*
*
O
O
O
*
30.7
38.4
46.1
53.7
61.4
69.1
76.8
84.4
92.1
99.7
107.5
138.2
153.5
168.9
176.6
184.3
192
199.6
207.3
215
230.3
245.7
307.1
08
10
12
14
16
18
20
22
24
26
28
36
40
44
46
48
50
52
54
56
60
64
80
continued on page 13
12
www.eaton.com/cooperpowerseries
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
82
84
86
88
90
92
94
96
98
A0
A4
A6
A8
B0
B2
B4
B6
B8
Digits
12 & 13
Leakage
Distance
(in.)
314.8
O
O
O
O
*
322.4
O
O
O
O
*
330.1
337.8
345.5
353.2
360.8
368.5
376.2
383.9
399.3
406.9
414.6
422.2
429.9
437.6
445.3
453
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
120
132
138
144
162
168
172
180
192
198
204
216
228
240
O
O
O
*
*
O
O
*
O
O
*
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
*
O
O
O
O
O
O
O
O
*
O
O
O
O
*
O
O
O
O
O
O
O
O
O
O
O
O
314.8
322.4
330.1
337.8
345.5
353.2
360.8
368.5
376.2
383.9
399.3
406.9
414.6
422.2
429.9
437.6
445.3
453
82
82
86
88
90
92
94
96
98
A0
A4
A6
A8
B0
B2
B4
B6
B8
Arrester
Rating
(kV rms)
Leakage
Distance (in.)
Arrester
Rating
(kV rms)
Digits
12 & 13
continued from page 12
www.eaton.com/cooperpowerseries
13
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Table 10. UltraQUIK Catalog Numbering System for UltraSIL Polymer-Housed Station-Class Arresters (continued)
1
U
2
3
4
A
A
5
6
7
8
9
10
11
12
A
13
14
15
16
17
18
Catalog Number Digits:
12 and 13 = Housing Code (Select from Table below): * = Standard Housing (31 mm/kV), 0 = Optional Housing
Type UH Housing Codes Digits12
& 13
Leakage
Distance
(in.)
Arrester
Rating
(kV rms)
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
120
132
138
144
162
168
172
180
192
198
204
216
228
240
08
10
12
14
16
18
20
22
24
26
28
30
32
36
40
44
46
48
50
52
54
56
58
30.7
38.4
46.1
53.7
61.4
69.1
76.8
84.4
92.1
99.8
107.5
115.2
122.8
138.2
153.5
168.9
176.6
184.3
192
199.6
207.3
215
222.7
*
*
*
O
O
O
*
*
O
O
O
O
O
*
*
*
O
O
O
O
O
O
O
O
*
O
O
O
O
*
O
O
*
O
O
O
*
O
O
O
O
*
O
O
O
O
O
O
O
O
O
*
O
O
O
O
*
Leakage
Distance (in.)
Arrester
Rating
(kV rms)
Digits
12 & 13
O
O
O
O
*
*
O
O
O
O
*
*
O
O
O
O
O
O
*
*
O
O
O
O
O
O
O
*
O
O
O
O
O
O
*
*
O
O
O
O
O
O
*
O
O
O
O
O
O
*
O
O
O
*
O
O
30.7
38.4
46.1
53.7
61.4
69.1
76.8
84.4
92.1
99.7
107.5
138.2
153.5
168.9
176.6
184.3
192
199.6
207.3
215
230.3
245.7
307.1
08
10
12
14
16
18
20
22
24
26
28
36
40
44
46
48
50
52
54
56
60
64
80
continued on page 15
14
www.eaton.com/cooperpowerseries
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
60
64
80
82
84
86
88
90
92
94
96
98
A0
A4
A6
A8
B0
B2
B4
B6
B8
C0
230.3
245.7
307.1
314.8
322.4
330.1
337.8
345.5
353.2
360.8
368.5
376.2
383.9
399.3
406.9
414.6
422.2
429.9
437.6
445.3
453
460.7
O
O
*
230.3
O
*
*
245.7
O
O
O
*
307.1
O
O
O
O
*
314.8
O
O
O
O
*
322.4
O
O
O
*
330.1
O
O
O
O
*
337.8
O
O
O
O
O
345.5
O
*
353.2
O
O
*
360.8
O
O
O
368.5
O
O
O
376.2
O
O
O
383.9
O
O
O
399.3
O
O
O
*
O
O
O
O
O
O
O
O
*
406.9
414.6
422.2
O
O
O
O
*
O
O
O
O
O
O
O
O
O
O
O
O
429.9
437.6
445.3
453
Digits 12
& 13
Leakage
Distance
(in.)
Arrester
Rating
(kV rms)
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
120
132
138
144
162
168
172
180
192
198
204
216
228
240
O
O
O
Leakage Distance
460.7 (in.)
Arrester
Rating
(kV rms)
60
64
80
82
84
86
88
90
92
94
96
98
A0
A4
A6
A8
B0
B2
B4
B6
B8
Digits 12
C0 & 13
continued from page 14
www.eaton.com/cooperpowerseries
15
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Table 10. UltraQUIK Catalog Numbering System for UltraSIL Polymer-Housed Station-Class Arresters (continued)
1
2
U
3
4
A
A
5
6
7
8
9
10
11
A
12
13
14
15
16
17
18
Catalog Number Digits:
12 and 13 = Housing Code (Select from Table below): * = Standard Housing (31 mm/kV), 0 = Optional Housing
Type UX Housing Codes Digits 12
& 13
Leakage
Distance
(in.)
08
10
12
14
16
18
20
22
24
26
28
30
32
36
40
44
46
48
50
52
54
56
58
60
30.7
38.4
46.1
53.7
61.4
69.1
76.8
84.4
92.1
99.8
107.5
115.2
122.8
138.2
153.5
168.9
176.6
184.3
192
199.6
207.3
215
222.7
230.3
*
*
*
O
O
O
*
*
O
O
O
O
O
*
*
*
O
O
O
O
O
O
O
O
*
O
O
O
O
*
O
O
*
O
O
O
*
O
O
O
*
O
O
O
O
O
O
O
O
O
*
O
O
O
O
O
O
O
O
O
O
O
Arrester
Rating
(kV rms)
3
6
9
10
12
15
18
21
24
27
30
33
36
39
42
45
48
54
60
66
72
78
84
90
96
108
Leakage
Distance (in.)
*
O
O
O
O
*
*
O
O
O
O
*
*
O
O
O
O
O
O
*
*
O
O
O
O
O
O
O
*
O
O
O
O
O
O
*
*
O
O
O
O
O
O
*
O
O
O
O
O
O
*
30.7
38.4
46.1
53.7
61.4
69.1
76.8
84.4
92.1
99.8
107.5
115.2
122.8
138.2
153.5
168.9
176.6
184.3
192
199.6
207.3
215
222.7
230.3
08
10
12
14
16
18
20
22
24
26
28
30
32
36
40
44
46
48
50
52
54
56
58
60
Arrester
Rating
(kV rms)
Digits
12 & 13
16
www.eaton.com/cooperpowerseries
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Table 10. UltraQUIK Catalog Numbering System for UltraSIL Polymer-Housed Station-Class Arresters (continued)
1
U
2
3
A
4
A
5
6
7
8
9
10
11
12
A
13
14
15
16
17
18
14 = Line Terminal Options
Optional Offering-Select A
Standard Offering-Select 4
TERMINAL
CLAMP–
STAINLESS
STEEL
3.50”
REF
WASHERS–
GALVANIZED
STEEL
NUT MATERIAL–
GALVANIZED
STEEL NUT
THREAD –.51”
1.75” SQ
BOLT
MATERIAL–
GALVANIZED
STEEL
3.50”
REF
1.75”
REF
4.72”
REF
4.25”
BOLT
THREAD–.51”
4.25”
4.72”
TIN PLATED
ALUMINUM
BRONZE
ALLOY TIN PLATED
SILICON BRONZE
TIN PLATED
COPPER
ALLOY
ALUMINUM
TERMINAL MATERIAL–ALUMINUM
NEMA® Four-hole Pad and Stainless Terminal Clamp
Accepts copper or aluminum conductors from .16” dia.
(#6) to 1.15” dia. (1000 MCM).
(Top illustration shows terminal clamp, bottom illustration
shows terminal clamp removed)
NEMA® Four-hole Pad and Two Eyebolts
Accepts conductors 1/0 SOL-500 MCM
(Top illustration shows two eyebolts, bottom illustration
shows two eyebolts removed)
1.97”
1.97”
1.57”
.69”
.51”
1.97”
1.38”
4.25”
1.57”
10 Hole Typ 4 PL
3.50”
2.75”
NEMA® Four-hole Pad is used in Standard
Offering 4 and Optional Offering A.
Consult factory for alternate terminal options.
Optional Offering-Select 1
TIN PLATED
THREAD –.51” BRASS NUT
ALUMINUM
BRONZE
1.65”
Optional Offering-Select 5
TIN
PLATED
BRASS
NUT
1.18" (30 mm)
3.19”
STAINLESS
STEEL LOCK
WASHER
TIN
PLATED
BRASS
COPPER ALLOY
1.65”
STAINLESS THREAD–.63”
STEEL LOCK
WASHER
Eyebolt Connector
Accepts copper or aluminum conductors from
.16” dia. (#6) up to .57” dia. (250 MCM)
Wire Clamp
Accepts copper or aluminum conductors
from .16" dia. (#6) to .575" dia. (250 MCM)
(Cubicle Mount)
For use with Option Code “B” digit 16
Cubicle Mount US Type (3-36 kV)
www.eaton.com/cooperpowerseries
17
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Table 10. UltraQUIK Catalog Numbering System for UltraSIL Polymer-Housed Station-Class Arresters (continued)
1
U
2
3
A
4
A
5
6
7
8
9
10
11
A
12
13
14
15
16
17
18
15 = Earth Terminal Options
Optional Offering-Select 1
Standard Offering-Select 5
2.52”
ALL NUTS,
BOLTS AND
WASHERSGALVANIZED
STEEL
BOLT –.51”
STAINLESS STEEL
NUT –.51” STAINLESS
STEEL
TERMINAL–
STAINLESS
STEEL
LOCK WASHER –.51”
STAINLESS STEEL
91 mm
3.58”
TERMINAL
CLAMPSTAINLESS
STEEL
WIRE CLAMPS –
STAINLESS STEEL
TERMINALGALVANIZED
STEEL
Clamp Style Connector
Accepts copper or aluminum
conductors from .16” dia. (#6) to
.575” dia. (250 MCM)
NEMA® Four-hole Pad
Accepts copper or aluminum conductors
from .16” dia. (#6) to .82” dia. (500 MCM)
Optional Offering-Select 9
EYEBOLT BODY–TIN
PLATED BRASS
WASHERS–.62”
STAINLESS STEEL
Optional Offering-Select B
EYEBOLT–.63”
TIN PLATED
ALUMINUM
BRONZE
2.01”
NUT MATERIAL–
STAINLESS STEEL
1.18" (30 mm)
WASHERS–.63”
STAINLESS STEEL
2.52”
MOUNTING BOLT–.63”
STAINLESS STEEL
Eyebolt Connector
Accepts copper or aluminum conductors
from .16” dia. (#6) to .575” dia. (250 MCM)
Wire Clamp
Accepts copper or aluminum conductors
from .16” dia. (#6) to .575” dia. (250 MCM)
(Cubicle Mount)
For use with Option Code “B” digit 16
Cubicle Mount US Type (3-36 kV)
16 = Mounting Arrangement
Standard Offering-Select A
Mounting Base Located on Bottom
Optional-Select B
No Mounting Base (Cubicle Mount)
(US Type 3-36 kV)
17 =“1” - Nameplate for Standard or Suspension Mount
“2” - Nameplate for Cubicle Mount (US Type 3-36 kV) Option Code “B” for digit 16
18 = “1” - Cardboard Packaging
“2” - Wood Crate Packaging
18
www.eaton.com/cooperpowerseries
Optional-Select C
Mounting Base Located on Top
(Suspension Mount)
UltraSIL polymer-housed VariSTAR station-class surge arresters
Catalog Data CA235013EN
Effective December 2015
Figure 6. Detail of base nameplate.
Figure 7. Detail of unit nameplate on base of arrester section.
Nameplate information
A stainless steel nameplate is at­tached to the base of every UltraSIL
Polymer-Housed Type US, UH, and UX Arrester. The arrester catalog
number, serial number, year of manufacture, duty-cycle rating,
MCOV ratings, and pressure relief rating are among the details
provided on the nameplate. For multi-unit arresters above 120 kV, an
additional unit nameplate is provided on the base of the arrester unit
section as shown in Figure 7. See Figure 6 for an example of a base
nameplate.
Additional information
•
S235-103-1
UltraSIL Polymer-Housed VariSTAR Station-Class Surge Arrester Installation and Maintenance Instructions.
•
CP1122
UltraSIL Polymer-Housed VariSTAR Type US, UH, and UX Station-Class Surge Arresters Certified Test Report.
www.eaton.com/cooperpowerseries
19
Catalog Data CA235013EN
UltraSIL polymer-housed VariSTAR station-class surge arresters
Effective December 2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. CA235013EN
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
For Eaton’s Cooper Power series product
information call 1-877-277-4636 or visit:
www.eaton.com/cooperpowerseries.