Communications Point Data Base COOPER POWER SERIES

advertisement
Switchgear
Technical Data
TD280017EN
Effective July 2015
Supersedes R280-90-36 8/2012
COOPER POWER
SERIES
Communications Point Data Base
for Communications Protocol IEC60870-5
For use with Eaton’s Cooper Power series
Form 6 Recloser Control
Form 6 IEC 60870-5 Device Profile Data Dictionary
Form 6 IEC 60870-5 Map Points
July 9, 2015
v3.00
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
1.01
1.02
1.03
1.04
2.00
3.00
Date
8/20/2003
9/3/2003
3/15/2004
8/4/2005
10/28/2005
8/24/2012
7/9/15
Description
Initial release.
Updated Definitions
Added Supervisory Enable Status for Single Commands and Minor Description Edits
Minor updates in the Measured Value and Single Command tabs.
Minor updates in the Single Input tab.
Updates and re-release for ProView 5.0
Updates and re-release for ProView 5.1
Point Numbering Convention
IEC 60870-5 data points consist of 7 main types: single input, double input, measured values, single command, double command,
floating point, and integrated totals. The numbering convention refers to the individual data points by prefixing their addresses so that
when looking at a number for a given point the user would know which type of data point was being referenced.
Data type
Single Input
Double Input
Measured Value
Single Command
Double Command
Floating Point
Integrated Totals
Base Address
0
4096
8192
12288
32000
16384
24576
Note: The Form 6 does not have any Double Input or Floating Point points defined.
Page 1
Cover Page
Form 6 IEC 60870-5 Device Profile Data Dictionary
INPUT SUBSYSTEM
Single Inputs
Base Address: 0
Description
Recloser Open
Recloser Closed
Control is Locked Out
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non-Reclosing
Ground Trip Blocked
SEF Blocked
CLPU Blocked
Fast Trips Blocked
Profile Selected (Normal)
Profile Selected (Alt1)
Profile Selected (Alt2)
Profile Selected (Alt3)
Hot Line Tag
Bus Voltage Present (Phase A)
Bus Voltage Present (Phase B)
Bus Voltage Present (Phase C)
Reverse Power Flow
Battery Test in Progress
No AC Power
Battery Alarm
ci8:Alt1 (TB3:9-10)
ci9:Alt2 (TB3:11-12)
ci10:Alt3 (TB3:13-14)
ci11:Nrml (TB3:15-16)
co1:aux (TB1:11-12,13)
co2:ok (TB1:14-15)
co3:hlt (TB1:16-17)
co4:gtb (TB1:18-19)
ss1:lo (TB1:9-10)
co5:nr (TB3:17-18)
co6:alm (TB3:19-20,21)
co7:nrm (TB4:1-2)
co8:alt1 (TB4:3-4)
co9:alt2 (TB4:5-6)
Offset
Hex Offset
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
Page 2
Single Inputs
Form 6 IEC 60870-5 Device Profile Data Dictionary
INPUT SUBSYSTEM
Single Inputs
Base Address: 0
Description
co10:alt3 (TB4:7-8)
co11:frq (TB4:9-10)
co12:vlt (TB4:11-12,13)
Reclose Retry Enabled
A Phase Fault Trip
B Phase Fault Trip
C Phase Fault Trip
Ground Fault Trip
SEF Trip
ci1:RTrip (TB1:3-4)
ci2:SClose (TB1:5-6)
ci3:STrip (TB1:7-8)
ci4:GTB (TB3:1-2)
ci5:NRecl (TB3:3-4)
ci6:TargR (TB3:5-6)
ci7 (TB3:7-8)
Ground Overcurrent Alarm
Phase Overcurrent Alarm
Negative Sequence Overcurrent Alarm
Hot Line Tag On from Workbench
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Control Circuit Interrupted
USEF Blocked
Profile Selected (Alt 4)
Profile Selected (Alt 5)
Offset
Hex Offset
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
25
26
27
28
29
2A
2B
2C
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
Page 3
Single Inputs
Form 6 IEC 60870-5 Device Profile Data Dictionary
INPUT SUBSYSTEM
Single Inputs (Triple-Single)
Base Address: 0
Description
Recloser Closed (Phase A)
Recloser Open (Phase A)
Control is Locked Out (Phase A)
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non-Reclosing
Ground Trip Blocked
SEF Blocked
CLPU Blocked
Fast Trips Blocked
Profile Selected (Normal)
Profile Selected (Alt1)
Profile Selected (Alt2)
Profile Selected (Alt3)
Hot Line Tag
Bus Voltage Present (Phase A)
Bus Voltage Present (Phase B)
Bus Voltage Present (Phase C)
Reverse Power Flow
Battery Test in Progress
No AC Power
Battery Alarm
ci8:Alt1 (TB3:9-10)
ci9:Alt2 (TB3:11-12)
ci10:Alt3 (TB3:13-14)
ci11:Nrml (TB3:15-16)
co1:aux (TB1:11-12,13)
co2:ok (TB1:14-15)
co3:hlt (TB1:16-17)
co4:gtb (TB1:18-19)
ss1:lo (TB1:9-10)
co5:nr (TB3:17-18)
co6:alm (TB3:19-20,21)
co7:nrm (TB4:1-2)
co8:alt1 (TB4:3-4)
co9:alt2 (TB4:5-6)
Offset
Hex Offset
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
Page 4
Single Inputs (Triple-Single)
Form 6 IEC 60870-5 Device Profile Data Dictionary
INPUT SUBSYSTEM
Single Inputs (Triple-Single)
Base Address: 0
Description
co10:alt3 (TB4:7-8)
co11:frq (TB4:9-10)
co12:vlt (TB4:11-12,13)
Reclose Retry Enabled
A Phase Fault Trip
B Phase Fault Trip
C Phase Fault Trip
Ground Fault Trip
SEF Trip
ci1:RTrip (TB1:3-4)
ci2:SClose (TB1:5-6)
ci3:STrip (TB1:7-8)
ci4:GTB (TB3:1-2)
ci5:NRecl (TB3:3-4)
ci6:TargR (TB3:5-6)
ci7 (TB3:7-8)
Ground Overcurrent Alarm
Phase A Overcurrent Alarm
Negative Sequence Overcurrent Alarm
Hot Line Tag On from Workbench
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Control Circuit Interrupted (Phase A)
Recloser Closed (Phase B)
Recloser Open (Phase B)
Control is Locked Out (Phase B)
Control Circuit Interrupted (Phase B)
Recloser Closed (Phase C)
Recloser Open (Phase C)
Control is Locked Out (Phase C)
Control Circuit Interrupted (Phase C)
Phase B Overcurrent Alarm
Phase C Overcurrent Alarm
Ganged Mode
1-3 Mode
1-1 Mode
USEF Blocked
Profile Selected (Alt 4)
Offset
Hex Offset
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
25
26
27
28
29
2A
2B
2C
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
40
41
42
43
44
45
46
47
48
49
4A
Page 5
Single Inputs (Triple-Single)
Form 6 IEC 60870-5 Device Profile Data Dictionary
INPUT SUBSYSTEM
Single Inputs (Triple-Single)
Base Address: 0
Description
Profile Selected (Alt 5)
Offset
Hex Offset
75
4B
Page 6
Single Inputs (Triple-Single)
Form 6 IEC 60870-5 Device Profile Data Dictionary
INPUT SUBSYSTEM
Measured Values (IEC 60870-5-101)
Base Address: 8192
Offset
Hex Offset
Division
Scale Factor
Default
Deadband
Units
Min
Max
A Phase Primary Current Magnitude
B Phase Primary Current Magnitude
C Phase Primary Current Magnitude
3I0 Primary Current Magnitude
00
01
02
03
00
01
02
03
10
10
10
10
100
100
100
100
Amps
Amps
Amps
Amps
-8000
-8000
-8000
-8000
8000
8000
8000
8000
A Phase Primary Voltage Magnitude
B Phase Primary Voltage Magnitude
C Phase Primary Voltage Magnitude
04
05
06
04
05
06
1
1
1
100
100
100
Volts
Volts
Volts
-19000
-19000
-19000
19000
19000
19000
A Phase Power Factor
B Phase Power Factor
C Phase Power Factor
07
08
09
07
08
09
10000
10000
10000
100
100
100
-0.50
-0.50
-0.50
0.50
0.50
0.50
A Phase Primary Apparent Power
B Phase Primary Apparent Power
C Phase Primary Apparent Power
10
11
12
0A
0B
0C
1
1
1
100
100
100
kVA
kVA
kVA
-304000
-304000
-304000
304000
304000
304000
A Phase Primary Real Power
B Phase Primary Real Power
C Phase Primary Real Power
13
14
15
0D
0E
0F
1
1
1
100
100
100
kW
kW
kW
-304000
-304000
-304000
304000
304000
304000
A Phase Primary Reactive Power
B Phase Primary Reactive Power
C Phase Primary Reactive Power
16
17
18
10
11
12
1
1
1
100
100
100
kvar
kvar
kvar
-304000
-304000
-304000
304000
304000
304000
Line Frequency
19
13
100
100
Hz
-35
35
A Phase Primary Demand Currents
B Phase Primary Demand Currents
C Phase Primary Demand Currents
20
21
22
14
15
16
10
10
10
100
100
100
Amps
Amps
Amps
-50000
-50000
-50000
50000
50000
50000
Battery Voltage
Battery Current
23
24
17
18
100
1000
100
100
Volts
Amps
-20
-0.50
31
0.50
Description
Page 7
Measured Values (-101)
Form 6 IEC 60870-5 Device Profile Data Dictionary
INPUT SUBSYSTEM
Measured Values (IEC 60870-5-104)
Base Address: 8192
Offset
Hex Offset
Division
Scale Factor
Default
Deadband
Units
Min
Max
A Phase Primary Current Magnitude
B Phase Primary Current Magnitude
C Phase Primary Current Magnitude
3I0 Primary Current Magnitude
00
01
02
03
00
01
02
03
10
10
10
10
100
100
100
100
Amps
Amps
Amps
Amps
-8000
-8000
-8000
-8000
8000
8000
8000
8000
A Phase Primary Voltage Magnitude
B Phase Primary Voltage Magnitude
C Phase Primary Voltage Magnitude
04
05
06
04
05
06
1
1
1
100
100
100
Volts
Volts
Volts
-19000
-19000
-19000
19000
19000
19000
A Phase Power Factor
B Phase Power Factor
C Phase Power Factor
07
08
09
07
08
09
10000
10000
10000
100
100
100
-0.50
-0.50
-0.50
0.50
0.50
0.50
A Phase Primary Apparent Power
B Phase Primary Apparent Power
C Phase Primary Apparent Power
10
11
12
0A
0B
0C
1
1
1
100
100
100
kVA
kVA
kVA
-304000
-304000
-304000
304000
304000
304000
A Phase Primary Real Power
B Phase Primary Real Power
C Phase Primary Real Power
C Phase Primary Real Power
13
14
15
16
0D
0E
0F
10
1
1
1
1
100
100
100
100
kW
kW
kW
kW
-304000
-304000
-304000
-304000
304000
304000
304000
304000
A Phase Primary Reactive Power
B Phase Primary Reactive Power
C Phase Primary Reactive Power
C Phase Primary Reactive Power
17
18
19
20
11
12
13
14
1
1
1
1
100
100
100
100
kvar
kvar
kvar
kvar
-304000
-304000
-304000
-304000
304000
304000
304000
304000
Line Frequency
21
15
100
100
Hz
-35
35
A Phase Primary Demand Currents
B Phase Primary Demand Currents
C Phase Primary Demand Currents
22
23
24
16
17
18
10
10
10
100
100
100
Amps
Amps
Amps
-50000
-50000
-50000
50000
50000
50000
Battery Voltage
Battery Current
25
26
19
1A
100
1000
100
100
Volts
Amps
-20
-0.50
31
0.50
Description
Page 8
Measured Values (-104)
Form 6 IEC 60870-5 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Single Commands
Base Address: 12288
Description
* Close Mechanism
* Trip Mechanism
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
*, *** Hot Line Tag Set
*, *** Hot Line Tag Reset
Enable Reclose Retry
Enable Sync Check
Combined Trip and Close
Block USEF
* Profile - Alt4
* Profile - Alt5
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Offset
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Conditioned by
Hex Offset Supervisory State
(Factory Default)
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
* Momentary/Self Resetting
*** Hot Line Tag activates a latching relay in the control "close" circuit.
Crosshatch
indicates point is supervised regardless of setting
Page 9
Single Commands
Form 6 IEC 60870-5 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Single Commands (Triple-Single)
Base Address: 12288
Description
* Close Mechanism (Phase A)
* Trip Mechanism (Phase A)
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
*, *** Hot Line Tag Set
*, *** Hot Line Tag Reset
Enable Reclose Retry
Combined Trip and Close
Enable Sync Check
* Trip Mechanism (Phase B)
* Trip Mechanism (Phase C)
* Close Mechanism (Phase B)
* Close Mechanism (Phase C)
* Activate Ganged Mode
* Activate 1-3 Mode
* Activate 1-1 Mode
* Trip All Phases
* Close All Phases
Block USEF
* Profile - Alt4
* Profile - Alt5
Offset
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Conditioned by
Hex Offset Supervisory State
(Factory Default)
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
* Momentary/Self Resetting
*** Hot Line Tag activates a latching relay in the control "close" circuit.
Crosshatch
indicates point is supervised regardless of setting
Page 10
Single Commands (Triple-Single)
Form 6 IEC 60870-5 Device Profile Data Dictionary
INPUT SUBSYSTEM
Integrated Totals
Base Address: 24576
Description
Trip Counter (Phase A)
Trip Counter (Phase B)
Trip Counter (Phase C)
Trip Counter (Ground)
Trip Counter (SEF)
Total Trip Counter
Offset
Hex Offset
Division
Scale Factor
Default
Deadband
00
01
02
03
04
05
00
01
02
03
04
05
1
1
1
1
1
1
0
0
0
0
0
0
Page 11
Integrated Totals
Form 6 IEC 60870-5 Device Profile Data Dictionary
INPUT SUBSYSTEM
Integrated Totals (Triple-Single)
Base Address: 24576
Description
Trip Counter (Phase A)
Trip Counter (Phase B)
Trip Counter (Phase C)
Trip Counter (Ground)
Trip Counter (SEF)
Total Trip Counter
Operations Counter (Phase A)
Operations Counter (Phase B)
Operations Counter (Phase C)
Offset
Hex Offset
Division
Scale Factor
Default
Deadband
00
01
02
03
04
05
06
07
08
00
01
02
03
04
05
06
07
08
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
Page 12
Integrated Totals (TS)
Technical Data TD280017EN
Communications
Point Data Base

Effective July 2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. TD280017EN
July 2015
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
For Eaton's Cooper Power series Form 6
recloser control information