R280-90-30 Communications Point Data Base Reclosers Data 3397

advertisement
Reclosers
Reference Information
Form 4D Microprocessor-Based Recloser Control
Serial Communications
R280-90-30
Communications Point Data Base
Data 3397
for
MODBUS Protocol
For Use With Cooper Power Systems
Form 4D Recloser Controls
September 2010 • New Issue
Form 4D MODBUS Device Profile Data Dictionary
Form 4D MODBUS Map Points
September 7, 2010
v1.01
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
1.01
Date
9/1/2010
9/7/2010
Description
Initial Release, ported from DNP3 maps
Revised point descriptions for consistency
MODBUS Register Numbering Convention
MODBUS data points consist of 4 main types: coils, status, input registers, and holding registers.
The numbering convention refers to the individual data points by prefixing their addresses so that
when looking at a number for a given point the user would know which type of data point was being referenced.
For example:
Coils do not have a prefix and so are referred to by their register number 1 through XXX.
Status registers are prefixed with 1X,XXX so they would fall in the range 10,001 through 1X,XXX.
Input registers are prefixed with 3X,XXX so they are in the range 30,001 to 3X,XXX.
Holding registers use a prefix of 4X,XXX so they are numbered between 40,001 and 4X,XXX.
These prefixes are automatically dropped in the actual low level messages and all data points are zero referenced.
When configuring master software to access these data points, care must be taken to address the registers
correctly, i.e. if the software used does not automatically remove the prefix, be certain only the register
portion of the address is used.
Data type
Coils
Status
Input
Holding
Range
1 through XXX
10,001 through 1X,XXX
30,001 through 3X,XXX
40,001 through 4X,XXX
Read func. Write func.
01
05
02
N/A
04
N/A
03
06
Note: The Form 4D does not have any Holding Registers defined.
Page 1
Cover Page
Form 4D MODBUS Device Profile Data Dictionary
INPUT SUBSYSTEM
Status Registers
Description
Recloser Closed
Recloser Open
Control is Locked Out
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non-Reclosing
Ground Trip Blocked
SEF Blocked
CLPU Blocked
Fast Trips Disabled
Profile Selected (Normal)
Profile Selected (Alt1)
Not Used
Not Used
Hot Line Tag
Bus Voltage Present (Phase A)
Bus Voltage Present (Phase B)
Bus Voltage Present (Phase C)
Reverse Power Flow
Battery Test in Progress
No AC Power
Battery Alarm
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Register
Hex
Register
10001
10002
10003
10004
10005
10006
10007
10008
10009
10010
10011
10012
10013
10014
10015
10016
10017
10018
10019
10020
10021
10022
10023
10024
10025
10026
10027
10028
10029
10030
10031
10032
10033
10034
10035
10036
10037
10038
2711
2712
2713
2714
2715
2716
2717
2718
2719
271A
271B
271C
271D
271E
271F
2720
2721
2722
2723
2724
2725
2726
2727
2728
2729
272A
272B
272C
272D
272E
272F
2730
2731
2732
2733
2734
2735
2736
Page 2
Status Registers (Binary)
Form 4D MODBUS Device Profile Data Dictionary
INPUT SUBSYSTEM
Status Registers
Description
Not Used
Not Used
Reclose Retry Blocked
A Phase Fault Trip
B Phase Fault Trip
C Phase Fault Trip
Ground Fault Trip
SEF Trip
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Hot Line Tag On from Configurable Logic
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Control Circuit Interrupted
Voltage Trip Blocked
Frequency Trip Blocked
Register
10039
10040
10041
10042
10043
10044
10045
10046
10047
10048
10049
10050
10051
10052
10053
10054
10055
10056
10057
10058
10059
10060
10061
10062
Hex
Register
2737
2738
2739
273A
273B
273C
273D
273E
273F
2740
2741
2742
2743
2744
2745
2746
2747
2748
2749
274A
274B
274C
274D
274E
Page 3
Status Registers (Binary)
Form 4D MODBUS Device Profile Data Dictionary
INPUT SUBSYSTEM
Inputs
Register
Hex
Register
Division
Scale Factor
Units
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
30001
30002
30003
30004
30005
30006
30007
30008
30009
30010
7531
7532
7533
7534
7535
7536
7537
7538
7539
753A
A Phase Primary Current Magnitude
B Phase Primary Current Magnitude
C Phase Primary Current Magnitude
3I0 Primary Current Magnitude
30011
30012
30013
30014
753B
753C
753D
753E
10
10
10
10
Amps
Amps
Amps
Amps
A Phase Primary Voltage Magnitude
B Phase Primary Voltage Magnitude
C Phase Primary Voltage Magnitude
30015
30016
30017
753F
7540
7541
1
1
1
Volts
Volts
Volts
A Phase Power Factor
B Phase Power Factor
C Phase Power Factor
30018
30019
30020
7542
7543
7544
10000
10000
10000
A Phase Primary Apparent Power
B Phase Primary Apparent Power
C Phase Primary Apparent Power
30021
30022
30023
7545
7546
7547
1
1
1
kVA
kVA
kVA
A Phase Primary Real Power
B Phase Primary Real Power
C Phase Primary Real Power
30024
30025
30026
7548
7549
754A
1
1
1
kW
kW
kW
A Phase Primary Reactive Power
B Phase Primary Reactive Power
C Phase Primary Reactive Power
30027
30028
30029
754B
754C
754D
1
1
1
kvar
kvar
kvar
Line Frequency
30030
754E
100
Hz
Description
Page 4
Input Registers (Analog)
Form 4D MODBUS Device Profile Data Dictionary
INPUT SUBSYSTEM
Inputs
A Phase Primary Demand Currents
B Phase Primary Demand Currents
C Phase Primary Demand Currents
30031
30032
30033
Hex
Register
754F
7550
7551
Battery Voltage
Battery Current
30034
30035
7552
7553
100
1000
Volts
Amps
Trip Counter (Phase A)
Trip Counter (Phase B)
Trip Counter (Phase C)
Trip Counter (Ground)
Trip Counter (SEF)
Total Trip Counter
30036
30037
30038
30039
30040
30041
7554
7555
7556
7557
7558
7559
1
1
1
1
1
1
(count)
(count)
(count)
(count)
(count)
(count)
Description
Register
Division
Scale Factor
10
10
10
Amps
Amps
Amps
Units
Page 5
Input Registers (Analog)
Form 4D MODBUS Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Coils
Description
*Close Mechanism
*Trip Mechanism
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Disable Fast Trips
*Profile - Normal
*Profile - Alt1
Not Used
Not Used
*Reset Targets
*Reset Demand Meters
Not Used
*Test Battery
*Hot Line Tag Set
*Hot Line Tag Reset
Block Reclose Retry
Combined Trip and Close
Enable Sync Check
Not Used
Reset Energy Meters
Block Voltage Trip
Block Frequency Trip
Register
Hex
Register
Conditioned by
Supervisory State
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
* Momentary/Self Resetting
Page 6
Coil Registers
Form 4D Microprocessor-Based Recloser Control Serial Communications MODBUS Protocol