Reclosers Service Information Vacuum Interrupter Withstand Test Voltage Ratings Information S280-90-1 Applicable to all Kyle® Vacuum Interrupters. 2. At test voltages listed in Columns C and D, radiation is negligible. The electric field present in a vacuum interrupter during normal operation or recommended testing will not produce any hazard to personnel from X-rays. WARNING: Hazardous voltage. The switchgear and high voltage transformer must be in a test cage or similar protective device to prevent accidental contact with the high voltage parts. Solidly ground all equipment. Failure to comply can result in death, severe personal injury, and equipment damage. T221.3 ! 3. Testing at voltages higher than those listed in Columns C and D may cause radiation emission injurious to personnel. 4. Vacuum interrupter testing above the value listed in Column C is not recommended. CAUTION: Radiation. At voltages up to the specified test voltages, the radiation emitted by the vacuum interrupter is negligible. However, above these voltages, radiation injurious to personnel can be G109.2 emitted. ! 5. If direct-current dielectric tests (15 minute dc) are to be conducted on an underground system with apparatus connected, be sure vacuum interrupter contacts are closed. 1. American National Standard C37.61-1973, “Guide for the Application, Operation, and Maintenance of Automatic Circuit Reclosers”, allows testing after delivery which includes application of 75% of rated low-frequency withstand voltage across open contacts of the interrupter. This voltage (50-60 Hz) is tabulated below. Column A Column B Apparatus Type Designation Interrupter Rated Maximum Voltage (kV rms) PADMOUNT PWE PWVE R-VAC/VFI R-VAC/VFI R-VAC/VFI PST PST 15.5 27.0 15.5 27.0 38.0 15.5 27.0 6. Normal electrical safety precautions should be observed. Column C 75% of Rated Low-Frequency Withstand Voltage (1 min dry) (kV rms) 25.5 ** 30.0 ** 25.5 ** 30.0 ** 37.5 ** 25.5 ** 30.0 ** Column D* Column E *** Recommended Dc Withstand Voltage (1 min dry) (kV) Nominal Open-Contact Gap (in) 37.1 ** 42.4 ** 37.1 ** 42.4 ** 74.2 ** 37.1 ** 42.4 ** 1/2 1/2 1/2 1/2 1/2 1/2 1/2 * To prevent possible interrupter damage, the dc test source should be limited to 5 mA (single-phase) or 2 mA (threephase) maximum. Dc test voltages listed in Column D are not intended to specify 15-minute dc system test voltages. ** Test voltages must not be applied directly to submersible bushing stud terminals without using proper termination. *** When testing vacuum interrupters not installed in distribution switchgear, the vacuum interrupter should have a nominal open-contact gap as listed in Column E. July 2001 • Supersedes 1/96 Printed in USA 1 Vacuum Interrupters Withstand Test Voltage Ratings Information Column A Column B Apparatus Type Designation Interrupter Rated Maximum Voltage (kV rms) Column C 75% of Rated Low-Frequency Withstand Voltage (1 min dry) (kV rms) Column D* Column E Recommended Dc Withstand Voltage (1 min dry) (kV) Nominal Open-Contact Gap (in) RECLOSERS 2 V4E V4H V6H V4L VSA12 VSA12B VSA16 VSA20 VSA20A 27.0 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 45.0 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 63.5 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 1/2 1/4 1/4 1/2 7/16 7/16 7/16 7/16 7/16 VSO12 VSO16 VW VWE VWV27 VWV38X VWVE27 VWVE38X 38.0 38.0 15.5 15.5 27.0 38.0 27.0 38.0 52.5 52.5 37.5 37.5 45.0 52.5 45.0 52.5 74.2 74.2 50.0 50.0 63.5 74.2 63.5 74.2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 VXE15 VXE27 15.5 27.0 37.5 45.0 50.0 63.5 7/16 7/16 NOVA1-15 NOVA1-27 15.5 29.2 37.5 45.0 53.0 63.5 7/16 7/16 NOVA-TS-15 NOVA-TS-27 15.5 29.2 37.5 45.0 53.0 63.5 7/16 7/16 NOVA15 NOVA27 15.5 29.2 37.5 45.0 53.0 63.5 7/16 7/16 S280-90-1 Column A Column B Apparatus Type Designation Interrupter Rated Maximum Voltage (kV rms) Column C 75% of Rated Low-Frequency Withstand Voltage (1 min dry) (kV rms) Column D* Column E Recommended Dc Withstand Voltage (1 min dry) (kV) Nominal Open-Contact Gap (in) BREAKERS VSA20B 15.5 37.5 50.0 7/16 FAULT INTERRUPTERS CI CI CI CM (600A) CM (1200A) CM (600A) 15.5 27.0 38.0 15.5 15.5 27.0 26.2 ** 30.0 ** 45.0 ** 26.2 26.2 30.0 37.1 ** 42.4 ** 63.5 ** 37.1 37.1 42.4 1/2 1/2 1/2 1/2 1/2 1/2 LOAD BREAK SWITCHES F F DAS15 DAS27 15.5 27.0 15.5 27.0 37.5 45.0 37.5 45.0 50.0 63.5 50.0 60.0 1/2 1/2 7/16 7/16 CAPACITOR SWITCHES SyncCap (110 kV BIL) SyncCap (125 kV BIL) VCS3-15 VCS3-27 VCS-1 VCS-1S 15.5 15.5 15.5 29.2 15.0 15.5 37.5 45.0 37.5 45.0 37.5 45.0 50.0 60.0 50.0 60.0 50.0 60.0 1/2 1/2 7/16 7/16 3/8 1/4 SECTIONALIZERS TVS15 TVS27 DAS15 DAS27 15.5 27.0 15.5 27.0 37.5 45.0 37.5 45.0 50.0 60.0 50.0 60.0 7/16 7/16 7/16 7/16 * To prevent possible interrupter damage, the dc test source should be limited to 5 mA (single-phase) or 2 mA (threephase) maximum. Dc test voltages listed in Column D are not intended to specify 15-minute dc system test voltages. ** Test voltages must not be applied directly to submersible bushing stud terminals without using proper termination. 3 Vacuum Interrupters Withstand Test Voltage Ratings Information ! SAFETY FOR LIFE © 2001 Cooper Power Systems, Inc. Kyle® is a registered trademark of Cooper Industries, Inc. NOVA™ is a trademark of Cooper Industries, Inc. KA2048-275 Rev. 01 P.O. Box 1640 Waukesha, WI 53187 www.cooperpower.com KRP Printed on Recycled Paper 7/01