Reference Information
R280-90-35
May 2011 • New Issue
Form 4D Available Data Points
Form 4D Communications Point Availability
May 30, 2011 v1.00
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document Date
1.00
5/31/2011
Description
Initial Release
The data points listed in this document are available for mapping to any of the Form 4D SCADA protocol
User Maps as described in service document S280-104-3, Form 4D Recloser Control Communications.
Page 1 Cover Page
Binary Points
Description
Recloser Closed
Recloser Open
Control is Locked Out
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non-Reclosing
Ground Trip Blocked
SEF Blocked
CLPU Blocked
Fast Trips Disabled
Profile Selected (Normal)
Profile Selected (Alt1)
Hot Line Tag
Bus Voltage Present (Phase A)
Bus Voltage Present (Phase B)
Bus Voltage Present (Phase C)
Reverse Power Flow
Battery Test in Progress
No AC Power
Battery Alarm
Reclose Retry Blocked
A Phase Fault Trip
B Phase Fault Trip
C Phase Fault Trip
Ground Fault Trip
SEF Trip
Hot Line Tag On from Configurable Logic
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Control Circuit Interrupted
Voltage Trip Blocked
Frequency Trip Blocked
Cfg Logic Pt 01 to SCADA
Cfg Logic Pt 02 to SCADA
Cfg Logic Pt 03 to SCADA
Cfg Logic Pt 04 to SCADA
Cfg Logic Pt 05 to SCADA
Cfg Logic Pt 06 to SCADA
Cfg Logic Pt 07 to SCADA
Cfg Logic Pt 08 to SCADA
Cfg Logic Pt 09 to SCADA
Cfg Logic Pt 10 to SCADA
Cfg Logic Pt 11 to SCADA
Cfg Logic Pt 12 to SCADA
Form 4D Available Data Points
Page 2 Binary Points
Binary Points
Description
Cfg Logic Pt 13 to SCADA
Cfg Logic Pt 14 to SCADA
Cfg Logic Pt 15 to SCADA
Cfg Logic Pt 16 to SCADA
Cfg Logic Pt 17 to SCADA
Cfg Logic Pt 18 to SCADA
Cfg Logic Pt 19 to SCADA
Cfg Logic Pt 20 to SCADA
Cfg Logic Pt 21 to SCADA
Cfg Logic Pt 22 to SCADA
Cfg Logic Pt 23 to SCADA
Cfg Logic Pt 24 to SCADA
Cfg Logic Pt 25 to SCADA
Cfg Logic Pt 26 to SCADA
Cfg Logic Pt 27 to SCADA
Cfg Logic Pt 28 to SCADA
Cfg Logic Pt 29 to SCADA
Cfg Logic Pt 30 to SCADA
Cfg Logic Pt 31 to SCADA
Cfg Logic Pt 32 to SCADA
Cfg Logic Pt 33 to SCADA
Cfg Logic Pt 34 to SCADA
Cfg Logic Pt 35 to SCADA
Cfg Logic Pt 36 to SCADA
Cfg Logic Pt 37 to SCADA
Cfg Logic Pt 38 to SCADA
Cfg Logic Pt 39 to SCADA
Cfg Logic Pt 40 to SCADA
Contact I/O Input 1
Contact I/O Input 2
Contact I/O Input 3
Contact I/O Input 4
Contact I/O Input 9
Contact I/O Input 10
Contact I/O Input 11
Contact I/O Input 12
Contact I/O Input 17
Contact I/O Input 18
Contact I/O Input 19
Contact I/O Input 20
Contact I/O Input 25
Contact I/O Input 26
Contact I/O Input 27
Contact I/O Input 28
Contact I/O Output State 1
Contact I/O Output State 2
Form 4D Available Data Points
Page 3 Binary Points
Binary Points
Description
Contact I/O Output State 3
Contact I/O Output State 4
Contact I/O Output State 9
Contact I/O Output State 10
Contact I/O Output State 11
Contact I/O Output State 12
Contact I/O Output State 17
Contact I/O Output State 18
Contact I/O Output State 19
Contact I/O Output State 20
Contact I/O Output State 25
Contact I/O Output State 26
Contact I/O Output State 27
Contact I/O Output State 28
Form 4D Available Data Points
Page 4 Binary Points
Analog Points
Description
A Phase Primary Current Magnitude
B Phase Primary Current Magnitude
C Phase Primary Current Magnitude
3I0 Primary Current Magnitude
A Phase Primary Voltage Magnitude
B Phase Primary Voltage Magnitude
C Phase Primary Voltage Magnitude
A Phase Power Factor
B Phase Power Factor
C Phase Power Factor
A Phase Primary Apparent Power
B Phase Primary Apparent Power
C Phase Primary Apparent Power
A Phase Primary Real Power
B Phase Primary Real Power
C Phase Primary Real Power
A Phase Primary Reactive Power
B Phase Primary Reactive Power
C Phase Primary Reactive Power
Line Frequency
A Phase Primary Demand Currents
B Phase Primary Demand Currents
C Phase Primary Demand Currents
Battery Voltage
Battery Current
Total Power Factor
Total Primary Apparent Power
Total Primary Real Power
Total Primary Reactive Power
A Phase Total Harmonic Current
B Phase Total Harmonic Current
C Phase Total Harmonic Current
Ground Total Harmonic Current
A Phase Total Harmonic Voltage
B Phase Total Harmonic Voltage
C Phase Total Harmonic Voltage
A Phase Demand Voltage
B Phase Demand Voltage
C Phase Demand Voltage
A Phase Demand Power Factor
A Phase Demand Apparent Power
A Phase Demand Real Power In
A Phase Demand Real Power Out
A Phase Demand Reactive Power In
A Phase Demand Reactive Power Out
Form 4D Available Data Points
Page 5 Analog Points
Form 4D Available Data Points
Analog Points
Description
B Phase Demand Power Factor
B Phase Demand Apparent Power
B Phase Demand Real Power In
B Phase Demand Real Power Out
B Phase Demand Reactive Power In
B Phase Demand Reactive Power Out
C Phase Demand Power Factor
C Phase Demand Apparent Power
C Phase Demand Real Power In
C Phase Demand Real Power Out
C Phase Demand Reactive Power In
C Phase Demand Reactive Power Out
Total Phase Demand Power Factor
Total Phase Demand Apparent Power
Total Phase Demand Real Power In
Total Phase Demand Real Power Out
Total Phase Demand Reactive Power In
Total Phase Demand Reactive Power Out
A Phase Depleted
B Phase Depleted
C Phase Depleted
A Phase KW Hours In
B Phase KW Hours In
C Phase KW Hours In
Total KW Hours In
A Phase KW Hours Out
B Phase KW Hours Out
C Phase KW Hours Out
Total KW Hours Out
A to B Phase Demand Voltage
B to C Phase Demand Voltage
C to A Phase Demand Voltage
Battery Test Voltage
Battery Test Current
Firmware Revision Number
Last Update Time
Fault Location Distance
A Phase Fault Current
B Phase Fault Current
C Phase Fault Current
Ground Fault Current
X Phase Primary Load Voltage Magnitude
Y Phase Primary Load Voltage Magnitude
Z Phase Primary Load Voltage Magnitude
Page 6 Analog Points
Counter Points
Description
Trip Counter (Phase A)
Trip Counter (Phase B)
Trip Counter (Phase C)
Trip Counter (Ground)
Trip Counter (SEF)
Total Trip Counter
Form 4D Available Data Points
Page 7 Counter Points
Control Points
Description
Close Mechanism
Trip Mechanism
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Disable Fast Trips
Profile - Normal
Profile - Alt1
Reset Targets
Reset Demand Meters
Test Battery
Hot Line Tag Set
Hot Line Tag Reset
Block Reclose Retry
Combined Trip and Close
Enable Sync Check
Reset Energy Meters
Block Voltage Trip
Block Frequency Trip
Cfg Logic Pt 01 from SCADA
Cfg Logic Pt 02 from SCADA
Cfg Logic Pt 03 from SCADA
Cfg Logic Pt 04 from SCADA
Cfg Logic Pt 05 from SCADA
Cfg Logic Pt 06 from SCADA
Cfg Logic Pt 07 from SCADA
Cfg Logic Pt 08 from SCADA
Cfg Logic Pt 09 from SCADA
Cfg Logic Pt 10 from SCADA
Cfg Logic Pt 11 from SCADA
Cfg Logic Pt 12 from SCADA
Cfg Logic Pt 13 from SCADA
Cfg Logic Pt 14 from SCADA
Cfg Logic Pt 15 from SCADA
Cfg Logic Pt 16 from SCADA
Cfg Logic Pt 17 from SCADA
Cfg Logic Pt 18 from SCADA
Cfg Logic Pt 19 from SCADA
Cfg Logic Pt 20 from SCADA
Cfg Logic Pt 21 from SCADA
Cfg Logic Pt 22 from SCADA
Cfg Logic Pt 23 from SCADA
Cfg Logic Pt 24 from SCADA
Cfg Logic Pt 25 from SCADA
Form 4D Available Data Points
Page 8 Control Points
Control Points
Description
Cfg Logic Pt 26 from SCADA
Cfg Logic Pt 27 from SCADA
Cfg Logic Pt 28 from SCADA
Cfg Logic Pt 29 from SCADA
Cfg Logic Pt 30 from SCADA
Cfg Logic Pt 31 from SCADA
Cfg Logic Pt 32 from SCADA
Cfg Logic Pt 33 from SCADA
Cfg Logic Pt 34 from SCADA
Cfg Logic Pt 35 from SCADA
Cfg Logic Pt 36 from SCADA
Cfg Logic Pt 37 from SCADA
Cfg Logic Pt 38 from SCADA
Cfg Logic Pt 39 from SCADA
Cfg Logic Pt 40 from SCADA
Form 4D Available Data Points
Page 9 Control Points
©2011 Cooper Industries. All Rights Reserved.