FREQUENTLY ASKED QUESTIONS NOVA-TS Triple-Single Recloser and Form 6-TS Control Frequently Asked Questions How To Use This Publication This publication (Bulletin B280-09007) contains detailed product and application information and provides answers to commonly asked questions about the NOVA-TS triple-single recloser. If you have additional questions concerning the design, operating features, or application of the NOVA-TS recloser and Form 6-TS control, contact your Cooper Power Systems representative. Important Information The information contained in this document is intended for Cooper Power Systems customers. The information contained in the questions and answers is generalized to present overall guidance in the use and application of these products. This information is in no way intended to be used in the creation of any, or supersede the application, use, and safety standards of any government authorities or the user. Users are cautioned to obtain the applicable service literature and instructions from Cooper Power Systems (available at www.cooperpower.com and shipped with each product) and to strictly follow those instructions. The information in this document is not in any way intended to modify or supersede those applicable product instructions. Ordering Information 1. Can I order a NOVA-TS recloser without ordering a Form 6-TS control? No. A NOVA-TS recloser is an integral unit consisting of three single-phase NOVA reclosers and one Form 6-TS microprocessor-based recloser control connected via a junction box. They must be installed together for proper operation. 2. Is there a separate cable for the internal voltage sensors similar to the three-phase NOVA recloser? No. The internal voltage sensors are brought out of the NOVA-TS recloser through the standard recloser and control cables. One Cooper | www.cooperpower.com | Online 3. Is there a control cable length restriction when using internal voltage sensors? Yes. The maximum control cable length when using internal voltage sensors is 50 feet. 4. Is the junction box included in the complete recloser package? One junction box with cables is included when ordering a complete recloser package. Three junction box cables are required per junction box. 5. Are there any recommended spare parts? NOVA-TS switchgear products are designed and manufactured to be virtually maintenance-free. A spare battery for the Form 6-TS control is the only recommended spare part. Technical Information 6. What is internal voltage sensing? Using a high-voltage resistor within each interrupter module the NOVA-TS recloser provides voltage sensing on each individual source phase. Used in conjunction with Form 6-TS controls the internal voltage sensors can be used for over/undervoltage protection, directional protection, custom logic protection and metering including voltage, power, kVA and kvar. 7. What is the accuracy of the internal voltage sensors? The internal voltage sensors and Form 6-TS control has a ±2% magnitude error and ±1.5 degrees phase angle error. NOVA-TS Recloser and Form 6-TS Control October 2012 B280-09007 Power Information Application Information 8. Where does the NOVA-TS mechanism gets its power from? 14.Why are the trip settings all the same for three separate reclosers? The magnetic actuator in each recloser mechanism derives its operating power from the energy-storage capacitors located within each unit. These capacitors are charged by two 53-volt dc/dc converters in the control which are driven by the Form 6 ac power supply and the two 12volt lead acid batteries located in the Form 6-TS recloser control. 9. Where does the Form 6-TS control gets its power from? As with other Cooper Power Systems microprocessorbased recloser controls, a control power transformer is needed to provide power (120 Vac or 240 Vac) to operate the Form 6-TS control. 10. When must the batteries in the Form 6-TS control be replaced? The two 12-Volt batteries have a life expectancy of four years. It is recommended that the battery be replaced after four years or if the battery fails a battery test after it has been recharging for 48 hours - whichever occurs first. Note: Battery life is decreased at higher temperatures. Recloser Information 11. What mechanism is used in the NOVA-TS recloser? The NOVA-TS recloser relies on the same low-energy magnetic actuator mechanism used in other NOVA products. The magnetic actuator provides accurate, reliable opening and closing operations, including any required operations, without ac presence. 12. Is there an OPEN/CLOSE contact position indicator? Each phase of the NOVA-TS recloser has a large visible OPEN/CLOSED position indicator located on the side of the sleet hood. 13.How is control lockout indicated? The steady green CONTROL LOCKOUT LED indicates the control for all three reclosers is in a locked out state, i.e. a reclosing sequence is not in progress for any recloser. The blinking green CONTROL LOCKOUT LED may indicate that the control for one or two reclosers is in a locked-out state, i.e. a reclosing sequence is not in progress on those one or two reclosers. If the control is in the LOCKOUT CONDITION (blinking or steady), it does not guarantee the recloser is open. 2 Typical utility operating practice is to balance the loading as much as possible on a three-phase distribution feeder to minimize the power delivery losses. 15.Can you have three separate phase and ground trip settings? No. A-phase, B-phase, and C-phase minimum trips will all have the same value. There are four profiles that can be stored in the control. Each profile could have different phase minimum trip values, but in each profile the A-phase, B-phase, and C-phase minimum trip values will be the same. 16.When in Mode B or C, why do we lock out all three phases on a ground current fault? In all modes, not only modes B and C, ground sensing remains the same. The performance of tripping all three phases for low magnitude faults for modes B and C is based upon the unbalanced current for a three-phase system. However, this does not mean that all ground faults will always trip three-phase. As an example, if a recloser is located where the available phase-to-ground fault is 8,000 amps and the ground/phase minimum trip level is set at 200/400 amps respectively, any ground fault from 400 amps to 8,000 amps will trip only the faulted phase, even if the phase time-current curve is faster than the ground time-current curve. It is only in the narrow band from 200 to 400 amps where a ground fault or system unbalance of any kind, not distinguishable by fault current magnitude, will trip all three phases. 17. Does the standard Form 6 software include configuration of the internal voltage sensor option or is this separate? Cooper Power Systems includes the internal voltage sensor configuration as standard. The software is flexible to adjust to various voltage systems. Refer to S28042-2 NOVA-TS Triple-Single, Electronically Controlled Recloser Installation and Operation Instructions for additional information. NOVA-TS Recloser and Form 6-TS Control October 2012 Reference Information 18.What TCC Curves are available for the NOVA-TS control? The same TCC Curves available for the Form 6 control are also available for the Form 6-TS control. See Reference Data R280-91-34. 19. Is there any recommended maintenance of the NOVA-TS recloser? Because NOVA-TS reclosers are applied under widely varying operating and climatic conditions, service intervals are best determined by the user based on actual operating experience. However, NOVA-TS solid-insulated vacuum interrupting reclosers should be inspected every six years. 20.What control is the NOVA-TS recloser designed to work with? The NOVA-TS recloser and Form 6-TS control must be used together. The NOVA-TS recloser is a unique threephase Kyle recloser because it is designed to work solely with the Form 6-TS control due to its triple-single control functionality. 21. Can a NOVA-TS recloser be used with an existing Form 6 control? No. The Form 6-TS control has been specially designed for use with the NOVA-TS recloser. The standard Form 6 control does not have triple-single control functionality. 24.Can I use a Form 6-TS control to operate only 1 or 2 NOVA-TS recloser tanks? Yes. In order to have this functionality, a customized scheme is required to be programmed into the control, which by default is not programmed into the recloser. For additonal information regarding this functionality, and how it may apply to your applications, contact your Cooper Power Systems representative. 25.What are the advantages of the NOVA-TS? Cooper Power Systems was the first recloser manufacturing company to offer single-phase trip/threephase lockout originally with the 3H and 6H reclosers. This commitment to innovation includes developing algorithms to provide dependable and predictable results in multiplefault scenarios. The NOVA-TS recloser includes the following salient features: • NOVA Technology. Cycloaliphatic epoxy insulation eliminates sealing of any type of dielectric (gas, foam, oil, etc.) and also provides superb Ultraviolet protection. Refer to Bulletin 98009 for additional cycloaliphatic testing and performance information. • Innovation. As a designer, developer, and manufacturer of patented axial-magnetic vacuum interrupters, Cooper Power Systems provides vertically-integrated manufacturing. • Advanced Electronic Actuator Control System. Guarantees proper mechanism operation with various control cable lengths through the entire operating range. • User-Designed Form 6-TS Control. Includes status of all three phases, including OPEN, CLOSED, and LOCKOUT. • Direct LED Status of Operation Modes. 22.Can I use a NOVA1 recloser with a Form 6-TS control? No. The NOVA1 recloser is not compatible with the Form 6-TS control. Though very similar, the NOVA1 and NOVATS reclosers have different operating mechanisms. This requires different electrical signals be sent to the respective controls for monitoring and response purposes. B280-09007 Just as the NOVA-TS and Form 6-TS control are an integral unit, so are the NOVA1 recloser and NOVA1 control. See Bulletin Number B280-99016 for more information on the NOVA1 system. ■■ Single-Phase Trip, Single-Phase Lockout ■■ Single-Phase Trip, Three-Phase Lockout ■■ Three-Phase Trip, Three-Phase Lockout • No. The NOVA-TS recloser is not compatible with the NOVA1 control. Though very similar, the NOVA1 and NOVATS reclosers have different operating mechanisms. This requires different electrical signals be sent to the respective controls for monitoring and response purposes. Dynamic Phase Tripping. In Mode C operation, this feature enhances protection by locking out all three phases, even non-faulted phases if a phaseto-phase or three-phase fault is detected on the system. As a result, any multi-phase energization from one phase is avoided. • Just as the NOVA-TS and Form 6-TS control are an integral unit, so are the NOVA1 recloser and NOVA1 control. See Bulletin Number B280-99016 for more information on the NOVA1 system. Interactive, High-Performance Triple-Single Demonstration Software. Includes a Reliability Indices Calculator for operation and training classes. • Worldwide Customer Service Network. Guarantees that application and system solutions are readily available for customer needs and expectations. 23.Can I use a NOVA-TS recloser with a NOVA1 control? 3 NOVA-TS Recloser and Form 6-TS Control • October 2012 B280-09007 Extensive Standard Form 6 Control Features. ■■ Accurate Three-Phase Metering (Source and Load) for Six Voltage Inputs ■■ Harmonic Metering ■■ TCC Editor ■■ Data Profiler ■■ Event Recorder ■■ User-Configurable ■■ DNP 3.0 Protocol ■■ 2179 Protocol ■■ Voltage and Frequency Protection ■■ Fault Location ■■ Plus, many other other features requested by our customers. • 60+ Years of Experience in the Design and Fabrication of Reclosers. Ensures manufacturing dependability, system application knowledge, and sustained customer service. Cooper Power Systems and NOVA are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use the Cooper Trademarks without the prior written consent of Cooper Industries. ©2012 Cooper Industries. All Rights Reserved. Cooper Power Systems 2300 Badger Drive Waukesha, WI 53188 P: 877-CPS-INFO www.cooperpower.com B280-09007 • 1012