Communications Point Data Base COOPER POWER SERIES for MODBUS Protocol

advertisement
Switchgear
Technical Data
TD280014EN
Effective July 2015
Supersedes R280-90-17 8/2012
COOPER POWER
SERIES
Communications Point Data Base
for MODBUS Protocol
For use with Eaton’s Cooper Power series
Form 6 Recloser Control
Form 6 Modbus Device Profile Data Dictionary
Form 6 Modbus Map Points
July 9, 2015
3.00
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
1.01
1.02
Date
5/8/2001
5/15/2001
5/30/2001
1.03
1.04
1.05
1.06
1.07
1.08
1.09
2.00
3.00
5/8/2002
5/29/2002
5/12/2003
8/29/2003
3/15/2004
7/26/2005
10/28/2005
8/24/2012
7/9/2015
Description
Initial release.
Changed status input 54 to "Reclose Retry Enable"; added HLT source indication to status input map
Changed wording on SGF "enable" to "block".
Made hot line tag coils self-resetting.
Changed status input 58 to "CCI: Control Circuit Interrupted".
Added Modbus register naming explanation to cover page.
Reworded Modbus register numbering explanation.
Added coil descriptions for 18 & 19, fixed descriptions for status registers 10058 thru 10061
Added Triple-Single Information, Supervisory Enable Status, and Minor Edits
Corrected the descriptions for the Triple-Single Coils 20 through 23.
Minor edits in the Status (Standard) and Status (Triple-Single) tabs.
Updates and re-release for ProView 5.0
Updates and re-release for ProView 5.1
Modbus Register Numbering Convention
Modbus data points consist of 4 main types: coils, status, input registers, and holding registers.
The numbering convention refers to the individual data points by prefixing their addresses so that
when looking at a number for a given point the user would know which type of data point was being referenced.
For example:
Coils do not have a prefix and so are referred to by their register number 1 through XXX.
Status registers are prefixed with 1X,XXX so they would fall in the range 10,001 through 1X,XXX.
Input registers are prefixed with 3X,XXX so they are in the range 30,001 to 3X,XXX.
Holding registers use a prefix of 4X,XXX so they are numbered between 40,001 and 4X,XXX.
These prefixes are automatically dropped in the actual low level messages and all data points are zero referenced.
When configuring master software to access these data points, care must be taken to address the registers
correctly, i.e. if the software used does not automatically remove the prefix, be certain only the register
portion of the address is used.
Data type
Coils
Status
Input
Holding
Range
1 through XXX
10,001 through 1X,XXX
30,001 through 3X,XXX
40,001 through 4X,XXX
Read func. Write func.
01
05
02
N/A
04
N/A
03
06
Note: The Form 6 does not have any Holding Registers defined.
Page 1
Cover Page
Form 6 Modbus Device Profile Data Dictionary
INPUT SUBSYSTEM
Status Registers
Description
Recloser Closed
Recloser Open
Control is Locked Out
Control OK
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non-Reclosing
Ground Trip Blocked
SEF Blocked
CLPU Blocked
Fast Trips Blocked
Profile Selected (Normal)
Profile Selected (Alt1)
Profile Selected (Alt2)
Profile Selected (Alt3)
Hot Line Tag
Bus Voltage Present (Phase A)
Bus Voltage Present (Phase B)
Bus Voltage Present (Phase C)
A Phase Fault Trip
B Phase Fault Trip
C Phase Fault Trip
Ground Fault Trip
SEF Trip
Reverse Power Flow
Battery Test in Progress
No AC Power
Battery Alarm
ci1:RTrip (TB1:3-4)
ci2:SClose (TB1:5-6)
ci3:STrip (TB1:7-8)
ci4:GTB (TB3:1-2)
ci5:NRecl (TB3:3-4)
ci6:TargR (TB3:5-6)
ci7 (TB3:7-8)
ci8:Alt1 (TB3:9-10)
ci9:Alt2 (TB3:11-12)
ci10:Alt3 (TB3:13-14)
ci11:Nrml (TB3:15-16)
co1:aux (TB1:11-12,13)
Register
Hex
Register
10001
10002
10003
10004
10005
10006
10007
10008
10009
10010
10011
10012
10013
10014
10015
10016
10017
10018
10019
10020
10021
10022
10023
10024
10025
10026
10027
10028
10029
10030
10031
10032
10033
10034
10035
10036
10037
10038
10039
10040
10041
2711
2712
2713
2714
2715
2716
2717
2718
2719
271A
271B
271C
271D
271E
271F
2720
2721
2722
2723
2724
2725
2726
2727
2728
2729
272A
272B
272C
272D
272E
272F
2730
2731
2732
2733
2734
2735
2736
2737
2738
2739
Page 2
Status Registers
Form 6 Modbus Device Profile Data Dictionary
INPUT SUBSYSTEM
Status Registers
Description
co2:ok (TB1:14-15)
co3:hlt (TB1:16-17)
co4:gtb (TB1:18-19)
ss1:lo (TB1:9-10)
co5:nr (TB3:17-18)
co6:alm (TB3:19-20,21)
co7:nrm (TB4:1-2)
co8:alt1 (TB4:3-4)
co9:alt2 (TB4:5-6)
co10:alt3 (TB4:7-8)
co11:frq (TB4:9-10)
co12:vlt (TB4:11-12,13)
Reclose Retry Enabled
Hot Line Tag On from Workbench
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Phase Overcurrent Alarm
Ground Overcurrent Alarm
Negative Sequence Overcurrent Alarm
Control Circuit Interrupted
USEF Blocked
Profile Selected (Alt4)
Profile Selected (Alt5)
Register
10042
10043
10044
10045
10046
10047
10048
10049
10050
10051
10052
10053
10054
10055
10056
10057
10058
10059
10060
10061
10062
10063
10064
Hex
Register
273A
273B
273C
273D
273E
273F
2740
2741
2742
2743
2744
2745
2746
2747
2748
2749
274A
274B
274C
274D
274E
274F
2750
Page 3
Status Registers
Form 6 Modbus Device Profile Data Dictionary
INPUT SUBSYSTEM
Status Registers (Triple-Single)
Description
Recloser Closed
Recloser Open
Control is Locked Out
Control OK
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non-Reclosing
Ground Trip Blocked
SEF Blocked
CLPU Blocked
Fast Trips Blocked
Profile Selected (Normal)
Profile Selected (Alt1)
Profile Selected (Alt2)
Profile Selected (Alt3)
Hot Line Tag
Bus Voltage Present (Phase A)
Bus Voltage Present (Phase B)
Bus Voltage Present (Phase C)
A Phase Fault Trip
B Phase Fault Trip
C Phase Fault Trip
Ground Fault Trip
SEF Trip
Reverse Power Flow
Battery Test in Progress
No AC Power
Battery Alarm
ci1:RTrip (TB1:3-4)
ci2:SClose (TB1:5-6)
ci3:STrip (TB1:7-8)
ci4:GTB (TB3:1-2)
ci5:NRecl (TB3:3-4)
ci6:TargR (TB3:5-6)
ci7 (TB3:7-8)
ci8:Alt1 (TB3:9-10)
ci9:Alt2 (TB3:11-12)
ci10:Alt3 (TB3:13-14)
ci11:Nrml (TB3:15-16)
co1:aux (TB1:11-12,13)
Register
Hex
Register
10001
10002
10003
10004
10005
10006
10007
10008
10009
10010
10011
10012
10013
10014
10015
10016
10017
10018
10019
10020
10021
10022
10023
10024
10025
10026
10027
10028
10029
10030
10031
10032
10033
10034
10035
10036
10037
10038
10039
10040
10041
2711
2712
2713
2714
2715
2716
2717
2718
2719
271A
271B
271C
271D
271E
271F
2720
2721
2722
2723
2724
2725
2726
2727
2728
2729
272A
272B
272C
272D
272E
272F
2730
2731
2732
2733
2734
2735
2736
2737
2738
2739
Page 4
Status Registers (TS)
Form 6 Modbus Device Profile Data Dictionary
INPUT SUBSYSTEM
Status Registers (Triple-Single)
Description
co2:ok (TB1:14-15)
co3:hlt (TB1:16-17)
co4:gtb (TB1:18-19)
ss1:lo (TB1:9-10)
co5:nr (TB3:17-18)
co6:alm (TB3:19-20,21)
co7:nrm (TB4:1-2)
co8:alt1 (TB4:3-4)
co9:alt2 (TB4:5-6)
co10:alt3 (TB4:7-8)
co11:frq (TB4:9-10)
co12:vlt (TB4:11-12,13)
Reclose Retry Enabled
Hot Line Tag On from Workbench
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Phase A Overcurrent Alarm
Ground Overcurrent Alarm
Negative Sequence Overcurrent Alarm
Control Circuit Interrupted (Phase A)
Recloser Closed (Phase B)
Recloser Open (Phase B)
Control is Locked Out (Phase B)
Control Circuit Interrupted (Phase B)
Recloser Closed (Phase C)
Recloser Open (Phase C)
Control is Locked Out (Phase C)
Control Circuit Interrupted (Phase C)
Phase B Overcurrent Alarm
Phase C Overcurrent Alarm
Ganged Mode
1-3 Mode
1-1 Mode
USEF Blocked
Profile Selected (Alt4)
Profile Selected (Alt5)
Reserved
Reserved
Reserved
Register
10042
10043
10044
10045
10046
10047
10048
10049
10050
10051
10052
10053
10054
10055
10056
10057
10058
10059
10060
10061
10062
10063
10064
10065
10066
10067
10068
10069
10070
10071
10072
10073
10074
10075
10076
10077
10078
10079
10080
Hex
Register
273A
273B
273C
273D
273E
273F
2740
2741
2742
2743
2744
2745
2746
2747
2748
2749
274A
274B
274C
274D
274E
274F
2750
2751
2752
2753
2754
2755
2756
2757
2758
2759
275A
275B
275C
275D
275E
275F
2760
Page 5
Status Registers (TS)
Form 6 Modbus Device Profile Data Dictionary
INPUT SUBSYSTEM
Input Registers
Register
Hex
Register
Division
Scale Factor
Units
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
30001
30002
30003
30004
30005
30006
30007
30008
30009
30010
7531
7532
7533
7534
7535
7536
7537
7538
7539
753A
A Phase Primary Current Magnitude
B Phase Primary Current Magnitude
C Phase Primary Current Magnitude
3I0 Primary Current Magnitude
30011
30012
30013
30014
753B
753C
753D
753E
10
10
10
10
Amps
Amps
Amps
Amps
A Phase Primary Voltage Magnitude
B Phase Primary Voltage Magnitude
C Phase Primary Voltage Magnitude
30015
30016
30017
753F
7540
7541
1
1
1
Volts
Volts
Volts
A Phase Power Factor
B Phase Power Factor
C Phase Power Factor
30018
30019
30020
7542
7543
7544
10000
10000
10000
A Phase Primary Apparent Power
B Phase Primary Apparent Power
C Phase Primary Apparent Power
30021
30022
30023
7545
7546
7547
1
1
1
kVA
kVA
kVA
A Phase Primary Real Power
B Phase Primary Real Power
C Phase Primary Real Power
30024
30025
30026
7548
7549
754A
1
1
1
kW
kW
kW
A Phase Primary Reactive Power
B Phase Primary Reactive Power
C Phase Primary Reactive Power
30027
30028
30029
754B
754C
754D
1
1
1
kvar
kvar
kvar
Line Frequency
30030
754E
100
Hz
A Phase Primary Demand Currents
B Phase Primary Demand Currents
C Phase Primary Demand Currents
30031
30032
30033
754F
7550
7551
10
10
10
Amps
Amps
Amps
Description
Page 6
Input Registers
Form 6 Modbus Device Profile Data Dictionary
INPUT SUBSYSTEM
Input Registers
Register
Hex
Register
Division
Scale Factor
Units
Battery Voltage
Battery Current
30034
30035
7552
7553
100
1000
Volts
Amps
Target Counter (Phase A)
Target Counter (Phase B)
Target Counter (Phase C)
Target Counter (Ground)
Target Counter (SEF)
Total Trip Counter
30036
30037
30038
30039
30040
30041
7554
7555
7556
7557
7558
7559
1
1
1
1
1
1
(count)
(count)
(count)
(count)
(count)
(count)
Reserved
Reserved
Reserved
Reserved
Reserved
30042
30043
30044
30045
30046
755A
755B
755C
755D
755E
Description
Page 7
Input Registers
Form 6 Modbus Device Profile Data Dictionary
INPUT SUBSYSTEM
Input Registers (Triple-Single)
Register
Hex
Register
Division
Scale Factor
Units
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
30001
30002
30003
30004
30005
30006
30007
30008
30009
30010
7531
7532
7533
7534
7535
7536
7537
7538
7539
753A
A Phase Primary Current Magnitude
B Phase Primary Current Magnitude
C Phase Primary Current Magnitude
3I0 Primary Current Magnitude
30011
30012
30013
30014
753B
753C
753D
753E
10
10
10
10
Amps
Amps
Amps
Amps
A Phase Primary Voltage Magnitude
B Phase Primary Voltage Magnitude
C Phase Primary Voltage Magnitude
30015
30016
30017
753F
7540
7541
1
1
1
Volts
Volts
Volts
A Phase Power Factor
B Phase Power Factor
C Phase Power Factor
30018
30019
30020
7542
7543
7544
10000
10000
10000
A Phase Primary Apparent Power
B Phase Primary Apparent Power
C Phase Primary Apparent Power
30021
30022
30023
7545
7546
7547
1
1
1
kVA
kVA
kVA
A Phase Primary Real Power
B Phase Primary Real Power
C Phase Primary Real Power
30024
30025
30026
7548
7549
754A
1
1
1
kW
kW
kW
A Phase Primary Reactive Power
B Phase Primary Reactive Power
C Phase Primary Reactive Power
30027
30028
30029
754B
754C
754D
1
1
1
kvar
kvar
kvar
Line Frequency
30030
754E
100
Hz
A Phase Primary Demand Currents
B Phase Primary Demand Currents
C Phase Primary Demand Currents
30031
30032
30033
754F
7550
7551
10
10
10
Amps
Amps
Amps
Description
Page 8
Input Registers (TS)
Form 6 Modbus Device Profile Data Dictionary
INPUT SUBSYSTEM
Input Registers (Triple-Single)
Register
Hex
Register
Division
Scale Factor
Units
Battery Voltage
Battery Current
30034
30035
7552
7553
100
1000
Volts
Amps
Target Counter (Phase A)
Target Counter (Phase B)
Target Counter (Phase C)
Target Counter (Ground)
Target Counter (SEF)
Total Trip Counter
Trip Counter (Phase A)
Trip Counter (Phase B)
Trip Counter (Phase C)
30036
30037
30038
30039
30040
30041
30042
30043
30044
7554
7555
7556
7557
7558
7559
755A
755B
755C
1
1
1
1
1
1
1
1
1
(count)
(count)
(count)
(count)
(count)
(count)
(count)
(count)
(count)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
30045
30046
30047
30048
30049
30050
30051
30052
30053
30054
755D
755E
755F
7560
7561
7562
7563
7564
7565
7566
Description
Page 9
Input Registers (TS)
Form 6 Modbus Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Coils
Description
* Close Mechanism
* Trip Mechanism
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
* Hot Line Tag Set
* Hot Line Tag Reset
Enable Reclose Retry
Enable Sync Check
Block USEF
* Profile - Alt4
* Profile - Alt5
User Defined
User Defined
User Defined
User Defined
User Defined
User Defined
User Defined
User Defined
User Defined
User Defined
Reserved
Reserved
Reserved
Reserved
* Momentary/Self Resetting
Register
Hex
Register
Conditioned by
Supervisory State
(Factory Default)
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-----
Crosshatch
indicates point is supervised regardless of setting
Page 10
Coil Registers
Form 6 Modbus Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Coils (Triple-Single)
Description
* Close Mechanism
* Trip Mechanism
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
* Hot Line Tag Set
* Hot Line Tag Reset
Enable Reclose Retry
Enable Sync Check
* Trip Mechanism (Phase B)
* Trip Mechanism (Phase C)
* Close Mechanism (Phase B)
* Close Mechanism (Phase C)
* Activate Ganged Mode
* Activate 1-3 Mode
* Activate 1-1 Mode
* Trip All Phases
* Close All Phases
User Defined
User Defined
User Defined
User Defined
Block USEF
* Profile - Alt4
* Profile - Alt5
Reserved
* Momentary/Self Resetting
Register
Hex
Register
Conditioned by
Supervisory State
(Factory Default)
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
--
Crosshatch
indicates point is supervised regardless of setting
Page 11
Coil Registers (TS)
Technical Data TD280014EN
Communications
Point Data Base

Effective July 2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. TD280014EN
June 2015
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
For Eaton's Cooper Power series Form 6
recloser control information
call 1-877-277-4636 or visit:
www.eaton.com/cooperpowerseries.