Switchgear Technical Data TD280014EN Effective July 2015 Supersedes R280-90-17 8/2012 COOPER POWER SERIES Communications Point Data Base for MODBUS Protocol For use with Eaton’s Cooper Power series Form 6 Recloser Control Form 6 Modbus Device Profile Data Dictionary Form 6 Modbus Map Points July 9, 2015 3.00 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON. UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED. Document 1.00 1.01 1.02 Date 5/8/2001 5/15/2001 5/30/2001 1.03 1.04 1.05 1.06 1.07 1.08 1.09 2.00 3.00 5/8/2002 5/29/2002 5/12/2003 8/29/2003 3/15/2004 7/26/2005 10/28/2005 8/24/2012 7/9/2015 Description Initial release. Changed status input 54 to "Reclose Retry Enable"; added HLT source indication to status input map Changed wording on SGF "enable" to "block". Made hot line tag coils self-resetting. Changed status input 58 to "CCI: Control Circuit Interrupted". Added Modbus register naming explanation to cover page. Reworded Modbus register numbering explanation. Added coil descriptions for 18 & 19, fixed descriptions for status registers 10058 thru 10061 Added Triple-Single Information, Supervisory Enable Status, and Minor Edits Corrected the descriptions for the Triple-Single Coils 20 through 23. Minor edits in the Status (Standard) and Status (Triple-Single) tabs. Updates and re-release for ProView 5.0 Updates and re-release for ProView 5.1 Modbus Register Numbering Convention Modbus data points consist of 4 main types: coils, status, input registers, and holding registers. The numbering convention refers to the individual data points by prefixing their addresses so that when looking at a number for a given point the user would know which type of data point was being referenced. For example: Coils do not have a prefix and so are referred to by their register number 1 through XXX. Status registers are prefixed with 1X,XXX so they would fall in the range 10,001 through 1X,XXX. Input registers are prefixed with 3X,XXX so they are in the range 30,001 to 3X,XXX. Holding registers use a prefix of 4X,XXX so they are numbered between 40,001 and 4X,XXX. These prefixes are automatically dropped in the actual low level messages and all data points are zero referenced. When configuring master software to access these data points, care must be taken to address the registers correctly, i.e. if the software used does not automatically remove the prefix, be certain only the register portion of the address is used. Data type Coils Status Input Holding Range 1 through XXX 10,001 through 1X,XXX 30,001 through 3X,XXX 40,001 through 4X,XXX Read func. Write func. 01 05 02 N/A 04 N/A 03 06 Note: The Form 6 does not have any Holding Registers defined. Page 1 Cover Page Form 6 Modbus Device Profile Data Dictionary INPUT SUBSYSTEM Status Registers Description Recloser Closed Recloser Open Control is Locked Out Control OK Any Control or System Alarm Above Minimum Trip Supervisory Off Non-Reclosing Ground Trip Blocked SEF Blocked CLPU Blocked Fast Trips Blocked Profile Selected (Normal) Profile Selected (Alt1) Profile Selected (Alt2) Profile Selected (Alt3) Hot Line Tag Bus Voltage Present (Phase A) Bus Voltage Present (Phase B) Bus Voltage Present (Phase C) A Phase Fault Trip B Phase Fault Trip C Phase Fault Trip Ground Fault Trip SEF Trip Reverse Power Flow Battery Test in Progress No AC Power Battery Alarm ci1:RTrip (TB1:3-4) ci2:SClose (TB1:5-6) ci3:STrip (TB1:7-8) ci4:GTB (TB3:1-2) ci5:NRecl (TB3:3-4) ci6:TargR (TB3:5-6) ci7 (TB3:7-8) ci8:Alt1 (TB3:9-10) ci9:Alt2 (TB3:11-12) ci10:Alt3 (TB3:13-14) ci11:Nrml (TB3:15-16) co1:aux (TB1:11-12,13) Register Hex Register 10001 10002 10003 10004 10005 10006 10007 10008 10009 10010 10011 10012 10013 10014 10015 10016 10017 10018 10019 10020 10021 10022 10023 10024 10025 10026 10027 10028 10029 10030 10031 10032 10033 10034 10035 10036 10037 10038 10039 10040 10041 2711 2712 2713 2714 2715 2716 2717 2718 2719 271A 271B 271C 271D 271E 271F 2720 2721 2722 2723 2724 2725 2726 2727 2728 2729 272A 272B 272C 272D 272E 272F 2730 2731 2732 2733 2734 2735 2736 2737 2738 2739 Page 2 Status Registers Form 6 Modbus Device Profile Data Dictionary INPUT SUBSYSTEM Status Registers Description co2:ok (TB1:14-15) co3:hlt (TB1:16-17) co4:gtb (TB1:18-19) ss1:lo (TB1:9-10) co5:nr (TB3:17-18) co6:alm (TB3:19-20,21) co7:nrm (TB4:1-2) co8:alt1 (TB4:3-4) co9:alt2 (TB4:5-6) co10:alt3 (TB4:7-8) co11:frq (TB4:9-10) co12:vlt (TB4:11-12,13) Reclose Retry Enabled Hot Line Tag On from Workbench Hot Line Tag On from Communications Hot Line Tag On from Front Panel Switch Phase Overcurrent Alarm Ground Overcurrent Alarm Negative Sequence Overcurrent Alarm Control Circuit Interrupted USEF Blocked Profile Selected (Alt4) Profile Selected (Alt5) Register 10042 10043 10044 10045 10046 10047 10048 10049 10050 10051 10052 10053 10054 10055 10056 10057 10058 10059 10060 10061 10062 10063 10064 Hex Register 273A 273B 273C 273D 273E 273F 2740 2741 2742 2743 2744 2745 2746 2747 2748 2749 274A 274B 274C 274D 274E 274F 2750 Page 3 Status Registers Form 6 Modbus Device Profile Data Dictionary INPUT SUBSYSTEM Status Registers (Triple-Single) Description Recloser Closed Recloser Open Control is Locked Out Control OK Any Control or System Alarm Above Minimum Trip Supervisory Off Non-Reclosing Ground Trip Blocked SEF Blocked CLPU Blocked Fast Trips Blocked Profile Selected (Normal) Profile Selected (Alt1) Profile Selected (Alt2) Profile Selected (Alt3) Hot Line Tag Bus Voltage Present (Phase A) Bus Voltage Present (Phase B) Bus Voltage Present (Phase C) A Phase Fault Trip B Phase Fault Trip C Phase Fault Trip Ground Fault Trip SEF Trip Reverse Power Flow Battery Test in Progress No AC Power Battery Alarm ci1:RTrip (TB1:3-4) ci2:SClose (TB1:5-6) ci3:STrip (TB1:7-8) ci4:GTB (TB3:1-2) ci5:NRecl (TB3:3-4) ci6:TargR (TB3:5-6) ci7 (TB3:7-8) ci8:Alt1 (TB3:9-10) ci9:Alt2 (TB3:11-12) ci10:Alt3 (TB3:13-14) ci11:Nrml (TB3:15-16) co1:aux (TB1:11-12,13) Register Hex Register 10001 10002 10003 10004 10005 10006 10007 10008 10009 10010 10011 10012 10013 10014 10015 10016 10017 10018 10019 10020 10021 10022 10023 10024 10025 10026 10027 10028 10029 10030 10031 10032 10033 10034 10035 10036 10037 10038 10039 10040 10041 2711 2712 2713 2714 2715 2716 2717 2718 2719 271A 271B 271C 271D 271E 271F 2720 2721 2722 2723 2724 2725 2726 2727 2728 2729 272A 272B 272C 272D 272E 272F 2730 2731 2732 2733 2734 2735 2736 2737 2738 2739 Page 4 Status Registers (TS) Form 6 Modbus Device Profile Data Dictionary INPUT SUBSYSTEM Status Registers (Triple-Single) Description co2:ok (TB1:14-15) co3:hlt (TB1:16-17) co4:gtb (TB1:18-19) ss1:lo (TB1:9-10) co5:nr (TB3:17-18) co6:alm (TB3:19-20,21) co7:nrm (TB4:1-2) co8:alt1 (TB4:3-4) co9:alt2 (TB4:5-6) co10:alt3 (TB4:7-8) co11:frq (TB4:9-10) co12:vlt (TB4:11-12,13) Reclose Retry Enabled Hot Line Tag On from Workbench Hot Line Tag On from Communications Hot Line Tag On from Front Panel Switch Phase A Overcurrent Alarm Ground Overcurrent Alarm Negative Sequence Overcurrent Alarm Control Circuit Interrupted (Phase A) Recloser Closed (Phase B) Recloser Open (Phase B) Control is Locked Out (Phase B) Control Circuit Interrupted (Phase B) Recloser Closed (Phase C) Recloser Open (Phase C) Control is Locked Out (Phase C) Control Circuit Interrupted (Phase C) Phase B Overcurrent Alarm Phase C Overcurrent Alarm Ganged Mode 1-3 Mode 1-1 Mode USEF Blocked Profile Selected (Alt4) Profile Selected (Alt5) Reserved Reserved Reserved Register 10042 10043 10044 10045 10046 10047 10048 10049 10050 10051 10052 10053 10054 10055 10056 10057 10058 10059 10060 10061 10062 10063 10064 10065 10066 10067 10068 10069 10070 10071 10072 10073 10074 10075 10076 10077 10078 10079 10080 Hex Register 273A 273B 273C 273D 273E 273F 2740 2741 2742 2743 2744 2745 2746 2747 2748 2749 274A 274B 274C 274D 274E 274F 2750 2751 2752 2753 2754 2755 2756 2757 2758 2759 275A 275B 275C 275D 275E 275F 2760 Page 5 Status Registers (TS) Form 6 Modbus Device Profile Data Dictionary INPUT SUBSYSTEM Input Registers Register Hex Register Division Scale Factor Units Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 30001 30002 30003 30004 30005 30006 30007 30008 30009 30010 7531 7532 7533 7534 7535 7536 7537 7538 7539 753A A Phase Primary Current Magnitude B Phase Primary Current Magnitude C Phase Primary Current Magnitude 3I0 Primary Current Magnitude 30011 30012 30013 30014 753B 753C 753D 753E 10 10 10 10 Amps Amps Amps Amps A Phase Primary Voltage Magnitude B Phase Primary Voltage Magnitude C Phase Primary Voltage Magnitude 30015 30016 30017 753F 7540 7541 1 1 1 Volts Volts Volts A Phase Power Factor B Phase Power Factor C Phase Power Factor 30018 30019 30020 7542 7543 7544 10000 10000 10000 A Phase Primary Apparent Power B Phase Primary Apparent Power C Phase Primary Apparent Power 30021 30022 30023 7545 7546 7547 1 1 1 kVA kVA kVA A Phase Primary Real Power B Phase Primary Real Power C Phase Primary Real Power 30024 30025 30026 7548 7549 754A 1 1 1 kW kW kW A Phase Primary Reactive Power B Phase Primary Reactive Power C Phase Primary Reactive Power 30027 30028 30029 754B 754C 754D 1 1 1 kvar kvar kvar Line Frequency 30030 754E 100 Hz A Phase Primary Demand Currents B Phase Primary Demand Currents C Phase Primary Demand Currents 30031 30032 30033 754F 7550 7551 10 10 10 Amps Amps Amps Description Page 6 Input Registers Form 6 Modbus Device Profile Data Dictionary INPUT SUBSYSTEM Input Registers Register Hex Register Division Scale Factor Units Battery Voltage Battery Current 30034 30035 7552 7553 100 1000 Volts Amps Target Counter (Phase A) Target Counter (Phase B) Target Counter (Phase C) Target Counter (Ground) Target Counter (SEF) Total Trip Counter 30036 30037 30038 30039 30040 30041 7554 7555 7556 7557 7558 7559 1 1 1 1 1 1 (count) (count) (count) (count) (count) (count) Reserved Reserved Reserved Reserved Reserved 30042 30043 30044 30045 30046 755A 755B 755C 755D 755E Description Page 7 Input Registers Form 6 Modbus Device Profile Data Dictionary INPUT SUBSYSTEM Input Registers (Triple-Single) Register Hex Register Division Scale Factor Units Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 30001 30002 30003 30004 30005 30006 30007 30008 30009 30010 7531 7532 7533 7534 7535 7536 7537 7538 7539 753A A Phase Primary Current Magnitude B Phase Primary Current Magnitude C Phase Primary Current Magnitude 3I0 Primary Current Magnitude 30011 30012 30013 30014 753B 753C 753D 753E 10 10 10 10 Amps Amps Amps Amps A Phase Primary Voltage Magnitude B Phase Primary Voltage Magnitude C Phase Primary Voltage Magnitude 30015 30016 30017 753F 7540 7541 1 1 1 Volts Volts Volts A Phase Power Factor B Phase Power Factor C Phase Power Factor 30018 30019 30020 7542 7543 7544 10000 10000 10000 A Phase Primary Apparent Power B Phase Primary Apparent Power C Phase Primary Apparent Power 30021 30022 30023 7545 7546 7547 1 1 1 kVA kVA kVA A Phase Primary Real Power B Phase Primary Real Power C Phase Primary Real Power 30024 30025 30026 7548 7549 754A 1 1 1 kW kW kW A Phase Primary Reactive Power B Phase Primary Reactive Power C Phase Primary Reactive Power 30027 30028 30029 754B 754C 754D 1 1 1 kvar kvar kvar Line Frequency 30030 754E 100 Hz A Phase Primary Demand Currents B Phase Primary Demand Currents C Phase Primary Demand Currents 30031 30032 30033 754F 7550 7551 10 10 10 Amps Amps Amps Description Page 8 Input Registers (TS) Form 6 Modbus Device Profile Data Dictionary INPUT SUBSYSTEM Input Registers (Triple-Single) Register Hex Register Division Scale Factor Units Battery Voltage Battery Current 30034 30035 7552 7553 100 1000 Volts Amps Target Counter (Phase A) Target Counter (Phase B) Target Counter (Phase C) Target Counter (Ground) Target Counter (SEF) Total Trip Counter Trip Counter (Phase A) Trip Counter (Phase B) Trip Counter (Phase C) 30036 30037 30038 30039 30040 30041 30042 30043 30044 7554 7555 7556 7557 7558 7559 755A 755B 755C 1 1 1 1 1 1 1 1 1 (count) (count) (count) (count) (count) (count) (count) (count) (count) Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 30045 30046 30047 30048 30049 30050 30051 30052 30053 30054 755D 755E 755F 7560 7561 7562 7563 7564 7565 7566 Description Page 9 Input Registers (TS) Form 6 Modbus Device Profile Data Dictionary OUTPUT SUBSYSTEM Coils Description * Close Mechanism * Trip Mechanism Block Reclosing Block Ground Trip Block SEF Block CLPU Block Fast Trips * Profile - Normal * Profile - Alt1 * Profile - Alt2 * Profile - Alt3 * Reset Targets * Reset Demand Meters * Reset Alarms * Test Battery * Hot Line Tag Set * Hot Line Tag Reset Enable Reclose Retry Enable Sync Check Block USEF * Profile - Alt4 * Profile - Alt5 User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined Reserved Reserved Reserved Reserved * Momentary/Self Resetting Register Hex Register Conditioned by Supervisory State (Factory Default) 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes ----- Crosshatch indicates point is supervised regardless of setting Page 10 Coil Registers Form 6 Modbus Device Profile Data Dictionary OUTPUT SUBSYSTEM Coils (Triple-Single) Description * Close Mechanism * Trip Mechanism Block Reclosing Block Ground Trip Block SEF Block CLPU Block Fast Trips * Profile - Normal * Profile - Alt1 * Profile - Alt2 * Profile - Alt3 * Reset Targets * Reset Demand Meters * Reset Alarms * Test Battery * Hot Line Tag Set * Hot Line Tag Reset Enable Reclose Retry Enable Sync Check * Trip Mechanism (Phase B) * Trip Mechanism (Phase C) * Close Mechanism (Phase B) * Close Mechanism (Phase C) * Activate Ganged Mode * Activate 1-3 Mode * Activate 1-1 Mode * Trip All Phases * Close All Phases User Defined User Defined User Defined User Defined Block USEF * Profile - Alt4 * Profile - Alt5 Reserved * Momentary/Self Resetting Register Hex Register Conditioned by Supervisory State (Factory Default) 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes -- Crosshatch indicates point is supervised regardless of setting Page 11 Coil Registers (TS) Technical Data TD280014EN Communications Point Data Base Effective July 2015 Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries © 2015 Eaton All Rights Reserved Printed in USA Publication No. TD280014EN June 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners. For Eaton's Cooper Power series Form 6 recloser control information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.