Capacitor Banks Technical Data TD916002EN Effective XXX 2015 Supersedes 240-40 August 2012 COOPER POWER SERIES Communications Point Data Base for Serial and Ethernet Communications Protocol DNP3 For use with Eaton’s Cooper Power series CBC-8000 Capacitor Bank Control CBC-8000 DNP3 Device Profile Data Dictionary CBC-8000 DNP3 Map Points July 13, 2015 v1.40 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON. UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED. Document 1.00 1.10 1.20 1.30 1.40 Date 5/16/2012 4/29/2013 11/19/2013 7/10/2014 7/13/2015 Description Initial Release Ethernet Release Updates Firmware Version 2.0.0 Updates Firmware Version 2.2.2 Updates Firmware Version 2.3.0 Updates Page 1 Cover Page CBC-8000 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Binary Inputs Default Static Variation Obj 01 Var 1 Binary Input – Packed format Default Event Variation Obj 02 Var 1 Binary Input Event – Without time (with time stamps disabled in configuration) Obj 02 Var 2 Binary Input Event – With absolute time (with time stamps enabled in configuration) Default Event Description Class Point Name Index Hex Index Bank State 00 00 1 Indicates state of capacitor bank. SCADA Override Mode 01 01 1 Indicates if CBC is in SCADA override mode (0=no,1=yes). Mode is enabled via CROB 1, 27, or 28 control. Mode is disabled via CROB 11 or local time reaches SCADA override clear time (if ignore SCADA override clear time setting is disabled). NC Lockout 02 02 1 Set if CBC is in NC lockout state. Cleared via CROB 2 control or front panel Neutral Lockout Reset button press (if CBC is in Manual mode). CVR Mode 03 03 1 Indicates if CBC is in CVR mode (0=no,1=yes). Mode is enabled or disabled via CROB 9 control. Mode is also disabled when local time reaches CVR disable time. Line Voltage High Alarm Line Voltage Low Alarm Line Voltage THD Alarm VAR KVAR High Alarm VAR KVAR Low Alarm VAR kW High Alarm VAR kW Low Alarm VAR Leading Pf Alarm VAR Lagging Pf Alarm Temperature High Alarm Temperature Low Alarm Va High Alarm Va Low Alarm Vb High Alarm Vb Low Alarm Vc High Alarm Vc Low Alarm Ia High Alarm Ia Low Alarm Ib High Alarm Ib Low Alarm Ic High Alarm Ic Low Alarm NC Total Alarm NC Fundamental Alarm NC THD Alarm Phase A Total Voltage Hi Alarm Phase A Total Voltage Lo Alarm Phase A Voltage THD Alarm Phase A Total Current Alarm Phase A Current THD Alarm Phase A Leading PF Alarm Phase A Lagging PF Alarm Phase A kW Hi Alarm Phase A kW Lo Alarm Phase A kVAR Hi Alarm Phase A kVAR Lo Alarm Phase B Total Voltage Hi Alarm Phase B Total Voltage Lo Alarm Phase B Voltage THD Alarm 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 29 2A 2B 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Page 2 Binary Inputs CBC-8000 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Binary Inputs Point Name Default Static Variation Obj 01 Var 1 Binary Input – Packed format Default Event Variation Obj 02 Var 1 Binary Input Event – Without time (with time stamps disabled in configuration) Obj 02 Var 2 Binary Input Event – With absolute time (with time stamps enabled in configuration) Default Event Description Class Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Tied to ProView NXG Data Alarm. 1 Indicates Power flow direction (0=normal,1=reverse). Tied to Proview Status Alarm. 1 Indicates Power flow direction (0=normal,1=reverse). Tied to Proview Status Alarm. 1 Indicates Power flow direction (0=normal,1=reverse). Tied to Proview Status Alarm. 1 Indicates Power flow direction (0=normal,1=reverse). Tied to Proview Status Alarm. 1 Tied to NC Verification function. 1 1 Set if voltage detected on the Close relay output during non-bank operation. 1 Set if voltage detected on the Trip relay output during non-bank operation. 1 Tied to delta voltage percent function. 1 Set when timer running. 1 Set when timer running. 1 Set when timer running. 1 Set when timer running. 1 Set when timer running. 1 Set when timer running. 1 Set when timer running. 1 Set when timer running. 1 Set when timer running. 1 Set when timer running. 1 Set when voltage is not detected on either relay output during bank operate time. 1 Index Hex Index Phase B Total Current Alarm Phase B Current THD Alarm Phase B Leading PF Alarm Phase B Lagging PF Alarm Phase B kW Hi Alarm Phase B kW Lo Alarm Phase B kVAR Hi Alarm Phase B kVAR Lo Alarm Phase C Total Voltage Hi Alarm Phase C Total Voltage Lo Alarm Phase C Voltage THD Alarm Phase C Total Current Alarm Phase C Current THD Alarm Phase C Leading PF Alarm Phase C Lagging PF Alarm Phase C kW Hi Alarm Phase C kW Lo Alarm Phase C kVAR Hi Alarm Phase C kVAR Lo Alarm VAR Power Flow Alarm PhA Power Flow Alarm PhB Power Flow Alarm PhC Power Flow Alarm Operation Failed Alarm Max Operation Count Alarm Bad Active Close Relay Alarm Bad Active Trip Relay Alarm Abnormal Delta Voltage Alarm OVUV Track Timer Alarm Emergency Track Timer Alarm Fault Current Timer Alarm VAR Track Timer Alarm Va Timer Alarm Vb Timer Alarm Vc Timer Alarm Ia Timer Alarm Ib Timer Alarm Ic Timer Alarm Relay Sense Failure Alarm 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 2C 2D 2E 2F 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F 50 51 52 Reclose Block Alarm 83 53 1 Fault Current Alarm Manual Mode Remote Mode Auto Mode OVUV Control Status 84 85 86 87 88 54 55 56 57 58 1 1 1 1 1 Set when remote close command received during reclose delay time indicating that the close command will be ignored. Cleared when reclose delay time expires. Indicates CBC is in Manual mode. Mutually exclusive with respect to Auto and Remote mode (i.e. only one mode allowed at a time). Indicates CBC is in Remote mode. Mutually exclusive with respect to Auto and Manual mode (i.e. only one mode allowed at a time). Indicates CBC is in Auto mode. Mutually exclusive with respect to Manual and Remote mode (i.e. only one mode allowed at a time). Indicates status of Season 1, Season 2, or non-seasonal OVUV control setting. Does not indicate comms loss control status or CVR control status. Page 3 Binary Inputs CBC-8000 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Binary Inputs Point Name Default Static Variation Obj 01 Var 1 Binary Input – Packed format Default Event Variation Obj 02 Var 1 Binary Input Event – Without time (with time stamps disabled in configuration) Obj 02 Var 2 Binary Input Event – With absolute time (with time stamps enabled in configuration) Default Event Description Class Indicates status of Season 1, Season 2, or non-seasonal VAR control setting. Does not indicate comms loss control status. 1 Indicates status of Season 1, Season 2, or non-seasonal Time control setting. Does not indicate comms loss control status. 1 Index Hex Index VAR Control Status Time Control Status 89 90 59 5A Temperature Control Status 91 5B 1 Ignore SCADA Override Clear Time In Daylight Savings Bank Tripped Bank Closed Va Control Status Vb Control Status Vc Control Status Ia Control Status Ib Control Status Ic Control Status OVUV Comms Loss Ctrl Status VAR Comms Loss Ctrl Status Temp Comms Loss Ctrl Status Va Comms Loss Ctrl Status Vb Comms Loss Ctrl Status Vc Comms Loss Ctrl Status Ia Comms Loss Ctrl Status Ib Comms Loss Ctrl Status Ic Comms Loss Ctrl Status Time Comms Loss Ctrl Status Phase AB Voltage High Alarm Phase AB Voltage Low Alarm Phase BC Voltage High Alarm Phase BC Voltage Low Alarm Phase CA Voltage High Alarm Phase CA Voltage Low Alarm Phase Voltage Unbalance % Alarm Phase A Current Sensor on Load Side Phase B Current Sensor on Load Side Phase C Current Sensor on Load Side 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 5C 5D 5E 5F 60 61 62 63 64 65 66 67 68 69 6A 6B 6C 6D 6E 6F 70 71 72 73 74 75 76 77 78 79 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Indicates status of temperature control actions. 0 if both min and max threshold actions are set to none, else 1. Applies to the appropriate season when seasonal control enabled. Season 1 actions apply when seasonal control disabled. Indicates the status of the ignore SCADA override clear time setting. Set if CBC local time is in Daylight savings period and DST support is enabled. Indicates capacitor bank is tripped. Mutually exclusive with respect to Bank Closed status point. Indicates capacitor bank is closed. Mutually exclusive with respect to Bank Tripped status point. Indicates status of Va control actions. 0 if both min and max threshold actions are set to none, else 1. Indicates status of Vb control actions. 0 if both min and max threshold actions are set to none, else 1. Indicates status of Vc control actions. 0 if both min and max threshold actions are set to none, else 1. Indicates status of Ia control actions. 0 if both min and max threshold actions are set to none, else 1. Indicates status of Ib control actions. 0 if both min and max threshold actions are set to none, else 1. Indicates status of Ic control actions. 0 if both min and max threshold actions are set to none, else 1. Indicates status of comms loss control setting. Indicates status of comms loss control setting. Indicates status of comms loss control setting. Indicates status of comms loss control setting. Indicates status of comms loss control setting. Indicates status of comms loss control setting. Indicates status of comms loss control setting. Indicates status of comms loss control setting. Indicates status of comms loss control setting. Indicates status of comms loss control setting. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Tied to ProView NXG Data Alarm. Indicates Phase A sensor location. 0 = Source, 1 = Load. Indicates Phase B sensor location. 0 = Source, 1 = Load. Indicates Phase C sensor location. 0 = Source, 1 = Load. Page 4 Binary Inputs CBC-8000 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Counters Point Name Total Operations Count OV Operations Count UV Operations Count Close Operation Count Trip Operation Count Daily Operation Count Default Static Variation Obj 20 Var 2 Counter – 16-bit with flag Default Event Variation Obj 22, see table for varation Index Hex Index Default Event Class Associated Obj 34 Analog Deadband 00 01 02 03 04 05 00 01 02 03 04 05 - AD-035 AD-036 AD-037 AD-038 AD-039 AD-040 Obj 32 Default Obj 32 Default Variation (time Variation (time stamp disabled) stamp enabled) 2 2 2 2 2 2 Page 5 6 6 6 6 6 6 Counters CBC-8000 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM INPUT SUBSYSTEM Analog Inputs Default Static Variation Obj 30, see table for variation Default Event Variation Obj 32, see table for varation Default Division Event Scale Factor Class Obj 32 Default Obj 32 Default Variation (time Variation (time stamp disabled) stamp enabled) Units Associated Obj 34 Analog Deadband Obj 30 Default Variation 1 1 1 1 10 10 -Lookup --Degrees Volts -----AD-000 1 2 2 2 2 2 -----2 -----4 -Reason For Last Control ----- - 10 Volts -- 2 -- -- -- 07 - 10 Volts -- 2 -- -- -- 08 09 10 08 09 0A - 10 10 10 Volts Volts Amps ---- 2 2 2 ---- ---- ---- Average Line Voltage 11 0B - 10 Volts -- 2 -- -- -- Line Voltage Total Line Voltage Fundamental Line Voltage 3rd Harmonic Line Voltage 5th Harmonic Line Voltage 7th Harmonic Line Voltage 9th Harmonic Line Voltage 11th Harmonic Line Voltage 13th Harmonic Line Voltage THD NC Fundamental NC Total NC 3rd Harmonic NC 5th Harmonic NC 7th Harmonic NC 9th Harmonic NC 11th Harmonic NC 13th Harmonic NC THD VAR kW VAR kVA VAR kVARs VAR Power Factor VAR Total Current VAR Fundamental Current VAR Fundamental Voltage VAR Fundamental Phase Va Secondary Vb Secondary Vc Secondary Ia Ib Ic Phase A Total Voltage Phase A Fundamental Voltage Phase A Voltage 3rd Harmonic Phase A Voltage 5th Harmonic Phase A Voltage 7th Harmonic Phase A Voltage 9th Harmonic Phase A Voltage 11th Harmonic Phase A Voltage 13th Harmonic Phase A Voltage THD Phase A Total Current Phase A Fundamental Current Phase A Current 3rd Harmonic Phase A Current 5th Harmonic Phase A Current 7th Harmonic Phase A Current 9th Harmonic 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 29 2A 2B 2C 2D 2E 2F 30 31 32 33 34 35 36 37 38 39 3A 1 1 1 1 1 1 1 10 10 10 10 10 10 10 10 1 10 10 10 10 10 10 10 10 1 1 1 1 1000 1 1 1 1 10 10 10 10 10 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Volts Volts Volts Volts Volts Volts Volts Volts % Amps Amps Amps Amps Amps Amps Amps Amps % kW kVA kVAR -Amps Amps Volts Degrees Volts Volts Volts Amps Amps Amps Volts Volts Volts Volts Volts Volts Volts Volts % Amps Amps Amps Amps Amps Amps AD-001 AD-002 -------AD-003 AD-004 -------AD-005 -AD-006 AD-007 ----AD-008 AD-009 AD-010 AD-011 AD-012 AD-013 AD-014 AD-015 -------AD-016 AD-017 ----- 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 -------2 2 -------2 2 2 ----2 2 2 2 2 2 2 2 -------2 2 ----- 4 4 -------4 4 -------4 4 4 ----4 4 4 4 4 4 4 4 -------4 4 ----- ------------------------------------------------ Point Name Index Hex Index Serial Number Last Control Reason Firmware Major Revision Firmware Minor Revision Temperature Average Delta Voltage 00 01 02 03 04 05 00 01 02 03 04 05 1 Average High Voltage 06 06 Average Low Voltage 07 Frozen Average High Voltage Frozen Average Low Voltage NC Fault Current 1 1 1 1 1 1 1 1 1 1 - Page 6 Enumeration Table (See MN916003EN) Description High nibble is the major version number, low nibble is the minor version number. Lowest value in the overall FW revision: Major.Minor.Version Average change in voltage due to an operation. Uses a window average based on the Line Voltage Average Time setting (same setting as Hi/Lo Average Time on HMI and ProView NXG). Uses a window average based on the Line Voltage Average Time setting (same setting as Hi/Lo Average Time on HMI and ProView NXG). NC current value at time of lockout. Uses a window average based on the Line Voltage Average Time setting (same setting as Hi/Lo Average Time on HMI and ProView NXG). Analog Inputs CBC-8000 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM INPUT SUBSYSTEM Analog Inputs Default Static Variation Obj 30, see table for variation Point Name Index Hex Index Phase A Current 11th Harmonic Phase A Current 13th Harmonic Phase A Current THD Phase A Power Factor Phase A kW Phase A kVA Phase A kVARs Phase A VI Phase Phase B Total Voltage Phase B Fundamental Voltage Phase B Voltage 3rd Harmonic Phase B Voltage 5th Harmonic Phase B Voltage 7th Harmonic Phase B Voltage 9th Harmonic Phase B Voltage 11th Harmonic Phase B Voltage 13th Harmonic Phase B Voltage THD Phase B Total Current Phase B Fundamental Current Phase B Current 3rd Harmonic Phase B Current 5th Harmonic Phase B Current 7th Harmonic Phase B Current 9th Harmonic Phase B Current 11th Harmonic Phase B Current 13th Harmonic Phase B Current THD Phase B Power Factor Phase B kW Phase B kVA Phase B kVARs Phase B VI Phase Phase C Total Voltage Phase C Fundamental Voltage Phase C Voltage 3rd Harmonic Phase C Voltage 5th Harmonic Phase C Voltage 7th Harmonic Phase C Voltage 9th Harmonic Phase C Voltage 11th Harmonic Phase C Voltage 13th Harmonic Phase C Voltage THD Phase C Total Current Phase C Fundamental Current Phase C Current 3rd Harmonic Phase C Current 5th Harmonic Phase C Current 7th Harmonic Phase C Current 9th Harmonic Phase C Current 11th Harmonic Phase C Current 13th Harmonic Phase C Current THD Phase C Power Factor Phase C kW Phase C kVA Phase C kVARs Phase C VI Phase Reason for Ignored Control Single Phase Delta KVAR Phase A Delta KVAR Phase B Delta KVAR Phase C Delta KVAR 3 Phase Total Delta KVAR 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 3B 3C 3D 3E 3F 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F 50 51 52 53 54 55 56 57 58 59 5A 5B 5C 5D 5E 5F 60 61 62 63 64 65 66 67 68 69 6A 6B 6C 6D 6E 6F 70 71 72 73 74 75 76 24-hour Average High Voltage 119 77 Default Event Variation Obj 32, see table for varation Default Division Event Scale Factor Class 1 1 1 1 1000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1000 1 1 1 1 1 1 1 1 1 1 1 1 - 10 Units Associated Obj 34 Analog Deadband Obj 30 Default Variation Amps Amps % -kW kVA kVAR Degrees Volts Volts Volts Volts Volts Volts Volts Volts % Amps Amps Amps Amps Amps Amps Amps Amps % -kW kVA kVAR Degrees Volts Volts Volts Volts Volts Volts Volts Volts % Amps Amps Amps Amps Amps Amps Amps Amps % -kW kVA kVAR Degrees Lookup kVAR kVAR kVAR kVAR kVAR ---AD-018 AD-019 -AD-020 -AD-021 AD-022 -------AD-023 AD-024 -------AD-025 AD-026 -AD-027 -AD-028 AD-029 -------AD-030 AD-031 -------AD-032 AD-033 -AD-034 -------- 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Volts -- 2 Obj 32 Default Obj 32 Default Enumeration Table Variation (time Variation (time Description (See MN916003EN) stamp disabled) stamp enabled) ---------2 4 -2 4 ----2 4 ----2 4 -2 4 ----------------------2 4 -2 4 ----------------------2 4 -2 4 ----2 4 ----2 4 -2 4 ----------------------2 4 -2 4 ----------------------2 4 -2 4 ----2 4 ------Reason for Ignored Control ---------------- Page 7 -- -- -- Uses a window average based on the Line Voltage Average Time setting (same setting as Hi/Lo Average Time on HMI and ProView NXG). Analog Inputs CBC-8000 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM INPUT SUBSYSTEM Analog Inputs Default Static Variation Obj 30, see table for variation Default Event Variation Obj 32, see table for varation Default Division Event Scale Factor Class Obj 32 Default Obj 32 Default Variation (time Variation (time stamp disabled) stamp enabled) Units Associated Obj 34 Analog Deadband Obj 30 Default Variation 10 Volts -- 2 -- -- -- - 1 1 1 1 1 1 1 1 1 1 10 1 1 1 1 1 1 1 1 1 Lookup % % % Volts Degrees Volts Degrees Volts Degrees % ---------- --------------------- 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 --------------------- --------------------- Bank Confirmation Status -------------------- 8D - 1 -- -- 2 -- -- -- 142 8E - 1 -- -- 2 -- -- CBC Build Month & Day 143 8F - 1 -- -- 2 -- -- -- CBC Build Year SelectComm Major Version SelectComm Minor Version SelectComm Rev Version 144 145 146 147 90 91 92 93 - 1 1 1 1 ----- ----- 2 2 2 2 ----- ----- ----- SelectComm Full Version 148 94 - 1 -- -- 2 -- -- -- SelectComm Build Date 149 95 - 1 -- -- 2 -- -- SelectComm Build Month & Day 150 96 - 1 -- -- 2 -- -- -- SelectComm Build Year 151 97 - 1 -- -- 2 -- -- --- Point Name Index Hex Index 24-hour Average Low Voltage 120 78 - Bank Confirmation Status Phase A Delta KVAR Percent Phase B Delta KVAR Percent Phase C Delta KVAR Percent Phase AB Voltage Phase AB Angle Phase BC Voltage Phase BC Angle Phase CA Voltage Phase CA Angle Phase Unbalance Percent Total Operations Count OV Operations Count UV Operations Count Close Operation Count Trip Operation Count Daily Operation Count CBC Major Version CBC Minor Version CBC Rev Version 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 79 7A 7B 7C 7D 7E 7F 80 81 82 83 84 85 86 87 88 89 8A 8B 8C CBC Full Version 141 CBC Build Date Page 8 Enumeration Table (See MN916003EN) Description Uses a window average based on the Line Voltage Average Time setting (same setting as Hi/Lo Average Time on HMI and ProView NXG). Matches the Binary counter of the same name Matches the Binary counter of the same name Matches the Binary counter of the same name Matches the Binary counter of the same name Matches the Binary counter of the same name Matches the Binary counter of the same name CBC version X value in X.Y.Z version CBC version Y value in X.Y.Z version CBC version Z value in X.Y.Z version Complete CBC version x.y.z value where x is highest nibble, y is next highest nibble, and z is low byte. NXG Firmware Build Date Complete CBC code build date coded in a set of bit fields CBC build month and day of month where month is highest byte and day of month is lowest byte CBC build year SelectComm version X value in X.Y.Z version SelectComm version Y value in X.Y.Z version SelectComm version Z value in X.Y.Z version Complete SelectComm version x.y.z value where x is highest nibble, y is next highest nibble, and z is low byte. NXG Firmware Build Date Complete SelectComm code build date coded in a set of bit fields SelectComm build month and day of month where month is highest byte and day of month is lowest byte SelectComm build year Analog Inputs CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Deadbands Point Name Avg Delta Voltage Line Voltage Total Line Voltage Fundamental NC Fundamental NC Total Three Phase kW Three Phase kVAR Three Phase Power Factor Va Secondary Vb Secondary Vc Secondary Ia Ib Ic Phase A Total Voltage Phase A Fundamental Voltage Phase A Total Current Phase A Fundamental Current Phase A Power Factor Phase A kW Phase A kVAR Phase B Total Voltage Phase B Fundamental Voltage Phase B Total Current Phase B Fundamental Current Phase B Power Factor Phase B kW Phase B kVAR Phase C Total Voltage Phase C Fundamental Voltage Phase C Total Current Phase C Fundamental Current Phase C Power Factor Phase C kW Phase C kVAR Default Static Variation Obj 34 Var 1 Analog Input Deadband – 16-bit Index Hex Index Division Scale Factor Units Associated Obj 22/32 Input Object 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 10 10 10 10 10 1 1 1000 10 10 10 10 10 10 1 1 1 1 1000 1 1 1 1 1 1 1000 1 1 1 1 1 1 1000 1 1 Volts Volts Volts Amps Amps kW kVAR -Volts Volts Volts Amps Amps Amps Volts Volts Amps Amps -kW kVAR Volts Volts Amps Amps -kW kVAR Volts Volts Amps Amps -kW kVAR AI-005 AI-012 AI-013 AI-021 AI-022 AI-030 AI-032 AI-033 AI-038 AI-039 AI-040 AI-041 AI-042 AI-043 AI-044 AI-045 AI-053 AI-054 AI-062 AI-063 AI-065 AI-067 AI-068 AI-076 AI-077 AI-085 AI-086 AI-088 AI-090 AI-091 AI-099 AI-100 AI-108 AI-109 AI-111 Page 9 Analog Deadbands CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Deadbands Point Name Total Operations Count OV Operations Count UV Operations Count Close Operation Count Trip Operation Count Daily Operation Count Temperature Average Line Voltage Line Voltage THD NC THD VAR kVA VAR Total Current VAR Fundamental Current VAR Fundamental Voltage Phase A Voltage THD Phase A Current THD Phase A kVA Phase B Voltage THD Phase B Current THD Phase B kVA Phase C Voltage THD Phase C Current THD Phase C kVA Single Phase Delta KVAR Phase A Delta KVAR Phase B Delta KVAR Phase C Delta KVAR 3 Phase Total Delta KVAR Phase AB Voltage Phase AB Angle Phase BC Voltage Phase BC Angle Phase CA Voltage Phase CA Angle Phase Unbalance Percent Default Static Variation Obj 34 Var 1 Analog Input Deadband – 16-bit Index Hex Index Division Scale Factor Units 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 23 24 25 26 27 28 29 2A 2B 2C 2D 2E 2F 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F 40 41 42 43 44 45 1 1 1 1 1 1 0.1 0.1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.1 ------Degrees Volts % % kVA Amps Amps Volts % % kVA % % kVA % % kVA kVAR kVAR kVAR kVAR kVAR Volts Degrees Volts Degrees Volts Degrees % Page 10 Associated Obj 22/32 Input Object AI-132, CI-000 AI-133, CI-001 AI-134, CI-002 AI-135, CI-003 AI-136, CI-004 AI-137, CI-005 AI-004 AI-011 AI-020 AI-029 AI-031 AI-034 AI-035 AI-036 AI-052 AI-061 AI-064 AI-075 AI-084 AI-087 AI-098 AI-107 AI-110 AI-114 AI-115 AI-116 AI-117 AI-118 AI-125 AI-126 AI-127 AI-128 AI-129 AI-130 AI-131 Analog Deadbands CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Outputs Point Name Season 1 OV Threshold Season 1 UV Threshold Season 1 OV Track Time Season 1 UV Track Time Daily Auto Control Limit Auto Close Delay Manual Close Delay Manual Trip Delay Bank Operate Time Reclose Delay Comms Loss Time CVR OV Threshold CVR UV Threshold CVR Disable Time Emergency OV Threshold Emergency UV Threshold Emergency Voltage Track Time Comms Loss OV Threshold Comms Loss UV Threshold Line Voltage Average Time Season 2 OV Threshold Season 2 UV Threshold Season 2 OV Track Time Season 2 UV Track Time Unused - Deprecated Random Voltage Time Adaptive Voltage Hysteresis Delta Voltage Percent Delta Voltage Sample Count Season 1 VAR Trip Threshold Season 1 VAR Close Threshold Season 1 VAR Track Time Season 2 VAR Trip Threshold Season 2 VAR Close Threshold Season 2 VAR Track Time VAR Sensor Phase Adjust VAR Bank Size Voltage Control Priority VAR Control Priority Temperature Control Priority Va Control Priority Vb Control Priority Vc Control Priority Ia Control Priority Ib Control Priority Ic Control Priority Va Minimum Threshold Default Static Variation Obj 40 Var 2 Analog Output Status – 16-bit with flag Default Event Variation None Supported Index Hex Index Division Scale Factor Units Enumeration Table (See MN916003EN) 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 29 2A 2B 2C 2D 2E 10 10 1 1 1 1 1 1 1 1 1 10 10 1 10 10 1 10 10 1 10 10 1 1 -1 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 10 Volts Volts Seconds Seconds -Seconds Seconds Seconds Seconds Minutes Minutes Volts Volts Minutes Volts Volts Seconds Volts Volts Seconds Volts Volts Seconds Seconds -Minutes Volts % KVAR KVAR KVAR Seconds KVAR KVAR Seconds Degrees KVAR ---------Volts ------------------------------------------------ Page 11 Description Number of operations to average over for determining average delta voltage. Analog Outputs CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Outputs Point Name Va Maximum Threshold Va Minimum Hysteresis Va Maximum Hysteresis Va Minimum Track Time Va Maximum Track Time Va Minimum Action Va Maximum Action Vb Minimum Threshold Vb Maximum Threshold Vb Minimum Hysteresis Vb Maximum Hysteresis Vb Minimum Track Time Vb Maximum Track Time Vb Minimum Action Vb Maximum Action Vc Minimum Threshold Vc Maximum Threshold Vc Minimum Hysteresis Vc Maximum Hysteresis Vc Minimum Track Time Vc Maximum Track Time Vc Minimum Action Vc Maximum Action Ia Minimum Threshold Ia Maximum Threshold Ia Minimum Hysteresis Ia Maximum Hysteresis Ia Minimum Track Time Ia Maximum Track Time Ia Minimum Action Ia Maximum Action Ib Minimum Threshold Ib Maximum Threshold Ib Minimum Hysteresis Ib Maximum Hysteresis Ib Minimum Track Time Ib Maximum Track Time Ib Minimum Action Ib Maximum Action Ic Minimum Threshold Ic Maximum Threshold Ic Minimum Hysteresis Ic Maximum Hysteresis Ic Minimum Track Time Ic Maximum Track Time Ic Minimum Action Ic Maximum Action Season 1 Month Default Static Variation Obj 40 Var 2 Analog Output Status – 16-bit with flag Default Event Variation None Supported Index Hex Index Division Scale Factor Units Enumeration Table (See MN916003EN) 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 2F 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F 50 51 52 53 54 55 56 57 58 59 5A 5B 5C 5D 5E 10 10 10 1 1 1 1 10 10 10 10 1 1 1 1 10 10 10 10 1 1 1 1 10 10 10 10 1 1 1 1 10 10 10 10 1 1 1 1 10 10 10 10 1 1 1 1 1 Volts Volts Volts Seconds Seconds Lookup Lookup Volts Volts Volts Volts Seconds Seconds Lookup Lookup Volts Volts Volts Volts Seconds Seconds Lookup Lookup Amps Amps Amps Amps Seconds Seconds Lookup Lookup Amps Amps Amps Amps Seconds Seconds Lookup Lookup Amps Amps Amps Amps Seconds Seconds Lookup Lookup -- -----Action Action ------Action Action ------Action Action ------Action Action ------Action Action ------Action Action -- Page 12 Description 0=Disable, 1=January, etc. Analog Outputs CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Outputs Point Name Season 1 Day of Month Season 2 Month Season 2 Day of Month Season 1 ON Time Season 1 OFF Time Season 1 Weekend ON Time Season 1 Weekend OFF Time Season 2 ON Time Season 2 OFF Time Season 2 Weekend ON Time Season 2 Weekend OFF Time Season 1 OFF Time State Season 2 OFF Time State Line Voltage High Alarm Threshold Line Voltage Low Alarm Threshold Line Voltage Alarm Threshold High Time Line Voltage Alarm Threshold Low Time Line Voltage THD Alarm Threshold Line Voltage THD Alarm Threshold Time VAR kVAR Lag Alarm Threshold VAR kVAR Lead Alarm Threshold VAR kVAR Lag Alarm Threshold Time VAR kVAR Lead Alarm Threshold Time VAR kW High Alarm Threshold VAR kW Low Alarm Threshold VAR kW High Alarm Threshold Time VAR kW Low Alarm Threshold Time VAR Leading PF Alarm Threshold VAR Lagging PF Alarm Threshold VAR Lagging PF Alarm Threshold Time VAR Leading PF Alarm Threshold Time Temperature High Alarm Threshold Temperature Low Alarm Threshold Temperature High Alarm Threshold Time Temperature Low Alarm Threshold Time Va High Alarm Threshold Va Low Alarm Threshold Va High Alarm Threshold Time Va Low Alarm Threshold Time Vb High Alarm Threshold Vb Low Alarm Threshold Vb High Alarm Threshold Time Vb Low Alarm Threshold Time Vc High Alarm Threshold Vc Low Alarm Threshold Vc High Alarm Threshold Time Vc Low Alarm Threshold Time Ia High Alarm Threshold Default Static Variation Obj 40 Var 2 Analog Output Status – 16-bit with flag Default Event Variation None Supported Index Hex Index Division Scale Factor Units Enumeration Table (See MN916003EN) 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 5F 60 61 62 63 64 65 66 67 68 69 6A 6B 6C 6D 6E 6F 70 71 72 73 74 75 76 77 78 79 7A 7B 7C 7D 7E 7F 80 81 82 83 84 85 86 87 88 89 8A 8B 8C 8D 8E 1 1 1 1 1 1 1 1 1 1 1 1 1 10 10 1 1 1 1 1 1 1 1 1 1 1 1 1000 1000 1 1 10 10 1 1 10 10 1 1 10 10 1 1 10 10 1 1 10 ---Minutes Minutes Minutes Minutes Minutes Minutes Minutes Minutes Lookup Lookup Volts Volts Seconds Seconds % Seconds KVAR KVAR Seconds Seconds KW KW Seconds Seconds --Seconds Seconds Degrees Degrees Seconds Seconds Volts Volts Seconds Seconds Volts Volts Seconds Seconds Volts Volts Seconds Seconds Amps -----------Time State Time State ------------------------------------ Page 13 Description 0=Disable 0=Disable, 1=January, etc. 0=Disable Time of Day. 1042 minutes = 17:22 (HH:MM). Time of Day. 1042 minutes = 17:22 (HH:MM). Time of Day. 1042 minutes = 17:22 (HH:MM). Time of Day. 1042 minutes = 17:22 (HH:MM). Time of Day. 1042 minutes = 17:22 (HH:MM). Time of Day. 1042 minutes = 17:22 (HH:MM). Time of Day. 1042 minutes = 17:22 (HH:MM). Time of Day. 1042 minutes = 17:22 (HH:MM). Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Analog Outputs CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Outputs Point Name Ia Low Alarm Threshold Ia High Alarm Threshold Time Ia Low Alarm Threshold Time Ib High Alarm Threshold Ib Low Alarm Threshold Ib High Alarm Threshold Time Ib Low Alarm Threshold Time Ic High Alarm Threshold Ic Low Alarm Threshold Ic High Alarm Threshold Time Ic Low Alarm Threshold Time NC Fundamental Alarm Threshold NC Fundamental Alarm Threshold Time NC Total Alarm Threshold NC Total Alarm Threshold Time NC THD Alarm Threshold NC THD Alarm Threshold Time Phase A Total Voltage High Alarm Threshold Phase A Total Voltage Low Alarm Threshold Phase A Total Voltage High Alarm Threshold Time Phase A Total Voltage Low Alarm Threshold Time Phase A Voltage THD Alarm Threshold Phase A Voltage THD Alarm Threshold Time Phase A Total Current Alarm Threshold Phase A Total Current Alarm Threshold Time Phase A Current THD Alarm Threshold Phase A Current THD Alarm Threshold Time Phase A Leading PF Alarm Threshold Phase A Lagging PF Alarm Threshold Phase A Lagging PF Alarm Threshold Time Phase A Leading PF Alarm Threshold Time Phase A kW High Alarm Threshold Phase A kW Low Alarm Threshold Phase A kW High Alarm Threshold Time Phase A kW Low Alarm Threshold Time Phase A kVAR Lag Alarm Threshold Phase A kVAR Lead Alarm Threshold Phase A kVAR Lag Alarm Threshold Time Phase A kVAR Lead Alarm Threshold Time Phase B Total Voltage High Alarm Threshold Phase B Total Voltage Low Alarm Threshold Phase B Total Voltage High Alarm Threshold Time Phase B Total Voltage Low Alarm Threshold Time Phase B Voltage THD Alarm Threshold Phase B Voltage THD Alarm Threshold Time Phase B Total Current Alarm Threshold Phase B Total Current Alarm Threshold Time Phase B Current THD Alarm Threshold Default Static Variation Obj 40 Var 2 Analog Output Status – 16-bit with flag Default Event Variation None Supported Index Hex Index Division Scale Factor Units Enumeration Table (See MN916003EN) 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 8F 90 91 92 93 94 95 96 97 98 99 9A 9B 9C 9D 9E 9F A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 AA AB AC AD AE AF B0 B1 B2 B3 B4 B5 B6 B7 B8 B9 BA BB BC BD BE 10 1 1 10 10 1 1 10 10 1 1 10 1 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1000 1000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Amps Seconds Seconds Amps Amps Seconds Seconds Amps Amps Seconds Seconds Amps Seconds Amps Seconds % Seconds Volts Volts Seconds Seconds % Seconds Amps Seconds Amps Seconds --Seconds Seconds KW KW Seconds Seconds KVAR KVAR Seconds Seconds Volts Volts Seconds Seconds % Seconds Amps Seconds Amps ------------------------------------------------- Page 14 Description Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Analog Outputs CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Outputs Point Name Phase B Current THD Alarm Threshold Time Phase B Leading PF Alarm Threshold Phase B Lagging PF Alarm Threshold Phase B Lagging PF Alarm Threshold Time Phase B Leading PF Alarm Threshold Time Phase B kW High Alarm Threshold Phase B kW Low Alarm Threshold Phase B kW High Alarm Threshold Time Phase B kW Low Alarm Threshold Time Phase B kVAR Lag Alarm Threshold Phase B kVAR Lead Alarm Threshold Phase B kVAR Lag Alarm Threshold Time Phase B kVAR Lead Alarm Threshold Time Phase C Total Voltage High Alarm Threshold Phase C Total Voltage Low Alarm Threshold Phase C Total Voltage High Alarm Threshold Time Phase C Total Voltage Low Alarm Threshold Time Phase C Voltage THD Alarm Threshold Phase C Voltage THD Alarm Threshold Time Phase C Total Current Alarm Threshold Phase C Total Current Alarm Threshold Time Phase C Current THD Alarm Threshold Phase C Current THD Alarm Threshold Time Phase C Leading PF Alarm Threshold Phase C Lagging PF Alarm Threshold Phase C Lagging PF Alarm Threshold Time Phase C Leading PF Alarm Threshold Time Phase C kW High Alarm Threshold Phase C kW Low Alarm Threshold Phase C kW High Alarm Threshold Time Phase C kW Low Alarm Threshold Time Phase C kVAR Lag Alarm Threshold Phase C kVAR Lead Alarm Threshold Phase C kVAR Lag Alarm Threshold Time Phase C kVAR Lead Alarm Threshold Time VAR Power Flow Time Phase A Power Flow Time Phase B Power Flow Time Phase C Power Flow Time Season 1 Temperature Minimum Threshold Season 1 Temperature Maximum Threshold Season 1 Temperature Minimum Hysteresis Season 1 Temperature Maximum Hysteresis Season 1 Temperature Minimum Track Time Season 1 Temperature Maximum Track Time Season 1 Minimum Action Season 1 Maximum Action Season 2 Temperature Minimum Threshold Default Static Variation Obj 40 Var 2 Analog Output Status – 16-bit with flag Default Event Variation None Supported Index Hex Index Division Scale Factor Units Enumeration Table (See MN916003EN) 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 BF C0 C1 C2 C3 C4 C5 C6 C7 C8 C9 CA CB CC CD CE CF D0 D1 D2 D3 D4 D5 D6 D7 D8 D9 DA DB DC DD DE DF E0 E1 E2 E3 E4 E5 E6 E7 E8 E9 EA EB EC ED EE 1 1000 1000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1000 1000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 10 10 10 10 1 1 1 1 10 Seconds --Seconds Seconds KW KW Seconds Seconds KVAR KVAR Seconds Seconds Volts Volts Seconds Seconds % Seconds Amps Seconds Amps Seconds --Seconds Seconds KW KW Seconds Seconds KVAR KVAR Seconds Seconds Seconds Seconds Seconds Seconds Degrees Degrees Degrees Degrees Seconds Seconds Lookup Lookup Degrees ---------------------------------------------Action Action -- Page 15 Description Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Status Alarm Setting in ProView NXG. Status Alarm Setting in ProView NXG. Status Alarm Setting in ProView NXG. Status Alarm Setting in ProView NXG. Analog Outputs CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Outputs Point Name Season 2 Temperature Maximum Threshold Season 2 Temperature Minimum Hysteresis Season 2 Temperature Maximum Hysteresis Season 2 Temperature Minimum Track Time Season 2 Temperature Maximum Track Time Season 2 Minimum Action Season 2 Maximum Action NC Fault Control Threshold NC Fault Control Track Time NC Fault Control Hysteresis NC Verification Setpoint NC Verification Retry Count SCADA Override Release Time Time Zone VAR Power Flow Alarm Flags Phase A Power Flow Alarm Flags Phase B Power Flow Alarm Flags Phase C Power Flow Alarm Flags Line Voltage High Alarm Flags Line Voltage Low Alarm Flags Line Voltage THD Alarm Flags VAR kVAR Lag Alarm Flags VAR kVAR Lead Alarm Flags VAR kW High Alarm Flags VAR kW Low Alarm Flags VAR Leading PF Alarm Flags VAR Lagging PF Alarm Flags Temperature High Alarm Flags Temperature Low Alarm Flags Va High Alarm Flags Va Low Alarm Flags Vb High Alarm Flags Vb Low Alarm Flags Vc High Alarm Flags Vc Low Alarm Flags Ia High Alarm Flags Ia Low Alarm Flags Ib High Alarm Flags Ib Low Alarm Flags Ic High Alarm Flags Ic Low Alarm Flags NC Total Alarm Flags NC Fundamental Alarm Flags NC THD Alarm Flags Phase A Total Voltage High Alarm Flags Phase A Total Voltage Low Alarm Flags Phase A Voltage THD Alarm Flags Phase A Total Current Alarm Flags Default Static Variation Obj 40 Var 2 Analog Output Status – 16-bit with flag Default Event Variation None Supported Index Hex Index Division Scale Factor Units Enumeration Table (See MN916003EN) 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 EF F0 F1 F2 F3 F4 F5 F6 F7 F8 F9 FA FB FC FD FE FF 100 101 102 103 104 105 106 107 108 109 10A 10B 10C 10D 10E 10F 110 111 112 113 114 115 116 117 118 119 11A 11B 11C 11D 11E 10 10 10 1 1 1 1 10 1 10 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Degrees Degrees Degrees Seconds Seconds Lookup Lookup Amps Seconds Amps Amps -Minutes Minutes Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup -----Action Action -------Status Alarm Flags Status Alarm Flags Status Alarm Flags Status Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Page 16 Description Time of Day. 1042 minutes = 17:22 (HH:MM). Number of minutes from GMT. (-) is east and (+) is west. Status Alarm Setting in ProView NXG. Status Alarm Setting in ProView NXG. Status Alarm Setting in ProView NXG. Status Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Analog Outputs CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Outputs Point Name Phase A Current THD Alarm Flags Phase A Leading PF Alarm Flags Phase A Lagging PF Alarm Flags Phase A kW High Alarm Flags Phase A kW Low Alarm Flags Phase A kVAR Lag Alarm Flags Phase A kVAR Lead Alarm Flags Phase B Total Voltage High Alarm Flags Phase B Total Voltage Low Alarm Flags Phase B Voltage THD Alarm Flags Phase B Total Current Alarm Flags Phase B Current THD Alarm Flags Phase B Leading PF Alarm Flags Phase B Lagging PF Alarm Flags Phase B kW High Alarm Flags Phase B kW Low Alarm Flags Phase B kVAR Lag Alarm Flags Phase B kVAR Lead Alarm Flags Phase C Total Voltage High Alarm Flags Phase C Total Voltage Low Alarm Flags Phase C Voltage THD Alarm Flags Phase C Total Current Alarm Flags Phase C Current THD Alarm Flags Phase C Leading PF Alarm Flags Phase C Lagging PF Alarm Flags Phase C kW High Alarm Flags Phase C kW Low Alarm Flags Phase C kVAR Lag Alarm Flags Phase C kVAR Lead Alarm Flags VAR Control Flags Voltage Control Flags Phase Input Control Flags 1 Phase Input Control Flags 2 Time Control Flags 1 Time Control Flags 2 Temperature Control Flags NC Control Flags Unused - Deprecated Unused - Deprecated Unused - Deprecated Unused - Deprecated Unused - Deprecated Unused - Deprecated Unused - Deprecated Unused - Deprecated Phase A Phase Adjust Unused - Deprecated Unused - Deprecated Default Static Variation Obj 40 Var 2 Analog Output Status – 16-bit with flag Default Event Variation None Supported Index Hex Index Division Scale Factor Units Enumeration Table (See MN916003EN) 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 11F 120 121 122 123 124 125 126 127 128 129 12A 12B 12C 12D 12E 12F 130 131 132 133 134 135 136 137 138 139 13A 13B 13C 13D 13E 13F 140 141 142 143 144 145 146 147 148 149 14A 14B 14C 14D 14E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 --------1 --- Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup Lookup --------Degrees --- Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags VAR Control Flags Voltage Control Flags Phase Control Flags Byte 1 Phase Control Flags Byte 2 Time Control Flags Byte 1 Time Control Flags Byte 2 Temperature Control Flags Neutral Current Flags ------------ Page 17 Description Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Analog Outputs CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Outputs Point Name Phase B Phase Adjust Unused - Deprecated Unused - Deprecated Phase C Phase Adjust Unused - Deprecated Unused - Deprecated VAR Current Input VAR Voltage Input Unused - Deprecated Power Setup Flags Select Timeout Status Link Timeout App Confirm Timeout App Confirm Retries Clock Valid time Class 1 Min Events Class 2 Min Events Class 3 Min Events Unsolicited Notification Delay Class1 Unsolicited Notification Delay Class2 Unsolicited Notification Delay Class3 Va Sensor Ratio Ia Sensor Ratio Vb Sensor Ratio Ib Sensor Ratio Vc Sensor Ratio Ic Sensor Ratio Line Voltage PT ratio NC Sensor Ratio 24-hour Report Time Delta KVAR Pass Percent Phase AB High Alarm Threshold Phase AB Low Alarm Threshold Phase AB High Alarm Threshold Time Phase AB Low Alarm Threshold Time Phase BC High Alarm Threshold Phase BC Low Alarm Threshold Phase BC High Alarm Threshold Time Phase BC Low Alarm Threshold Time Phase CA High Alarm Threshold Phase CA Low Alarm Threshold Phase CA High Alarm Threshold Time Phase CA Low Alarm Threshold Time Phase Unbalance High Percent Threshold Phase Unbalance High Percent Threshold Time Phase AB High Alarm Flags Phase AB Low Alarm Flags Phase BC High Alarm Flags Default Static Variation Obj 40 Var 2 Analog Output Status – 16-bit with flag Default Event Variation None Supported Index Hex Index Division Scale Factor Units Enumeration Table (See MN916003EN) 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 14F 150 151 152 153 154 155 156 157 158 159 15A 15B 15C 15D 15E 15F 160 161 162 163 164 165 166 167 168 169 16A 16B 16C 16D 16E 16F 170 171 172 173 174 175 176 177 178 179 17A 17B 17C 17D 17E 1 --1 --1 1 -1 1 1 1 1 1 1 1 1 1 1 1 1 10 1 10 1 10 10 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Degrees --Degrees -----Lookup Seconds Minutes msX10 -Minutes ---msX10 msX10 msX10 --------Minutes % Volts Volts Seconds Seconds Volts Volts Seconds Seconds Volts Volts Seconds Seconds % Seconds Lookup Lookup Lookup ---------Power Setup Flags -----------------------------------Data Alarm Flags Data Alarm Flags Data Alarm Flags Page 18 Description 0="Phase A", 1="Phase B", 2="Phase C" 0="CBC Line", 1="Phase A", 2="Phase B", 3="Phase C" DNP3 Select before operate time. Applies only to Serial comms. Time of Day. 1042 minutes = 17:22 (HH:MM). Time of Day. 1042 minutes = 17:22 (HH:MM). Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Analog Outputs CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Outputs Default Static Variation Obj 40 Var 2 Analog Output Status – 16-bit with flag Default Event Variation None Supported Index Hex Index Division Scale Factor Units Enumeration Table (See MN916003EN) Phase BC Low Alarm Flags Phase CA High Alarm Flags Phase CA Low Alarm Flags Phase Unbalance Alarm Flags Comms Logging Flags 383 384 385 386 387 17F 180 181 182 183 1 1 1 1 1 Lookup Lookup Lookup Lookup Lookup Data Alarm Flags Data Alarm Flags Data Alarm Flags Data Alarm Flags Comms Logging Flags Auto Trip Delay 388 184 1 Seconds -- Point Name Page 19 Description Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Data Alarm Setting in ProView NXG. Time delay before a trip operation when the operation is requested via remote command or local auto control. Analog Outputs CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status Description Index Hex Index Obj Var Desc Operation Type Point Name Description Trip/Close SCADA Override Trip/Close Reset NC Lockout Clear Counters Clear High/Low Voltage Freeze High/Low Voltage Requests Trip or Close operation. Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output 00 01 02 03 04 05 00 01 02 03 04 05 12 12 12 12 12 12 01 01 01 01 01 01 CROB CROB CROB CROB CROB CROB Pulse ON, Trip/Close; Latch ON/OFF, Null Pulse ON, Trip/Close; Latch ON/OFF, Null Pulse ON, Null Pulse ON, Null Pulse ON, Null Pulse ON, Null Binary Output 06 06 12 01 CROB Pulse ON, Null Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output 07 08 09 10 11 12 13 14 07 08 09 0A 0B 0C 0D 0E 12 12 12 12 12 12 12 12 01 01 01 01 01 01 01 01 CROB CROB CROB CROB CROB CROB CROB CROB Pulse ON, Null Pulse ON, Null Latch ON/OFF, Null Latch ON/OFF, Null Pulse ON, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Clear Average Delta Voltage Update Firmware CVR Mode Set Auto/Remote Mode Clear SCADA Override Enable Event Time Stamp Enable OVUV Control Enable VAR Control Binary Output 15 0F 12 01 CROB Latch ON/OFF, Null Enable Temp Control Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would be set to none). Binary Output 16 10 12 01 CROB Latch ON/OFF, Null Enable Va Control Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would be set to none). Binary Output 17 11 12 01 CROB Latch ON/OFF, Null Enable Vb Control Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would be set to none). Binary Output 18 12 12 01 CROB Latch ON/OFF, Null Enable Vc Control Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would be set to none). Binary Output 19 13 12 01 CROB Latch ON/OFF, Null Enable Ia Control Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would be set to none). Binary Output 20 14 12 01 CROB Latch ON/OFF, Null Enable Ib Control Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would be set to none). Binary Output 21 15 12 01 CROB Latch ON/OFF, Null Enable Ic Control Latch OFF sets all threshold actions to none. Latch ON resets the actions to their original settings (if actions were none than they would be set to none). Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Pulse ON, Trip; Latch ON, Null Pulse ON, Close; Latch ON, Null Pulse ON, Trip; Latch ON, Null Pulse ON, Close; Latch ON, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Binary Output 41 29 12 01 CROB Binary Output 42 2A 12 01 Binary Output 43 2B Binary Output Binary Output Binary Output Binary Output 44 45 46 47 2C 2D 2E 2F Freeze & Clear High/Low Voltage Requests SCADA override Trip or Close operation. Puts CBC into SCADA override mode. Releases CBC from NC Lockout state. Resets all binary counters to 0 and saves time stamp of clear operation. Resets the average high and low voltages to 0 and saves time stamp of clear operation. Copies average high and low voltages to frozen values. Copies average high and low voltages to frozen values, resets average high and low voltages to 0, and saves time stamp of clear operation. Resets the average delta voltage and all operation delta voltages to 0. Causes CBC to update its main firmware with the image that is stored in external flash. Causes CBC to enter or exit CVR mode (Latch ON = enter). Puts CBC into Auto or Remote mode (Latch ON = Auto, Latch OFF = Remote). Ignored if CBC is in Manual mode. Takes CBC out of SCADA override mode. Enables/disables storage of time stamps for DNP events. Enables/disables OVUV control (specifically, season 1 and 2 control settings). Enables/disables VAR control (specifically, season 1 and 2 control settings). Enable Time Control Allow Unsolicited Reporting Enable Analog Events Trip Control Close Control SCADA Override Trip SCADA Override Close Enable OVUV Comms Loss Control Enable VAR Comms Loss Control Enable Temp Comms Loss Control Enable Va Comms Loss Control Enable Vb Comms Loss Control Enable Vc Comms Loss Control Enable Ia Comms Loss Control Enable Ib Comms Loss Control Enable Ic Comms Loss Control Enable Time Comms Loss Control Enable Ignore SCADA Override Cear Time Delta KVAR Confirmation DNP Reporting Enables/disables Time control (specifically, season 1 and 2 control settings). Latch ON/OFF, Null Set Phase A Current Sensor to Load Side Latch OFF sets Phase A current sensor location to Source side. Latch ON sets Phase A current sensor location to Load side. CROB Latch ON/OFF, Null Set Phase B Current Sensor to Load Side Latch OFF sets Phase B current sensor location to Source side. Latch ON sets Phase B current sensor location to Load side. 12 01 CROB Latch ON/OFF, Null Set Phase C Current Sensor to Load Side Latch OFF sets Phase C current sensor location to Source side. Latch ON sets Phase C current sensor location to Load side. 12 12 12 12 CROB CROB CROB CROB Pulse ON, Null Latch ON/OFF, Null Latch ON/OFF, Null Latch ON/OFF, Null Clear Daily Counter Enable Season 2 OVUV Control Enable Season 2 VAR Control Enable Season 2 Time Control Resets the daily counter to 0. 01 01 01 01 Page 20 Enables/disables setting that indicates CBC supports unsolicited event reporting. Enables/disables storage of analog input events. Requests Trip operation. Requests Close Operation. Requests SCADA override Trip operation. Puts CBC into SCADA override mode. Requests SCADA override Close operation. Puts CBC into SCADA override mode. Enables/disables comms loss control setting. Enables/disables comms loss control setting. Enables/disables comms loss control setting. Enables/disables comms loss control setting. Enables/disables comms loss control setting. Enables/disables comms loss control setting. Enables/disables comms loss control setting. Enables/disables comms loss control setting. Enables/disables comms loss control setting. Enables/disables comms loss control setting. Enables/disables ignore SCADA override clear time setting. Enables/disables storage of delta KVAR DNP analog event data. Enables/disables Season 2 OVUV control. Enables/disables Season 2 VAR control. Enables/disables Season 2 Time control. CROB CBC-8000 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status Description Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Index Hex Index Obj Var 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 29 2A 2B 2C 2D 2E 2F 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 Desc Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Operation Type Point Name Description Trip/Close SCADA Override Trip/Close Reset NC Lockout Clear Counters Clear High/Low Voltage Freeze High/Low Voltage Freeze & Clear High/Low Voltage Clear Average Delta Voltage Update Firmware CVR Mode Set Auto/Remote Mode Clear SCADA Override Enable Event Time Stamp Enable OVUV Control Enable VAR Control Enable Temp Control Enable Va Control Enable Vb Control Enable Vc Control Enable Ia Control Enable Ib Control Enable Ic Control Enable Time Control Allow Unsolicited Reporting Enable Analog Events Trip Control Close Control SCADA Override Trip SCADA Override Close Enable OVUV Comms Loss Control Enable VAR Comms Loss Control Enable Temp Comms Loss Control Enable Va Comms Loss Control Enable Vb Comms Loss Control Enable Vc Comms Loss Control Enable Ia Comms Loss Control Enable Ib Comms Loss Control Enable Ic Comms Loss Control Enable Time Comms Loss Control Enable Ignore SCADA Override Clear Time Delta KVAR Confirmation DNP Reporting Set Phase A Current Sensor to Load Side Set Phase B Current Sensor to Load Side Set Phase C Current Sensor to Load Side Clear Daily Counter Enable Season 2 OVUV Control Enable Season 2 VAR Control Enable Season 2 Time Control Status of associated Object 12 control point. Page 21 Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. Status of associated Object 12 control point. CROB Technical Data TD916002EN Communications Point Data Base Effective September 2015 Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries © 2015 Eaton All Rights Reserved Printed in USA Publication No. TD916002EN September 2015 Supersedes R1160-80-1 (5/2012) Eaton is a registered trademark. All other trademarks are property of their respective owners. For Eaton's Cooper Power series CBC-8000 capacitor bank control information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.