Reclosers Reference Information Form 4D Microprocessor-Based Recloser Control Serial Communications R280-90-30 Communications Point Data Base Data 3397 for MODBUS Protocol For Use With Cooper Power Systems Form 4D Recloser Controls September 2010 • New Issue Form 4D MODBUS Device Profile Data Dictionary Form 4D MODBUS Map Points September 7, 2010 v1.01 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC. UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED. Document 1.00 1.01 Date 9/1/2010 9/7/2010 Description Initial Release, ported from DNP3 maps Revised point descriptions for consistency MODBUS Register Numbering Convention MODBUS data points consist of 4 main types: coils, status, input registers, and holding registers. The numbering convention refers to the individual data points by prefixing their addresses so that when looking at a number for a given point the user would know which type of data point was being referenced. For example: Coils do not have a prefix and so are referred to by their register number 1 through XXX. Status registers are prefixed with 1X,XXX so they would fall in the range 10,001 through 1X,XXX. Input registers are prefixed with 3X,XXX so they are in the range 30,001 to 3X,XXX. Holding registers use a prefix of 4X,XXX so they are numbered between 40,001 and 4X,XXX. These prefixes are automatically dropped in the actual low level messages and all data points are zero referenced. When configuring master software to access these data points, care must be taken to address the registers correctly, i.e. if the software used does not automatically remove the prefix, be certain only the register portion of the address is used. Data type Coils Status Input Holding Range 1 through XXX 10,001 through 1X,XXX 30,001 through 3X,XXX 40,001 through 4X,XXX Read func. Write func. 01 05 02 N/A 04 N/A 03 06 Note: The Form 4D does not have any Holding Registers defined. Page 1 Cover Page Form 4D MODBUS Device Profile Data Dictionary INPUT SUBSYSTEM Status Registers Description Recloser Closed Recloser Open Control is Locked Out Any Control or System Alarm Above Minimum Trip Supervisory Off Non-Reclosing Ground Trip Blocked SEF Blocked CLPU Blocked Fast Trips Disabled Profile Selected (Normal) Profile Selected (Alt1) Not Used Not Used Hot Line Tag Bus Voltage Present (Phase A) Bus Voltage Present (Phase B) Bus Voltage Present (Phase C) Reverse Power Flow Battery Test in Progress No AC Power Battery Alarm Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Register Hex Register 10001 10002 10003 10004 10005 10006 10007 10008 10009 10010 10011 10012 10013 10014 10015 10016 10017 10018 10019 10020 10021 10022 10023 10024 10025 10026 10027 10028 10029 10030 10031 10032 10033 10034 10035 10036 10037 10038 2711 2712 2713 2714 2715 2716 2717 2718 2719 271A 271B 271C 271D 271E 271F 2720 2721 2722 2723 2724 2725 2726 2727 2728 2729 272A 272B 272C 272D 272E 272F 2730 2731 2732 2733 2734 2735 2736 Page 2 Status Registers (Binary) Form 4D MODBUS Device Profile Data Dictionary INPUT SUBSYSTEM Status Registers Description Not Used Not Used Reclose Retry Blocked A Phase Fault Trip B Phase Fault Trip C Phase Fault Trip Ground Fault Trip SEF Trip Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Hot Line Tag On from Configurable Logic Hot Line Tag On from Communications Hot Line Tag On from Front Panel Switch Control Circuit Interrupted Voltage Trip Blocked Frequency Trip Blocked Register 10039 10040 10041 10042 10043 10044 10045 10046 10047 10048 10049 10050 10051 10052 10053 10054 10055 10056 10057 10058 10059 10060 10061 10062 Hex Register 2737 2738 2739 273A 273B 273C 273D 273E 273F 2740 2741 2742 2743 2744 2745 2746 2747 2748 2749 274A 274B 274C 274D 274E Page 3 Status Registers (Binary) Form 4D MODBUS Device Profile Data Dictionary INPUT SUBSYSTEM Inputs Register Hex Register Division Scale Factor Units Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 30001 30002 30003 30004 30005 30006 30007 30008 30009 30010 7531 7532 7533 7534 7535 7536 7537 7538 7539 753A A Phase Primary Current Magnitude B Phase Primary Current Magnitude C Phase Primary Current Magnitude 3I0 Primary Current Magnitude 30011 30012 30013 30014 753B 753C 753D 753E 10 10 10 10 Amps Amps Amps Amps A Phase Primary Voltage Magnitude B Phase Primary Voltage Magnitude C Phase Primary Voltage Magnitude 30015 30016 30017 753F 7540 7541 1 1 1 Volts Volts Volts A Phase Power Factor B Phase Power Factor C Phase Power Factor 30018 30019 30020 7542 7543 7544 10000 10000 10000 A Phase Primary Apparent Power B Phase Primary Apparent Power C Phase Primary Apparent Power 30021 30022 30023 7545 7546 7547 1 1 1 kVA kVA kVA A Phase Primary Real Power B Phase Primary Real Power C Phase Primary Real Power 30024 30025 30026 7548 7549 754A 1 1 1 kW kW kW A Phase Primary Reactive Power B Phase Primary Reactive Power C Phase Primary Reactive Power 30027 30028 30029 754B 754C 754D 1 1 1 kvar kvar kvar Line Frequency 30030 754E 100 Hz Description Page 4 Input Registers (Analog) Form 4D MODBUS Device Profile Data Dictionary INPUT SUBSYSTEM Inputs A Phase Primary Demand Currents B Phase Primary Demand Currents C Phase Primary Demand Currents 30031 30032 30033 Hex Register 754F 7550 7551 Battery Voltage Battery Current 30034 30035 7552 7553 100 1000 Volts Amps Trip Counter (Phase A) Trip Counter (Phase B) Trip Counter (Phase C) Trip Counter (Ground) Trip Counter (SEF) Total Trip Counter 30036 30037 30038 30039 30040 30041 7554 7555 7556 7557 7558 7559 1 1 1 1 1 1 (count) (count) (count) (count) (count) (count) Description Register Division Scale Factor 10 10 10 Amps Amps Amps Units Page 5 Input Registers (Analog) Form 4D MODBUS Device Profile Data Dictionary OUTPUT SUBSYSTEM Coils Description *Close Mechanism *Trip Mechanism Block Reclosing Block Ground Trip Block SEF Block CLPU Disable Fast Trips *Profile - Normal *Profile - Alt1 Not Used Not Used *Reset Targets *Reset Demand Meters Not Used *Test Battery *Hot Line Tag Set *Hot Line Tag Reset Block Reclose Retry Combined Trip and Close Enable Sync Check Not Used Reset Energy Meters Block Voltage Trip Block Frequency Trip Register Hex Register Conditioned by Supervisory State 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes * Momentary/Self Resetting Page 6 Coil Registers Form 4D Microprocessor-Based Recloser Control Serial Communications MODBUS Protocol ©2010 Cooper Industries. All Rights Reserved. All Cooper logos and Cooper Power Systems are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use Cooper trademarks without the prior written consent of Cooper Industries. 2300 Badger Drive Waukesha, WI 53188 www.cooperpower.com