Communications Point Data Base COOPER POWER SERIES

advertisement
Capacitor Banks
Technical Data
TD916002EN
Effective XXX 2015
Supersedes 240-40 August 2012
COOPER POWER
SERIES
Communications Point Data Base
for Serial and Ethernet Communications Protocol DNP3
For use with Eaton’s Cooper Power series
CBC-8000 Capacitor Bank Control
CBC-8000 DNP3 Device Profile Data Dictionary
CBC-8000 DNP3 Map Points
July 13, 2015
v1.40
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
1.10
1.20
1.30
1.40
Date
5/16/2012
4/29/2013
11/19/2013
7/10/2014
7/13/2015
Description
Initial Release
Ethernet Release Updates
Firmware Version 2.0.0 Updates
Firmware Version 2.2.2 Updates
Firmware Version 2.3.0 Updates
Page 1
Cover Page
CBC-8000 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Default Static Variation
Obj 01 Var 1 Binary Input – Packed format
Default Event Variation
Obj 02 Var 1 Binary Input Event – Without time (with time stamps disabled in configuration)
Obj 02 Var 2 Binary Input Event – With absolute time (with time stamps enabled in configuration)
Default
Event Description
Class
Point Name
Index
Hex Index
Bank State
00
00
1
Indicates state of capacitor bank.
SCADA Override Mode
01
01
1
Indicates if CBC is in SCADA override mode (0=no,1=yes). Mode is enabled via CROB 1, 27, or 28 control. Mode is disabled via CROB 11 or local time reaches SCADA
override clear time (if ignore SCADA override clear time setting is disabled).
NC Lockout
02
02
1
Set if CBC is in NC lockout state. Cleared via CROB 2 control or front panel Neutral Lockout Reset button press (if CBC is in Manual mode).
CVR Mode
03
03
1
Indicates if CBC is in CVR mode (0=no,1=yes). Mode is enabled or disabled via CROB 9 control. Mode is also disabled when local time reaches CVR disable time.
Line Voltage High Alarm
Line Voltage Low Alarm
Line Voltage THD Alarm
VAR KVAR High Alarm
VAR KVAR Low Alarm
VAR kW High Alarm
VAR kW Low Alarm
VAR Leading Pf Alarm
VAR Lagging Pf Alarm
Temperature High Alarm
Temperature Low Alarm
Va High Alarm
Va Low Alarm
Vb High Alarm
Vb Low Alarm
Vc High Alarm
Vc Low Alarm
Ia High Alarm
Ia Low Alarm
Ib High Alarm
Ib Low Alarm
Ic High Alarm
Ic Low Alarm
NC Total Alarm
NC Fundamental Alarm
NC THD Alarm
Phase A Total Voltage Hi Alarm
Phase A Total Voltage Lo Alarm
Phase A Voltage THD Alarm
Phase A Total Current Alarm
Phase A Current THD Alarm
Phase A Leading PF Alarm
Phase A Lagging PF Alarm
Phase A kW Hi Alarm
Phase A kW Lo Alarm
Phase A kVAR Hi Alarm
Phase A kVAR Lo Alarm
Phase B Total Voltage Hi Alarm
Phase B Total Voltage Lo Alarm
Phase B Voltage THD Alarm
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Page 2
Binary Inputs
CBC-8000 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Point Name
Default Static Variation
Obj 01 Var 1 Binary Input – Packed format
Default Event Variation
Obj 02 Var 1 Binary Input Event – Without time (with time stamps disabled in configuration)
Obj 02 Var 2 Binary Input Event – With absolute time (with time stamps enabled in configuration)
Default
Event Description
Class
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Tied to ProView NXG Data Alarm.
1
Indicates Power flow direction (0=normal,1=reverse). Tied to Proview Status Alarm.
1
Indicates Power flow direction (0=normal,1=reverse). Tied to Proview Status Alarm.
1
Indicates Power flow direction (0=normal,1=reverse). Tied to Proview Status Alarm.
1
Indicates Power flow direction (0=normal,1=reverse). Tied to Proview Status Alarm.
1
Tied to NC Verification function.
1
1
Set if voltage detected on the Close relay output during non-bank operation.
1
Set if voltage detected on the Trip relay output during non-bank operation.
1
Tied to delta voltage percent function.
1
Set when timer running.
1
Set when timer running.
1
Set when timer running.
1
Set when timer running.
1
Set when timer running.
1
Set when timer running.
1
Set when timer running.
1
Set when timer running.
1
Set when timer running.
1
Set when timer running.
1
Set when voltage is not detected on either relay output during bank operate time.
1
Index
Hex Index
Phase B Total Current Alarm
Phase B Current THD Alarm
Phase B Leading PF Alarm
Phase B Lagging PF Alarm
Phase B kW Hi Alarm
Phase B kW Lo Alarm
Phase B kVAR Hi Alarm
Phase B kVAR Lo Alarm
Phase C Total Voltage Hi Alarm
Phase C Total Voltage Lo Alarm
Phase C Voltage THD Alarm
Phase C Total Current Alarm
Phase C Current THD Alarm
Phase C Leading PF Alarm
Phase C Lagging PF Alarm
Phase C kW Hi Alarm
Phase C kW Lo Alarm
Phase C kVAR Hi Alarm
Phase C kVAR Lo Alarm
VAR Power Flow Alarm
PhA Power Flow Alarm
PhB Power Flow Alarm
PhC Power Flow Alarm
Operation Failed Alarm
Max Operation Count Alarm
Bad Active Close Relay Alarm
Bad Active Trip Relay Alarm
Abnormal Delta Voltage Alarm
OVUV Track Timer Alarm
Emergency Track Timer Alarm
Fault Current Timer Alarm
VAR Track Timer Alarm
Va Timer Alarm
Vb Timer Alarm
Vc Timer Alarm
Ia Timer Alarm
Ib Timer Alarm
Ic Timer Alarm
Relay Sense Failure Alarm
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
2C
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
40
41
42
43
44
45
46
47
48
49
4A
4B
4C
4D
4E
4F
50
51
52
Reclose Block Alarm
83
53
1
Fault Current Alarm
Manual Mode
Remote Mode
Auto Mode
OVUV Control Status
84
85
86
87
88
54
55
56
57
58
1
1
1
1
1
Set when remote close command received during reclose delay time indicating that the close command will be ignored. Cleared when reclose delay time expires.
Indicates CBC is in Manual mode. Mutually exclusive with respect to Auto and Remote mode (i.e. only one mode allowed at a time).
Indicates CBC is in Remote mode. Mutually exclusive with respect to Auto and Manual mode (i.e. only one mode allowed at a time).
Indicates CBC is in Auto mode. Mutually exclusive with respect to Manual and Remote mode (i.e. only one mode allowed at a time).
Indicates status of Season 1, Season 2, or non-seasonal OVUV control setting. Does not indicate comms loss control status or CVR control status.
Page 3
Binary Inputs
CBC-8000 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Point Name
Default Static Variation
Obj 01 Var 1 Binary Input – Packed format
Default Event Variation
Obj 02 Var 1 Binary Input Event – Without time (with time stamps disabled in configuration)
Obj 02 Var 2 Binary Input Event – With absolute time (with time stamps enabled in configuration)
Default
Event Description
Class
Indicates status of Season 1, Season 2, or non-seasonal VAR control setting. Does not indicate comms loss control status.
1
Indicates status of Season 1, Season 2, or non-seasonal Time control setting. Does not indicate comms loss control status.
1
Index
Hex Index
VAR Control Status
Time Control Status
89
90
59
5A
Temperature Control Status
91
5B
1
Ignore SCADA Override Clear Time
In Daylight Savings
Bank Tripped
Bank Closed
Va Control Status
Vb Control Status
Vc Control Status
Ia Control Status
Ib Control Status
Ic Control Status
OVUV Comms Loss Ctrl Status
VAR Comms Loss Ctrl Status
Temp Comms Loss Ctrl Status
Va Comms Loss Ctrl Status
Vb Comms Loss Ctrl Status
Vc Comms Loss Ctrl Status
Ia Comms Loss Ctrl Status
Ib Comms Loss Ctrl Status
Ic Comms Loss Ctrl Status
Time Comms Loss Ctrl Status
Phase AB Voltage High Alarm
Phase AB Voltage Low Alarm
Phase BC Voltage High Alarm
Phase BC Voltage Low Alarm
Phase CA Voltage High Alarm
Phase CA Voltage Low Alarm
Phase Voltage Unbalance % Alarm
Phase A Current Sensor on Load Side
Phase B Current Sensor on Load Side
Phase C Current Sensor on Load Side
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
5C
5D
5E
5F
60
61
62
63
64
65
66
67
68
69
6A
6B
6C
6D
6E
6F
70
71
72
73
74
75
76
77
78
79
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Indicates status of temperature control actions. 0 if both min and max threshold actions are set to none, else 1. Applies to the appropriate season when seasonal control
enabled. Season 1 actions apply when seasonal control disabled.
Indicates the status of the ignore SCADA override clear time setting.
Set if CBC local time is in Daylight savings period and DST support is enabled.
Indicates capacitor bank is tripped. Mutually exclusive with respect to Bank Closed status point.
Indicates capacitor bank is closed. Mutually exclusive with respect to Bank Tripped status point.
Indicates status of Va control actions. 0 if both min and max threshold actions are set to none, else 1.
Indicates status of Vb control actions. 0 if both min and max threshold actions are set to none, else 1.
Indicates status of Vc control actions. 0 if both min and max threshold actions are set to none, else 1.
Indicates status of Ia control actions. 0 if both min and max threshold actions are set to none, else 1.
Indicates status of Ib control actions. 0 if both min and max threshold actions are set to none, else 1.
Indicates status of Ic control actions. 0 if both min and max threshold actions are set to none, else 1.
Indicates status of comms loss control setting.
Indicates status of comms loss control setting.
Indicates status of comms loss control setting.
Indicates status of comms loss control setting.
Indicates status of comms loss control setting.
Indicates status of comms loss control setting.
Indicates status of comms loss control setting.
Indicates status of comms loss control setting.
Indicates status of comms loss control setting.
Indicates status of comms loss control setting.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Tied to ProView NXG Data Alarm.
Indicates Phase A sensor location. 0 = Source, 1 = Load.
Indicates Phase B sensor location. 0 = Source, 1 = Load.
Indicates Phase C sensor location. 0 = Source, 1 = Load.
Page 4
Binary Inputs
CBC-8000 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Counters
Point Name
Total Operations Count
OV Operations Count
UV Operations Count
Close Operation Count
Trip Operation Count
Daily Operation Count
Default Static Variation
Obj 20 Var 2 Counter – 16-bit with flag
Default Event Variation
Obj 22, see table for varation
Index
Hex Index
Default
Event
Class
Associated
Obj 34 Analog Deadband
00
01
02
03
04
05
00
01
02
03
04
05
-
AD-035
AD-036
AD-037
AD-038
AD-039
AD-040
Obj 32 Default Obj 32 Default
Variation (time Variation (time
stamp disabled) stamp enabled)
2
2
2
2
2
2
Page 5
6
6
6
6
6
6
Counters
CBC-8000 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
INPUT SUBSYSTEM
Analog Inputs
Default Static Variation
Obj 30, see table for variation
Default Event Variation
Obj 32, see table for varation
Default
Division
Event
Scale Factor
Class
Obj 32 Default Obj 32 Default
Variation (time Variation (time
stamp disabled) stamp enabled)
Units
Associated
Obj 34 Analog Deadband
Obj 30 Default
Variation
1
1
1
1
10
10
-Lookup
--Degrees
Volts
-----AD-000
1
2
2
2
2
2
-----2
-----4
-Reason For Last Control
-----
-
10
Volts
--
2
--
--
--
07
-
10
Volts
--
2
--
--
--
08
09
10
08
09
0A
-
10
10
10
Volts
Volts
Amps
----
2
2
2
----
----
----
Average Line Voltage
11
0B
-
10
Volts
--
2
--
--
--
Line Voltage Total
Line Voltage Fundamental
Line Voltage 3rd Harmonic
Line Voltage 5th Harmonic
Line Voltage 7th Harmonic
Line Voltage 9th Harmonic
Line Voltage 11th Harmonic
Line Voltage 13th Harmonic
Line Voltage THD
NC Fundamental
NC Total
NC 3rd Harmonic
NC 5th Harmonic
NC 7th Harmonic
NC 9th Harmonic
NC 11th Harmonic
NC 13th Harmonic
NC THD
VAR kW
VAR kVA
VAR kVARs
VAR Power Factor
VAR Total Current
VAR Fundamental Current
VAR Fundamental Voltage
VAR Fundamental Phase
Va Secondary
Vb Secondary
Vc Secondary
Ia
Ib
Ic
Phase A Total Voltage
Phase A Fundamental Voltage
Phase A Voltage 3rd Harmonic
Phase A Voltage 5th Harmonic
Phase A Voltage 7th Harmonic
Phase A Voltage 9th Harmonic
Phase A Voltage 11th Harmonic
Phase A Voltage 13th Harmonic
Phase A Voltage THD
Phase A Total Current
Phase A Fundamental Current
Phase A Current 3rd Harmonic
Phase A Current 5th Harmonic
Phase A Current 7th Harmonic
Phase A Current 9th Harmonic
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
3A
1
1
1
1
1
1
1
10
10
10
10
10
10
10
10
1
10
10
10
10
10
10
10
10
1
1
1
1
1000
1
1
1
1
10
10
10
10
10
10
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
%
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
%
kW
kVA
kVAR
-Amps
Amps
Volts
Degrees
Volts
Volts
Volts
Amps
Amps
Amps
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
%
Amps
Amps
Amps
Amps
Amps
Amps
AD-001
AD-002
-------AD-003
AD-004
-------AD-005
-AD-006
AD-007
----AD-008
AD-009
AD-010
AD-011
AD-012
AD-013
AD-014
AD-015
-------AD-016
AD-017
-----
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
-------2
2
-------2
2
2
----2
2
2
2
2
2
2
2
-------2
2
-----
4
4
-------4
4
-------4
4
4
----4
4
4
4
4
4
4
4
-------4
4
-----
------------------------------------------------
Point Name
Index
Hex Index
Serial Number
Last Control Reason
Firmware Major Revision
Firmware Minor Revision
Temperature
Average Delta Voltage
00
01
02
03
04
05
00
01
02
03
04
05
1
Average High Voltage
06
06
Average Low Voltage
07
Frozen Average High Voltage
Frozen Average Low Voltage
NC Fault Current
1
1
1
1
1
1
1
1
1
1
-
Page 6
Enumeration Table
(See MN916003EN)
Description
High nibble is the major version number, low nibble is the minor version number.
Lowest value in the overall FW revision: Major.Minor.Version
Average change in voltage due to an operation.
Uses a window average based on the Line Voltage Average Time setting (same setting
as Hi/Lo Average Time on HMI and ProView NXG).
Uses a window average based on the Line Voltage Average Time setting (same setting
as Hi/Lo Average Time on HMI and ProView NXG).
NC current value at time of lockout.
Uses a window average based on the Line Voltage Average Time setting (same setting
as Hi/Lo Average Time on HMI and ProView NXG).
Analog Inputs
CBC-8000 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
INPUT SUBSYSTEM
Analog Inputs
Default Static Variation
Obj 30, see table for variation
Point Name
Index
Hex Index
Phase A Current 11th Harmonic
Phase A Current 13th Harmonic
Phase A Current THD
Phase A Power Factor
Phase A kW
Phase A kVA
Phase A kVARs
Phase A VI Phase
Phase B Total Voltage
Phase B Fundamental Voltage
Phase B Voltage 3rd Harmonic
Phase B Voltage 5th Harmonic
Phase B Voltage 7th Harmonic
Phase B Voltage 9th Harmonic
Phase B Voltage 11th Harmonic
Phase B Voltage 13th Harmonic
Phase B Voltage THD
Phase B Total Current
Phase B Fundamental Current
Phase B Current 3rd Harmonic
Phase B Current 5th Harmonic
Phase B Current 7th Harmonic
Phase B Current 9th Harmonic
Phase B Current 11th Harmonic
Phase B Current 13th Harmonic
Phase B Current THD
Phase B Power Factor
Phase B kW
Phase B kVA
Phase B kVARs
Phase B VI Phase
Phase C Total Voltage
Phase C Fundamental Voltage
Phase C Voltage 3rd Harmonic
Phase C Voltage 5th Harmonic
Phase C Voltage 7th Harmonic
Phase C Voltage 9th Harmonic
Phase C Voltage 11th Harmonic
Phase C Voltage 13th Harmonic
Phase C Voltage THD
Phase C Total Current
Phase C Fundamental Current
Phase C Current 3rd Harmonic
Phase C Current 5th Harmonic
Phase C Current 7th Harmonic
Phase C Current 9th Harmonic
Phase C Current 11th Harmonic
Phase C Current 13th Harmonic
Phase C Current THD
Phase C Power Factor
Phase C kW
Phase C kVA
Phase C kVARs
Phase C VI Phase
Reason for Ignored Control
Single Phase Delta KVAR
Phase A Delta KVAR
Phase B Delta KVAR
Phase C Delta KVAR
3 Phase Total Delta KVAR
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
3B
3C
3D
3E
3F
40
41
42
43
44
45
46
47
48
49
4A
4B
4C
4D
4E
4F
50
51
52
53
54
55
56
57
58
59
5A
5B
5C
5D
5E
5F
60
61
62
63
64
65
66
67
68
69
6A
6B
6C
6D
6E
6F
70
71
72
73
74
75
76
24-hour Average High Voltage
119
77
Default Event Variation
Obj 32, see table for varation
Default
Division
Event
Scale Factor
Class
1
1
1
1
1000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1000
1
1
1
1
1
1
1
1
1
1
1
1
-
10
Units
Associated
Obj 34 Analog Deadband
Obj 30 Default
Variation
Amps
Amps
%
-kW
kVA
kVAR
Degrees
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
%
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
%
-kW
kVA
kVAR
Degrees
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
%
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
%
-kW
kVA
kVAR
Degrees
Lookup
kVAR
kVAR
kVAR
kVAR
kVAR
---AD-018
AD-019
-AD-020
-AD-021
AD-022
-------AD-023
AD-024
-------AD-025
AD-026
-AD-027
-AD-028
AD-029
-------AD-030
AD-031
-------AD-032
AD-033
-AD-034
--------
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volts
--
2
Obj 32 Default Obj 32 Default
Enumeration Table
Variation (time Variation (time
Description
(See MN916003EN)
stamp disabled) stamp enabled)
---------2
4
-2
4
----2
4
----2
4
-2
4
----------------------2
4
-2
4
----------------------2
4
-2
4
----2
4
----2
4
-2
4
----------------------2
4
-2
4
----------------------2
4
-2
4
----2
4
------Reason for Ignored Control
----------------
Page 7
--
--
--
Uses a window average based on the Line Voltage Average Time setting (same setting
as Hi/Lo Average Time on HMI and ProView NXG).
Analog Inputs
CBC-8000 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
INPUT SUBSYSTEM
Analog Inputs
Default Static Variation
Obj 30, see table for variation
Default Event Variation
Obj 32, see table for varation
Default
Division
Event
Scale Factor
Class
Obj 32 Default Obj 32 Default
Variation (time Variation (time
stamp disabled) stamp enabled)
Units
Associated
Obj 34 Analog Deadband
Obj 30 Default
Variation
10
Volts
--
2
--
--
--
-
1
1
1
1
1
1
1
1
1
1
10
1
1
1
1
1
1
1
1
1
Lookup
% % % Volts
Degrees Volts
Degrees Volts
Degrees % ----------
---------------------
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
---------------------
---------------------
Bank Confirmation Status
--------------------
8D
-
1
--
--
2
--
--
--
142
8E
-
1
--
--
2
--
--
CBC Build Month & Day
143
8F
-
1
--
--
2
--
--
--
CBC Build Year
SelectComm Major Version
SelectComm Minor Version
SelectComm Rev Version
144
145
146
147
90
91
92
93
-
1
1
1
1
-----
-----
2
2
2
2
-----
-----
-----
SelectComm Full Version
148
94
-
1
--
--
2
--
--
--
SelectComm Build Date
149
95
-
1
--
--
2
--
--
SelectComm Build Month & Day
150
96
-
1
--
--
2
--
--
--
SelectComm Build Year
151
97
-
1
--
--
2
--
--
---
Point Name
Index
Hex Index
24-hour Average Low Voltage
120
78
-
Bank Confirmation Status
Phase A Delta KVAR Percent
Phase B Delta KVAR Percent
Phase C Delta KVAR Percent
Phase AB Voltage
Phase AB Angle
Phase BC Voltage
Phase BC Angle
Phase CA Voltage
Phase CA Angle
Phase Unbalance Percent
Total Operations Count
OV Operations Count
UV Operations Count
Close Operation Count
Trip Operation Count
Daily Operation Count
CBC Major Version
CBC Minor Version
CBC Rev Version
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
79
7A
7B
7C
7D
7E
7F
80
81
82
83
84
85
86
87
88
89
8A
8B
8C
CBC Full Version
141
CBC Build Date
Page 8
Enumeration Table
(See MN916003EN)
Description
Uses a window average based on the Line Voltage Average Time setting (same setting
as Hi/Lo Average Time on HMI and ProView NXG).
Matches the Binary counter of the same name
Matches the Binary counter of the same name
Matches the Binary counter of the same name
Matches the Binary counter of the same name
Matches the Binary counter of the same name
Matches the Binary counter of the same name
CBC version X value in X.Y.Z version
CBC version Y value in X.Y.Z version
CBC version Z value in X.Y.Z version
Complete CBC version x.y.z value where x is highest nibble, y is next highest nibble,
and z is low byte.
NXG Firmware Build Date Complete CBC code build date coded in a set of bit fields
CBC build month and day of month where month is highest byte and day of month is
lowest byte
CBC build year
SelectComm version X value in X.Y.Z version
SelectComm version Y value in X.Y.Z version
SelectComm version Z value in X.Y.Z version
Complete SelectComm version x.y.z value where x is highest nibble, y is next highest
nibble, and z is low byte.
NXG Firmware Build Date Complete SelectComm code build date coded in a set of bit fields
SelectComm build month and day of month where month is highest byte and day of
month is lowest byte
SelectComm build year
Analog Inputs
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Deadbands
Point Name
Avg Delta Voltage
Line Voltage Total
Line Voltage Fundamental
NC Fundamental
NC Total
Three Phase kW
Three Phase kVAR
Three Phase Power Factor
Va Secondary
Vb Secondary
Vc Secondary
Ia
Ib
Ic
Phase A Total Voltage
Phase A Fundamental Voltage
Phase A Total Current
Phase A Fundamental Current
Phase A Power Factor
Phase A kW
Phase A kVAR
Phase B Total Voltage
Phase B Fundamental Voltage
Phase B Total Current
Phase B Fundamental Current
Phase B Power Factor
Phase B kW
Phase B kVAR
Phase C Total Voltage
Phase C Fundamental Voltage
Phase C Total Current
Phase C Fundamental Current
Phase C Power Factor
Phase C kW
Phase C kVAR
Default Static Variation
Obj 34 Var 1 Analog Input Deadband – 16-bit
Index
Hex Index
Division
Scale Factor
Units
Associated
Obj 22/32 Input
Object
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
10
10
10
10
10
1
1
1000
10
10
10
10
10
10
1
1
1
1
1000
1
1
1
1
1
1
1000
1
1
1
1
1
1
1000
1
1
Volts
Volts
Volts
Amps
Amps
kW
kVAR
-Volts
Volts
Volts
Amps
Amps
Amps
Volts
Volts
Amps
Amps
-kW
kVAR
Volts
Volts
Amps
Amps
-kW
kVAR
Volts
Volts
Amps
Amps
-kW
kVAR
AI-005
AI-012
AI-013
AI-021
AI-022
AI-030
AI-032
AI-033
AI-038
AI-039
AI-040
AI-041
AI-042
AI-043
AI-044
AI-045
AI-053
AI-054
AI-062
AI-063
AI-065
AI-067
AI-068
AI-076
AI-077
AI-085
AI-086
AI-088
AI-090
AI-091
AI-099
AI-100
AI-108
AI-109
AI-111
Page 9
Analog Deadbands
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Deadbands
Point Name
Total Operations Count
OV Operations Count
UV Operations Count
Close Operation Count
Trip Operation Count
Daily Operation Count
Temperature
Average Line Voltage
Line Voltage THD
NC THD
VAR kVA
VAR Total Current
VAR Fundamental Current
VAR Fundamental Voltage
Phase A Voltage THD
Phase A Current THD
Phase A kVA
Phase B Voltage THD
Phase B Current THD
Phase B kVA
Phase C Voltage THD
Phase C Current THD
Phase C kVA
Single Phase Delta KVAR
Phase A Delta KVAR
Phase B Delta KVAR
Phase C Delta KVAR
3 Phase Total Delta KVAR
Phase AB Voltage
Phase AB Angle
Phase BC Voltage
Phase BC Angle
Phase CA Voltage
Phase CA Angle
Phase Unbalance Percent
Default Static Variation
Obj 34 Var 1 Analog Input Deadband – 16-bit
Index
Hex Index
Division
Scale Factor
Units
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
40
41
42
43
44
45
1
1
1
1
1
1
0.1
0.1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0.1
------Degrees
Volts
%
%
kVA
Amps
Amps
Volts
%
%
kVA
%
%
kVA
%
%
kVA
kVAR
kVAR
kVAR
kVAR
kVAR
Volts
Degrees
Volts
Degrees
Volts
Degrees
%
Page 10
Associated
Obj 22/32 Input
Object
AI-132, CI-000
AI-133, CI-001
AI-134, CI-002
AI-135, CI-003
AI-136, CI-004
AI-137, CI-005
AI-004
AI-011
AI-020
AI-029
AI-031
AI-034
AI-035
AI-036
AI-052
AI-061
AI-064
AI-075
AI-084
AI-087
AI-098
AI-107
AI-110
AI-114
AI-115
AI-116
AI-117
AI-118
AI-125
AI-126
AI-127
AI-128
AI-129
AI-130
AI-131
Analog Deadbands
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Point Name
Season 1 OV Threshold
Season 1 UV Threshold
Season 1 OV Track Time
Season 1 UV Track Time
Daily Auto Control Limit
Auto Close Delay
Manual Close Delay
Manual Trip Delay
Bank Operate Time
Reclose Delay
Comms Loss Time
CVR OV Threshold
CVR UV Threshold
CVR Disable Time
Emergency OV Threshold
Emergency UV Threshold
Emergency Voltage Track Time
Comms Loss OV Threshold
Comms Loss UV Threshold
Line Voltage Average Time
Season 2 OV Threshold
Season 2 UV Threshold
Season 2 OV Track Time
Season 2 UV Track Time
Unused - Deprecated
Random Voltage Time
Adaptive Voltage Hysteresis
Delta Voltage Percent
Delta Voltage Sample Count
Season 1 VAR Trip Threshold
Season 1 VAR Close Threshold
Season 1 VAR Track Time
Season 2 VAR Trip Threshold
Season 2 VAR Close Threshold
Season 2 VAR Track Time
VAR Sensor Phase Adjust
VAR Bank Size
Voltage Control Priority
VAR Control Priority
Temperature Control Priority
Va Control Priority
Vb Control Priority
Vc Control Priority
Ia Control Priority
Ib Control Priority
Ic Control Priority
Va Minimum Threshold
Default Static Variation
Obj 40 Var 2 Analog Output Status – 16-bit with flag
Default Event Variation
None Supported
Index
Hex Index
Division
Scale Factor
Units
Enumeration Table
(See MN916003EN)
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
10
10
1
1
1
1
1
1
1
1
1
10
10
1
10
10
1
10
10
1
10
10
1
1
-1
10
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10
Volts
Volts
Seconds
Seconds
-Seconds
Seconds
Seconds
Seconds
Minutes
Minutes
Volts
Volts
Minutes
Volts
Volts
Seconds
Volts
Volts
Seconds
Volts
Volts
Seconds
Seconds
-Minutes
Volts
%
KVAR
KVAR
KVAR
Seconds
KVAR
KVAR
Seconds
Degrees
KVAR
---------Volts
------------------------------------------------
Page 11
Description
Number of operations to average over for determining average delta voltage.
Analog Outputs
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Point Name
Va Maximum Threshold
Va Minimum Hysteresis
Va Maximum Hysteresis
Va Minimum Track Time
Va Maximum Track Time
Va Minimum Action
Va Maximum Action
Vb Minimum Threshold
Vb Maximum Threshold
Vb Minimum Hysteresis
Vb Maximum Hysteresis
Vb Minimum Track Time
Vb Maximum Track Time
Vb Minimum Action
Vb Maximum Action
Vc Minimum Threshold
Vc Maximum Threshold
Vc Minimum Hysteresis
Vc Maximum Hysteresis
Vc Minimum Track Time
Vc Maximum Track Time
Vc Minimum Action
Vc Maximum Action
Ia Minimum Threshold
Ia Maximum Threshold
Ia Minimum Hysteresis
Ia Maximum Hysteresis
Ia Minimum Track Time
Ia Maximum Track Time
Ia Minimum Action
Ia Maximum Action
Ib Minimum Threshold
Ib Maximum Threshold
Ib Minimum Hysteresis
Ib Maximum Hysteresis
Ib Minimum Track Time
Ib Maximum Track Time
Ib Minimum Action
Ib Maximum Action
Ic Minimum Threshold
Ic Maximum Threshold
Ic Minimum Hysteresis
Ic Maximum Hysteresis
Ic Minimum Track Time
Ic Maximum Track Time
Ic Minimum Action
Ic Maximum Action
Season 1 Month
Default Static Variation
Obj 40 Var 2 Analog Output Status – 16-bit with flag
Default Event Variation
None Supported
Index
Hex Index
Division
Scale Factor
Units
Enumeration Table
(See MN916003EN)
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
40
41
42
43
44
45
46
47
48
49
4A
4B
4C
4D
4E
4F
50
51
52
53
54
55
56
57
58
59
5A
5B
5C
5D
5E
10
10
10
1
1
1
1
10
10
10
10
1
1
1
1
10
10
10
10
1
1
1
1
10
10
10
10
1
1
1
1
10
10
10
10
1
1
1
1
10
10
10
10
1
1
1
1
1
Volts
Volts
Volts
Seconds
Seconds
Lookup
Lookup
Volts
Volts
Volts
Volts
Seconds
Seconds
Lookup
Lookup
Volts
Volts
Volts
Volts
Seconds
Seconds
Lookup
Lookup
Amps
Amps
Amps
Amps
Seconds
Seconds
Lookup
Lookup
Amps
Amps
Amps
Amps
Seconds
Seconds
Lookup
Lookup
Amps
Amps
Amps
Amps
Seconds
Seconds
Lookup
Lookup
--
-----Action
Action
------Action
Action
------Action
Action
------Action
Action
------Action
Action
------Action
Action
--
Page 12
Description
0=Disable, 1=January, etc.
Analog Outputs
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Point Name
Season 1 Day of Month
Season 2 Month
Season 2 Day of Month
Season 1 ON Time
Season 1 OFF Time
Season 1 Weekend ON Time
Season 1 Weekend OFF Time
Season 2 ON Time
Season 2 OFF Time
Season 2 Weekend ON Time
Season 2 Weekend OFF Time
Season 1 OFF Time State
Season 2 OFF Time State
Line Voltage High Alarm Threshold
Line Voltage Low Alarm Threshold
Line Voltage Alarm Threshold High Time
Line Voltage Alarm Threshold Low Time
Line Voltage THD Alarm Threshold
Line Voltage THD Alarm Threshold Time
VAR kVAR Lag Alarm Threshold
VAR kVAR Lead Alarm Threshold
VAR kVAR Lag Alarm Threshold Time
VAR kVAR Lead Alarm Threshold Time
VAR kW High Alarm Threshold
VAR kW Low Alarm Threshold
VAR kW High Alarm Threshold Time
VAR kW Low Alarm Threshold Time
VAR Leading PF Alarm Threshold
VAR Lagging PF Alarm Threshold
VAR Lagging PF Alarm Threshold Time
VAR Leading PF Alarm Threshold Time
Temperature High Alarm Threshold
Temperature Low Alarm Threshold
Temperature High Alarm Threshold Time
Temperature Low Alarm Threshold Time
Va High Alarm Threshold
Va Low Alarm Threshold
Va High Alarm Threshold Time
Va Low Alarm Threshold Time
Vb High Alarm Threshold
Vb Low Alarm Threshold
Vb High Alarm Threshold Time
Vb Low Alarm Threshold Time
Vc High Alarm Threshold
Vc Low Alarm Threshold
Vc High Alarm Threshold Time
Vc Low Alarm Threshold Time
Ia High Alarm Threshold
Default Static Variation
Obj 40 Var 2 Analog Output Status – 16-bit with flag
Default Event Variation
None Supported
Index
Hex Index
Division
Scale Factor
Units
Enumeration Table
(See MN916003EN)
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
5F
60
61
62
63
64
65
66
67
68
69
6A
6B
6C
6D
6E
6F
70
71
72
73
74
75
76
77
78
79
7A
7B
7C
7D
7E
7F
80
81
82
83
84
85
86
87
88
89
8A
8B
8C
8D
8E
1
1
1
1
1
1
1
1
1
1
1
1
1
10
10
1
1
1
1
1
1
1
1
1
1
1
1
1000
1000
1
1
10
10
1
1
10
10
1
1
10
10
1
1
10
10
1
1
10
---Minutes
Minutes
Minutes
Minutes
Minutes
Minutes
Minutes
Minutes
Lookup
Lookup
Volts
Volts
Seconds
Seconds
%
Seconds
KVAR
KVAR
Seconds
Seconds
KW
KW
Seconds
Seconds
--Seconds
Seconds
Degrees
Degrees
Seconds
Seconds
Volts
Volts
Seconds
Seconds
Volts
Volts
Seconds
Seconds
Volts
Volts
Seconds
Seconds
Amps
-----------Time State
Time State
------------------------------------
Page 13
Description
0=Disable
0=Disable, 1=January, etc.
0=Disable
Time of Day. 1042 minutes = 17:22 (HH:MM).
Time of Day. 1042 minutes = 17:22 (HH:MM).
Time of Day. 1042 minutes = 17:22 (HH:MM).
Time of Day. 1042 minutes = 17:22 (HH:MM).
Time of Day. 1042 minutes = 17:22 (HH:MM).
Time of Day. 1042 minutes = 17:22 (HH:MM).
Time of Day. 1042 minutes = 17:22 (HH:MM).
Time of Day. 1042 minutes = 17:22 (HH:MM).
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Analog Outputs
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Point Name
Ia Low Alarm Threshold
Ia High Alarm Threshold Time
Ia Low Alarm Threshold Time
Ib High Alarm Threshold
Ib Low Alarm Threshold
Ib High Alarm Threshold Time
Ib Low Alarm Threshold Time
Ic High Alarm Threshold
Ic Low Alarm Threshold
Ic High Alarm Threshold Time
Ic Low Alarm Threshold Time
NC Fundamental Alarm Threshold
NC Fundamental Alarm Threshold Time
NC Total Alarm Threshold
NC Total Alarm Threshold Time
NC THD Alarm Threshold
NC THD Alarm Threshold Time
Phase A Total Voltage High Alarm Threshold
Phase A Total Voltage Low Alarm Threshold
Phase A Total Voltage High Alarm Threshold Time
Phase A Total Voltage Low Alarm Threshold Time
Phase A Voltage THD Alarm Threshold
Phase A Voltage THD Alarm Threshold Time
Phase A Total Current Alarm Threshold
Phase A Total Current Alarm Threshold Time
Phase A Current THD Alarm Threshold
Phase A Current THD Alarm Threshold Time
Phase A Leading PF Alarm Threshold
Phase A Lagging PF Alarm Threshold
Phase A Lagging PF Alarm Threshold Time
Phase A Leading PF Alarm Threshold Time
Phase A kW High Alarm Threshold
Phase A kW Low Alarm Threshold
Phase A kW High Alarm Threshold Time
Phase A kW Low Alarm Threshold Time
Phase A kVAR Lag Alarm Threshold
Phase A kVAR Lead Alarm Threshold
Phase A kVAR Lag Alarm Threshold Time
Phase A kVAR Lead Alarm Threshold Time
Phase B Total Voltage High Alarm Threshold
Phase B Total Voltage Low Alarm Threshold
Phase B Total Voltage High Alarm Threshold Time
Phase B Total Voltage Low Alarm Threshold Time
Phase B Voltage THD Alarm Threshold
Phase B Voltage THD Alarm Threshold Time
Phase B Total Current Alarm Threshold
Phase B Total Current Alarm Threshold Time
Phase B Current THD Alarm Threshold
Default Static Variation
Obj 40 Var 2 Analog Output Status – 16-bit with flag
Default Event Variation
None Supported
Index
Hex Index
Division
Scale Factor
Units
Enumeration Table
(See MN916003EN)
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
8F
90
91
92
93
94
95
96
97
98
99
9A
9B
9C
9D
9E
9F
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
AA
AB
AC
AD
AE
AF
B0
B1
B2
B3
B4
B5
B6
B7
B8
B9
BA
BB
BC
BD
BE
10
1
1
10
10
1
1
10
10
1
1
10
1
10
1
1
1
1
1
1
1
1
1
1
1
1
1
1000
1000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Amps
Seconds
Seconds
Amps
Amps
Seconds
Seconds
Amps
Amps
Seconds
Seconds
Amps
Seconds
Amps
Seconds
%
Seconds
Volts
Volts
Seconds
Seconds
%
Seconds
Amps
Seconds
Amps
Seconds
--Seconds
Seconds
KW
KW
Seconds
Seconds
KVAR
KVAR
Seconds
Seconds
Volts
Volts
Seconds
Seconds
%
Seconds
Amps
Seconds
Amps
-------------------------------------------------
Page 14
Description
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Analog Outputs
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Point Name
Phase B Current THD Alarm Threshold Time
Phase B Leading PF Alarm Threshold
Phase B Lagging PF Alarm Threshold
Phase B Lagging PF Alarm Threshold Time
Phase B Leading PF Alarm Threshold Time
Phase B kW High Alarm Threshold
Phase B kW Low Alarm Threshold
Phase B kW High Alarm Threshold Time
Phase B kW Low Alarm Threshold Time
Phase B kVAR Lag Alarm Threshold
Phase B kVAR Lead Alarm Threshold
Phase B kVAR Lag Alarm Threshold Time
Phase B kVAR Lead Alarm Threshold Time
Phase C Total Voltage High Alarm Threshold
Phase C Total Voltage Low Alarm Threshold
Phase C Total Voltage High Alarm Threshold Time
Phase C Total Voltage Low Alarm Threshold Time
Phase C Voltage THD Alarm Threshold
Phase C Voltage THD Alarm Threshold Time
Phase C Total Current Alarm Threshold
Phase C Total Current Alarm Threshold Time
Phase C Current THD Alarm Threshold
Phase C Current THD Alarm Threshold Time
Phase C Leading PF Alarm Threshold
Phase C Lagging PF Alarm Threshold
Phase C Lagging PF Alarm Threshold Time
Phase C Leading PF Alarm Threshold Time
Phase C kW High Alarm Threshold
Phase C kW Low Alarm Threshold
Phase C kW High Alarm Threshold Time
Phase C kW Low Alarm Threshold Time
Phase C kVAR Lag Alarm Threshold
Phase C kVAR Lead Alarm Threshold
Phase C kVAR Lag Alarm Threshold Time
Phase C kVAR Lead Alarm Threshold Time
VAR Power Flow Time
Phase A Power Flow Time
Phase B Power Flow Time
Phase C Power Flow Time
Season 1 Temperature Minimum Threshold
Season 1 Temperature Maximum Threshold
Season 1 Temperature Minimum Hysteresis
Season 1 Temperature Maximum Hysteresis
Season 1 Temperature Minimum Track Time
Season 1 Temperature Maximum Track Time
Season 1 Minimum Action
Season 1 Maximum Action
Season 2 Temperature Minimum Threshold
Default Static Variation
Obj 40 Var 2 Analog Output Status – 16-bit with flag
Default Event Variation
None Supported
Index
Hex Index
Division
Scale Factor
Units
Enumeration Table
(See MN916003EN)
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
BF
C0
C1
C2
C3
C4
C5
C6
C7
C8
C9
CA
CB
CC
CD
CE
CF
D0
D1
D2
D3
D4
D5
D6
D7
D8
D9
DA
DB
DC
DD
DE
DF
E0
E1
E2
E3
E4
E5
E6
E7
E8
E9
EA
EB
EC
ED
EE
1
1000
1000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1000
1000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10
10
10
10
1
1
1
1
10
Seconds
--Seconds
Seconds
KW
KW
Seconds
Seconds
KVAR
KVAR
Seconds
Seconds
Volts
Volts
Seconds
Seconds
%
Seconds
Amps
Seconds
Amps
Seconds
--Seconds
Seconds
KW
KW
Seconds
Seconds
KVAR
KVAR
Seconds
Seconds
Seconds
Seconds
Seconds
Seconds
Degrees
Degrees
Degrees
Degrees
Seconds
Seconds
Lookup
Lookup
Degrees
---------------------------------------------Action
Action
--
Page 15
Description
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Status Alarm Setting in ProView NXG.
Status Alarm Setting in ProView NXG.
Status Alarm Setting in ProView NXG.
Status Alarm Setting in ProView NXG.
Analog Outputs
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Point Name
Season 2 Temperature Maximum Threshold
Season 2 Temperature Minimum Hysteresis
Season 2 Temperature Maximum Hysteresis
Season 2 Temperature Minimum Track Time
Season 2 Temperature Maximum Track Time
Season 2 Minimum Action
Season 2 Maximum Action
NC Fault Control Threshold
NC Fault Control Track Time
NC Fault Control Hysteresis
NC Verification Setpoint
NC Verification Retry Count
SCADA Override Release Time
Time Zone
VAR Power Flow Alarm Flags
Phase A Power Flow Alarm Flags
Phase B Power Flow Alarm Flags
Phase C Power Flow Alarm Flags
Line Voltage High Alarm Flags
Line Voltage Low Alarm Flags
Line Voltage THD Alarm Flags
VAR kVAR Lag Alarm Flags
VAR kVAR Lead Alarm Flags
VAR kW High Alarm Flags
VAR kW Low Alarm Flags
VAR Leading PF Alarm Flags
VAR Lagging PF Alarm Flags
Temperature High Alarm Flags
Temperature Low Alarm Flags
Va High Alarm Flags
Va Low Alarm Flags
Vb High Alarm Flags
Vb Low Alarm Flags
Vc High Alarm Flags
Vc Low Alarm Flags
Ia High Alarm Flags
Ia Low Alarm Flags
Ib High Alarm Flags
Ib Low Alarm Flags
Ic High Alarm Flags
Ic Low Alarm Flags
NC Total Alarm Flags
NC Fundamental Alarm Flags
NC THD Alarm Flags
Phase A Total Voltage High Alarm Flags
Phase A Total Voltage Low Alarm Flags
Phase A Voltage THD Alarm Flags
Phase A Total Current Alarm Flags
Default Static Variation
Obj 40 Var 2 Analog Output Status – 16-bit with flag
Default Event Variation
None Supported
Index
Hex Index
Division
Scale Factor
Units
Enumeration Table
(See MN916003EN)
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
EF
F0
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
FE
FF
100
101
102
103
104
105
106
107
108
109
10A
10B
10C
10D
10E
10F
110
111
112
113
114
115
116
117
118
119
11A
11B
11C
11D
11E
10
10
10
1
1
1
1
10
1
10
10
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Degrees
Degrees
Degrees
Seconds
Seconds
Lookup
Lookup
Amps
Seconds
Amps
Amps
-Minutes
Minutes
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
-----Action
Action
-------Status Alarm Flags
Status Alarm Flags
Status Alarm Flags
Status Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Page 16
Description
Time of Day. 1042 minutes = 17:22 (HH:MM).
Number of minutes from GMT. (-) is east and (+) is west.
Status Alarm Setting in ProView NXG.
Status Alarm Setting in ProView NXG.
Status Alarm Setting in ProView NXG.
Status Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Analog Outputs
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Point Name
Phase A Current THD Alarm Flags
Phase A Leading PF Alarm Flags
Phase A Lagging PF Alarm Flags
Phase A kW High Alarm Flags
Phase A kW Low Alarm Flags
Phase A kVAR Lag Alarm Flags
Phase A kVAR Lead Alarm Flags
Phase B Total Voltage High Alarm Flags
Phase B Total Voltage Low Alarm Flags
Phase B Voltage THD Alarm Flags
Phase B Total Current Alarm Flags
Phase B Current THD Alarm Flags
Phase B Leading PF Alarm Flags
Phase B Lagging PF Alarm Flags
Phase B kW High Alarm Flags
Phase B kW Low Alarm Flags
Phase B kVAR Lag Alarm Flags
Phase B kVAR Lead Alarm Flags
Phase C Total Voltage High Alarm Flags
Phase C Total Voltage Low Alarm Flags
Phase C Voltage THD Alarm Flags
Phase C Total Current Alarm Flags
Phase C Current THD Alarm Flags
Phase C Leading PF Alarm Flags
Phase C Lagging PF Alarm Flags
Phase C kW High Alarm Flags
Phase C kW Low Alarm Flags
Phase C kVAR Lag Alarm Flags
Phase C kVAR Lead Alarm Flags
VAR Control Flags
Voltage Control Flags
Phase Input Control Flags 1
Phase Input Control Flags 2
Time Control Flags 1
Time Control Flags 2
Temperature Control Flags
NC Control Flags
Unused - Deprecated
Unused - Deprecated
Unused - Deprecated
Unused - Deprecated
Unused - Deprecated
Unused - Deprecated
Unused - Deprecated
Unused - Deprecated
Phase A Phase Adjust
Unused - Deprecated
Unused - Deprecated
Default Static Variation
Obj 40 Var 2 Analog Output Status – 16-bit with flag
Default Event Variation
None Supported
Index
Hex Index
Division
Scale Factor
Units
Enumeration Table
(See MN916003EN)
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
11F
120
121
122
123
124
125
126
127
128
129
12A
12B
12C
12D
12E
12F
130
131
132
133
134
135
136
137
138
139
13A
13B
13C
13D
13E
13F
140
141
142
143
144
145
146
147
148
149
14A
14B
14C
14D
14E
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
--------1
---
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
Lookup
--------Degrees
---
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
VAR Control Flags
Voltage Control Flags
Phase Control Flags Byte 1
Phase Control Flags Byte 2
Time Control Flags Byte 1
Time Control Flags Byte 2
Temperature Control Flags
Neutral Current Flags
------------
Page 17
Description
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Analog Outputs
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Point Name
Phase B Phase Adjust
Unused - Deprecated
Unused - Deprecated
Phase C Phase Adjust
Unused - Deprecated
Unused - Deprecated
VAR Current Input
VAR Voltage Input
Unused - Deprecated
Power Setup Flags
Select Timeout
Status Link Timeout
App Confirm Timeout
App Confirm Retries
Clock Valid time
Class 1 Min Events
Class 2 Min Events
Class 3 Min Events
Unsolicited Notification Delay Class1
Unsolicited Notification Delay Class2
Unsolicited Notification Delay Class3
Va Sensor Ratio
Ia Sensor Ratio
Vb Sensor Ratio
Ib Sensor Ratio
Vc Sensor Ratio
Ic Sensor Ratio
Line Voltage PT ratio
NC Sensor Ratio
24-hour Report Time
Delta KVAR Pass Percent
Phase AB High Alarm Threshold
Phase AB Low Alarm Threshold
Phase AB High Alarm Threshold Time
Phase AB Low Alarm Threshold Time
Phase BC High Alarm Threshold
Phase BC Low Alarm Threshold
Phase BC High Alarm Threshold Time
Phase BC Low Alarm Threshold Time
Phase CA High Alarm Threshold
Phase CA Low Alarm Threshold
Phase CA High Alarm Threshold Time
Phase CA Low Alarm Threshold Time
Phase Unbalance High Percent Threshold
Phase Unbalance High Percent Threshold Time
Phase AB High Alarm Flags
Phase AB Low Alarm Flags
Phase BC High Alarm Flags
Default Static Variation
Obj 40 Var 2 Analog Output Status – 16-bit with flag
Default Event Variation
None Supported
Index
Hex Index
Division
Scale Factor
Units
Enumeration Table
(See MN916003EN)
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
14F
150
151
152
153
154
155
156
157
158
159
15A
15B
15C
15D
15E
15F
160
161
162
163
164
165
166
167
168
169
16A
16B
16C
16D
16E
16F
170
171
172
173
174
175
176
177
178
179
17A
17B
17C
17D
17E
1
--1
--1
1
-1
1
1
1
1
1
1
1
1
1
1
1
1
10
1
10
1
10
10
10
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Degrees
--Degrees
-----Lookup
Seconds
Minutes
msX10
-Minutes
---msX10
msX10
msX10
--------Minutes % Volts Volts Seconds Seconds Volts Volts Seconds Seconds Volts Volts Seconds Seconds % Seconds Lookup
Lookup
Lookup
---------Power Setup Flags
-----------------------------------Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Page 18
Description
0="Phase A", 1="Phase B", 2="Phase C"
0="CBC Line", 1="Phase A", 2="Phase B", 3="Phase C"
DNP3 Select before operate time.
Applies only to Serial comms.
Time of Day. 1042 minutes = 17:22 (HH:MM).
Time of Day. 1042 minutes = 17:22 (HH:MM).
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Analog Outputs
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Default Static Variation
Obj 40 Var 2 Analog Output Status – 16-bit with flag
Default Event Variation
None Supported
Index
Hex Index
Division
Scale Factor
Units
Enumeration Table
(See MN916003EN)
Phase BC Low Alarm Flags
Phase CA High Alarm Flags
Phase CA Low Alarm Flags
Phase Unbalance Alarm Flags
Comms Logging Flags
383
384
385
386
387
17F
180
181
182
183
1
1
1
1
1
Lookup
Lookup
Lookup
Lookup
Lookup
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Data Alarm Flags
Comms Logging Flags
Auto Trip Delay
388
184
1
Seconds
--
Point Name
Page 19
Description
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Data Alarm Setting in ProView NXG.
Time delay before a trip operation when the operation is requested via remote command or local
auto control.
Analog Outputs
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status
Description
Index Hex Index Obj Var
Desc
Operation Type
Point Name
Description
Trip/Close SCADA Override Trip/Close Reset NC Lockout Clear Counters Clear High/Low Voltage Freeze High/Low Voltage Requests Trip or Close operation.
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
00
01
02
03
04
05
00
01
02
03
04
05
12
12
12
12
12
12
01
01
01
01
01
01
CROB
CROB
CROB
CROB
CROB
CROB
Pulse ON, Trip/Close; Latch ON/OFF, Null
Pulse ON, Trip/Close; Latch ON/OFF, Null
Pulse ON, Null
Pulse ON, Null
Pulse ON, Null
Pulse ON, Null
Binary Output
06
06
12 01
CROB
Pulse ON, Null
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
07
08
09
10
11
12
13
14
07
08
09
0A
0B
0C
0D
0E
12
12
12
12
12
12
12
12
01
01
01
01
01
01
01
01
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
Pulse ON, Null
Pulse ON, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Pulse ON, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Clear Average Delta Voltage Update Firmware CVR Mode Set Auto/Remote Mode Clear SCADA Override Enable Event Time Stamp Enable OVUV Control Enable VAR Control Binary Output
15
0F
12 01
CROB
Latch ON/OFF, Null
Enable Temp Control Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would
be set to none).
Binary Output
16
10
12 01
CROB
Latch ON/OFF, Null
Enable Va Control
Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would
be set to none).
Binary Output
17
11
12 01
CROB
Latch ON/OFF, Null
Enable Vb Control
Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would
be set to none).
Binary Output
18
12
12 01
CROB
Latch ON/OFF, Null
Enable Vc Control
Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would
be set to none).
Binary Output
19
13
12 01
CROB
Latch ON/OFF, Null
Enable Ia Control
Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would
be set to none).
Binary Output
20
14
12 01
CROB
Latch ON/OFF, Null
Enable Ib Control
Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would
be set to none).
Binary Output
21
15
12 01
CROB
Latch ON/OFF, Null
Enable Ic Control
Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would
be set to none).
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Pulse ON, Trip; Latch ON, Null
Pulse ON, Close; Latch ON, Null
Pulse ON, Trip; Latch ON, Null
Pulse ON, Close; Latch ON, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Binary Output
41
29
12 01
CROB
Binary Output
42
2A
12 01
Binary Output
43
2B
Binary Output
Binary Output
Binary Output
Binary Output
44
45
46
47
2C
2D
2E
2F
Freeze & Clear High/Low Voltage Requests SCADA override Trip or Close operation. Puts CBC into SCADA override mode.
Releases CBC from NC Lockout state.
Resets all binary counters to 0 and saves time stamp of clear operation.
Resets the average high and low voltages to 0 and saves time stamp of clear operation.
Copies average high and low voltages to frozen values.
Copies average high and low voltages to frozen values, resets average high and low voltages to 0, and saves time stamp of clear
operation.
Resets the average delta voltage and all operation delta voltages to 0.
Causes CBC to update its main firmware with the image that is stored in external flash.
Causes CBC to enter or exit CVR mode (Latch ON = enter).
Puts CBC into Auto or Remote mode (Latch ON = Auto, Latch OFF = Remote). Ignored if CBC is in Manual mode.
Takes CBC out of SCADA override mode.
Enables/disables storage of time stamps for DNP events.
Enables/disables OVUV control (specifically, season 1 and 2 control settings).
Enables/disables VAR control (specifically, season 1 and 2 control settings).
Enable Time Control Allow Unsolicited Reporting Enable Analog Events Trip Control Close Control SCADA Override Trip SCADA Override Close Enable OVUV Comms Loss Control Enable VAR Comms Loss Control Enable Temp Comms Loss Control Enable Va Comms Loss Control Enable Vb Comms Loss Control Enable Vc Comms Loss Control Enable Ia Comms Loss Control Enable Ib Comms Loss Control Enable Ic Comms Loss Control Enable Time Comms Loss Control Enable Ignore SCADA Override Cear Time Delta KVAR Confirmation DNP Reporting Enables/disables Time control (specifically, season 1 and 2 control settings).
Latch ON/OFF, Null
Set Phase A Current Sensor to Load Side
Latch OFF sets Phase A current sensor location to Source side. Latch ON sets Phase A current sensor location to Load side.
CROB
Latch ON/OFF, Null
Set Phase B Current Sensor to Load Side
Latch OFF sets Phase B current sensor location to Source side. Latch ON sets Phase B current sensor location to Load side.
12 01
CROB
Latch ON/OFF, Null
Set Phase C Current Sensor to Load Side
Latch OFF sets Phase C current sensor location to Source side. Latch ON sets Phase C current sensor location to Load side.
12
12
12
12
CROB
CROB
CROB
CROB
Pulse ON, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Latch ON/OFF, Null
Clear Daily Counter
Enable Season 2 OVUV Control
Enable Season 2 VAR Control
Enable Season 2 Time Control
Resets the daily counter to 0.
01
01
01
01
Page 20
Enables/disables setting that indicates CBC supports unsolicited event reporting.
Enables/disables storage of analog input events.
Requests Trip operation.
Requests Close Operation.
Requests SCADA override Trip operation. Puts CBC into SCADA override mode.
Requests SCADA override Close operation. Puts CBC into SCADA override mode.
Enables/disables comms loss control setting.
Enables/disables comms loss control setting.
Enables/disables comms loss control setting.
Enables/disables comms loss control setting.
Enables/disables comms loss control setting.
Enables/disables comms loss control setting.
Enables/disables comms loss control setting.
Enables/disables comms loss control setting.
Enables/disables comms loss control setting.
Enables/disables comms loss control setting.
Enables/disables ignore SCADA override clear time setting.
Enables/disables storage of delta KVAR DNP analog event data.
Enables/disables Season 2 OVUV control.
Enables/disables Season 2 VAR control.
Enables/disables Season 2 Time control.
CROB
CBC-8000 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status
Description
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Index Hex Index Obj Var
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
Desc
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Operation Type
Point Name
Description
Trip/Close SCADA Override Trip/Close Reset NC Lockout Clear Counters Clear High/Low Voltage Freeze High/Low Voltage Freeze & Clear High/Low Voltage Clear Average Delta Voltage Update Firmware CVR Mode Set Auto/Remote Mode Clear SCADA Override Enable Event Time Stamp Enable OVUV Control Enable VAR Control Enable Temp Control Enable Va Control
Enable Vb Control
Enable Vc Control
Enable Ia Control
Enable Ib Control
Enable Ic Control
Enable Time Control Allow Unsolicited Reporting Enable Analog Events Trip Control Close Control SCADA Override Trip SCADA Override Close Enable OVUV Comms Loss Control Enable VAR Comms Loss Control Enable Temp Comms Loss Control Enable Va Comms Loss Control Enable Vb Comms Loss Control Enable Vc Comms Loss Control Enable Ia Comms Loss Control Enable Ib Comms Loss Control Enable Ic Comms Loss Control Enable Time Comms Loss Control Enable Ignore SCADA Override Clear Time Delta KVAR Confirmation DNP Reporting Set Phase A Current Sensor to Load Side
Set Phase B Current Sensor to Load Side
Set Phase C Current Sensor to Load Side
Clear Daily Counter
Enable Season 2 OVUV Control
Enable Season 2 VAR Control
Enable Season 2 Time Control
Status of associated Object 12 control point.
Page 21
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
Status of associated Object 12 control point.
CROB
Technical Data TD916002EN
Communications
Point Data Base

Effective September 2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. TD916002EN
September 2015
Supersedes R1160-80-1 (5/2012)
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
For Eaton's Cooper Power series CBC-8000
capacitor bank control information
call 1-877-277-4636 or visit:
www.eaton.com/cooperpowerseries.
Download